UTC Keningau ACMV O&M Manual PDF
UTC Keningau ACMV O&M Manual PDF
UTC Keningau ACMV O&M Manual PDF
LIST OF CONTENTS
SECTION TITLE
1. System Overview
(A) Air Conditioning System (VRV)
(B) Air-conditioning System (Split Air-cooled)
2. Operation Procedure
(A) Air Conditioning System (VRV)
(B) Air-conditioning System (Split Air-cooled)
3. Operator's Knowledge
4. Maintenance
SECTION 1
System
Overview
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
1. SYSTEM OVERVIEW
UTC KENINGAU
The air conditioning systems used in UTC Keningau are:
1) VRV air cooled system
2) Air cooled split unit system
One VRV systems are provided for each government department. Split unit
systems are used in the Lower ground floor and in special requirement areas within the
building. Daikin products are used for all the cooling equipment in the building. Refer to
the appendix for details of the nearest dealer and the contact details of Daikin Malaysia
Sdn Bhd in Sabah.
(ii) Wall Mounted and Cassette Type Indoor Units in Each department.
2 VRV Overview
VRFs are typically installed with an Air conditioner inverter which adds a DC inverter to the compressor
to support variable motor speed and thus variable refrigerant flow rather than simply perform on/off
operation. By operating at varying speeds, VRF units work only at the needed rate allowing for substantial
energy savings at partial-load conditions. Energy savings of up to 55% are predicted over comparable
unitary equipment. This also results in greater control of the building's interior temperature by the
building's occupants.
VRFs in UTC Keningau come in two pipe system format, a liquid line and a gas line. The main pipes are
insulated with metal jackets and the branch pipes are insulation by conventional rubber nitrite insulation.
Refnet joints are used to branch out the refrigerant pipes from the main pipes to each indoor unit.
The picture in the next page shows the components of the VRV system
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
System Overview
Components include:
1. Indoor units:
a. Ceiling Mounted Cassette Units
b. Wall Mounted Units
2. Outdoor unit
3. Remote Control
4. Suction Gas Refrigerant Pipe
5. Liquid Refrigerant Pipe
6. Refnet Joints
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
System Overview
There are certain areas in the building that are cooled by Air-cooled Split Air-conditioning units.
The Air-cooled Split Air-conditioning unit consists of an indoor unit and condensing unit.
The air conditioning units used in UTC Keningau are inverter units
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
SECTION 2
Operation
Procedure
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
Operation Procedure
2. OPERATION PROCEDURE
a) Check power supply to main outdoor unit is switched on and all 3 phase are on.
b) Check the oil heater - It must be energized for 12 hours prior to starting the outdoor unit.
c) Check the indoor units are all switched on and in standby mode.
d) Turn on air conditioners at the indoor unit. Point the remote control at the desired indoor unit
and press the ON/OFF button one by one.
e) To turn OFF the air conditioner, point the remote control at the desired indoor unit and press
the ON/OFF button one by one.
Notes:
Do not switch off indoor unit power.
Do not switch off outdoor unit power.
When there is a power failure. Air conditioning must be switched on again after
power is restored.
1. Switch on the Air-con switch for the power supply. Press ON/OFF on the remote controller
to turn on or off the Air-cooled Air-conditioning unit.
2. The target room temperature can be set on the Remote Controller.
3. Other functions like timer, Fan speed, and other mode of operation can be set on the Remote
controller.
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
SECTION 3
Operator’s
Knowledge
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
3. OPERATOR'S KNOWLEDGE
Operator should be familiar with the following equipment: -
3. How to operate the remote control to get error codes from the VRV or Inverter split system.
4. Location of all equipment's as listed in item (1) above and their control panels as described
in system overview and indicated in the as-built drawings.
VRV
Cannot switch on 1. Check power supply
2. Check for power trip in control panel
Not cold 1. Check Error Codes
2. Where to get help
SECTION 4
Maintenance
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
Maintenance
4. MAINTENANCE
In general, daily Operation logbooks for all major equipments must be implemented to detect any
abnormality of the equipments. A good planned program of regularly scheduled maintenance is
recommended to maintain the good running condition of all the equipments. The following scheduled
maintenance for individual equipments are listed for implementation.
Annually maintenance
Maintenance
Quarterly Maintenance
SECTION 5
List Of
Equipment
(Appendix)
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.
1. Material List
Model Qty Description
RXQ12TY1 2 Cooling only VRV IV STANDARD
RXQ16TY1 1 Cooling only VRV IV STANDARD
RXQ18TY1 2 Cooling only VRV IV SPACE SAVING
RXQ20TY1 3 Cooling only VRV IV SPACE SAVING
RXQ8TY1 3 Cooling only VRV IV STANDARD
FXAQ25PVE 32 VRV AP - Wall Mounted(Flat Panel)
FXAQ50PVE 1 VRV AP - Wall Mounted(Flat Panel)
FXFQ100LUV1 6 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ125LUV1 3 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ25LUV1 5 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ32LUV1 3 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ40LUV1 17 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ50LUV1 11 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ63LUV1 3 VRV FLU - Ceiling Mounted Cassette(Round Flow)
FXFQ80LUV1 7 VRV FLU - Ceiling Mounted Cassette(Round Flow)
KHRP26A22T 48 Refnet branch piping kit
KHRP26A33T 11 Refnet branch piping kit
KHRP26A72T 16 Refnet branch piping kit
KHRP26A73T + KHRP26M73TP 6 Refnet branch piping kit
BRC1E62 2 Wired Remote Controller (Navigation Remote Controller)
BRC7EA619 33 Wireless remote controller CO
BRC7F635F 55 Wireless remote controller CO
BYCP125K-W1 55 Decoration panel
BHFP22P100 4 Outdoor unit multi connection piping kit
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Rq SC Required sensible cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tmp H Indoor temperature in heating
Rq HC Required heating capacity
Max HC Available heating capacity
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
Fuses Fuses
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 2
2.2. CU-GF-PDRM - RXQ8TY1
Capacity data at conditions and connection ratio (90%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
FCU-GF-PDRM01 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-GF-PDRM02 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-PDRM03 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-PDRM04 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-PDRM05 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
Σ 20.2 n/a
The sum of the required indoor unit capacities is 20.2kW for cooling.
However, the outdoor unit selection uses reduced load values for cooling of 18.2kW (= -10%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 3
2.3. CU-GF-SC - RXQ8TY1
Capacity data at conditions and connection ratio (88%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
FCU-GF-SC-01 FXFQ63LUV1 27.0 / 19.0 n/a 7.1 n/a 5.6 6.0 n/a n/a n/a 317
FCU-GF-SC-02 FXFQ32LUV1 27.0 / 19.0 n/a 3.6 n/a 3.1 6.0 n/a n/a n/a 217
FCU-GF-SC-03 FXFQ32LUV1 27.0 / 19.0 n/a 3.6 n/a 3.1 6.0 n/a n/a n/a 217
FCU-GF-SC-04 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-SC-05 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
Σ 19.9 n/a
The sum of the required indoor unit capacities is 19.9kW for cooling.
However, the outdoor unit selection uses reduced load values for cooling of 15.9kW (= -20%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 4
2.4. CU-GF-K1RM - RXQ26TSY1
Capacity data at conditions and connection ratio (101%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
FCU-GF-K1RM-01 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-GF-K1RM-02 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-GF-K1RM-03 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-GF-K1RM-04 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-K1RM-05 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-K1RM-06 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-K1RM-07 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-K1RM-08 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-K1RM-09 FXFQ25LUV1 27.0 / 19.0 n/a 2.8 n/a 2.8 6.0 n/a n/a n/a 217
FCU-GF-K1RM-10 FXFQ25LUV1 27.0 / 19.0 n/a 2.8 n/a 2.8 6.0 n/a n/a n/a 217
FCU-GF-K1RM-11 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-K1RM-12 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-K1RM-13 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-K1RM-14 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-K1RM-15 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-K1RM-16 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-K1RM-17 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-K1RM-18 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-K1RM-19 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
Σ 73.5 n/a
The sum of the required indoor unit capacities is 73.5kW for cooling.
However, the outdoor unit selection uses reduced load values for cooling of 63.2kW (= -14%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 5
Outdoor unit placed 20.0m above the indoor units.
The minimum connection ratio for this height difference is 50%.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 6
2.5. CU-GF-JPN - RXQ40TSY1
Capacity data at conditions and connection ratio (103%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
FCU-GF-JPN-01 FXFQ125LUV1 27.0 / 19.0 n/a 14.0 n/a 10.3 6.0 n/a n/a n/a 550
FCU-GF-JPN-02 FXFQ100LUV1 27.0 / 19.0 n/a 11.2 n/a 8.9 6.0 n/a n/a n/a 533
FCU-GF-JPN-03 FXFQ100LUV1 27.0 / 19.0 n/a 11.2 n/a 8.9 6.0 n/a n/a n/a 533
FCU-GF-JPN-04 FXFQ80LUV1 27.0 / 19.0 n/a 9.0 n/a 6.6 6.0 n/a n/a n/a 350
FCU-GF-JPN-05 FXFQ80LUV1 27.0 / 19.0 n/a 9.0 n/a 6.6 6.0 n/a n/a n/a 350
FCU-GF-JPN-06 FXFQ80LUV1 27.0 / 19.0 n/a 9.0 n/a 6.6 6.0 n/a n/a n/a 350
FCU-GF-JPN-07 FXFQ63LUV1 27.0 / 19.0 n/a 7.1 n/a 5.6 6.0 n/a n/a n/a 317
FCU-GF-JPN-08 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-JPN-09 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-JPN-10 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-GF-JPN-11 FXFQ63LUV1 27.0 / 19.0 n/a 7.1 n/a 5.6 6.0 n/a n/a n/a 317
FCU-GF-JPN-12 FXAQ50PVE 27.0 / 19.0 n/a 5.6 n/a 4.2 6.0 n/a n/a n/a 250
FCU-GF-JPN-13 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-GF-JPN-14 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-GF-JPN-15 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-JPN-16 FXFQ32LUV1 27.0 / 19.0 n/a 3.6 n/a 3.1 6.0 n/a n/a n/a 217
Σ 115.4 n/a
The sum of the required indoor unit capacities is 115.4kW for cooling.
However, the outdoor unit selection uses reduced load values for cooling of 98.1kW (= -15%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 7
2.6. CU-GF-MDK - RXQ20TY1
Capacity data at conditions and connection ratio (99%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
FCU-GF-MDK-01 FXFQ100LUV1 27.0 / 19.0 n/a 11.2 n/a 8.9 6.0 n/a n/a n/a 533
FCU-GF-MDK-02 FXFQ125LUV1 27.0 / 19.0 n/a 14.0 n/a 10.3 6.0 n/a n/a n/a 550
FCU-GF-MDK-03 FXFQ125LUV1 27.0 / 19.0 n/a 14.0 n/a 10.3 6.0 n/a n/a n/a 550
FCU-GF-MDK-04 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-GF-MDK-05 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-GF-MDK-06 FXFQ80LUV1 27.0 / 19.0 n/a 9.0 n/a 6.6 6.0 n/a n/a n/a 350
Σ 55.5 n/a
The sum of the required indoor unit capacities is 55.5kW for cooling.
However, the outdoor unit selection uses reduced load values for cooling of 47.2kW (= -15%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 8
2.7. CU-1F-JI - RXQ30TSY1
Capacity data at conditions and connection ratio (105%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
FCU-1F-JI-01 FXFQ100LUV1 27.0 / 19.0 n/a 11.2 n/a 8.9 6.0 n/a n/a n/a 533
FCU-1F-JI-02 FXFQ100LUV1 27.0 / 19.0 n/a 11.2 n/a 8.9 6.0 n/a n/a n/a 533
FCU-1F-JI-03 FXFQ100LUV1 27.0 / 19.0 n/a 11.2 n/a 8.9 6.0 n/a n/a n/a 533
FCU-1F-JI-04 FXFQ25LUV1 27.0 / 19.0 n/a 2.8 n/a 2.8 6.0 n/a n/a n/a 217
FCU-1F-JI-05 FXFQ25LUV1 27.0 / 19.0 n/a 2.8 n/a 2.8 6.0 n/a n/a n/a 217
FCU-1F-JI-06 FXFQ25LUV1 27.0 / 19.0 n/a 2.8 n/a 2.8 6.0 n/a n/a n/a 217
FCU-1F-JI-07 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-1F-JI-08 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-1F-JI-09 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-10 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-11 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-1F-JI-12 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-1F-JI-13 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-14 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-15 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-16 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-17 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-18 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-19 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JI-20 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
Σ 88.0 n/a
The sum of the required indoor unit capacities is 88.0kW for cooling.
However, the outdoor unit selection uses reduced load values for cooling of 71.3kW (= -19%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.
Page 9
Outdoor unit placed 20.0m above the indoor units.
The minimum connection ratio for this height difference is 50%.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 10
2.8. CU-1F-JPJ - RXQ28TSY1
Capacity data at conditions and connection ratio (101%) as entered
Name FCU Tmp C Rq TC Max TC Rq SC Max SC Tevap Tmp H Rq HC Max HC Airflow
°C kW kW kW kW °C °C kW kW l/s
FCU-1F-JPJ-01 FXFQ80LUV1 27.0 / 19.0 n/a 9.0 n/a 6.6 6.0 n/a n/a n/a 350
FCU-1F-JPJ-02 FXFQ80LUV1 27.0 / 19.0 n/a 9.0 n/a 6.6 6.0 n/a n/a n/a 350
FCU-1F-JPJ-03 FXFQ80LUV1 27.0 / 19.0 n/a 9.0 n/a 6.6 6.0 n/a n/a n/a 350
FCU-1F-JPJ-04 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-1F-JPJ-05 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-1F-JPJ-06 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
FCU-1F-JPJ-07 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-08 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-09 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-10 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-11 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-12 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-13 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-14 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-15 FXFQ40LUV1 27.0 / 19.0 n/a 4.5 n/a 3.8 6.0 n/a n/a n/a 250
FCU-1F-JPJ-16 FXAQ25PVE 27.0 / 19.0 n/a 2.8 n/a 2.2 6.0 n/a n/a n/a 133
FCU-1F-JPJ-17 FXFQ50LUV1 27.0 / 19.0 n/a 5.6 n/a 4.4 6.0 n/a n/a n/a 267
Σ 79.1 n/a
The sum of the required indoor unit capacities is 79.1kW for cooling.
However, the outdoor unit selection uses reduced load values for cooling of 67.2kW (= -15%).
Be aware that unrealistic reductions may lead to reduced comfort levels, different noise levels or increased wear
and tear.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 11
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
MFA Maximum Fuse Amps
Run Amps Running Amps
St Curr Starting current
Fuses Fuses
WxHxD WidthxHeightxDepth
Wght Weight of the device
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 12
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC Tmp H HC Rq HC Piping
% °C kW kW °C kW kW m
CU-GF-PDRM RXQ8TY1 90 35.0 19.2 18.2 70.0
CU-GF-SC RXQ8TY1 88 35.0 19.2 15.9 70.0
CU-GF-K1RM RXQ26TSY1 101 35.0 63.3 63.2 70.0
CU-GF-JPN RXQ40TSY1 103 35.0 98.3 98.1 70.0
CU-GF-MDK RXQ20TY1 99 35.0 48.7 47.2 70.0
CU-1F-JI RXQ30TSY1 105 35.0 73.6 71.3 70.0
CU-1F-JPJ RXQ28TSY1 101 35.0 68.7 67.2 70.0
Name Model PS MCA MFA Run Amps St Curr Fuses WxHxD Wght
A A A A mm kg
CU-GF-PDRM RXQ8TY1 400V 3ph 16.1 20 Factory Std 930x1657x765 185
CU-GF-SC RXQ8TY1 400V 3ph 16.1 20 Factory Std 930x1657x765 185
CU-GF-K1RM RXQ26TSY1 400V 3ph
* RXQ18TY1 31 35 Factory Std 1240x1657x765 285
* RXQ8TY1 16.1 20 Factory Std 930x1657x765 185
CU-GF-JPN RXQ40TSY1 400V 3ph
* RXQ20TY1 40 50 Factory Std 1240x1657x765 320
* RXQ20TY1 40 50 Factory Std 1240x1657x765 320
CU-GF-MDK RXQ20TY1 400V 3ph 40 50 Factory Std 1240x1657x765 320
CU-1F-JI RXQ30TSY1 400V 3ph
* RXQ18TY1 31 35 Factory Std 1240x1657x765 285
* RXQ12TY1 24 25 Factory Std 930x1657x765 195
CU-1F-JPJ RXQ28TSY1 400V 3ph
* RXQ16TY1 31 35 Factory Std 1240x1657x765 285
* RXQ12TY1 24 25 Factory Std 930x1657x765 195
Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 13
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.
⅜"×¾" ¼"×½"
KHRP26A33T
FCU-GF-PDRM05
FXAQ25PVE
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-GF-PDRM04
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-PDRM02
FXFQ40LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-PDRM01
FXFQ50LUV1
¼"×½"
FCU-GF-PDRM03
FXFQ40LUV1
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 14
4.2. Piping CU-GF-SC
CU-GF-SC
RXQ8TY1
⅜"×¾" ¼"×½"
KHRP26A33T
FCU-GF-SC-05
FXAQ25PVE
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-GF-SC-02
FXFQ32LUV1
FCU-GF-SC-03
FXFQ32LUV1
⅜"×⅝"
FCU-GF-SC-01
FXFQ63LUV1
¼"×½"
FCU-GF-SC-04
FXAQ25PVE
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 15
4.3. Piping CU-GF-K1RM
CU-GF-K1RM
RXQ26TSY1
RXQ18TY1 RXQ8TY1
⅝"×1⅛" ⅜"×¾"
BHFP22P100
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-18
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-19
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-16
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-15
FXAQ25PVE
¼"×½"
FCU-GF-K1RM-14
FXFQ40LUV1
⅝"×1⅛" ¼"×½"
KHRP26A72T
FCU-GF-K1RM-03
FXFQ50LUV1
⅝"×1⅛" ¼"×½"
KHRP26A72T
FCU-GF-K1RM-02
FXFQ50LUV1
½"×1⅛" ¼"×½"
KHRP26A72T
FCU-GF-K1RM-01
FXFQ50LUV1
½"×1⅛" ¼"×½"
KHRP26A72T
FCU-GF-K1RM-04
FXFQ40LUV1
FCU-GF-K1RM-05
FXFQ40LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-06
FXFQ40LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-07
FXAQ25PVE
¼"×½"
FCU-GF-K1RM-08
FXAQ25PVE
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-09
FXFQ25LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-10
FXFQ25LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-11
FXFQ40LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-K1RM-12
FXFQ40LUV1
¼"×½"
FCU-GF-K1RM-13
FXFQ40LUV1
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 16
4.4. Piping CU-GF-JPN
CU-GF-JPN
RXQ40TSY1
RXQ20TY1 RXQ20TY1
⅝"×1⅛" ⅝"×1⅛"
BHFP22P100
¾"×1⅝" ⅜"×⅝"
KHRP26A73T +
KHRP26M73TP
FCU-GF-JPN-01
FXFQ125LUV1
⅜"×⅝"
FCU-GF-JPN-03
FXFQ100LUV1
⅜"×¾" ⅜"×⅝"
KHRP26A22T
FCU-GF-JPN-05
FXFQ80LUV1
⅜"×⅝"
FCU-GF-JPN-06
FXFQ80LUV1
FCU-GF-JPN-07
FXFQ63LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-JPN-08
FXFQ40LUV1
¼"×½"
FCU-GF-JPN-09
FXFQ40LUV1
FCU-GF-JPN-10
FXFQ50LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-JPN-12
FXAQ50PVE
⅜"×⅝"
FCU-GF-JPN-11
FXFQ63LUV1
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-GF-JPN-14
FXFQ50LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-JPN-13
FXFQ50LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-JPN-15
FXAQ25PVE
¼"×½"
FCU-GF-JPN-16
FXFQ32LUV1
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 17
4.5. Piping CU-GF-MDK
CU-GF-MDK
RXQ20TY1
⅝"×1⅛" ⅜"×⅝"
KHRP26A72T
FCU-GF-MDK-01
FXFQ100LUV1
½"×1⅛" ⅜"×⅝"
KHRP26A72T
FCU-GF-MDK-06
FXFQ80LUV1
½"×1⅛" ⅜"×⅝"
KHRP26A72T
FCU-GF-MDK-02
FXFQ125LUV1
⅜"×¾" ⅜"×⅝"
KHRP26A22T
FCU-GF-MDK-03
FXFQ125LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-GF-MDK-04
FXFQ40LUV1
¼"×½"
FCU-GF-MDK-05
FXAQ25PVE
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 18
4.6. Piping CU-1F-JI
CU-1F-JI
RXQ30TSY1
RXQ18TY1 RXQ12TY1
⅝"×1⅛" ½"×1⅛"
BHFP22P100
½"×1⅛" ¼"×½"
KHRP26A72T
FCU-1F-JI-07
FXFQ40LUV1
½"×1⅛" ⅜"×⅝"
KHRP26A72T
FCU-1F-JI-02
FXFQ100LUV1
⅜"×⅞" ¼"×½"
KHRP26A33T
FCU-1F-JI-04
FXFQ25LUV1
⅜"×⅞" ⅜"×⅝"
KHRP26A33T
FCU-1F-JI-03
FXFQ100LUV1
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-1F-JI-05
FXFQ25LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JI-18
FXAQ25PVE
FCU-1F-JI-17
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JI-19
FXAQ25PVE
¼"×½"
FCU-1F-JI-20
FXAQ25PVE
¼"×½"
FCU-1F-JI-16
FXAQ25PVE
⅜"×⅞" ¼"×½"
KHRP26A33T
FCU-1F-JI-06
FXFQ25LUV1
⅜"×⅞" ¼"×½"
KHRP26A33T
FCU-1F-JI-08
FXFQ40LUV1
⅜"×⅞" ¼"×½"
KHRP26A33T
FCU-1F-JI-09
FXAQ25PVE
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-1F-JI-11
FXFQ40LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JI-10
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JI-12
FXFQ40LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JI-13
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JI-14
FXAQ25PVE
¼"×½"
FCU-1F-JI-15
FXAQ25PVE
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 19
4.7. Piping CU-1F-JPJ
CU-1F-JPJ
RXQ28TSY1
RXQ16TY1 RXQ12TY1
½"×1⅛" ½"×1⅛"
BHFP22P100
¼"×½"
FCU-1F-JPJ-07
FXAQ25PVE
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-1F-JPJ-05
FXFQ50LUV1
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JPJ-09
FXAQ25PVE
FCU-1F-JPJ-15
FXFQ40LUV1
¼"×½"
FCU-1F-JPJ-17
FXFQ50LUV1
¼"×½"
FCU-1F-JPJ-16
FXAQ25PVE
½"×1⅛" ⅜"×⅝"
KHRP26A72T
FCU-1F-JPJ-01
FXFQ80LUV1
½"×1⅛" ⅜"×⅝"
KHRP26A72T
FCU-1F-JPJ-02
FXFQ80LUV1
⅜"×⅞" ¼"×½"
KHRP26A33T
FCU-1F-JPJ-06
FXFQ50LUV1
⅜"×⅞" ¼"×½"
KHRP26A33T
FCU-1F-JPJ-04
FXFQ50LUV1
⅜"×¾" ¼"×½"
KHRP26A22T
FCU-1F-JPJ-08
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JPJ-10
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JPJ-13
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JPJ-11
FXAQ25PVE
⅜"×⅝" ¼"×½"
KHRP26A22T
FCU-1F-JPJ-12
FXAQ25PVE
¼"×½"
FCU-1F-JPJ-14
FXAQ25PVE
Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 20
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.
