Chapter 4: Introduction To Components of Transmission & Distribution System in Malaysia
Chapter 4: Introduction To Components of Transmission & Distribution System in Malaysia
Chapter 4: Introduction To Components of Transmission & Distribution System in Malaysia
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Table 1: Voltage classes as applied to industrial and commercial power Supply Voltage Options
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
iii. Three-phase, four-wire, C.T. metered, 415 V, up to 1000 Copper has very low resistivity and is widely used as a power
kVA maximum demand. conductor, although use as an overhead conductor has become
Medium Voltage & High Voltage rare because copper is heavier and more expensive than
i. Three-phase, three-wire and 11 kV for load of 1000 kVA aluminium. It has significantly lower resistance than aluminium
maximum demand and above. by volume.
ii. Three-phase, three-wire, 22 kV or 33 kV for load of 5000 Steel cored aluminium – due to low tensile strength, aluminium
kVA maximum demand and above. conductors produce greater sag. To increased the tensile
iii. Three-phase, three-wire, 66 kV, 132 kV and 275 kV for strength, the aluminium conductor is reinforced with a core of
exceptionally large load of above 25 MVA maximum galvanized steel wires.
demands. Electrical energy is carried by conductors such as overhead
transmission lines and underground cable.
Components of HV transmission line Several variations of aluminium conductors area available:
AAC – all aluminium conductor
1. Conductors ACSR – aluminium conductor steel reinforced
2. Insulators AAAC – all aluminium alloy conductor
3. Supporting structures ACAR – aluminium conductor, alloy reinforced
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Classification of underground cables divided in 2 ways To increase the leakage path (and hence the leakage resistance),
according to: the insulators are modelled with wave-like folds.
1. Type of insulating material used in their manufacture. From a mechanical standpoint, they must be strong enough to
2. The voltage for which they are manufactured. withstand the dynamic pull and weight of the conductors.
There are two main types of insulators: pin-type insulators as
Table 4: Classification of Cables
shown in Figure 4 and suspension-type insulators as in Figure 5.
Low-tension (L.T) cables Up to 1000 V
High-tension (H.T) cables Up to 11 kV
Super tension (S.T) cables From 22 kV to 33 kV Fig 4: Sectional view of a 69 kV pin-
Extra high-tension (E.H.T) cables From 33 kV to 66 kV type insulator. BIL: 270 kV; 60 Hz
Extra super voltage cables Beyond 132 kV flash-over voltage, under wet
conditions: 125 kV.
(Courtesy of Canadian Ohio Brass Co.
Ltd.)
The pin-type has several has several porcelain skirts (folds) and
B. Insulators
the conductor is fixed at the top. A steep pin screws into the
insulator so it can be bolted to a support.
Insulators serve to support and anchor the conductors and to
For voltages above 70 kV, suspension-type insulators are used,
insulate them from ground. Insulators are usually made of
strung together by their cap and pin metallic parts.
porcelain, but glass and other synthetic insulating materials are
The number of insulators depends upon voltage: for 110 kV,
also used.
generally use from 4 to 7; for 230 kV, from 13 to 16. Figure 6
From an electrical standpoint, insulators must offer a high
shows an insulator arrangement for a 735 kV line.
resistance to surface leakage currents and must be sufficiently
It is composed of 4 strings in parallel of 35 insulators each, to
thick to prevent breakdown under the high voltage stresses they
provide both electrical and mechanical strength.
have to withstand.
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
C. Supporting structures
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
A. Radial System
Supplementary flashovers
(a) Lightning strike and flashovers (b) Arcing downed conductor
Fig 9: Example of a lightning flash to a 132 kV distribution line and the downed wire
that carry load.
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
C. Network System
Load 1 Load 2
A combination of the radial and ring distribution system.
Although such a system is more complex than either of the
Power lines previous configurations, reliability is improved significantly.
Substation Load 3
The network system, illustrated in figure below is one of the
most common power distribution configurations.
Power lines
Load 4
B. Ring System
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Arrangement of a Substation
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Distribution substations are capacity injection points from 11 Circuit breakers are designed to interrupt either normal or short
kV, 22 kV and sometimes 33 kV systems to the low voltage circuit currents.
network (415 V, 240 V). They behave like a big switch that may be opened or closed by
Typically capacity ratings are 1000 kVA, 750 kVA, 500 kVA local pushbuttons or by the system telecommunication signals
and 300 kVA. emitted by the system of protection.
Conventional substation designs are of indoor type (equipment Thus, circuit breakers will automatically open a circuit
housed in a permanent building) and out-door type (ground- whenever the line current, line voltage, frequency and so on,
mounted or pole-mounted). departs from a present limit.
