Actuators For Three Point Control Amv 56K: Data Sheet
Actuators For Three Point Control Amv 56K: Data Sheet
Actuators For Three Point Control Amv 56K: Data Sheet
Main data:
• The advanced design incorporates load
related 'switch-off' to ensure that actuator
and valve are not exposed to overload.
• Digitale feedback end position indication
signal for valve end position is available by
terminal 4 or 5.
• Manual override.
• Low weight and robust
Accessories
(only one potentiometer or additional
switches can be added)
Type Code No.
Potentiometer (10 kOhm/15 mm) 082H7034
Potentiometer (10 kOhm/40 mm) 082H7036
Potentiometer (1 kOhm/40 mm) 082H7039
Additional switches (2x) 082H7037
Installation
Note that the actuator should be mounted
horizontally at media temperatures over 150 oC.
Lmin=500
Mechanical Electrical
The actuator should be mounted with the Electrical connections can be accessed by
valve stem in either horizontal position or removing the cover. Two Pg11 cable entries
pointing upwards. Use a 4 mm Allen key (not are provided. Both entries are provided with a
supplied) to fit the actuator to the valve body. rubber grommet for use with flexible cable.
Allow for necessary clearance for Note that in order to maintain the enclosure IP
maintenance purposes. rating, appropriate cable glands must be
The valve has position indication rings which used.
should be pushed together before
commissioning; after stroking they indicate
the ends of the stroke.
Wiring Terminals 2, 3:
Control voltage input from the controller.
Power supply 24 V~, 230 V~ (dependent on
type)
Terminals 4, 5:
Output used for position indication or
230 Vac version: monitoring.
Do not touch anything on
the PCB! Lethal voltage!
Terminal 1
Neutral / common (0 V)
Wiring - accessories
Dimensions
Ø 47