FCU-GF-PDRM02 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-PDRM01 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-PDRM03 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 21
5.2. Wiring CU-GF-SC
CU-GF-SC FCU-GF-SC-05 BRC7EA619
RXQ8TY1 FXAQ25PVE
IN F1,F2 F1,F2 L,N 0.4A 1ph
L1,L2,L3,N 16A 3ph
FCU-GF-SC-02 BRC7F635F
FXFQ32LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-SC-03 BRC7F635F
FXFQ32LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-SC-01 BRC7F635F
FXFQ63LUV1
F1,F2 L,N 0.4A 1ph
FCU-GF-SC-04 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 22
5.3. Wiring CU-GF-K1RM
CU-GF-K1RM FCU-GF-K1RM-17 BRC7EA619
RXQ26TSY1 FXAQ25PVE
IN F1,F2 F1,F2 L,N 0.4A 1ph
RXQ18TY1
Q1,Q2 L1,L2,L3,N
FCU-GF-K1RM-18 BRC7EA619
31A 3ph
FXAQ25PVE
RXQ8TY1 F1,F2 L,N 0.4A 1ph
Q1,Q2 L1,L2,L3,N
16A 3ph
FCU-GF-K1RM-19 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-GF-K1RM-16 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-GF-K1RM-15 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-GF-K1RM-14 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-03 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-02 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-01 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-04 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-05 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-06 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-07 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-GF-K1RM-08 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-GF-K1RM-09 BRC7F635F
FXFQ25LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-10 BRC7F635F
FXFQ25LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-11 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-12 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-K1RM-13 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 23
5.4. Wiring CU-GF-JPN
CU-GF-JPN FCU-GF-JPN-01 BRC7F635F
RXQ40TSY1 FXFQ125LUV1
IN F1,F2 F1,F2 L,N 1.5A 1ph
RXQ20TY1
Q1,Q2 L1,L2,L3,N
FCU-GF-JPN-02 BRC7F635F
40A 3ph
FXFQ100LUV1
RXQ20TY1 F1,F2 L,N 1.3A 1ph
Q1,Q2 L1,L2,L3,N
40A 3ph
FCU-GF-JPN-03 BRC7F635F
FXFQ100LUV1
F1,F2 L,N 1.3A 1ph
FCU-GF-JPN-04 BRC7F635F
FXFQ80LUV1
F1,F2 L,N 0.5A 1ph
FCU-GF-JPN-05 BRC7F635F
FXFQ80LUV1
F1,F2 L,N 0.5A 1ph
FCU-GF-JPN-06 BRC7F635F
FXFQ80LUV1
F1,F2 L,N 0.5A 1ph
FCU-GF-JPN-07 BRC7F635F
FXFQ63LUV1
F1,F2 L,N 0.4A 1ph
FCU-GF-JPN-08 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-JPN-09 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-JPN-10 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-JPN-12 BRC7EA619
FXAQ50PVE
F1,F2 L,N 0.5A 1ph
FCU-GF-JPN-11 BRC7F635F
FXFQ63LUV1
F1,F2 L,N 0.4A 1ph
FCU-GF-JPN-14 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-JPN-13 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-JPN-15 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-GF-JPN-16 BRC7F635F
FXFQ32LUV1
F1,F2 L,N 0.3A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 24
5.5. Wiring CU-GF-MDK
CU-GF-MDK FCU-GF-MDK-01 BRC7F635F
RXQ20TY1 FXFQ100LUV1
IN F1,F2 F1,F2 L,N 1.3A 1ph
L1,L2,L3,N 40A 3ph
FCU-GF-MDK-06 BRC7F635F
FXFQ80LUV1
F1,F2 L,N 0.5A 1ph
FCU-GF-MDK-02 BRC7F635F
FXFQ125LUV1
F1,F2 L,N 1.5A 1ph
FCU-GF-MDK-03 BRC7F635F
FXFQ125LUV1
F1,F2 L,N 1.5A 1ph
FCU-GF-MDK-04 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-GF-MDK-05 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 25
5.6. Wiring CU-1F-JI
CU-1F-JI FCU-1F-JI-01 BRC7F635F
RXQ30TSY1 FXFQ100LUV1
IN F1,F2 F1,F2 L,N 1.3A 1ph
RXQ18TY1
Q1,Q2 L1,L2,L3,N
FCU-1F-JI-07 BRC7F635F
31A 3ph
FXFQ40LUV1
RXQ12TY1 F1,F2 L,N 0.3A 1ph
Q1,Q2 L1,L2,L3,N
24A 3ph
FCU-1F-JI-02 BRC7F635F
FXFQ100LUV1
F1,F2 L,N 1.3A 1ph
FCU-1F-JI-04 BRC7F635F
FXFQ25LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JI-03 BRC7F635F
FXFQ100LUV1
F1,F2 L,N 1.3A 1ph
FCU-1F-JI-05 BRC7F635F
FXFQ25LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JI-18 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-17 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-19 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-20 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-16 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-06 BRC7F635F
FXFQ25LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JI-08 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JI-09 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-11 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JI-10 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-12 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JI-13 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-14 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JI-15 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 26
5.7. Wiring CU-1F-JPJ
CU-1F-JPJ FCU-1F-JPJ-03 BRC7F635F
RXQ28TSY1 FXFQ80LUV1
IN F1,F2 F1,F2 L,N 0.5A 1ph
RXQ16TY1
Q1,Q2 L1,L2,L3,N
FCU-1F-JPJ-07 BRC7EA619
31A 3ph
FXAQ25PVE
RXQ12TY1 F1,F2 L,N 0.4A 1ph
Q1,Q2 L1,L2,L3,N
24A 3ph
FCU-1F-JPJ-05 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JPJ-09 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JPJ-15 BRC7F635F
FXFQ40LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JPJ-17 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JPJ-16 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JPJ-01 BRC7F635F
FXFQ80LUV1
F1,F2 L,N 0.5A 1ph
FCU-1F-JPJ-02 BRC7F635F
FXFQ80LUV1
F1,F2 L,N 0.5A 1ph
FCU-1F-JPJ-06 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JPJ-04 BRC7F635F
FXFQ50LUV1
F1,F2 L,N 0.3A 1ph
FCU-1F-JPJ-08 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JPJ-10 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JPJ-13 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JPJ-11 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JPJ-12 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
FCU-1F-JPJ-14 BRC7EA619
FXAQ25PVE
F1,F2 L,N 0.4A 1ph
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 27
6. Device Options
6.1. Outdoor Unit Options
Model Description Used by
BHFP22P100 Outdoor unit multi connection piping kit CU-GF-K1RM [RXQ26TSY1] CU-GF-JPN [RXQ40TSY1] CU-1F-JI [RXQ30TSY1]
CU-1F-JPJ [RXQ28TSY1]
The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.
Page 28
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
SECTION 6
Manual of Main
Equipment
(Appendix)
OPERATION AND MAINTENANCE MANUAL
UTC KENINGAU ACMV O&M
PCVMY1321A
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
P15
Specifications
P37
Outdoor Unit
Combinations
P57
Option List
P59
Control Systems
P65
Air Treatment
Equipment Lineup
P79
Enhanced lineup Energy saving Air Handling
Unit
01 02
Next Generation VRV IV System
First launched in Japan in 1982, the Daikin VRV system INDEX
has been embraced by world markets for over 30 years.
Main Features
Now, Daikin proudly introduces the next generation VRV IV system.
P03
It now offers an enhanced lineup to meet an ever
Outdoor Unit
Lineup
wider variety of needs while improving energy savings,
comfort, and ease of installation. P13
Indoor Unit
Lineup
P15
Specifications
P37
Outdoor Unit
Combinations
P57
Option List
P59
Control Systems
P65
Air Treatment
Equipment Lineup
P79
Enhanced lineup Energy saving Air Handling
Unit
01 02
Excellent Operation Performance
Main Features
12 HP-50 HP with 4 new models lineup 3.5
Saving 3.25 *Cooling operation conditions: Indoor temp. of
3 27ºCDB, 19ºCWB, and outdoor temp. of 35ºCDB.
VRV 0 *12 HP of VRV IV improves more compact
6 HP 8 HP 10 HP * 12 HP 14 HP 16 HP 18 HP design and more saving space than VRV III
COP 3.94 COP 4.35 10%
Increase
Installation Space 1.66 m2 Installation Space 2.13 m2
20 HP Product Weight 490 kg Product Weight 555 kg
Ease of installation
Compact & lightweight design VRV 12 HP 12 HP
New series with compact & lightweight design Large airflow, high static pressure and Nighttime quiet operation function
Compact 18 HP-50 HP with 17 new models lineup quiet technology Outdoor PCB automatically memorises the time when
Design
Without increasing operation sound, advanced the peak outdoor temperature appears. It will enable
VRV analytic technologies are utilised to optimise fan quiet operation mode after 8 h*1, and return to normal
COP 3.94 COP 3.11 43% design and increase airflow rate and high external mode after it keeps for 9 h*2.
Installation Space 1.66 m2 Installation Space 0.95 m2 Decrease static pressure.
Streamlined air grille *1 8 h is the initial setting with 6 h or 10 h also available.
35% It promotes the discharge of *2 9 h is the initial setting with 8 h or 10 h also available.
Product Weight 490 kg Product Weight 320 kg Decrease
20 HP swirling airflow, further Peak in outdoor temperature
Capacity
reducing the Night mode
(%)
100
pressure loss.
50
Load
Lineup Streamlined scroll fan
(%)
The sharp edge of each fan blade 8 hrs 9 hrs
Mo/C New Lineup has a certain curvature, reducing
0
60
sound (dB)
Operating
both the vibration and the pressure 57
HP loss. 50
VRV IV
Enable night mode min. 40 dB(A)
High-COP Type Streamlined 40
8:00
8:00 12:00 16:00 20:00 0:00 4:00
scroll fan
Standard Type Notes: · This function is available in setting at site.
· The operating sound in quiet operation mode is the actual value
Illustrated measured by our company.
Space Saving Type fan · The relationship of outdoor temperature (load) and time shown
above is just an example.
03 04
VRT-Variable Refrigerant Temperature
State-of-the-art energy saving technology for VRV Fine control to match user preference available through mode selection
Basic mode is selected to maintain optimal comfort.
Customise your VRV for optimal annual efficiency VRT is selected to save energy and prevent excessive cooling.
The new VRV IV system now features VRT technology. Capacity priority Energy saving priority
VRT automatically adjusts refrigerant temperature to individual
Fixed Refrigerant Variable Refrigerant Temperature
building and climate requirement, thus further improving annual Temperature
Main Features
energy efficiency and maintaining comfort.
With this excellent technology, running costs are reduced.
How is energy reduced? Basic Mode Auto Mode High Sensible Mode
Fixed Te - Standard control Floating target Te depending on heat load Fixed target Te
Refrigerant cycle
During cooling, the refrigerant evaporating temperature (Te) (default setting on VRV IV)
Evaporator
Typical changes in evaporating temperature and COP depending on changing indoor load Powerful Mode Quick Mode Mild Mode Eco Mode
100% Reaction speed Very Fast Reaction speed Fast Reaction speed Medium Unable to change Te
Cooling load
& capacity
Capacity
changes Required capacity changes
to match
heat load as air conditioning load VRT offers quicker cool down
changes according to to shorten uncomfortable pull down time. • Can boost capacity above 100% if needed.
outdoor temperature. The refrigerant temperature can go lower in cooling than the set minimum.
25% Powerful • Gives priority to very fast reaction speed.
30
Powerful mode The refrigerant temperature goes down fast to keep the room setpoint
Quick stable.
Mild
temp. / Te(℃)
Automatic control to Very Fast Time The refrigerant temperature goes down gradually giving priority to the
adjust temperature Fast mode efficiency of the system instead of the reaction speed.
Medium
Low
Energy efficiency is 25
COP
improved without 20
sacrificing comfort. Av. min. temp.
Low
Without VRT
15
(Typical example)
0
20℃ 25℃ 30℃ 35℃ Outdoor
Mar. Jun. Sep. Dec.
Temp.
05 06
More Flexible System Design
Main Features
indoor units
a b c d
k VRV : VRV indoor unit
RA : Residential indoor unit e f g Max.
q BP : BP unit First indoor branch
BP o
40 m
165 m
Max. actual piping length
Max. Max.
h i m
First
indoor branch 50 m n BP 15 m
a f j
p
190 m
Max. equivalent piping length First outdoor branch b RA RA VRV
k
Single use Max. RA VRV
l 15 m
*The rest of indoor units are
1000 m
Max. total piping length the same as for single use. RA
a
f g h
When a mixed combination of VRV and residential indoor units is connected
b c d e i or when only residential indoor units are connected Actual
piping length Example
First indoor branch
90 m
Max. level difference
between the outdoor units 2 Refrigerant piping length 100 m a+b+c+g+k, a+b+c+d
and the indoor units r Max. Total piping length 250 m a+b+c+d+e+f+g+h+i+j+k
90 m 2 Maximum allowable If indoor unit capacity index < 60. 2 m–15 m
Max. Between BP unit
s piping length
30 m and indoor unit
If indoor unit capacity index is 60. 2 m–12 m h, i, j, k
30 m
Max. level difference 15 m higher
between the indoor units If indoor unit capacity index is 71. 2 m–8 m
than VRV
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a . Between the first indoor branch and the farthest BP unit or
50 m*1 b+c+g, b+c+d
between the first indoor branch and the farthest VRV indoor unit
Minimum allowable piping length Between outdoor unit and the first indoor branch 5m a
Actual Equivalent
piping length Example piping length
Refrigerant piping length 165 m a+f+g+h+i 190 m Level Difference Example
Maximum Total piping length 1000 m a+b+c+d+e+f+g+h+i — Between the indoor units 15 m l
allowable
Between the first indoor branch and the farthest indoor unit 90 m* 1
f+g+h+i — Between BP units 15 m m
piping length
Maximum allowable
Between the outdoor unit If the outdoor unit is above. 50 m n
Between the outdoor branch and the last outdoor unit 10 m k+p 13 m level difference
and the indoor unit If the outdoor unit is below. 40 m n
Level Between the outdoor unit and the BP unit 40 m o
Example
Difference
*1. When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased. Please refer to Engineering
Between the outdoor units (Multiple use) 5m q
Data Book for details.
Maximum Between the indoor units 30 m s
allowable
level difference Between the outdoor units If the outdoor unit is above. 90 m 2
r
and the indoor units If the outdoor unit is below. 90 m r
1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. Various conditions and requirements have to be met
to allow utilisation of 90 m piping length. Be sure to refer to the Engineering Data Book for details of these conditions and requirements. High external static pressure
2. When level differences are 50 m or more, the diameter of the main liquid piping size must be increased and connection ratio must be 80% to 130%. If the outdoor unit
is above the indoor unit, a dedicated setting on the outdoor unit is required. Refer to the Engineering Data Book and contact your local dealer for more information.
VRV IV outdoor unit has been achieved high
50%–200%
intensive arrangement
200%
200%
Single outdoor units
07 08
More Flexible System Design
Main Features
indoor units
a b c d
k VRV : VRV indoor unit
RA : Residential indoor unit e f g Max.
q BP : BP unit First indoor branch
BP o
40 m
165 m
Max. actual piping length
Max. Max.
h i m
First
indoor branch 50 m n BP 15 m
a f j
p
190 m
Max. equivalent piping length First outdoor branch b RA RA VRV
k
Single use Max. RA VRV
l 15 m
*The rest of indoor units are
1000 m
Max. total piping length the same as for single use. RA
a
f g h
When a mixed combination of VRV and residential indoor units is connected
b c d e i or when only residential indoor units are connected Actual
piping length Example
First indoor branch
90 m
Max. level difference
between the outdoor units 2 Refrigerant piping length 100 m a+b+c+g+k, a+b+c+d
and the indoor units r Max. Total piping length 250 m a+b+c+d+e+f+g+h+i+j+k
90 m 2 Maximum allowable If indoor unit capacity index < 60. 2 m–15 m
Max. Between BP unit
s piping length
30 m and indoor unit
If indoor unit capacity index is 60. 2 m–12 m h, i, j, k
30 m
Max. level difference 15 m higher
between the indoor units If indoor unit capacity index is 71. 2 m–8 m
than VRV
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a . Between the first indoor branch and the farthest BP unit or
50 m*1 b+c+g, b+c+d
between the first indoor branch and the farthest VRV indoor unit
Minimum allowable piping length Between outdoor unit and the first indoor branch 5m a
Actual Equivalent
piping length Example piping length
Refrigerant piping length 165 m a+f+g+h+i 190 m Level Difference Example
Maximum Total piping length 1000 m a+b+c+d+e+f+g+h+i — Between the indoor units 15 m l
allowable
Between the first indoor branch and the farthest indoor unit 90 m* 1
f+g+h+i — Between BP units 15 m m
piping length
Maximum allowable
Between the outdoor unit If the outdoor unit is above. 50 m n
Between the outdoor branch and the last outdoor unit 10 m k+p 13 m level difference
and the indoor unit If the outdoor unit is below. 40 m n
Level Between the outdoor unit and the BP unit 40 m o
Example
Difference
*1. When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased. Please refer to Engineering
Between the outdoor units (Multiple use) 5m q
Data Book for details.