Standardized M&E design of 11/0.433 kV sub-station is The most of important types of circuit breakers are:
available at TNB offices. o Oil circuit breakers (OCBs)
Compact substation (11/0.415 kV) has limited application and is o Air-blast circuit breakers
to be strictly applied in selective situations under the following o SF6 (sulphur hexafluoride) CB
circumstances: o Vacuum CB
o System reinforcement projects for highly built-up areas Nameplate on the CB usually indicates:
where substation land is difficult to acquire. o The max steady-state current it can carry
o Any request to use compact substation for dedicated o The max interrupting current
supply to a single or limited group of low voltage o The max line voltage
consumers is subject to TNB approval in accordance to o The interrupting time in cycles
site constraints situation and to be considered as ‘special
feature design schemes’. A. Advantages of Oil Circuit Breakers (OCBs)
The main reasons for the above application criteria are as
follows: Oil is very good insulator.
o Compact design reduces future system flexibility in Dielectric strength of oil is very high.
terms of network expansion. Oil has great heat dissipating property.
o Compact design features, which limits the capacity of The gases formed due to decomposition of oil during arcing
outgoing circuits. have good cooling properties.
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
The arc in the air breaker is extinguished early. 1. Efficient (open and close in the shortest possible time under any
Duration of arc being smaller, the contact points of the breaker network conditions).
is increased. 2. Conduct rated current without exceeding rated design
Frequent operations of the circuit breaker are not a problem. temperature.
Less maintenance is required. 3. Withstand, thermally and mechanically, any short circuit
Less possibility of fire hazard. currents.
Operates at high speed. 4. Maintain its voltage to earth and across the open contacts under
both clean and polluted conditions.
C. Advantages of SF6 Circuit Breakers 5. Not create any large overvoltage during opening and closing.
6. Be easily maintained.
7. Be not too expensive / economical.
Dielectric strength of SF6 is higher that air and it is even more
than that of oil used in circuit breaker at high pressure.
Table 7: Differences between Fuse and Circuit Breaker
Good ability to interrupt low and high fault currents,
magnetizing and capacitive currents Particular Fuse Circuit Breaker
Breaker has enough overload margins. Performs interruption
It performs both
function only. The
Maintenance needed for this breaker is minimum. Function detection and
detection of fault is made
No risk of fire or explosion (gas is non-flammable/chemically interruption function.
by relay system.
stable).
Required elaborate
Inherently completely
Operation equipment (i.e relay) for
D. Advantages of Vacuum Circuit Breakers automatic.
automatic action.
Breaking
High dielectric strength. Small Very large
Capacity
Operating mechanism is very simple.
Very small (0.002 sec Comparatively large (0.1
Arc interruption is very rapid. Operating Time
or so) to 0.2 sec)
Suitable for repeated operation.
Required replacement No replacement after
No possibility of explosion. Replacement
after every operation. operation.
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Fuse
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Fig 21: Minimum oil circuit breaker installed in a 420 kV, 50 Hz substation. Rated
Fig 19: Cross section of an oil circuit breaker. The diagram shows four of the six current: 2000 A; rupturing capacity: 25 kA; height (less support): 5400 mm; length:
bushings; the heater keeps the oil at a satisfactory temperature during cold weather. 6200mm; 4 circuit-breaking modules in series per circuit breaker.
(Courtesy of Canadian General Electric) (Courtesy of ABB)
Fig 22: Air-blast circuit breaker rated 2000 A at 362 kV. It can interrupt a current of
40 kA in 3 cycles on a 60 Hz system. It consists of 3 identical modules connected in
Fig 20: Three-phase oil circuit breaker rated 1200 A and 115 kV. It can interrupt a series, each rated for a nominal voltage of 121 kV. The compressed-air reservoir can
current of 50 kA in 3 cycles on a 60 Hz system. Other characteristics; height: 3660 be seen at the left. Other characteristics; height: 5640 mm; overall length: 9150 mm;
mm; diameter: 3050 mm; mass: 21 t; BIL: 550 kV. BIL: 1300 kV.
(Courtesy of Canadian General Electric) (Courtesy of General Electric)
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Fig 23: Cross section of one module of an air-blast circuit breaker. When the circuit
breaker trips, the rod is driven upward, separating the fixed and movable contacts. The
intense arc is immediately blown out by a jet of compressed air coming from the
carifice. The resistor dampens the overvoltages that occur when the breaker opens.
(Courtesy of General Electric) Fig 25: MOV surge arresters protect this EHV transformer.
(Courtesy of General Electric)
Fig 24: Group of 15 totally enclosed SF6 circuit breakers installed in an underground Fig 26: MV busbar feeding eight lines, each protected by a circuit breaker.
substation of a large city. Rated current: 1600 A; rupturing current: 34 kA; normal
operating pressure: 256 kPa (38 psi); pressure during arc extinction: 1250 kPa (180
psi). These SF6 circuit breakers take up only 1/16 of the volume of conventional
circuit breakers having the same interrupting capacity.
(Courtesy of ABB)
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
Fig 28: Three 2.2 Ω reactors rated 500 A are connected in series with a 120 kV, 3-
phase, 60 Hz line. They are connected from ground by four insulating, and each is
protected by a surge arrester.
(Courtesy of Hydro-Quebec)
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE
DET 308: Power System II (SEM I 2011/2012)
References:
Chapter 4: Introduction to Components of Transmission & Distribution System in Malaysia Prepared by Ms. Melaty binti Amirruddin, PPKSE