Maximum Between the indoor units 30 m s
allowable
level difference Between the outdoor units If the outdoor unit is above. 90 m 2
r
and the indoor units If the outdoor unit is below. 90 m r
1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, depending on conditions. Various conditions and requirements have to be met
to allow utilisation of 90 m piping length. Be sure to refer to the Engineering Data Book for details of these conditions and requirements. High external static pressure
2. When level differences are 50 m or more, the diameter of the main liquid piping size must be increased and connection ratio must be 80% to 130%. If the outdoor unit
is above the indoor unit, a dedicated setting on the outdoor unit is required. Refer to the Engineering Data Book and contact your local dealer for more information.
VRV IV outdoor unit has been achieved high
50%–200%
intensive arrangement
200%
200%
Single outdoor units
07 08
Reliable and Stable System
Multiple advanced features ensuring more accurate test operation and stable system Outdoor unit sequencing technology
Main Features
Automatic check
Stage 1 Stage 2 Stage 3
Automatically checks the wirings between
outdoor units and indoor units to confirm Wiring
whether there is a defective wiring. check
Automatic Automatic
Confirms and corrects the actual piping sequencing sequencing
length. Piping
check Priority: Priority: Priority:
Automatically check whether the stop
valve in each outdoor unit is in normal
status to ensure the smooth operation of Stop valve
air conditioning system. check
VRV configurator
The VRV configurator is an advanced software solution
that allows for easy system configuration and
commissioning. Simplified
commissioning Compressor backup operation function
less time is required on the roof configuring the outdoor If malfunction occurs in a compressor...
unit. Emergency operation can be easily set and
enabled by the outdoor unit (for a single
multiple systems at different sites can be managed in outdoor unit system RXQ14-20TY1 models).
exactly the same way, thus offering simplified Retrieve initial
system settings
commissioning for key accounts.
09 10
Reliable and Stable System
Multiple advanced features ensuring more accurate test operation and stable system Outdoor unit sequencing technology
Main Features
Automatic check
Stage 1 Stage 2 Stage 3
Automatically checks the wirings between
outdoor units and indoor units to confirm Wiring
whether there is a defective wiring. check
Automatic Automatic
Confirms and corrects the actual piping sequencing sequencing
length. Piping
check Priority: Priority: Priority:
Automatically check whether the stop
valve in each outdoor unit is in normal
status to ensure the smooth operation of Stop valve
air conditioning system. check
VRV configurator
The VRV configurator is an advanced software solution
that allows for easy system configuration and
commissioning. Simplified
commissioning Compressor backup operation function
less time is required on the roof configuring the outdoor If malfunction occurs in a compressor...
unit. Emergency operation can be easily set and
enabled by the outdoor unit (for a single
multiple systems at different sites can be managed in outdoor unit system RXQ14-20TY1 models).
exactly the same way, thus offering simplified Retrieve initial
system settings
commissioning for key accounts.
09 10
Advanced Technologies Achieve Excellent Performance
Large capacity all DC inverter compressor in compact casing Various advanced control main PC board
Large capacity all DC inverter compressor using high tension strength material, SMT* packaging technology
realise 12 HP compressor using 8 HP casing. Computer control board surface Conventional
SMT packaging technology adopted by the
adopting SMT packaging computer control
whole computer control panel improves the
technology board surface
anti-clutter performance.
Protects your computer boards from the
Main Features
Development of high Small type high efficiency adverse effect of sandy and humid weather.
strength material concentrated winding motor
Gives 2.4 times tensile strength compare Distributed winding motor Concentrated winding motor
to conventional material (Current 8 HP compressor) (New 12 HP compressor)
New Material: 600 MPa
Conventional Material : 250 MPa Computer control board SMT
Increase compression chamber volume packaging
by using thin spiral design. material
Coil
end *SMT: Surface mounted technology
Small sizing coil end using concentrated Refrigerant cooling technology, ensures stability of PCB temperature
winding, reduce copper loss
(winding resistance).
Improved inner design to increase smooth airflow
Improve motor efficiency in low rpm Bell mouth
range (improve intermediate Downsize electric component, re-locate to dead
efficiency). space of bell mouth side to decrease airflow resistance.
As a result of having thinned a wall -
thickness of the scroll, compression
chamber volume increase 50%
Electric Component Space
20 HP
3 row with small pipe design, Improve reliability at high ambient temperature
increases heat transfer efficiency Heat exchanger Contribution of COP
area (cooling)
It is possible to cool the inverter power module stability even at high ambient temperature.
Fine Louvre Fin Waffle Fin 10 HP 13%UP 105.5% This helps to keep air-conditioning capacity and also reduces failure ratio.
Change fin shape from fine louvre to waffle fin.
Fin pitch can be reduced fin pitch from 2.0 mm to 1.4 mm, to realise unit 16 HP 24%UP 111.5%
efficiency which increased heat exchanger area.
11 12
Advanced Technologies Achieve Excellent Performance
Large capacity all DC inverter compressor in compact casing Various advanced control main PC board
Large capacity all DC inverter compressor using high tension strength material, SMT* packaging technology
realise 12 HP compressor using 8 HP casing. Computer control board surface Conventional
SMT packaging technology adopted by the
adopting SMT packaging computer control
whole computer control panel improves the
technology board surface
anti-clutter performance.
Protects your computer boards from the
Main Features
Development of high Small type high efficiency adverse effect of sandy and humid weather.
strength material concentrated winding motor
Gives 2.4 times tensile strength compare Distributed winding motor Concentrated winding motor
to conventional material (Current 8 HP compressor) (New 12 HP compressor)
New Material: 600 MPa
Conventional Material : 250 MPa Computer control board SMT
Increase compression chamber volume packaging
by using thin spiral design. material
Coil
end *SMT: Surface mounted technology
Small sizing coil end using concentrated Refrigerant cooling technology, ensures stability of PCB temperature
winding, reduce copper loss
(winding resistance).
Improved inner design to increase smooth airflow
Improve motor efficiency in low rpm Bell mouth
range (improve intermediate Downsize electric component, re-locate to dead
efficiency). space of bell mouth side to decrease airflow resistance.
As a result of having thinned a wall -
thickness of the scroll, compression
chamber volume increase 50%
Electric Component Space
20 HP
3 row with small pipe design, Improve reliability at high ambient temperature
increases heat transfer efficiency Heat exchanger Contribution of COP
area (cooling)
It is possible to cool the inverter power module stability even at high ambient temperature.
Fine Louvre Fin Waffle Fin 10 HP 13%UP 105.5% This helps to keep air-conditioning capacity and also reduces failure ratio.
Change fin shape from fine louvre to waffle fin.
Fin pitch can be reduced fin pitch from 2.0 mm to 1.4 mm, to realise unit 16 HP 24%UP 111.5%
efficiency which increased heat exchanger area.
11 12
Outdoor Unit Lineup
The outdoor unit capacity is up to 60 HP in increment of 2 HP. Lineup Mo/C New Lineup
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building. HP
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing
High-COP Type
the system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met. Standard Type
High-COP Type
Double Outdoor Units Triple Outdoor Units
Standard Type
Single Outdoor Units Double Outdoor Units Triple Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 18, 20 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP 42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
RXQ6TY1 RXQ14TY1 RXQ18TNY1 RXQ22TNY1 RXQ28TNY1 RXQ34TNY1 RXQ38TNY1 RXQ42TNY1 RXQ46TNY1 RXQ54TNY1
RXQ8TY1 RXQ16TY1 RXQ20TNY1 RXQ24TNY1 RXQ30TNY1 RXQ36TNY1 RXQ40TNY1 RXQ44TNY1 RXQ48TNY1 RXQ56TNY1
RXQ10TY1 RXQ26TNY1 RXQ32TNY1 RXQ50TNY1 RXQ58TNY1
RXQ12TY1 RXQ52TNY1 RXQ60TNY1
13 14
Outdoor Unit Lineup
The outdoor unit capacity is up to 60 HP in increment of 2 HP. Lineup Mo/C New Lineup
VRV IV outdoor unit offers a higher capacity of up to 60 HP, responding to the needs of large-sized building. HP
The single outdoor unit has only 2 different shapes and dimensions, not only simplifying the design process, but also bringing
High-COP Type
the system flexibility to a new level.
With the outdoor unit capacity increased in increment of 2 HP, customers' needs can be precisely met. Standard Type
High-COP Type
Double Outdoor Units Triple Outdoor Units
Standard Type
Single Outdoor Units Double Outdoor Units Triple Outdoor Units
6, 8, 10, 12 HP 14, 16 HP 18, 20 HP 22, 24, 26 HP 28, 30, 32 HP 34, 36 HP 38, 40 HP 42, 44 HP 46, 48, 50, 52, 54, 56, 58, 60 HP
RXQ6TY1 RXQ14TY1 RXQ18TNY1 RXQ22TNY1 RXQ28TNY1 RXQ34TNY1 RXQ38TNY1 RXQ42TNY1 RXQ46TNY1 RXQ54TNY1
RXQ8TY1 RXQ16TY1 RXQ20TNY1 RXQ24TNY1 RXQ30TNY1 RXQ36TNY1 RXQ40TNY1 RXQ44TNY1 RXQ48TNY1 RXQ56TNY1
RXQ10TY1 RXQ26TNY1 RXQ32TNY1 RXQ50TNY1 RXQ58TNY1
RXQ12TY1 RXQ52TNY1 RXQ60TNY1
13 14
Indoor Unit Lineup
VRV indoor units 18 types 86 models Residential indoor units with connection to BP units 8 types 22 models
25 35 50 60 71
Type Model Name Type Model Name
Rated Capacity 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW
Capacity Index 25 35 50 60 71
Ceiling Mounted
Cassette FFQ-BV1B
(Compact Multi Flow)
Ceiling Mounted
Built-in FBQ-BV1
FDKS-EAVMB
(700 mm width type)
Slim Ceiling
FTKS-DVM
FTKS-FVM
Note: BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20TY1) can be connected.
Max.
VRV indoor units only
64 indoor
units
BP unit
FXVQ-MY1
FXVQ-MY16 Max.
Residential indoor units VRV indoor units
32
(high static pressure type) indoor
units
15 16
Indoor Unit Lineup
VRV indoor units 18 types 86 models Residential indoor units with connection to BP units 8 types 22 models
25 35 50 60 71
Type Model Name Type Model Name
Rated Capacity 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW
Capacity Index 25 35 50 60 71
Ceiling Mounted
Cassette FFQ-BV1B
(Compact Multi Flow)
Ceiling Mounted
Built-in FBQ-BV1
FDKS-EAVMB
(700 mm width type)
Slim Ceiling
FTKS-DVM
FTKS-FVM
Note: BP units are necessary for residential indoor units. Only single outdoor unit (RXQ6-20TY1) can be connected.
Max.
VRV indoor units only
64 indoor
units
BP unit
FXVQ-MY1
FXVQ-MY16 Max.
Residential indoor units VRV indoor units
32
(high static pressure type) indoor
units
15 16
Indoor Unit Lineup
Daikin offers a wide range of indoor units includes both VRV and residential Ceiling Suspended Type Wall Mounted Type
models responding to variety of needs of our customers that require FXHQ-MAVE FXAQ-PVE
air-conditioning solutions.
FDKS-C(A)VMB
Thin, lightweight, and easy to install Slim design for flexible Flexible air discharge unit to fit Slim and smooth design suits your
in narrow ceiling spaces installation various forms of space shallow ceiling
Slim Ceiling Mounted Duct Ceiling Mounted Duct Wall Mounted Type
Type Type FTKS-DVM
FXDQ-PBVE(T) FXMQ-PVE
FTKS-BVMA
FXDQ-NBVE(T) FXMQ-MAVE
FTKS-FVM
Slim design, quietness and High external static pressure Stylish flat panel harmonises with
static pressure switching allows flexible installations your interior décor
17 18
Indoor Unit Lineup
Daikin offers a wide range of indoor units includes both VRV and residential Ceiling Suspended Type Wall Mounted Type
models responding to variety of needs of our customers that require FXHQ-MAVE FXAQ-PVE
air-conditioning solutions.
FDKS-C(A)VMB
Thin, lightweight, and easy to install Slim design for flexible Flexible air discharge unit to fit Slim and smooth design suits your
in narrow ceiling spaces installation various forms of space shallow ceiling
Slim Ceiling Mounted Duct Ceiling Mounted Duct Wall Mounted Type
Type Type FTKS-DVM
FXDQ-PBVE(T) FXMQ-PVE
FTKS-BVMA
FXDQ-NBVE(T) FXMQ-MAVE
FTKS-FVM
Slim design, quietness and High external static pressure Stylish flat panel harmonises with
static pressure switching allows flexible installations your interior décor
17 18
Indoor Unit Lineup
Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Cassette (Compact Multi Flow) Type
360° airflow improves temperature distribution Quiet, compact, and designed for user comfort
and offers a comfortable living environment. Dimensions correspond with 600 mm x 600 mm
architectural module ceiling design specifications.
The industry’s first* Round Flow Ceiling Mounted
Cassette type offers 360° airflow with improved
Comfortable airflow
Example of airflow patterns: All-round flow 4-way flow 3-way flow L-shaped 2-way flow
All-round flow is available, as well as 2-way to
4-way flows, so you can choose the most
suitable airflow pattern depending on location or L-shaped
room layout. 4-way flow 3-way flow 2-way flow
*For 3-way or 2-way flow installation, the sealing member for air discharge outlet
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet. (option) must be used to close each unused outlet.
21 22
Indoor Unit Lineup
Drain pan and air filter can be kept clean by mould-proof Concealed Floor Standing Type
polystyrene.
accessory.
* Applies also to Floor Standing type (FXLQ-MA).
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3
29 30
Specifications
Ceiling Mounted Cassette (Round Flow with Sensing) Type Ceiling Mounted Cassette (Compact Multi Flow) Type
MODEL FXFQ25SVM FXFQ32SVM FXFQ40SVM FXFQ50SVM FXFQ63SVM FXFQ80SVM FXFQ100SVM FXFQ125SVM MODEL FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ240MVE FXZQ50MVE
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
kcal/h 2,400 3,100 3,900 4,800 6,100 7,700 9,600 12,000 kcal/h 1,900 2,400 3,100 3,900 4,800
Cooling capacity Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 Cooling capacity Btu/h 7,500 9,600 12,300 15,400 19,100
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 kW 2.2 2.8 3.6 4.5 5.6
Power consumption Cooling kW 0.031 0.031 0.041 0.080 0.095 0.095 0.194 0.219 Power consumption Cooling kW 0.073 0.076 0.089 0.115
Casing Galvanised steel plate Casing Galvanised steel plate
m3/min 12.5/11.5/10.0 12.5/11.5/10.0 14.5/13.0/11.0 22.0/17.5/13.5 23.5/18.5/13.5 23.5/19.5/15.0 33.0/26.0/19.0 34.5/27.5/21.0 m3/min 9/7 9.5/7.5 11/8 14/10
Airflow rate (H/M/L) Airflow rate (H/L)
cfm 441/406/353 441/406/353 512/459/388 777/618/477 830/653/477 830/688/530 1,165/918/671 1,218/971/741 cfm 318/247 335/265 388/282 493/353
Sound level(H/M/L) dB(A) 30/28.5/27 30/28.5/27 31/29/27 36/32/28 38/33/28 38/35/31 44/38/32 45/40/35 Sound level 230 V, 50 Hz-
dB(A) 30/25-32/26 32/26-34/28 36/28-37/29 41/33-42/35
Dimensions (H×W×D) mm 246×840×840 288×840×840 (H/L) 240 V,50Hz
Specifications
Ceiling Mounted Cassette (Round Flow) Type 4-way Flow Ceiling Suspended Type
MODEL FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1 FXFQ63LUV1 FXFQ80LUV1 FXFQ100LUV1FXFQ125LUV1 MODEL FXUQ71AVEB FXUQ100AVEB
Power supply 1-phase, 220-240 V, 50 Hz Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz
kcal/h 2,400 3,100 3,900 4,800 6,100 7,700 9,600 12,000 kcal/h 6,900 9,600
Cooling capacity Btu/h 9,600 12,300 15,400 19,100 24,200 30,700 38,200 47,800 Cooling capacity Btu/h 27,300 38,200
kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 kW 8.0 11.2
Power consumption Cooling kW 0.033 0.033 0.047 0.052 0.066 0.093 0.187 0.209 Power consumption Cooling kW 0.090 0.200
Casing Galvanised steel plate Casing colour Fresh white
m3/min 13/11.5/10 13/11.5/10 15/13/11 16/13.5/11 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5 m3/min 22.5/19.5/16 31/26/21
Airflow rate (HH/H/L) Airflow rate (H/M/L)
cfm 459/406/353 459/406/353 530/459/388 565/477/388 671/583/477 742/636/530 1,130/918/706 1,165/989/794 cfm 794/688/565 1,094/918/741
Sound level (HH/H/L) dB(A) 30/28.5/27 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34 Sound level (H/M/L) dB(A) 40/38/36 47/44/40
Dimensions (H×W×D) mm 246X840X840 288X840X840 Dimensions (H×W×D) mm 198×950×950
Machine weight kg 19.5 22 25 Machine weight kg 26 27
Liquid (Flare) 6.4 9.5 Liquid (Flare) 9.5
Piping Piping
Gas (Flare) mm 12.7 15.9 Gas (Flare) mm 15.9
connections connections
Drain VP25 (External Dia, 32/Internal Dia, 25) Drain VP20 (External Dia, 26/Internal Dia, 20)
Model BYCP125K-W1
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Panel Colour Fresh white • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(Option) Dimensions(H×W×D) mm 50X950X950 (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
Weight kg 5.5 During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5m, Level difference: 0m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5m downward from the unit centre.
37 38
Specifications
MODEL FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE MODEL FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY1 FXVQ500MY16
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz Power supply 3-phase 4-wire system, 380-415 V, 50 Hz
kcal/h 1,900 2,400 3,100 3,900 4,800 6,100 kcal/h 12,000 19,300 24,100 38,700 48,200
Cooling capacity Btu/h 7,500 9,600 12,300 15,400 19,100 24,200 Cooling capacity Btu/h 47,800 76,400 95,500 154,000 191,000
kW 2.2 2.8 3.6 4.5 5.6 7.1 kW 14.0 22.4 28.0 45.0 56.0
Power consumption Cooling kW 0.019 0.028 0.030 0.020 0.033 0.050 Power consumption Cooling kW 0.59 1.41 1.68 3.97 2.62 5.02
Casing White (3.0Y8.5/0.5) Casing colour Ivory white (5Y7.5/1)
m3/min 7.5/4.5 8/5 8.5/5.5 12/9 15/12 19/14 Dimensions (HXWXD) mm 1,670×750×510 1,670×950×510 1,670×1,170×510 1,900×1,170×720 1,900×1,470×720
Airflow rate (H/L)
cfm 265/159 282/177 300/194 424/318 530/424 671/494 Machine weight kg 115 140 165 225 270 295
Sound level (H/L) dB(A) 35/31 36/31 38/31 39/34 42/37 47/41 Sound level *1 dB(A) 52 55 59 64 61 67
Dimensions (H×W×D) mm 290×795×238 290×795×238 290×795×238 290×1,050×238 290×1,050×238 290×1,050×238 Liquid mm 9.5 (Brazing) 12.7 (Brazing) 15.9 (Brazing)
Piping
Machine weight kg 11.0 11.0 11.0 14.0 14.0 14.0 connections Gas mm 15.9 (Brazing) 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing)
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5 Drain mm Rp1 (PS 1B internal thread)
Piping Air filter Type Long-life filter (anti-mould resin net)
Gas (Flare) mm 12.7 12.7 12.7 12.7 12.7 15.9
connections
Drain VP13 (External Dia, 18/Internal Dia, 13) Motor output kW 0.75 1.5 1.5 3.7 3.7 5.5
Airflow rate m3/min 43 69 86 134 165 172
Fan External static
Pa 150 210 270 380 125 480
pressure *2
Drive system Belt drive system
Floor Standing Type/Concealed Floor Standing Type Notes: Specifications are based on the following conditions;
Specifications
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
*1 Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
MODEL *2 The value is the external static pressure with standard pulley.
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
kcal/h 1,900 2,400 3,100 3,900 4,800 6,100
FXLQ
Cooling capacity Btu/h 7,500 9,600 12,300 15,400 19,100 24,200
kW 2.2 2.8 3.6 4.5 5.6 7.1
Power consumption Cooling kW 0.049 0.049 0.090 0.090 0.110 0.110
Casing FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate
m3/min 7/6 7/6 8/6 11/8.5 14/11 16/12
FXNQ Airflow rate (H/L)
cfm 247/212 247/212 282/212 388/300 494/388 565/424
Sound level (H/L) dB(A) 35/32 35/32 35/32 38/33 39/34 40/35
Dimensions FXLQ 600×1,000×222 600×1,000×222 600×1,140×222 600×1,140×222 600×1,420×222 600×1,420×222
mm
(H×W×D) FXNQ 610×930×220 610×930×220 610×1,070×220 610×1,070×220 610×1,350×220 610×1,350×220
FXLQ 25.0 25.0 30.0 30.0 36.0 36.0
Machine weight kg
FXNQ 19.0 19.0 23.0 23.0 27.0 27.0
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5
Piping
Gas (Flare) mm 12.7 12.7 12.7 12.7 12.7 15.9
connections
Drain VP13 (External Dia, 18/Internal Dia, 13)
• Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
• Sound level: (FXAQ-P) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
(FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
43 44
Specifications
Outdoor Units
MODEL RXQ42THY1(E) RXQ44THY1(E) RXQ46THY1(E) RXQ48THY1(E) RXQ50THY1(E) MODEL RXQ6TY1(E) RXQ8TY1(E) RXQ10TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ16TY1(E)
RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ16TY1(E)
Combination units RXQ14TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ16TY1(E) RXQ16TY1(E) Combination units – – – – – –
RXQ14TY1(E) RXQ16TY1(E) RXQ16TY1(E) RXQ16TY1(E) RXQ18TY1(E)
Power supply 3-phase 4-wire system, 380–415 V, 50 Hz Power supply 3-phase 4-wire system, 380–415 V, 50 Hz
kcal/h 103,000 108,000 112,000 116,000 120,000 kcal/h 13,800 19,300 24,100 28,800 34,400 38,700
Cooling capacity Btu/h 409,000 427,000 444,000 461,000 478,000 Cooling capacity Btu/h 54,600 76,400 95,500 114,000 136,000 154,000
kW 120 125 130 135 140 kW 16.0 22.4 28.0 33.5 40.0 45.0
Power consumption kW 32.7 34.8 36.9 39.0 41.4 Power consumption kW 3.63 5.21 7.29 9.01 10.9 13.0
Specifications
Capacity control % 4-100 3-100 3-100 3-100 3-100 Capacity control % 20-100 20-100 16-100 15-100 11-100 10-100
Casing colour Ivory white (5Y7.5/1) Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Type Hermetically Sealed Scroll Type
mm
19.1 19.1 19.1 19.1 19.1 mm
9.5 12.7
Liquid Liquid
Piping (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) Piping (Brazing) (Brazing)
connections connections
mm
41.3 41.3 41.3 41.3 41.3 mm
19.1 22.2 28.6
Gas Gas
(Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing)
Note: 1. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric Note: 1. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are
subject to salt damage and atmospheric pollution. Please contact Daikin for more information. subject to salt damage and atmospheric pollution. Please contact Daikin for more information.
2. Specifications are based on the following conditions; 2. Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. •Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. •Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
49 50
Specifications
Outdoor Units
Standard Type
MODEL RXQ18TNY1(E) RXQ20TNY1(E) RXQ22TNY1(E) RXQ24TNY1(E) RXQ26TNY1(E) RXQ28TNY1(E) RXQ30TNY1(E) RXQ32TNY1(E) RXQ34TNY1(E) RXQ36TNY1(E) RXQ38TNY1(E) RXQ40TNY1(E) RXQ42TNY1(E) RXQ44TNY1(E) RXQ46TNY1(E)
RXQ8TY1(E) RXQ8TY1(E) RXQ8TY1(E) RXQ10TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ10TY1(E) RXQ12TY1(E) RXQ8TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ14TY1(E)
Combination units RXQ10TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ18TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ14TY1(E)
– – – – – – – – RXQ12TY1(E) RXQ12TY1(E) RXQ18TY1(E) RXQ16TY1(E) RXQ16TY1(E) RXQ16TY1(E) RXQ18TY1(E)
Power supply 3-phase 4-wire system, 380–415 V, 50 Hz 3-phase 4-wire system, 380–415 V, 50 Hz
kcal/h 43,300 48,100 53,700 58,500 63,200 68,800 73,100 77,400 81,700 86,900 91,200 96,300 102,000 107,000 112,000
Cooling capacity Btu/h 172,000 191,000 213,000 232,000 251,000 273,000 290,000 307,000 324,000 345,000 362,000 382,000 406,000 423,000 444,000
kW 50.4 55.9 62.4 68.0 73.5 80.0 85.0 90.0 95.0 101 106 112 119 124 130
Power consumption kW 12.5 14.2 16.1 18.2 19.9 21.8 23.9 26.3 25.3 27.0 29.6 31.0 32.9 35.0 37.2
Specifications
Capacity control % 8-100 8-100 7-100 6-100 6-100 5-100 5-100 5-100 5-100 5-100 4-100 4-100 4-100 4-100 3-100
Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
(3.4X1)+ (4.1X1)+ (5.2X1)+ (5.2X1)+(2.9X1)+ (5.2X1)+(3.6X1)+ (2.9X1)+(3.3X1)+
Compressor (3.4X1)+ (3.4X1)+ (2.9X1)+(3.3X1)+ (2.9X1)+(3.3X1)+ (2.9X1)+(3.3X1)+ (4.1X1)+(5.2X1)+ (5.2X1)+(5.2X1)+ (3.4X1)+(5.2X1)+ (5.2X1)+(5.2X1)+
Motor output kW (2.9X1)+ (2.9X1)+ (2.9X1)+ (3.3X1)+(3.6X1)+ (3.7X1)+(3.6X1)+ (2.9X1)+(3.3X1)+
(4.1X1) (5.2X1) (2.9X1)+(3.3X1) (3.6X1)+(3.7X1) (4.4X1)+(4.0X1) (5.2X1) (5.2X1) (4.4X1)+(4.0X1) (3.6X1)+(3.7X1)
(3.3X1) (3.3X1) (3.3X1) (3.7X1) (3.7X1) (4.4X1)+(4.0X1)
Airflow rate m³/min 157+165 157+178 157+233 165+233 178+233 233+233 233+233 233+233 165+178+178 178+178+178 157+178+233 178+178+233 178+233+233 178+233+233 233+233+233
(1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X1,240X765)+
(1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+
Dimensions (H×W×D) mm (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+
(1,657X930X765) (1,657X930X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765)
(1,657X930X765) (1,657X930X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765)
Machine weight kg 185+195 185+195 185+285 195+285 195+285 285+285 285+285 285+285 195+195+195 195+195+195 185+195+285 195+195+285 195+285+285 195+285+285 285+285+285
Sound level dB(A) 60 61 61 62 63 63 64 64 63 64 64 65 65 65 66
Operation range ºCDB -5 to 43 -5 to 43
Type R-410A R-410A
Refrigerant
Charge kg 5.9+6.0 5.9+6.3 5.9+10.3 6.0+10.3 6.3+10.3 10.3+10.3 10.3+10.4 10.3+10.5 6.0+6.3+6.3 6.3+6.3+6.3 5.9+6.3+10.5 6.3+6.3+10.4 6.3+10.3+10.4 6.3+10.4+10.4 10.3+10.3+10.5
Liquid mm
15.9 15.9 15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
Piping (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing)
connections
mm
28.6 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3
Gas
(Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing)
Note: 1. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are
subject to salt damage and atmospheric pollution. Please contact Daikin for more information.
2. Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
51 52
Specifications
Outdoor Units
Standard Type
MODEL RXQ18TNY1(E) RXQ20TNY1(E) RXQ22TNY1(E) RXQ24TNY1(E) RXQ26TNY1(E) RXQ28TNY1(E) RXQ30TNY1(E) RXQ32TNY1(E) RXQ34TNY1(E) RXQ36TNY1(E) RXQ38TNY1(E) RXQ40TNY1(E) RXQ42TNY1(E) RXQ44TNY1(E) RXQ46TNY1(E)
RXQ8TY1(E) RXQ8TY1(E) RXQ8TY1(E) RXQ10TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ10TY1(E) RXQ12TY1(E) RXQ8TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ14TY1(E)
Combination units RXQ10TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ18TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ12TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ14TY1(E)
– – – – – – – – RXQ12TY1(E) RXQ12TY1(E) RXQ18TY1(E) RXQ16TY1(E) RXQ16TY1(E) RXQ16TY1(E) RXQ18TY1(E)
Power supply 3-phase 4-wire system, 380–415 V, 50 Hz 3-phase 4-wire system, 380–415 V, 50 Hz
kcal/h 43,300 48,100 53,700 58,500 63,200 68,800 73,100 77,400 81,700 86,900 91,200 96,300 102,000 107,000 112,000
Cooling capacity Btu/h 172,000 191,000 213,000 232,000 251,000 273,000 290,000 307,000 324,000 345,000 362,000 382,000 406,000 423,000 444,000
kW 50.4 55.9 62.4 68.0 73.5 80.0 85.0 90.0 95.0 101 106 112 119 124 130
Power consumption kW 12.5 14.2 16.1 18.2 19.9 21.8 23.9 26.3 25.3 27.0 29.6 31.0 32.9 35.0 37.2
Specifications
Capacity control % 8-100 8-100 7-100 6-100 6-100 5-100 5-100 5-100 5-100 5-100 4-100 4-100 4-100 4-100 3-100
Casing colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
(3.4X1)+ (4.1X1)+ (5.2X1)+ (5.2X1)+(2.9X1)+ (5.2X1)+(3.6X1)+ (2.9X1)+(3.3X1)+
Compressor (3.4X1)+ (3.4X1)+ (2.9X1)+(3.3X1)+ (2.9X1)+(3.3X1)+ (2.9X1)+(3.3X1)+ (4.1X1)+(5.2X1)+ (5.2X1)+(5.2X1)+ (3.4X1)+(5.2X1)+ (5.2X1)+(5.2X1)+
Motor output kW (2.9X1)+ (2.9X1)+ (2.9X1)+ (3.3X1)+(3.6X1)+ (3.7X1)+(3.6X1)+ (2.9X1)+(3.3X1)+
(4.1X1) (5.2X1) (2.9X1)+(3.3X1) (3.6X1)+(3.7X1) (4.4X1)+(4.0X1) (5.2X1) (5.2X1) (4.4X1)+(4.0X1) (3.6X1)+(3.7X1)
(3.3X1) (3.3X1) (3.3X1) (3.7X1) (3.7X1) (4.4X1)+(4.0X1)
Airflow rate m³/min 157+165 157+178 157+233 165+233 178+233 233+233 233+233 233+233 165+178+178 178+178+178 157+178+233 178+178+233 178+233+233 178+233+233 233+233+233
(1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X1,240X765)+
(1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+
Dimensions (H×W×D) mm (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X930X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+ (1,657X1,240X765)+
(1,657X930X765) (1,657X930X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765)
(1,657X930X765) (1,657X930X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765) (1,657X1,240X765)
Machine weight kg 185+195 185+195 185+285 195+285 195+285 285+285 285+285 285+285 195+195+195 195+195+195 185+195+285 195+195+285 195+285+285 195+285+285 285+285+285
Sound level dB(A) 60 61 61 62 63 63 64 64 63 64 64 65 65 65 66
Operation range ºCDB -5 to 43 -5 to 43
Type R-410A R-410A
Refrigerant
Charge kg 5.9+6.0 5.9+6.3 5.9+10.3 6.0+10.3 6.3+10.3 10.3+10.3 10.3+10.4 10.3+10.5 6.0+6.3+6.3 6.3+6.3+6.3 5.9+6.3+10.5 6.3+6.3+10.4 6.3+10.3+10.4 6.3+10.4+10.4 10.3+10.3+10.5
Liquid mm
15.9 15.9 15.9 15.9 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
Piping (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing)
connections
mm
28.6 28.6 28.6 34.9 34.9 34.9 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 41.3
Gas
(Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing) (Brazing)
Note: 1. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are
subject to salt damage and atmospheric pollution. Please contact Daikin for more information.
2. Specifications are based on the following conditions;
•Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
51 52
Specifications
Outdoor Units
MODEL RXQ48TNY1(E) RXQ50TNY1(E) RXQ52TNY1(E) RXQ54TNY1(E) RXQ56TNY1(E) RXQ58TNY1(E) RXQ60TNY1(E) MODEL RXQ18TY1(E) RXQ20TY1(E) RXQ22TSY1(E) RXQ24TSY1(E)
RXQ14TY1(E) RXQ14TY1(E) RXQ16TY1(E) RXQ18TY1(E) RXQ18TY1(E) RXQ18TY1(E) RXQ20TY1(E) RXQ10TY1(E) RXQ12TY1(E)
Combination units RXQ16TY1(E) RXQ18TY1(E) RXQ18TY1(E) RXQ18TY1(E) RXQ18TY1(E) RXQ20TY1(E) RXQ20TY1(E) Combination units – – RXQ12TY1(E) RXQ12TY1(E)
RXQ18TY1(E) RXQ18TY1(E) RXQ18TY1(E) RXQ18TY1(E) RXQ20TY1(E) RXQ20TY1(E) RXQ20TY1(E) – –
Power supply 3-phase 4-wire system, 380–415 V, 50 Hz Power supply 3-phase 4-wire system, 380–415 V, 50 Hz
kcal/h 116,000 120,000 125,000 129,000 134,000 139,000 144,000 kcal/h 43,000 48,200 52,900 57,600
Cooling capacity Btu/h 461,000 478,000 495,000 512,000 532,000 553,000 573,000 Cooling capacity Btu/h 171,000 191,000 210,000 229,000
kW 135 140 145 150 156 162 168 kW 50.0 56.0 61.5 67.0
Power consumption kW 39.3 41.7 43.8 46.2 48.8 51.4 54.0 Power consumption kW 15.4 18.0 16.3 18.0
Specifications
Capacity control % 3-100 3-100 3-100 3-100 3-100 3-100 3-100 Capacity control % 10-100 8-100 8-100 8-100
Casing colour Ivory white (5Y7.5/1) Casing colour Ivory white (5Y7.5/1)
Type Hermetically Sealed Scroll Type Type Hermetically Sealed Scroll Type
53 54
Outdoor Unit Combinations
50 1,250 RXQ50TH RXQ16Tx 2 + RXQ18T 625 to 1,625 (1,625) 44 1,100 RXQ44TN RXQ12T + RXQ16T × 2 550 to 1,430 (1,430)
46 1,150 RXQ46TN RXQ14T × 2 + RXQ18T 575 to 1,495 (1,495)
Note: *1 The outdoor unit multi connection piping kit (separately sold) is required for multiple connection. BHFP22P151
*2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double outdoor 48 1,200 RXQ48TN RXQ14T + RXQ16T + RXQ18T 600 to 1,560 (1,560)
units, and 130% for triple outdoor units. Refer to page 7 for notes on connection capacity of indoor units. 50 1,250 RXQ50TN RXQ14T + RXQ18T × 2 625 to 1,625 (1,625) 64 (64)
52 1,300 RXQ52TN RXQ16T + RXQ18T × 2 650 to 1,690 (1,690)
57 58
Option List
Ceiling Mounted Cassette (Round Flow With Sensing) Type Ceiling Mounted Cassette (Double Flow) Type
No. Type FXFQ25S FXFQ32S FXFQ40S FXFQ50S FXFQ63S FXFQ80S FXFQ100S FXFQ125S No. Type FXCQ20M
Item FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M
1 Decoration panel BYCQ125B-W1 Item FXCQ25M
2 Sealing material of air discharge outlet KDBHQ55B140 1 Decoration panel BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
3 Panel spacer KDBP55H160FA High efficiency filter 65% 1 KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160
High efficiency filter unit 65% KAFP556B80 KAFP556B160 High efficiency filter 90% 1 KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160
2 Filter related
High efficiency filter unit 90% KAFP557B80 KAFP557B160 Filter chamber bottom suction KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160 Long life replacement filter KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 Note: 1 Filter chamber is required if installing high efficiency filter.
4 Filter related
Filter chamber KDDFP55B160
Long life replacement filter KAFP551K160
Ultra long-life filter KAFP55B160 Ceiling Mounted Cassette Corner Type
Replacement ultra long-life filter KAFP55H160H
Without T joint-pipe and fan KDDQ55B140
Chamber type No. Type FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA
5 Fresh air intake kit With T joint-pipe without fan KDDP55B160K Item
Direct installation type KDDP55X160 Decoration panel BYK45FJW1 BYK71FJW1
1 Panel related
6 Branch duct chamber KDJP55B80 KDJP55B160 Panel spacer KPBJ52F56W KPBJ52F80W
7 Insulation kit for high humidity KDTP55K80 KDTP55K160 Long life replacement filter KAFJ521F56 KAFJ521F80
Air inlet and air
Air discharge grille K-HV7AW K-HV9AW
2 discharge outlet
Air discharge blind panel KDBJ52F56W KDBJ52F80W
related
Flexible duct (with shutter) KFDJ52FA56 KFDJ52FA80
Ceiling Mounted Cassette (Round Flow) Type
No. Type FXFQ25LU FXFQ32LU FXFQ40LU FXFQ50LU FXFQ63LU FXFQ80LU FXFQ100LU FXFQ125LU Slim Ceiling Mounted Duct Type (700 mm width type)
Item
1 Decoration panel BYCP125K-W1
2 Sealing material of air discharge outlet KDBH55K160F No. Item Type FXDQ20PB FXDQ25PB FXDQ32PB
3 Panel spacer KDBP55H160FA 1 Insulation kit for high humidity KDT25N32
High efficiency filter unit 65% KAFP556B80 KAFP556B160
High efficiency filter unit 90% KAFP557B80 KAFP557B160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
4 Filter related
Filter chamber KDDFP55B160
Long life replacement filter KAFP551K160 No. Type
Item FXDQ40NB FXDQ50NB FXDQ63NB
Ultra long-life filter KAFP55B160
Replacement ultra long-life filter KAFP55H160H 1 Insulation kit for high humidity KDT25N50 KDT25N63
Without T joint-pipe and fan KDDP55B160
Chamber type
5 Fresh air intake kit With T joint-pipe without fan KDDP55B160K
Direct installation type KDDP55X160 Ceiling Mounted Duct Type
6 Branch duct chamber KDJP55B80 KDJP55B160
7 Chamber connection kit KKSJ55KA160
8 Insulation kit for high humidity KDTP55K80 KDTP55K160 No. Type FXMQ20P FXMQ50P FXMQ100P FXMQ200MA
FXMQ25P FXMQ40P FXMQ63P FXMQ125P
Item FXMQ32P FXMQ80P FXMQ140P FXMQ250MA
Option List
1 Drain pump kit — KDU30L250VE
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280
Ceiling Mounted Cassette (Compact Multi Flow) Type 2 High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280
3 Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
No. Type FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280
Item 4
1 Decoration panel BYFQ60B8W1 5 Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
2 Sealing material of air discharge outlet KDBH44BA60 White KTBJ25K36W KTB25KA56W KTB25KA80W KTB25KA160W
3 Panel spacer KDBQ44BA60A
6 Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F —
4 Replacement long-life filter KAFQ441BA60
5 Fresh air intake kit Direct installation type KDDQ44XA60 Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
7 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
03
59 04
60
Option List
Ceiling Mounted Cassette (Round Flow With Sensing) Type Ceiling Mounted Cassette (Double Flow) Type
No. Type FXFQ25S FXFQ32S FXFQ40S FXFQ50S FXFQ63S FXFQ80S FXFQ100S FXFQ125S No. Type FXCQ20M
Item FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M
1 Decoration panel BYCQ125B-W1 Item FXCQ25M
2 Sealing material of air discharge outlet KDBHQ55B140 1 Decoration panel BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
3 Panel spacer KDBP55H160FA High efficiency filter 65% 1 KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160
High efficiency filter unit 65% KAFP556B80 KAFP556B160 High efficiency filter 90% 1 KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160
2 Filter related
High efficiency filter unit 90% KAFP557B80 KAFP557B160 Filter chamber bottom suction KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160 Long life replacement filter KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 Note: 1 Filter chamber is required if installing high efficiency filter.
4 Filter related
Filter chamber KDDFP55B160
Long life replacement filter KAFP551K160
Ultra long-life filter KAFP55B160 Ceiling Mounted Cassette Corner Type
Replacement ultra long-life filter KAFP55H160H
Without T joint-pipe and fan KDDQ55B140
Chamber type No. Type FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA
5 Fresh air intake kit With T joint-pipe without fan KDDP55B160K Item
Direct installation type KDDP55X160 Decoration panel BYK45FJW1 BYK71FJW1
1 Panel related
6 Branch duct chamber KDJP55B80 KDJP55B160 Panel spacer KPBJ52F56W KPBJ52F80W
7 Insulation kit for high humidity KDTP55K80 KDTP55K160 Long life replacement filter KAFJ521F56 KAFJ521F80
Air inlet and air
Air discharge grille K-HV7AW K-HV9AW
2 discharge outlet
Air discharge blind panel KDBJ52F56W KDBJ52F80W
related
Flexible duct (with shutter) KFDJ52FA56 KFDJ52FA80
Ceiling Mounted Cassette (Round Flow) Type
No. Type FXFQ25LU FXFQ32LU FXFQ40LU FXFQ50LU FXFQ63LU FXFQ80LU FXFQ100LU FXFQ125LU Slim Ceiling Mounted Duct Type (700 mm width type)
Item
1 Decoration panel BYCP125K-W1
2 Sealing material of air discharge outlet KDBH55K160F No. Item Type FXDQ20PB FXDQ25PB FXDQ32PB
3 Panel spacer KDBP55H160FA 1 Insulation kit for high humidity KDT25N32
High efficiency filter unit 65% KAFP556B80 KAFP556B160
High efficiency filter unit 90% KAFP557B80 KAFP557B160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
4 Filter related
Filter chamber KDDFP55B160
Long life replacement filter KAFP551K160 No. Type
Item FXDQ40NB FXDQ50NB FXDQ63NB
Ultra long-life filter KAFP55B160
Replacement ultra long-life filter KAFP55H160H 1 Insulation kit for high humidity KDT25N50 KDT25N63
Without T joint-pipe and fan KDDP55B160
Chamber type
5 Fresh air intake kit With T joint-pipe without fan KDDP55B160K
Direct installation type KDDP55X160 Ceiling Mounted Duct Type
6 Branch duct chamber KDJP55B80 KDJP55B160
7 Chamber connection kit KKSJ55KA160
8 Insulation kit for high humidity KDTP55K80 KDTP55K160 No. Type FXMQ20P FXMQ50P FXMQ100P FXMQ200MA
FXMQ25P FXMQ40P FXMQ63P FXMQ125P
Item FXMQ32P FXMQ80P FXMQ140P FXMQ250MA
Option List
1 Drain pump kit — KDU30L250VE
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280
Ceiling Mounted Cassette (Compact Multi Flow) Type 2 High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280
3 Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
No. Type FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280
Item 4
1 Decoration panel BYFQ60B8W1 5 Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
2 Sealing material of air discharge outlet KDBH44BA60 White KTBJ25K36W KTB25KA56W KTB25KA80W KTB25KA160W
3 Panel spacer KDBQ44BA60A
6 Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F —
4 Replacement long-life filter KAFQ441BA60
5 Fresh air intake kit Direct installation type KDDQ44XA60 Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
7 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
03
59 04
60
Option List
Wall Mounted Type Ceiling Mounted Cassette (Compact Multi Flow) Type
Option List
No. Item
1 Titanium apatite photocatalytic air-purifying filter KAF970A46 KAF952A42 KAF952B42
Residential Indoor Units with connection to BP units Note: Filter is a standard accessory. It should be replaced approximately 3 years.
Ceiling Mounted Cassette Type BP Units for connection to residential indoor units
Notes: *1. With a suction chamber. Fresh air intake is from 2 holes on the sides of the connection chamber. (This method should be selected if a wireless remote controller is used.)
*2. Without a suction chamber. Fresh air intake is from 2 holes on the connection chamber via a T-shaped pipe connection. (A wireless remote controller cannot be used in this case.)
*3. Without a suction chamber. Fresh air intake is directly from a hole on the main unit.
03
61 04
62
Option List
Outdoor Units
High-COP Type
RXQ12THY1(E) RXQ46TNY1(E)
Optional Accessories RXQ14THY1(E) RXQ48TNY1(E)
RXQ16THY1(E) RXQ50TNY1(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H Optional Accessories RXQ34TNY1(E) RXQ38TNY1(E) RXQ42TNY1(E) RXQ52TNY1(E)
Distributive REFNET header
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) RXQ36TNY1(E) RXQ40TNY1(E) RXQ44TNY1(E) RXQ54TNY1(E)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T RXQ56TNY1(E)
Outdoor unit multi connection piping kit BKG26A12×2
RXQ58TNY1(E)
RXQ60TNY1(E)
Left BKG26A20L×2
Protection
Right BKG26A20R×2 REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
net Distributive
Back BKG26A12B×2 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
RXQ24THY1(E) Pipe size reducer KHRP26M73TP, KHPR26M73HP
RXQ18THY1(E) RXQ26THY1(E) Outdoor unit multi connection piping kit BHFP22P151
Optional Accessories RXQ20THY1(E) RXQ28THY1(E) RXQ34THY1(E) Left BKG26A20L×3 BKG26A20L×3 BKG26A20L×3 BKG26A20L×3
RXQ22THY1(E) RXQ30THY1(E) Protection Right BKG26A20R×3 BKG26A20R×3 BKG26A20R×3 BKG26A20R×3
RXQ32THY1(E) net
Back BKG26A12B×3 BKG26A12B×2 BKG26A12B×1 BKG26A20B×3
KHRP26M22H BKG26A20B×1 BKG26A20B×2
(Max. 4 branch),
KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
REFNET header (Max. 8 branch), (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive
piping KHRP26M72H
(Max. 8 branch)
KHRP26A22T,
Space Saving Type
REFNET joint KHRP26A33T, KHRP26A72T KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer − KHRP26M73TP, KHPR26M73HP Optional Accessories RXQ18TY1(E)
Outdoor unit multi connection piping kit BHFP22P151
RXQ20TY1(E)
Left BKG26A20L×3 BKG26A20L×3 REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H
Disinbutive
Protection Right BKG26A20R×3 BKG26A20R×3 piping (Max.4 branch) (Max.8 branch) (Max.8 branch)
net REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
Back BKG26A12B×3 BKG26A12B×2
BKG26A20B×1 Left BKG26A20L
Protection
Right BKG26A20R
net
RXQ42THY1(E) Back BKG26A20B
RXQ44THY1(E)
Optional Accessories RXQ36THY1(E) RXQ38THY1(E) RXQ40THY1(E) RXQ46THY1(E)
RXQ48THY1(E) RXQ26TSY1(E) RXQ34TSY1(E)
RXQ50THY1(E) Optional Accessories RXQ28TSY1(E) RXQ36TSY1(E)
RXQ22TSY1(E) RXQ24TSY1(E) RXQ30TSY1(E) RXQ38TSY1(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive REFNET header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch) RXQ32TSY1(E) RXQ40TSY1(E)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T KHRP26M22H
Pipe size reducer KHRP26M73TP, KHPR26M73HP (Max.4 branch),
Outdoor unit multi connection piping kit BHFP22P151 REFNET header KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
(Max.8 branch), (Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
Left BKG26A20L×3 BKG26A20L×3 BKG26A20L×3 BKG26A20L×3 Disinbutive KHRP26M72H
Protection Right BKG26A20R×3 BKG26A20R×3 BKG26A20R×3 BKG26A20R×3 piping (Max.8 branch),
net BKG26A12B×1 BKG26A12B×2 BKG26A12B×1
Back BKG26A20B×3 KHRP26A22T,
BKG26A20B×2 BKG26A20B×1 BKG26A20B×2 REFNET joint KHRP26M33T, KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
KHRP26M72T,
Pipe size reducer — KHRP26M73TP, KHRP26M73HP
Standard Type Outdoor unit connection piping kit BHFP22P100
Left BKG26A20L×2 BKG26A20L×2 BKG26A20L×2
RXQ6TY1(E)
Option List
Protection Right BKG26A20R×2 BKG26A20R×2 BKG26A20R×2
RXQ14TY1(E)
Optional Accessories RXQ8TY1(E) RXQ12TY1(E) RXQ16TY1(E)
net
BKG26A12B×1 BKG26A20B×2
Back BKG26A12B×2
RXQ10TY1(E) BKG26A20B×1
KHRP26M22H,
REFNET header (Max. 4 branch) KHRP26M22H, KHRP26M33H, KHRP26M72H
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Distributive KHRP26M33H RXQ46TSY1(E)
piping (Max. 8 branch)
Optional Accessories RXQ42TSY1(E) RXQ48TSY1(E)
KHRP26A22T
RXQ44TSY1(E) RXQ50TSY1(E)
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
KHRP26A33T
Disinbutive REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Left BKG26A20L BKG26A20L (Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
Protection piping
net Right BKG26A20R BKG26A20R REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Back BKG26A12B BKG26A20B
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit connection piping kit BHFP22P151
RXQ18TNY1(E) RXQ24TNY1(E) RXQ28TNY1(E) Left BKG26A20L×3 BKG26A20L×3
Optional Accessories RXQ22TNY1(E) RXQ30TNY1(E)
RXQ20TNY1(E) RXQ26TNY1(E) RXQ32TNY1(E) Protection Right BKG26A20R×3 BKG26A20R×3
net BKG26A12B×2 BKG26A12B×1
KHRP26M22H, KHRP26M33H, KHRP26M22H, KHRP26M33H, Back BKG26A20B×1 BKG26A20B×2
REFNET header (Max. 4 branch) (Max. 8 branch) (Max. 4 branch) (Max. 8 branch)
Distributive KHRP26M72H KHRP26M72H, KHRP26M73H
piping (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
03
63 04
64
Option List
Outdoor Units
High-COP Type
RXQ12THY1(E) RXQ46TNY1(E)
Optional Accessories RXQ14THY1(E) RXQ48TNY1(E)
RXQ16THY1(E) RXQ50TNY1(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H Optional Accessories RXQ34TNY1(E) RXQ38TNY1(E) RXQ42TNY1(E) RXQ52TNY1(E)
Distributive REFNET header
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) RXQ36TNY1(E) RXQ40TNY1(E) RXQ44TNY1(E) RXQ54TNY1(E)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T RXQ56TNY1(E)
Outdoor unit multi connection piping kit BKG26A12×2
RXQ58TNY1(E)
RXQ60TNY1(E)
Left BKG26A20L×2
Protection
Right BKG26A20R×2 REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
net Distributive
Back BKG26A12B×2 (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
RXQ24THY1(E) Pipe size reducer KHRP26M73TP, KHPR26M73HP
RXQ18THY1(E) RXQ26THY1(E) Outdoor unit multi connection piping kit BHFP22P151
Optional Accessories RXQ20THY1(E) RXQ28THY1(E) RXQ34THY1(E) Left BKG26A20L×3 BKG26A20L×3 BKG26A20L×3 BKG26A20L×3
RXQ22THY1(E) RXQ30THY1(E) Protection Right BKG26A20R×3 BKG26A20R×3 BKG26A20R×3 BKG26A20R×3
RXQ32THY1(E) net
Back BKG26A12B×3 BKG26A12B×2 BKG26A12B×1 BKG26A20B×3
KHRP26M22H BKG26A20B×1 BKG26A20B×2
(Max. 4 branch),
KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
REFNET header (Max. 8 branch), (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Distributive
piping KHRP26M72H
(Max. 8 branch)
KHRP26A22T,
Space Saving Type
REFNET joint KHRP26A33T, KHRP26A72T KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer − KHRP26M73TP, KHPR26M73HP Optional Accessories RXQ18TY1(E)
Outdoor unit multi connection piping kit BHFP22P151
RXQ20TY1(E)
Left BKG26A20L×3 BKG26A20L×3 REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H
Disinbutive
Protection Right BKG26A20R×3 BKG26A20R×3 piping (Max.4 branch) (Max.8 branch) (Max.8 branch)
net REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
Back BKG26A12B×3 BKG26A12B×2
BKG26A20B×1 Left BKG26A20L
Protection
Right BKG26A20R
net
RXQ42THY1(E) Back BKG26A20B
RXQ44THY1(E)
Optional Accessories RXQ36THY1(E) RXQ38THY1(E) RXQ40THY1(E) RXQ46THY1(E)
RXQ48THY1(E) RXQ26TSY1(E) RXQ34TSY1(E)
RXQ50THY1(E) Optional Accessories RXQ28TSY1(E) RXQ36TSY1(E)
RXQ22TSY1(E) RXQ24TSY1(E) RXQ30TSY1(E) RXQ38TSY1(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive REFNET header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch) RXQ32TSY1(E) RXQ40TSY1(E)
piping
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T KHRP26M22H
Pipe size reducer KHRP26M73TP, KHPR26M73HP (Max.4 branch),
Outdoor unit multi connection piping kit BHFP22P151 REFNET header KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
(Max.8 branch), (Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
Left BKG26A20L×3 BKG26A20L×3 BKG26A20L×3 BKG26A20L×3 Disinbutive KHRP26M72H
Protection Right BKG26A20R×3 BKG26A20R×3 BKG26A20R×3 BKG26A20R×3 piping (Max.8 branch),
net BKG26A12B×1 BKG26A12B×2 BKG26A12B×1
Back BKG26A20B×3 KHRP26A22T,
BKG26A20B×2 BKG26A20B×1 BKG26A20B×2 REFNET joint KHRP26M33T, KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
KHRP26M72T,
Pipe size reducer — KHRP26M73TP, KHRP26M73HP
Standard Type Outdoor unit connection piping kit BHFP22P100
Left BKG26A20L×2 BKG26A20L×2 BKG26A20L×2
RXQ6TY1(E)
Option List
Protection Right BKG26A20R×2 BKG26A20R×2 BKG26A20R×2
RXQ14TY1(E)
Optional Accessories RXQ8TY1(E) RXQ12TY1(E) RXQ16TY1(E)
net
BKG26A12B×1 BKG26A20B×2
Back BKG26A12B×2
RXQ10TY1(E) BKG26A20B×1
KHRP26M22H,
REFNET header (Max. 4 branch) KHRP26M22H, KHRP26M33H, KHRP26M72H
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Distributive KHRP26M33H RXQ46TSY1(E)
piping (Max. 8 branch)
Optional Accessories RXQ42TSY1(E) RXQ48TSY1(E)
KHRP26A22T
RXQ44TSY1(E) RXQ50TSY1(E)
REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T
KHRP26A33T
Disinbutive REFNET header KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Left BKG26A20L BKG26A20L (Max.4 branch) (Max.8 branch) (Max.8 branch) (Max.8 branch)
Protection piping
net Right BKG26A20R BKG26A20R REFNET joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Back BKG26A12B BKG26A20B
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit connection piping kit BHFP22P151
RXQ18TNY1(E) RXQ24TNY1(E) RXQ28TNY1(E) Left BKG26A20L×3 BKG26A20L×3
Optional Accessories RXQ22TNY1(E) RXQ30TNY1(E)
RXQ20TNY1(E) RXQ26TNY1(E) RXQ32TNY1(E) Protection Right BKG26A20R×3 BKG26A20R×3
net BKG26A12B×2 BKG26A12B×1
KHRP26M22H, KHRP26M33H, KHRP26M22H, KHRP26M33H, Back BKG26A20B×1 BKG26A20B×2
REFNET header (Max. 4 branch) (Max. 8 branch) (Max. 4 branch) (Max. 8 branch)
Distributive KHRP26M72H KHRP26M72H, KHRP26M73H
piping (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
03
63 04
64
Control Systems
Wireless remote
controller
* Wireless remote controller and signal receiver unit are sold as a set.
* Refer to page 77 for the name of each model. Signal receiver unit
(Installed type)
The wired remote controller supports a wide range of control functions Simplified remote controller (Option)
Control of Cool/Heat In all the series of VRV, Cool/Heat changeover in the same refrigerant circuit can be changed by the remote ● The remote controller
changeover controller of the indoor unit.
has centralised its
frequently used operation
selectors and switches
Group control
(on/off, operation mode,
Equipment One remote controller can control the
Outdoor operation of max.16 indoor units at the temperature setting and
unit
related to the
central control
same time. airflow volume), making
Concealed type
(For hotel use)
itself suitable for use in
(BRC3A61) hotel rooms or
Exposed type conference rooms.
(BRC2C51) The concealed type remote controller smartly fits into a
● The exposed type night table or console panel in a hotel room.
Indoor unit remote controller is fitted
Remote controller
Remote controller
with a thermostat sensor.
Remote
controller
Control Systems
(Wired remote controller)
Ventilator (BRC1E62)
Remote controller Remote
controller Remote
Remote controller controller Remote Wired remote controller
controller (BRC1C62)
03
67 04
68
Air Handling Unit
Integrate your air handling unit in a total solution for large size spaces such as
factories and large stores.
System overview
93 94
PCVMY1321A
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
MODEL English
RXYQ72TTJU RXYQ72TYDN
RXYQ96TTJU RXYQ96TYDN
RXYQ120TTJU RXYQ120TYDN Français
RXYQ144TTJU RXYQ144TYDN
RXYQ168TTJU RXYQ168TYDN
RXYQ192TTJU RXYQ192TYDN
RXYQ216TTJU RXYQ216TYDN
Español
RXYQ240TTJU RXYQ240TYDN
RXYQ264TTJU RXYQ264TYDN
RXYQ288TTJU RXYQ288TYDN
RXYQ312TTJU RXYQ312TYDN
RXYQ336TTJU RXYQ336TYDN
RXYQ360TTJU RXYQ360TYDN
RXYQ384TTJU RXYQ384TYDN
RXYQ408TTJU RXYQ408TYDN
3P362438-2C
i 3P362438-2C English
3P362438-2C English ii
Contents
Safety Considerations.................................................[i] [ii] [iii]
Specifications........................................................................ 2
What to do before Operation................................................. 3
Operation Range................................................................... 3
Operation Procedure............................................................. 4
Cool/Heat Selector :
Name and Function of Each Switch and Display................... 4
Basic Operation..................................................................... 5
Maintenance.......................................................................... 6
Reference Information........................................................... 7
Optimum Operation............................................................... 8
Seasonal Maintenance.......................................................... 8
Following Symptoms are not Air Conditioner Troubles.......... 9
Trouble Shooting.................................................................. 11
After-Sales Service and Warranty....................................... 12
3P362438-2C English 1
2 3P362438-2C English
If your installation has a customized control system, ask your local dealer for the operation that corresponds to your system.
Operation Range
COOLING HEATING
Outdoor temperature 23°–110°FDB 0°–60°FWB
Indoor temperature 57°–77°FWB 59°–80°FDB
Indoor humidity 80% —
Note
•• Cooling operation:
If the air conditioner is operated continuously while the indoor temperature is 70°F or below and the humidity is 80% or over, the interiors
of the indoor units may cause icing and water leakage may result.
•• Heating operation:
The air conditioner may stop operating for the protection of the machine if the outdoor temperature is 70°F or over.
3P362438-2C English 3
Cool/Heat Selector :
Name and Function of Each Switch and Display
<Cool/Heat selector> 1. Fan only/air conditioning selector switch
•• Set the switch to “ ” for fan only operation or to “ ” for
heating or cooling operation.
Heating operation
4 3P362438-2C English
When the master indoor The other indoor units in the system can be set to
unit is set to
Cool Dry Heat Fan
Cool mode
Dry mode
Heat mode
Fan mode
Auto mode (Cooling operation)
Auto mode (Heating operation)
Precautions for Selecting the COOL / HEAT Changeover Master Indoor Unit
•• The COOL/HEAT changeover master must be set for a single indoor unit in the following applications
Indoor unit
3P362438-2C English 5
1 Cool Set to
Cool 74F
•• When it is time to clean or replace the filter, one of the following messages will appear
on the bottom of the basic screen.
“Time to clean filter”
Time to clean filter “Time to clean filter & element”
“Time to clean element”
2 •• Reset the filter indicator when the filter or element is cleaned or replaced.
•• Press Menu/OK button.
The main menu screen will appear.
3 Main Menu
Reset Filter Indicator
Air Flow Direction
Ventilation
Schedule
Off Timer
1/2
•• Press buttons to select Reset Filter Indicator on the main menu
screen and press Menu/OK button.
Celsius / Fahrenheit
Setting
Cool Set to
Cool 74F •• The display shown in illustration 1 will disappear from the basic screen
when the filter sign is reset.
6 3P362438-2C English
1 Cool Set to
Cool 74F
•• If an error occurs, either one of the following items will flash in the basic screen.
“Error: Press Menu button”
* The operation lamp will flash.
Operation
Error : Press Menu button “Warning: Press Menu button” lamp
* The operation lamp will not flash.
•• Press Menu/OK button.
2 Error code AI
Contact Info
0123-456-7890
Precautions for Group Control System or Two Remote Controller Control System
This system provides two other control systems beside individual control (one remote controller controls one indoor unit) system.
Confirm which type of your unit is the following system.
•• Group control system
One remote controller controls up to 16 indoor units. All indoor units are equally set.
•• Two remote controller control system
Two remote controllers control one indoor unit (in case of group control system, one group of indoor units). The unit is
individually operated.
Note
•• Contact your local dealer in case of changing the combination or setting of group control and two remote controller control systems.
3P362438-2C English 7
Seasonal Maintenance
Caution
•• Do not touch the air inlets or aluminum fins of the outside or indoor units.
Touching them may result in injury.
•• Do not wash the outside or indoor units with water.
An electric shock or fire may result.
•• Watch your steps at the time of air filter cleaning etc.
If the scaffold is unstable, you may fall or topple down, thus causing injury.
•• Be sure to stop the operation, and turn the breaker off before cleaning.
This may cause electric shock and injury.
•• Consult with the dealer for cleaning the interior of the indoor units.
Incorrect cleaning may damage the plastic parts and cause failures, such as water leakage, and an electric shock may result.
8 3P362438-2C English
stops sometimes
It
•• The remote controller display reads “U4” or “U5” and stops but then restarts after a few minutes.
This is because the remote control is intercepting noise from electrical appliances other than the air conditioner, and this prevents communication
between the units, causing them to stop.
Operation automatically restarts when the noise goes away.
Cool/heat cannot be changed over
MASTER
•• When the display shows “ CONTROLLED ”.
It shows that this is a slave remote controller.
Refer to “Setting the Cool/Heat Change over Master”.
MASTER
•• When the Cool/Heat selector switch is installed and the display shows “ CONTROLLED ”.
This is because COOL/HEAT changeover is controlled by the Cool/Heat selector. Ask your local dealer where the remote control switch is
installed.
Fan operation is possible, but cooling and heating do not work
•• Immediately after the power is turned on.
The micro computer is getting ready to operate. Wait 10 minutes.
The fan speed does not correspond to the setting
•• The fan speed does not change even if the fan speed control button is pressed.
During heating operation, when the room temperature reaches the set temperature, the outside unit goes off and the indoor unit changes to
whisper the fan speed.
This is to prevent cold air blowing directly on occupants of the room.
The fan speed will not change even if the button is pressed, when another indoor unit is in heating operation.
The fan direction does not correspond to the setting
•• The fan direction does not correspond to the remote control display.
The fan direction does not swing.
This is because the unit is being controlled by the micro computer.
3P362438-2C English 9
Noise of air conditioners
Indoor unit
•• A “zeen” sound is heard immediately after the power supply is turned on.
The electronic expansion valve inside an indoor unit starts working and makes the noise. Its volume will reduce in about 1 minute.
•• A continuous low hissing sound like flowing water is heard when the system is in cooling operation or at a stop.
When the drain pump (an optional accessory) is in operation, this noise is heard.
•• A squeaking sound is heard when the system stops after heating operation.
Expansion and contraction of plastic parts caused by temperature change make this noise.
•• A low sound like dripping water is heard while the indoor unit is stopped.
When the other indoor unit is in operation, this noise is heard. In order to prevent oil and refrigerant from remaining in the system, a small amount
of refrigerant is kept flowing.
Outside unit
•• When the tone of operating noise changes.
This noise is caused by the change of frequency.
Indoor unit, outside unit
•• A continuous low hissing sound is heard when the system is in cooling or defrost operation.
This is the sound of refrigerant gas flowing through both indoor and outside units.
•• A hissing sound which is heard at the start or immediately after stopping operation or defrost operation.
This is the noise of refrigerant caused by flow stop or flow change.
Dust comes out of the unit
•• When the unit is used after stopping for a long time.
This is because dust has gotten into the unit.
The units can give off odors
•• During operation.
The unit can absorb the smell of rooms, furniture, cigarettes, etc., and then emit it again.
The outside unit fan does not rotate
•• During operation.
The speed of the fan is controlled in order to optimize product operation.
The compressor or fan in the outside unit does not stop
•• This is to prevent oil and refrigerant from remaining in the compressor. The unit will stop after 5 to 10 minutes.
The inside of outside unit is warm even when the unit has stopped
•• This is because the crankcase heater is warming the compressor so that the compressor can start smoothly.
10 3P362438-2C English
MODELS
Ceiling-mounted Cassette type (Multi flow model)
FXFQ12MVJU
FXFQ18MVJU
FXFQ24MVJU
FXFQ30MVJU
FXFQ36MVJU
2 English
• Never touch the internal parts of the controller. • Dismantling of the unit, treatment of the refrigerant,
Do not remove the front panel. Some parts inside are dan- oil and eventual other parts, should be done in accor-
gerous to touch, and a machine trouble may happen. For dance with the relevant local and national regulations.
checking and adjusting the internal parts, contact your • Do not dry the filter by exposing it to direct sunlight or
dealer. warming it using fire, etc. Doing so can result in the
• Avoid placing the controller in a spot splashed with deformation of the filter.
water.
Water coming inside the machine may cause an electric
leak or may damage the internal electronic parts.
• Do not operate the air conditioner when using a room
fumigation - type insecticide.
Failure to observe could cause the chemicals to become
deposited in the unit, which could endanger the health of
those who are hypersensitive to chemicals.
• Do not put a finger, a rod or other objects into the air
inlet or outlet. As the fan is rotating at high speed, it
will cause injury.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or
wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that
children will not play with them. If children play with a plas-
tic bag which was not torn apart, they face the risk of suf-
focation.
• Do not turn off the power immediately after stopping
operation.
Always wait at least five minutes before turning off the
power. Otherwise, water leakage and trouble may occur.
• The appliance is not intended for use by young chil-
dren or infirm persons without supervision.
• The remote controller should be installed in such
away that children cannot play with it.
NOTE
• Never touch the air outlet or the horizontal blades
while the swing flap is in operation.
Fingers may become caught or the unit may break down.
• Never press the button of the remote controller with a
hard, pointed object.
The remote controller may be damaged.
• Never pull or twist the electric wire of the remote
controller.
It may cause the unit to malfunction.
• Do not place appliances which produce open fire in
places exposed to the air flow from the unit or under
the indoor unit. It may cause incomplete combustion
or deformation of the unit due to the heat.
• Arrange the drain hose to ensure smooth drainage.
Incomplete drainage may cause wetting of the build-
ing, furniture etc.
• Do not place the controller exposed to direct sunlight.
The LCD display may get discolored, failing to display the
data.
• Do not wipe the controller operation panel with ben-
zine, thinner, chemical dustcloth, etc.
The panel may get discolored or the coating peeled off. If
it is heavily dirty, soak a cloth in water-diluted neutral
detergent, squeeze it well and wipe the panel clean. And
wipe it with another dry cloth.
English 3
MAINTENANCE 2. Remove the air filter.
Pull the air filter clips downward at an angle to detach the
HOW TO CLEAN THE AIR FILTER filter.
Clean the air filter when the display shows “ ” (TIME TO
CLEAN AIR FILTER).
Increase the frequency of cleaning if the unit is installed in a
room where the air is extremely contaminated.
(As a yardstick for regulating yourself, consider cleaning the
filter once a half year.)
If the dirt becomes impossible to clean, change the air filter.
(Air filter for exchange is optional)
4 English
3. Clean the air filter. HOW TO CLEAN THE SUCTION GRILLE
Use vacuum cleaner A) or wash the air filter with water
1. Open the suction grille.
B).
Slide the latches (× 2) and carefully lower the grille.
A) Using a vacuum cleaner
(Do the same procedure for closing.)
(Do not use air of 120°F or higher)
NOTE
5. Shut the suction grille.
Refer to item No. 1. • When badly soiled, spray with a typical kitchen cleanser
and let sit for about 10 minutes. Then, wash with water.
6. Press the FILTER SIGN RESET BUTTON on the
remote controller. 5. Reattach the suction grille.
The display “ ” (TIME TO CLEAN AIR FILTER) Refer to item No. 3.
vanishes. 6. Fix the air filter.
(For details, see the operation manual for the outdoor Refer to HOW TO CLEAN THE AIR FILTER.
unit.)
7. Close the suction grille.
NOTE Refer to item No. 1.
• Do not remove the air filter except when cleaning.
Unnecessary handling may damage the filter.
HOW TO CLEAN AIR OUTLET AND OUTSIDE
PANELS
• Clean with soft cloth.
• When it is difficult to remove stains, use water or neutral
detergent.
NOTE
• Do not use gasoline, benzene, thinner, polishing powder,
liquid insecticide. It may cause discoloring or warping.
• Do not let the indoor unit get wet. It may cause an electric
shock or a fire.
English 5
MEMO
6
Daikin US Corporation
375 Park Avenue, Suite 3308
New York, NY 10152
��
www.daikinac.com
info@daikinac.com
��
OPERATION MANUAL
MODELS
Wall-mounted type
FXAQ07PVJU
FXAQ09PVJU
English
FXAQ12PVJU
FXAQ18PVJU
FXAQ24PVJU
Français
Español
• Safely dispose of the packing materials. Packing materi- • Never touch the internal parts of the controller. Do not
als, such as nails and other metal or wooden parts, may remove the front panel because some parts inside are
cause stabs or other injuries. dangerous to touch. To check and adjust internal parts,
contact your dealer.
• Tear apart and throw away plastic packaging bags so
that children will not play with them. • Be sure to establish a ground.
Children playing with plastic bags face the danger of Do not ground the unit to a utility pipe, arrester, or tele-
death by suffocation. phone ground. Incomplete grounding may cause electri-
cal shock, or fire. A high surge current from lightning or
other sources may cause damage to the air conditioner.
• Be sure to install a ground fault circuit interrupter.
Failure to install a ground fault circuit interrupter may
result in electric shocks, or fire.
1 English
01_EN_3PN07520-6E.fm Page 2 Thursday, December 8, 2011 5:11 PM
English 2
01_EN_3PN07520-6E.fm Page 3 Thursday, December 8, 2011 5:11 PM
Refrigerant pipe
Transmission wiring
Drain pipe
Remote controller
Air outlet
Ground wire
Louver Conducts electricity from the
(horizontal air outlet direction unit into the ground to prevent
adjustment flaps) electric shock.
Vertical flaps
(vertical air outlet direction adjustment flaps)
3 English
01_EN_3PN07520-6E.fm Page 4 Thursday, December 8, 2011 5:11 PM
2. Pullout the air filter. • Do not let the indoor unit get wet. It may cause an electric
Push up the tab in the center of the air filter slightly then pull shock or a fire.
out in a downward direction. • Do not scrub firmly when washing the blade with water.
The surface sealing may peel off.
• Do not use water or air of 120°F or higher for cleaning air fil-
ters and outside panels.
• Make sure the front panel is solidly in place.
NOTE
• Do not wash the air filter with hot water of more than 120°F,
as doing so may result in discoloration and/or deformation.
• Do not expose it to fire, as doing so may result in burning.
NOTE
• Hold the front panel firmly so that it does not fall.
• Do not use gasoline, benzene, thinner, polishing powder, liq-
uid insecticide. It may cause discoloring or warping.
English 4
00_CV_3PN07520-6E.fm Page 2 Friday, December 2, 2011 11:05 AM
MODEL
BRC7C812
TEMP
3
H M L H M L TIME 11
DOWN 10
F F
UP UP
6
DOWN
FAN
13
FAN
4 RESERVE CANCEL
9
hr. hr.
TIMER 12
2 hr. hr.
MODE 15
SWING 14
5
16
TEST TEST
7 TEST 17
Fig. 1-2
24
21 20 19
25
18
Fig. 2
23 22 COOL/HEAT CHANGEOVER
REMOTE CONTROL SWITCH
Fig. 1-3
3
CONTENTS • Do not touch the switch with wet fingers.
Touching a switch with wet fingers can cause electric shock.
ILLUSTRATIONS .....................................................................3 • Do not operate the air conditioner with a wet hand.
1. SAFETY CONSIDERATIONS ..........................................4 Otherwise, you could receive an electric shock.
2. NAMES AND FUNCTIONS OF THE OPERATING
SECTION ........................................................................4 CAUTION
3. HANDLING FOR WIRELESS REMOTE
• Do not use the air conditioner for other purposes.
CONTROLLER.................................................................5 In order to avoid any quality deterioration, do not use the unit
4. OPERATION PROCEDURE ............................................6 for cooling precision instruments, food, plants, animals or
5. NOT MALFUNCTION OF THE AIR CONDITIONER .......9 works of art.
6. HOW TO DIAGNOSE TROUBLE SPOTS......................10 • To avoid oxygen deficiency, ventilate the room suffi-
ciently if equipment with burner is used together with
the air conditioner.
• Do not allow a child to mount on the unit or avoid placing
any object on it.
1. SAFETY CONSIDERATIONS Falling or tumbling may result in injury.
Please read these “SAFETY CONSIDERATIONS” carefully • Do not let children play on and around the unit.
before installing air conditioning equipment and be sure to If they touch the unit carelessly, it may result in injury.
install it correctly. After completing the installation, make sure • Do not place a flower vase and anything containing
that the unit operates properly during the start-up operation. water.
Please instruct the customer on how to operate the unit and Water may enter the unit, causing an electric shock or fire.
keep it maintained. • Do not operate the air conditioner when using a room
Also, inform customers that they should store this operation fumigation - type insecticide.
manual along with the installation manual for future reference. Failure to observe could cause the chemicals to become
This air conditioner comes under the term “appliances not deposited in the unit, which could endanger the health of
accessible to the general public”. those who are hypersensitive to chemicals.
Meaning of warning, caution and note symbols. • Never use flammable spray such as hair spray, lacquer
WARNING ......... Indication a potentially hazardous situa- or paint near the unit.
tion which, if not avoided, could result in It may cause a fire.
death or serious injury.
CAUTION .......... Indication a potentially hazardous situa-
tion which, if not avoided, may result in
minor or moderate injury. It may also be 2. NAMES AND FUNCTIONS OF THE
sued to alert against unsafe practices.
OPERATING SECTION (Fig. 1-1~3, 2)
NOTE..................Indication situation that may result in equip-
ment or property-damage-only accidents.
DISPLAY “ ” “ I ” (SIGNAL TRANSMISSION)
Keep these warning sheets handy so that you can refer to 1
them if needed. This lights up when a signal is being transmitted.
Also, if this equipment is transferred to a new user, make sure to DISPLAY “ ”“ ”“ ”“ ”“ ”
hand over this operation manual to the new user. (OPERATION MODE)
2
This display shows the current OPERATION MODE. For
WARNING VRV system, “ ” is not installed.
• It is not good for your health to expose your body to the
H M L
air flow for a long time. DISPLAY “ ” (SET TEMPERATURE)
3 F
• In order to avoid electric shock, fire or injury, or if you
This display shows the set temperature.
detect any abnormality such as smell of fire, turn off
power and call your dealer for instructions. DISPLAY “ hr. hr. ” (PROGRAMMED TIME)
• Ask your dealer for installation of the air conditioner. 4 This display shows PROGRAMMED TIME of the sys-
Incomplete installation performed by yourself may result in a tem start or stop.
water leakage, electric shock, and fire.
• Ask your dealer for improvement, repair, and maintenance. DISPLAY “ ” (AIR FLOW FLAP)
5
Incomplete improvement, repair, and maintenance may Refer to page 7.
result in a water leakage, electric shock, and fire.
DISPLAY “ ” “ ” (FAN SPEED)
• Do not put a finger, a rod or other objects into the air inlet 6
This display shows the set fan speed.
or outlet. As the fan is rotating at high speed, it will
cause injury. DISPLAY “ TEST ” (INSPECTION/ TEST OPERA-
• Ask your dealer to move and reinstall the air conditioner. TION)
7
Incomplete installation may result in a water leakage, electric When the INSPECTION/TEST OPERATION BUTTON
shock, and fire. is pressed, the display shows the system mode is in.
4
ON/OFF BUTTON NOTE
8 Press the button and the system will start. Press the • For the sake of explanation, all indications are shown on the
button again and the system will stop. display in Fig. 1-1 contrary to actual running situations.
FAN SPEED CONTROL BUTTON • Fig. 1-2 shows the remote controller with the front cover
9 Press this button to select the fan speed, HIGH or LOW, opened.
of your choice. • Fig. 2 shows this remote controller can be used in conjunc-
TEMPERATURE SETTING BUTTON tion with the one provided with the VRV system.
Use this button for SETTING TEMPERATURE. • If the air filter cleaning time indicator lamp lights up, clean
10 the air filter as explained in the operation manual provided
(Operates with the front cover of the remote controller
closed.) with the indoor unit.
After cleaning and reinstalling the air filter, press the filter
PROGRAMMING TIMER BUTTON
sign reset button on the remote controller. The air filter
11 Use this button for programming “START and/or STOP” cleaning time indicator lamp on the receiver will go out.
time. (Operates with the front cover of the remote con-
• The DEFROST lamp will flash when the power is turned on.
troller opened.)
This is not a malfunction.
TIMER MODE START/STOP BUTTON
12
Refer to page 8.
TIMER RESERVE/CANCEL BUTTON
13
Refer to page 8. 3. HANDLING FOR WIRELESS REMOTE
AIR FLOW DIRECTION ADJUST BUTTON CONTROLLER
14
Refer to page 7. • Precautions in handling remote controller
OPERATION MODE SELECTOR BUTTON • Direct the transmitting part of the remote controller to
15
Press this button to select OPERATION MODE. the receiving part of the air conditioner.
FILTER SIGN RESET BUTTON If something blocks the transmitting and receiving path of the
indoor unit and the remote controller as curtains, it will not
16 Refer to the section of MAINTENANCE in the operation
operate.
manual attached to the indoor unit.
INSPECTION/TEST OPERATION BUTTON
17 This button is pressed for inspection or test operation.
Do not use for normal operation.
EMERGENCY OPERATION SWITCH
18 This switch is readily used if the remote controller does
not work.
2 short beeps from the
RECEIVER receiver indicates that
19
This receives the signals from the remote controller. the transmission is
properly done.
OPERATING INDICATOR LAMP (Red)
20 This lamp stays lit while the air conditioner runs.
It flashes when the unit is in trouble. • Transmitting distance is approximately 23 ft..
TIMER INDICATOR LAMP (Green) • Do not drop or get it wet.
21 It may be damaged.
This lamp stays lit while the timer is set.
AIR FILTER CLEANING TIME INDICATOR LAMP (Red) • Never press the button of the remote controller with a
22 hard, pointed object.
Lights up when it is time to clean the air filter.
The remote controller may be damaged.
DEFROST LAMP (Orange)
• Installation site
23 Lights up when the defrosting operation has started. It is possible that signals will not be received in rooms that
(For cooling only type this lamp does not turn on.) have electronic fluorescent lighting. Please consult with the
FAN/AIR CONDITIONING SELECTOR SWITCH salesman before buying new fluorescent lights.
24 If the remote controller operated some other electrical appa-
Set the switch to “ ” (FAN) for FAN and “ ” (A/C)
ratus, move that machine away or consult your dealer.
for HEAT or COOL.
Placing the remote controller in the remote controller
COOL/HEAT CHANGEOVER SWITCH
holder
25 Set the switch to “ ” (COOL) for COOL and “ ” Install the remote controller holder to a wall or a pillar with the
(HEAT) for HEAT. attached screw. (Make sure it transmits.)
5
〈〈FOR SYSTEMS WITHOUT COOL/HEAT
Placing the remote Removing the CHANGEOVER REMOTE CONTROL SWITCH
controller remote controller
(Fig. 1-1~2 on page 3)〉〉
Slide from above. Pull it upward.
2 ON/OFF
When to change batteries
Under normal use, batteries last about 1 year. However, change Press ON/OFF button.
them whenever the indoor unit doesn’t respond or responds OPERATING INDICATOR lamp lights up or goes off and the
slowly to commands, or if the display becomes dark. system starts or stops OPERATION.
CAUTION NOTE
• Replace all batteries at the same time, do not use new and • Do not turn off power immediately after the unit stops. Then,
old batteries intermixed. wait no less than 5 minutes.
• In case the remote controller is not used for a long time take Water is leaking or there is something else wrong with the unit.
out all batteries in order to prevent liquid leak of the battery.
〈〈FOR SYSTEMS WITH COOL/HEAT CHANGEOVER
IN THE CASE OF CENTRALIZED CONTROL SYSTEM REMOTE CONTROL SWITCH (Fig. 2 on page 3)〉〉
If the indoor unit is under centralized control, it is necessary to
switch the remote controller’s setting.
In this case, contact your dealer. 1 OPERATION MODE SELECTOR
6
(2)Press OPERATION MODE SELECTOR button several [°F]
times and select “ ”.
H • M • L
(This operation is only available during dry operation.)
Setting temperature 77 73 71 70 66
ON OFF
• The setting is impossible for fan operation.
2 ON/OFF
NOTE
Press ON/OFF button. • The setting temperature range of the remote controller is
OPERATING INDICATOR lamp lights up or goes off and the 60°F to 90°F.
system starts or stops OPERATION.
NOTE FAN
FAN SPEED CONTROL
• Do not turn off power immediately after the unit stops. Then,
wait no less than 5 minutes.
Water is leaking or there is something else wrong with the unit. Press FAN SPEED CONTROL button.
High or Low fan speed can be selected.
The microchip may sometimes control the fan speed in order to
[EXPLANATION OF HEATING OPERATION] protect the unit.
DEFROST OPERATION
• As the frost on the coil of an outdoor unit increase, heating SWING AIR FLOW DIRECTION ADJUST
effect decreases and the system goes into DEFROST
OPERATION.
• The fan operation stops and the DEFROST lamp of the Press the AIR FLOW DIRECTION ADJUST button to
indoor unit goes on. adjust the air flow angle.
• After 6 to 8 minutes (maximum 10 minutes) of DEFROST
OPERATION, the system returns to HEATING OPERATION.
Heating capacity & Outdoor air temperature
• Heating capacity drops as outdoor air temperature lowers.
If feeling cold, use another heater at the same time as this air
conditioner.
• Hot air is circulated to warm the room. It will take some time
from when the air conditioner is first started until the entire Up and down adjustment
room becomes warm. The internal fan automatically turns at
• The movable limit of the blade is changeable.
low speed until the air conditioner reaches a certain temper-
Contact your dealer for details.
ature on the inside. In this situation, all you can do is wait.
• If hot air accumulates on the ceiling and feet are left feeling Press the AIR FLOW DIRECTION ADJUST button to
cold, it is recommended to use a circulator. For details, con- select the air direction as shown below.
tact the place of purchase. DISPLAY appears and the air flow direction contin-
uously varies. (Automatic swing setting)
ADJUSTMENT
For programming TEMPERATURE, FAN SPEED and AIR
FLOW DIRECTION, follow the procedure shown below. Press AIR FLOW DIRECTION ADJUST button to
select the air direction of your choice.
DOWN
TEMPERATURE SETTING
UP
DISPLAY vanishes and the air flow direction is
fixed. (Fixed air flow direction setting)
Press TEMPERATURE SETTING button and program
the setting temperature.
Each time this button is pressed, setting tempera- MOVEMENT OF THE AIR FLOW FLAP
ture rises 1°F. For the following conditions, the microchip controls the air flow
UP
direction so it may be different from the display.
Each time this button is pressed, setting tempera-
DOWN ture lowers 1°F.
7
Operation CANCEL
mode
Cooling Heating 4 TIMER CANCEL
• When operating con- • When room
tinuously at horizon- temperature is higher Press the TIMER CANCEL button to cancel programming.
tal at horizontal air than the set tempera- The display vanishes.
flow direction. ture For example.
Operation • At defrost operation When the timer is programmed to
condition (Air flow direction stop the system after 3 hours and
ON OFF
becomes horizontal start the system after 4 hours, the
so that cool air is not TEMP system will stop after 3 hours and
TIME
exposed directly to then 1 hour later the system will start.
F
the human body) UP
DOWN
FAN
NOTE
• If you try cooling or programmed drying, while the flaps are fac- RESERVE CANCEL
ping.
• Operation mode includes automatic operation.
NOTE
PROGRAM TIMER OPERATION • After the timer is programmed, the display shows the remain-
ing time.
Operate in the following order.
• The timer is operated in the following 2 ways. HOW TO SET MASTER REMOTE CONTROLLER
Programming the stop time ( ) (For VRV system)
.... The system stops operating after the set time has elapsed.
• When the system is installed as shown below, it is necessary
Programming the start time ( )
to designate the master remote controller.
.... The system starts operating after the set time has elapsed.
For Heat pump system
• The timer can be programmed a maximum of 72 hours.
When 1 outdoor unit is connected with several indoor units.
• The start and the stop time can be simultaneously pro-
grammed.
Outdoor unit
1 TIMER
TIMER MODE START/STOP
DOWN
One of these remote controllers needs to be
2 UP
PROGRAMMING TIMER designated as the master remote controller.
8
• Only the master remote controller can select HEATING, PRECAUTIONS FOR GROUP CONTROL SYSTEM
COOLING or AUTOMATIC OPERATION.
OR 2 REMOTE CONTROLLERS CONTROL SYSTEM
When the indoor unit with master remote controller is set to
“COOL”, you can switch over operation mode between “FAN”, This system provides 2 other control systems beside individual
“DRY” and “COOL”. control (1 remote controller controls 1 indoor unit) system. Confirm
When the indoor unit with master remote controller is set to the following if your unit is of the following control system type.
“HEAT”, you can switch over operation mode between “FAN” Group control system
and “HEAT”. 1 remote controller controls up to 16 indoor units.
When the indoor unit with master remote controller is set to All indoor units are equally set.
“FAN”, you cannot switch operation mode. 2 remote controllers control system
1 long beep .............. When attempting settings than that con- 2 remote controllers control 1 indoor unit.
sented above. (In case of group control system, 1 group of indoor units)
Only with Heat recovery system, you can The unit follows individual operation.
set the indoor unit to AUTOMATIC.
Attempting to do so. NOTE
• Cannot have 2 remote controllers control system with only wire-
How to designate the master remote controller less remote controllers. (It will be a 2 remote controllers control
Operate in the following order. system having 1 wired and 1 wireless remote controllers.)
• Under 2 remote controllers control system, wireless remote
MODE
1 controller cannot control timer operation.
• Only the operating indicator lamp out of 3 other lamps on the
Continuously press the OPERATION MODE SELEC- indoor unit display functions.
TOR button for 4 seconds. • Contact your dealer in case of changing the combination or set-
The displays showing “ ” of all slave indoor unit connected to ting of group control and 2 remote controllers control systems.
the same outdoor unit or BS unit flash.
MODE
2
5. NOT MALFUNCTION OF THE AIR
Press the OPERATION MODE SELECTOR button to CONDITIONER
the indoor unit that you wish to designate as the mas-
ter remote controller. Then designation is completed. The following symptoms do not indicate air condi-
This indoor unit is designated as the master remote tioner malfunction.
controller and the display showing “ ” vanishes. THE SYSTEM DOES NOT OPERATE
• To change settings, repeat steps 1 and 2 . • The system does not restart immediately after the ON/
OFF button is pressed.
EMERGENCY OPERATION If the OPERATING INDICATOR lamp lights, the system is in
When the remote controller does not work due to battery failure normal condition. It does not restart immediately because a
or the absence there of, use this switch which is located beside safety device operates to prevent overload of the system.
the discharge grille on the indoor unit. When the remote control- After 3 minutes, the system will turn on again automatically.
ler does not work, but the battery low indicator on it is not lit, • The system does not restart immediately when TEM-
contact your dealer. PERATURE SETTING button is returned to the former
position after pushing the button.
It does not restart immediately because a safety device oper-
ates to prevent overload of the system. After 3 minutes, the
system will turn on again automatically.
• If the reception beep is rapidly repeated 3 times.
1·2 (It sounds only 2 times when operating normally.)
Control is set to the optional controller for centralized control.
• If the DEFROST lamp on the indoor unit’s display is lit
[START] when heating is started.
This indication is to warn against cold air being blown from
the unit. There is nothing wrong with the equipment.
1 Press the EMERGENCY OPERATION switch.
The unit stops operation from time to time.
The machine runs in the previous mode. • With “U4” “U5” displayed on the remote controller, the
The system operates with the previously set air flow direction. unit stops, but it resumes operation in a few minutes.
Since electric noises produced from other equipment than
[STOP] the air conditioner interrupt communication between the
units, the unit stops operation.
2 Press the EMERGENCY OPERATION If these electric noises subside, operation is restarted auto-
switch again. matically.
9
COOLING / HEATING changeover is impossible. Number of beeps
• If the indoor unit emits a receiving sound “1 long beep”. 3 short beeps ........... Perform all steps from 3 to 6 .
It is because the indoor unit under the control of operation 1 short beep ............. Perform 3 and 6 steps.
changeover is set to the mode that cannot be selected.
1 long beep .............. Normal state
Display Indicates only a part.
• Even if the unit is in operation, the display shows only MODE
the indoor unit starts blinking. Take the following steps yourself
to read the malfunction code that appears on the display. Con- Press PROGRAMMING TIMER button and change the
tact your dealer with this code. It will help pinpoint the cause of malfunction code.
the trouble, speeding up the repair. Press until the indoor unit makes 1 long beep.
The malfunction code is fixed when the indoor unit makes 1 long
ON OFF beep.
24
6 TEMP
TIME MODE
7 Reset of the display
UP 24
CODE DOWN
FAN 6
Press OPERATION MODE SELECTOR button to get
UNIT NO. RESERVE CANCEL
the display back to the normal state.
TIMER
MODE
IN CASE BESIDES EMERGENCY STOP
SWING
35 • The unit does not operate at all.
7 • Check if the receiver is exposed of sunlight or strong light.
Keep receiver away from light.
/TEST • Check if there are batteries in the remote controller. Place
the batteries.
• Check if the indoor unit number and wireless remote con-
1 troller number are equal.
Number
TEST
1
Press the INSPECTION/TEST OPERATION button to
select the inspection mode “ ”.
“ ” appears on display and blinks. “UNIT No.” lights up.
DOWN
2 UP
Number
10
Operate the indoor unit with the remote controller of the same
number.
Signal transmitted from 1 remote controller of a different number
cannot be accepted. (If the number is not mentioned, it is con-
sidered as “1”.)
The system operates but it does not sufficiently cool or
heat.
• If the set temperature is not proper. (See page 7)
• If the FAN SPEED is set to LOW SPEED. (See page 7)
• If the air flow angle is not proper. (See page 7)
Contact the place of purchase in the following case.
WARNING
When you detect a burning odor, shut OFF power immedi-
ately and contact the place of purchase. Using the equipment
in anything but proper working condition can result in equip-
ment damage, electric shock or fire.
[Trouble]
The OPERATING INDICATOR lamp of the indoor unit is
flashing and the unit does not work at all.
Malfunction Code
Unit No. which
sensed trouble
ON OFF
TEMP
TIME
UP
CODE DOWN
FAN
TIMER
MODE
SWING
/TEST
INSPECTION
display
11
3P153711-2B EM04A061A (0504) FS
R410A
TECHNICAL MANUAL
Inverter Single Split
Series Air Conditioner
FTK - Q & T Series
— Cooling only [50Hz] —
TM-FTK-0616-A
Nomenclature
Nomenclature
Indoor
FT K 10 T V1 W
Controller
W/L: Wireless
M: Wired
Power Supply
V1: 220-240V / 1 Phase / 50 Hz
Product Series
T: T Series
Q: Q Series
Capacity*
10 : 10,000 Btu/hr
System
K: Inverter Cooling Only
Model
FT: Wall Mounted
Outdoor
R K 10 F G V1
Power Supply
V1: 220-240V / 1 Phase / 50 Hz
Fin
G : Gold Fin,
‘-’ : Bare Fin
Product Series
F: F Series
C: C Series
Capacity*
10 : 10,000 Btu/hr
System
K: Inverter Cooling Only
Model
R: Single Split Condensing Unit
Remark:
* : Capacity value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value.
2
Nomenclature
Product Line-Up
Indoor Unit
FTK
Classification
Air Purification
Handset
PCB
Fins
Nomenclature
DSLM8
DGS01
FTK10TV1W X X X X X
FTK15TV1W X X X X X
FTK20TV1W X X X X X
FTK25TV1W X X X X X
FTK10QV1L X X X X
COOLING
FTK15QV1L X X X X
FTK20QV1L X X X X
FTK25QV1L X X X X
FTK10QV1M X X X X
FTK15QV1M X X X X
FTK20QV1M X X X X
FTK25QV1M X X X X
3
Nomenclature
Outdoor Unit
RK
Classification
Refrigerant Control
Compressor
PCB
Fins
Nomenclature
Hydrophilic (Gold)
Bare Aluminium
Cap Tube
Swing
EXV
RK10FV1 X X X X
RK10FGV1 X X X X
RK15FV1 X X X X
COOLING
RK15FGV1 X X X X
RK20CV1 X X X X X
RK20CGV1 X X X X X
RK25CV1 X X X X X
RK25CGV1 X X X X X
4
Table of Contents
Table of Contents
Nomenclature......................................................................................................................2
Indoor.............................................................................................................................2
Outdoor...........................................................................................................................2
Product Line-Up..............................................................................................................3
Application Information......................................................................................................5
Operating Range............................................................................................................5
Refrigerant Circuit Diagrams..........................................................................................5
Installation Guideline......................................................................................................6
Sound Data...........................................................................................................................9
Sound Pressure Level ...................................................................................................9
NC Curve......................................................................................................................10
Engineering & Physical Data............................................................................................12
Performance Data..............................................................................................................14
Calculation Steps..........................................................................................................14
Performance Tables......................................................................................................17
Outline & Dimension.........................................................................................................21
Wiring Diagram..................................................................................................................26
Service & Maintenance.....................................................................................................30
Troubleshooting................................................................................................................35
Application Information
Application Information
Operating Range
Ensure the operating temperature is in allowable range.
Cooling
FTK10/15TV1 - RK10/15FV1 FTK20/25TV1 - RK20/25CV1
FTK10/15QV1 - RK10/15FV1 FTK20/25QV1 - RK20/25CV1
COOLING COOLING
50 50
46 46
43
43
OUTDOOR TEMP. (°CDB)
30
30
20
20 10
0
10
-10
0
10 14 15 19 20 23 25 -20
10 14 15 19 20 23 25
10/15 20/25
COOLING OPERATION
PIPING
GAS 3 WAY
VALVE
MUFFLER
RETURN AIR SENSOR
RETURN AIR SENSOR
DISCHARGE
HEAT EXCHANGER
(OUTDOOR UNIT)
COMPRESSOR
ELECTRONIC EXPANSION
PIPING VALVE
LIQUID
3 WAY STRAINER
VALVE
INDOOR UNIT OUTDOOR UNIT
5
Application Information
Installation Guideline
Sharp edges and coil surfaces are potential injury hazard. Avoid from contact with them.
Installation Diagram
Service lid
M4 x 12L ■ Opening service lid
Air filter Service lid is opening/
closing type.
■ Opening method
1) Remove the service
lid screws.
2) Pull out the service
lid diagonally down
in the direction of the
arrow.
3) Pull down.
Outdoor Unit
500mm from
wall
6
Application Information
Outdoor Clearance
• Where a wall or order obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the
installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Model: RK10/15FV1
Wall facing one side Wall facing two side
More than 50 More than 100
Top View
Unit : mm
Model: RK20/25CV1
A C D
B
Service access
Return air
Discharge air
Return air
Obstacle
Obstacle
Obstacle
Obstacle
H/2
ALL MODELS A B C D
Minimum Distance 300 mm 1000 mm 300 mm 500 mm
7
Application Information
Cable Size
FTK10/15TV1 FTK20/25TV1
Indoor
Model FTK10/15QV1 FTK20/25QV1
Outdoor RK10/15FV1 RK20/25CV1
Power supply cable size mm2 1.5 2.5
Number of wire 3 3
Interconnection cable size mm2 1.5 2.5
Number of wire 4 4
Recommended fuse A 15 20
Refrigerant Piping
Piping Length and Elevation
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends increases,
system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and as the result
the compressor may become defective. Always choose the shortest path and follow the recommendation as
tabulated below:
Indoor Unit
L E
Outdoor Unit
Additional Charge
• The refrigerant gas is charged in the outdoor unit and, if the piping length is 7.5m, additional charge of the
refrigerant after vacuuming is not necessary.
• When the piping length is more than 7.5m, additional refrigerant charge (g) per additional 1m length as
tabulated:
Example:
FTK10TV1 & RK10FV1 with 15m piping length, additional piping length is 7.5m. Thus,
Additional charge = 7.5m x [20g/m]
= 150 [g]
8
Sound Data
Sound Data
Sound Pressure Level
1/1 Octave A-weighted Sound Pressure Level
(dB, ref 20µPa) Overall Noise
Model Speed
(dBA) Criteria
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Turbo 43 39 37 37 33 26 13 41 36
Hi 42 38 37 36 32 24 12 40 35
FTK10TV1
Me 37 33 32 30 25 17 13 34 29
FTK10QV1
Lo 32 29 28 24 19 14 13 29 22
Quiet 21 22 20 15 10 7 8 21 -
Turbo 41 39 38 38 36 29 15 42 37
Hi 40 38 38 37 34 27 14 41 36
FTK15TV1
Me 36 32 32 30 26 18 11 34 29
FTK15QV1
Lo 33 29 29 25 21 15 11 30 23
Quiet 24 22 21 17 11 7 7 22 -
Turbo 39 41 40 40 37 29 16 44 39
Hi 35 37 37 36 32 25 12 40 35
FTK20TV1
Me 34 36 36 34 29 22 11 38 33
FTK20QV1
Lo 30 34 33 31 26 18 10 35 30
Quiet 28 32 30 28 22 14 10 32 26
Turbo 42 44 43 42 40 35 20 46 41
Hi 39 41 40 38 36 31 16 43 37
FTK25TV1
Me 37 39 38 37 33 28 13 41 36
FTK25QV1
Lo 33 36 35 33 28 22 11 37 32
Quiet 28 33 32 28 23 17 9 33 26
FTK10TV1
FTK15TV1
FTK20TV1
FTK25TV1
FTK10QV1 0.8m
FTK15QV1
Microphone
FTK20QV1
FTK25QV1 1.0m
Standard : JIS C 9612
9
Sound Data
NC Curve
FTK10TV1 / FTK10QV1
80
70 NC-70
Sound pressure level (dB, ref 20µPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
T NC-40
NC-35
H
30 M
NC-30
NC-25
L
20
NC-20
Q
10
0
125 250 500 1000 2000 4000 8000
FTK15TV1 / FTK15QV1
80
70 NC-70
Sound pressure level (dB, ref 20µPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
T NC-40
H NC-35
30
M NC-30
NC-25
L
20
NC-20
Q
10
0
125 250 500 1000 2000 4000 8000
10
Sound Data
FTK20TV1 / FTK20QV1
80
70 NC-70
Sound pressure level (dB, ref 20µPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
T NC-40
H NC-35
30 M
NC-30
L
Q NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
FTK25TV1 / FTK25QV1
80
70 NC-70
Sound pressure level (dB, ref 20µPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40 T
NC-40
H
M NC-35
30
L NC-30
Q NC-25
20
NC-20
10
0
125 250 500 1000 2000 4000 8000
11
Engineering & Physical Data
12
Engineering & Physical Data
13
Performance Data
Performance Data
Calculation Steps
Interpolation method can be used to get the total cooling capacity, TC and sensible cooling capacity, SC
and power input, PI at those temperatures which are not stated out in the table. Extrapolation method is not
allowed to be used.
Example:
Outdoor temperature
AFR
EWB EDB 19°C 25°C 30°C 35°C 40°C 46°C
(CFM)
TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI
21°C 2.02 1.54 0.49 1.95 1.50 0.53 1.87 1.46 0.58 1.80 1.42 0.63 1.65 1.32 0.68 1.52 1.24 0.75
24°C 2.02 1.84 0.49 1.95 1.80 0.53 1.88 1.76 0.58 1.80 1.71 0.63 1.66 1.60 0.68 1.53 1.51 0.75
16°C
27°C 2.04 2.04 0.49 1.97 1.97 0.54 1.90 1.90 0.58 1.83 1.83 0.63 1.69 1.69 0.68 1.57 1.57 0.75
30°C 2.10 2.10 0.50 2.04 2.04 0.54 1.98 1.98 0.58 1.91 1.91 0.63 1.77 1.77 0.69 1.66 1.66 0.76
24°C 2.23 1.44 0.50 2.15 1.40 0.54 2.07 1.36 0.59 1.99 1.32 0.64 1.83 1.23 0.69 1.69 1.16 0.76
27°C 2.23 1.64 0.50 2.15 1.61 0.54 2.07 1.57 0.59 1.99 1.53 0.64 1.83 1.43 0.69 1.69 1.36 0.76
195 19°C
30°C 2.23 2.03 0.50 2.15 1.99 0.54 2.08 1.94 0.59 2.00 1.89 0.64 1.84 1.77 0.69 1.71 1.68 0.76
33°C 2.26 2.26 0.50 2.18 2.18 0.54 2.11 2.11 0.59 2.04 2.04 0.64 1.89 1.89 0.70 1.77 1.77 0.77
27°C 2.45 1.41 0.51 2.36 1.37 0.55 2.28 1.34 0.60 2.19 1.30 0.65 2.01 1.21 0.71 1.86 1.14 0.78
30°C 2.45 1.71 0.51 2.36 1.68 0.55 2.28 1.64 0.60 2.19 1.60 0.65 2.01 1.50 0.71 1.86 1.42 0.78
22°C
33°C 2.45 2.00 0.51 2.37 1.96 0.55 2.28 1.92 0.60 2.19 1.88 0.65 2.02 1.77 0.71 1.87 1.68 0.78
36°C 2.46 2.27 0.51 2.38 2.22 0.55 2.29 2.18 0.60 2.21 2.13 0.65 2.04 2.00 0.71 1.90 1.89 0.78
Solution:
14
Performance Data
TC SC PI
Repeat the same process for (c) & (d) in 1st Step (d) x4 = 1.83 W; y4 = 1.30 kW; z4 = 0.69 kW
15
Performance Data
3rd Step:
To obtain the TC, SC & PI for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Outdoor temperature
EWB EDB 35°C 37°C 40°C
TC SC PI TC SC PI TC SC PI
16
Performance Data
Performance Tables
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 10°C to 46°C without pressure trip.
17
Performance Data
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 10°C to 46°C without pressure trip.
18
Performance Data
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from -10°C to 46°C without pressure trip.
19
Performance Data
Notes:
1. Ratings shown are gross capacities which do not include a deduction for indoor fan motor heat.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from -10°C to 46°C without pressure trip.
20
Outline & Dimension
Model: FTK10/15/20/25QV1
TOP VIEW
A C
STICKER
SERIAL NO.
B
SIGNAL RECEIVER TERMINAL
INDOOR UNIT ON/ BLOCK WITH
BOTTOM BOTTOM OFF SWITCH EARTH
LOUVER ROOM TEMPARATURE TERMINAL
FRONT GRILLE
FIXED SCREWS THERMISTOR (INSIDE)
(INSIDE)
FRONT VIEW SIDE VIEW
Note: Dimension in mm
hole Ø 65mm
G
Dimension
A B C D E F G H I J K L M
Model
FTK10/15QV1 859 288 209 104 141 30 46 55 56 153 181 207 52
Note: Dimension in mm
21
Outline & Dimension
D E
F
F
B
G
H J Liquid pipe end Gas pipe end K I Drain hose position
L M
A
Dimension
A B C D E F G H I J K L M
Model
FTK20/25QV1 1124 310 237 190 173 61 40 45 48 91 219 580 45
Note: Dimension in mm
22
Outline & Dimension
Model: FTK10/15/20/25TV1
REAR REAR
LEFT RIGHT
TOP VIEW
NAME PLATE
SIGNAL RECEIVER
B
B
TERMINAL
BLOCK WITH
INDOOR UNIT EARTH
ON/OFF SWITCH TERMINAL
BOTTOM BOTTOM SIDE VIEW
ROOM TEMPERATURE
LOUVER FRONT GRILLE FIXED SCREWS THERMISTOR (INSIDE)
(INSIDE)
FRONT VIEW
Note: Dimension in mm
hole Ø 65mm
G
Dimension
A B C D E F G H I J K L M
Model
FTK10/15TV1 890 297 210 104 141 30 46 55 56 153 181 207 52
Note: Dimension in mm
23
Outline & Dimension
D E
F
F
B
G
H J Liquid pipe end Gas pipe end K I Drain hose position
L M
A
Dimension
A B C D E F G H I J K L M
Model
FTK20/25TV1 1172 320 242 190 173 61 40 45 48 91 219 580 45
Note: Dimension in mm
24
Outline & Dimension
Outdoor Unit
Model: RK10/15FV1
J H I
O
N
Q
P
E F D B C
2.0
L
M K
Dimension
A B C D E F G H I J K L M N O P Q
Model
RK10/15FV1 550 658 51 11 273 16 14 470 96 93 94 60 14 133 8 10 299
Note: Dimension in mm
Model: RK20/25CV1
L K L
N
M
A C
N
O D G H
F
3.0
U
V
E
B
R S
I J
P
Dimension
A B C D E F G H I J K L M N
Model
RK20CV1 855 628 328 520 179 46 93 149 101 113 603 126 164 15
RK25CV1 855 730 328 520 179 46 93 149 101 113 603 126 164 15
Dimension
O P Q R S T U V
Model
RK20CV1 34 23 362 73 75 8 67 7
RK25CV1 34 23 362 73 75 8 67 7
Note: Dimension in mm
25
Wiring Diagram
Wiring Diagram
Cooling Only
Indoor Unit Outdoor Unit
Model: FTK10/15TV1 Model: RK10/15FV1
FAN
G
SWIN E
MOD
BO P
TUR SLEE OFF
T R
QUIE TIME CEL
CAN
K
ON CLOC
CEL
CAN
INTELLIGENT SENSE OR
WIRED
CONTROLLER
(OPTIONAL)
L 220-240V
N 1PHASE
E 50Hz
26
Wiring Diagram
FAN
G
SWIN E
MOD
BO P
TUR SLEE OFF
T R
QUIE TIME CEL
CAN
K
ON CLOC
CEL
CAN
INTELLIGENT SENSE OR
WIRED
CONTROLLER
(OPTIONAL)
L 220-240V
N 1PHASE
E 50Hz
27
Wiring Diagram
FAN
G
SWIN E
MOD
BO P
TUR SLEE OFF
T R
QUIE TIME CEL
CAN
K
ON CLOC
CEL
CAN
L 220-240V
N 1PHASE
E 50Hz
28
Wiring Diagram
FAN
G
SWIN E
MOD
BO P
TUR SLEE OFF
T R
QUIE TIME CEL
CAN
K
ON CLOC
CEL
CAN
L 220-240V
N 1PHASE
E 50Hz
29
Service & Maintenance
• Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform as a result
of chemical reaction.
• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, support the panel securely with hand to prevent it from falling.
• For cleansing, do not use hot water above 40°C, benzine, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed.
When The Unit Is Not To Be Used For An Extended Long Period Of Time
Operate the unit for 2 hours Remove the power plug.
with the following setting. If you are using an
independent electric
Operating mode : cool circuit for your unit, cut
Temperature : 30°C/86°F off the circuit.
Remove the batteries in
the remote control.
30
Service & Maintenance
Air Filter
1. Open the front panel. 3. Clean or replace each filter.
• Hold the panel at the recesses on the main unit • When shaking off remaining water, do not
(2 recesses on right and left sides) and lift it until wring the filter.
it stops. 4. Set the air filter and close the front panel.
• Insert claws of the filters into slots of the front
Recess on panel. Close the front panel slowly and push
main unit
the panel at the 3 points. (1 on each side and
1 in the middle.)
• The air filter have a symmetrical form in the
horizontal direction.
2. Pull out the air filters.
• Push a little upwards the tab at the center of
each air filter, then pull it down.
FRONT
31
Service & Maintenance
• Avoid direct contact of any coil treatment cleaners on plastic part. This may cause plastic part to deform as a result
of chemical reaction.
Step Step
Step Step
32
Service & Maintenance
• Don’t touch the metal parts of the indoor unit. It may cause an injury.
• When removing or attaching the front panel, support the panel securely with hand to prevent it from falling.
• For cleaning, do not use hot water above 40°C, benzine, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
• After cleaning, make sure that the front panel is securely fixed.
33
Service & Maintenance
Air Filter
1. Open the front panel. 4. Clean or replace each filter.
• Hold the panel at the recesses on the main unit See figure.
(2 recesses on right and left sides) and lift it until • When shaking off remaining water, do not
it stops. wring the filter.
Tab
2. Pull out the air filters. 5. Set the air filter and close the front panel.
• Push a little upwards the tab at the center of • Insert claws of the filters into slots of the front
each air filter, then pull it down. panel. Close the front panel slowly and push
3. Take off the Titanium Apatite Filter. the panel at the 3 points. (1 on each side and
• Hold the recessed parts of the frame and unhook 1 in the middle.)
the four claws. • The air filter have a symmetrical form in the
horizontal direction.
Titanium Apatite Filter Air filter
Attached Concept
Heat exchanger
34
Troubleshooting
Troubleshooting
Indicator Lights
IR Signal Receiver
When an infrared remote control operating signal has been transmitted, the signal receiver on the indoor unit
will respond as below to confirm acceptance of the signal transmission.
Indoor : FTK10/15/20/25QV1
The table below shows the LED indicator lights for the air conditioner unit under normal operation and fault
conditions. The LED lights are located at the middle of the air conditioner unit.
The heatpump units are equipped with an “auto” mode sensor whereby it will provide reasonable room
temperature by switching automatically to either “cool” or “heat” mode according to the temperature set by the
user.
IR Receiver
Cool
Timer
Sleep
ON/OFF ON/OFF switch
Operation
Cooling mode
Timer on
Sleep mode on
Fan mode on
Dry mode on
Unit error
ON Blinking
35
Troubleshooting
Indoor : FTK10/15/20/25TV1
The table shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions.
The LED indicator lights are located at the side of the air conditioner unit. The heat pump units are equipped
with an “auto” mode sensor whereby it will provide reasonable room temperature by switching automatically to
either “cool” or “heat” mode according to the temperature set by the user.
Cool/Timer
IR Receiver
ON/OFF
ON/OFF switch
IR Receiver
LED Indicator Lights for Cooling Unit Pump Unit This is applicable for FTK10/15/20/25TV1.
LED Indicator Lights: Normal Operation And Fault Conditions For Cooling Unit
Operation
COOL/TIMER
(BLUE/VIOLET)
Cooling mode
BLUE
Timer on
VIOLET
Fan mode on
BLUE
Dry mode on
BLUE
Unit error
BLUE
ON Blinking
36
Troubleshooting
SWING FAN
TURBO MODE
QUIET SLEEP
TIMER
ON OFF
DGS01 BRC52B65
Diagnosis Step
1. Hold down ON TIMER CANCEL button or OFF TIMER CANCEL button for 5 seconds, a “ ” indication
flashes on the temperature display section.
2. Press TIMER CANCEL repeatedly until indoor buzzer produces a long beep. This indicates the error
code, refers to Error Codes table and is displayed on the temperature display section.
3. A short beep or two consecutive beeps indicate non-corresponding error codes.
4. To cancel the error code display, hold down ON TIMER CANCEL button or OFF TIMER CANCEL button
for 5 seconds. Alternatively, the code display will cancel itself if the button is not pressed for 1 minute.
37
Troubleshooting
Troubleshooting Guidelines
Error Codes Error Description Action
0 Normal No action.
1. Check sensor connection.
2. Check stop valve.
U0 Insufficient gas 3. Check for gas leak.
4. Check the EXV.
5. Check H8.
1. Check the supply voltage.
2. Check the outdoor fan by rotating with hand.
U2 DC voltage out of range
3. Restart the system.
4. Check power supply waveform.
1. Check the indoor unit - outdoor unit connection wires.
2. Check the voltage of the signal terminal.
U4 Communication error
3. Check the indoor fan by rotating with hand.
4. Check the power supply waveform.
1. Check the indoor and outdoor unit model name.
UA Installation error
2. Check the part code on the indoor and outdoor PCB.
1. Check connector connection.
A1 Indoor PCB error
2. Replace indoor PCB.
1. Check the air passage.
2. Check the intake air filter.
3. Check dust accumulation on indoor coil.
4. Check wiring and piping.
A5 Antifreeze
5. Check the EXV.
6. Check indoor coil sensor resistance value.
7. Check refrigerant level.
8. Check room sensor resistance value.
1. Check the indoor fan by rotating with hand.
2. Replace indoor fan motor if not rotating smoothly.
3. Check fan motor voltage.
A6 Indoor fan motor abnormal
4. Replace indoor PCB if not at the rated voltage.
5. Check fan capacitor’s conductivity (AC Motor).
6. Replace fan capacitor if there’s conductivity.
Indoor heat exchanger
C4
thermistor short/open 1. Check the connector connection.
Indoor room thermistor 2. Check the sensor resistance value.
C9
short/open
1. Restart the system.
2. Replace outdoor PCB.
E1 Outdoor PCB error
3. Check to see that the unit is grounded.
4. Check power supply waveform.
1. Check connection on discharge pipe sensor.
Compressor motor lock/ 2. Check discharge pipe sensor resistance value.
E5
overload 3. Check the EXV.
4. Check the refrigerant line on blockage or shortage.
38
Troubleshooting
39
Troubleshooting
40
w w w. d a i k i n . c o m . m y
English
MODELS Français
(Ceiling-mounted Multi flow Cassette type)
FCQ71DV3B FCQ71DAV3B
FCQ100DV3B FCQ100DAV3B Español
FCQ125DV3B FCQ125DAV3B
FCQ140DV3B FCQ140DAV3B
Italiano
ÅëëçíéêÜ
Nederlands
Portugues
Ðóññêèé
Thank you for purchasing this Daikin air condi- Σας ευχαριστούµε που αγοράσατε τη συσκευή
tioner. Carefully read this operation manual κλιµατισµού. ∆ιαβάστε προσεκτικά αυτές τις
before using the air conditioner. It will tell you οδηγίες χρήσης πριν να χρησιµοποιήσετε τη
how to use the unit properly and help you if any συσκευή κλιµατισµού.
trouble occurs. After reading the manual, file it Θα σας πουν πως θα χρησιµοποιήσετε σωστά
away for future reference. τη µονάδα και θα σας βοηθήσουν αν
εµφανιστούν προβλήµατα. Aφού διαβάσετε τις
οδηγίες, βάλτε τις στο αρχείο σας για µελλοντική
αναφορά.
Vielen Dank für den Kauf einer Klimaanlage von Wij danken u voor de aankoop van deze Daikin
Daikin. Bitte lesen Sie diese Bedienungsanlei- airconditioner. Lees deze bedrijfshandleiding
tung vor der Inbetriebnahme des Gerätes aandachtig door voordat u de airconditioner
gründlich durch. Hier wird erklärt, wie das Gerät gebruikt. Het omvat uitleg over het correcte
richtig eingesetzt wird und was bei Störungen zu gebruik van de unit en biedt hulp in geval een
tun ist. In dieser Anleitung wird nur das Innenag- storing mocht optreden. Gebruik deze handled-
gregat beschrieben. Verwenden Sie diese Anlei- ing voor verdere raadpleging.
tung zusammen mit der Bedienungsanleitung
des Außenaggregats. Nach dem Lesen der
Anleitung legen Sie diese griffbereit zum Nach-
schlagen auf.
Nous vous remercions pour votre acquisition de Obrigado pela sua compra deste aparelho de ar
ce climatiseur Daikin. condicionado Daikin.
Lisez attentivement ce manuel avant d’utiliser le Leia com atenção este manual de operação
climatiseur. Il vous expliquera comment vous antes de proceder à utilização do aparelho de ar
servir correctement de l’appareil et vous guidera condicionado. Este indicar-lhe-á como deverá
en cas de problème. Lorsque vous aurez lu le utilizar a unidade correctamente e ajudá-lo-á no
manuel, rangez-le afin de pouvoir vous y référer caso de surgir qualquer problema. Depois de ler
ultérieurement. o manual, guarde-o num local seguro a fim de o
poder consultar caso venha a ser preciso.
l
Outdoor unit
a Indoor unit
Unit with Unit without romote b Outdoor unit
remote controller c Remote controller
controller (When used as d Inlet air
simultaneous
operation system) e Discharge air
f Air outlet
NOTE
• If the unit you purchased is controlled by a wire- g Air flow flap (at air outlet)
less remote controller, also refer to the wireless h Refrigerant piping, connection electric wire
remote controller’s operation manual. i Drain pipe
If your installation has a customized control system, Air inlet
ask your Daikin dealer for the operation that corre- j
The built-in air filter removes dust and dirt.
sponds to your system.
Drain pumping out device(built-in)
• Heat pump type k Condensate removed from the room during
This system provides cooling, heating, automatic, cooling.
program dry, and fan operation modes.
Ground wire
l Wire to ground from the outdoor unit to pre-
vent electrical shocks.
1 English
For installation of separately sold compo-
2. SAFETY CONSIDERATIONS nent parts, ask a specialist.
We recommend that you read this instruction man- Be sure to use the separately sold component
ual carefully before use to gain full advantage of the parts designated by our company.
function of the air conditioner, and to avoid malfunc- Incomplete installation performed by yourself may
tion due to mishandling. result in a water leakage, electric shock, and fire.
This air conditioner comes under the term “appli- Ask your dealer to move and reinstall the air
ances not accessible to the general public”. conditioner.
• The precautions described below are WARN- Incomplete installation may result in a water
ING and CAUTION. These are very important leakage, electric shock, and fire.
precautions concerning safety. Be sure to The refrigerant in the air conditioner is safe
observe all of them without fail. and normally does not leak. If the refrigerant
leaks inside the room, the contact with a fire
WARNING ...These are the matters with possi- of a burner, a heater or a cooker may result in
bilities leading to serious conse- a harmful gas.
quences such as death or serious Do not use the air conditioner until when a ser-
injury due to erroneous handling. vice person confirms to finish repairing the por-
CAUTION ....These are the matters with possi- tion where the refrigerant leaks.
bilities leading to injury or material Do not use any fuse with improper capacity.
damage due to erroneous han- The use of a piece of wire and whatnot may
dling including probabilities lead- result in a failure and fire.
ing to serious consequences in Be sure to establish an earth.
some cases. Do not earth the unit to a utility pipe, arrester, or
telephone earth.
• After reading, keep this manual at a place Incomplete earth may cause electrical shock, or
where any user can read at any time. Further- fire.
more, make certain that this operation manual A high surge current from lightning or other
is handed to a new user when he takes over sources may cause damage to the air conditioner.
the operation. Be sure to install an earth leakage breaker.
WARNING Failure to install an earth leakage breaker may
result in electric shocks, or fire.
Avoid exposure of your body directly to the Consult the dealer if the air conditioner sub-
cold air for a long time, or avoid excessive merges owing to a natural disaster, such as a
exposure of your body to the cold air. flood or typhoon.
Otherwise, your physical condition may be dete- Do not operate the air conditioner in that case, or
riorated and/or your health may be ruined. otherwise a malfunction, electric shock, or fire may
When the air conditioner is in abnormal con- result.
ditions (smell of something burning, etc),
turn off power, and contact the dealer where
you purchased the air conditioner. CAUTION
Continued operation under such circumstances Do not use the air conditioner for other pur-
may result in a failure, electric shock, and fire. poses.
Ask your dealer for installation of the air con- Do not use the air conditioner for a special appli-
ditioner. cation such as the storage of foods, animals and
Incomplete installation performed by yourself plants, precision machines, and art objects as
may result in a water leakage, electric shock, otherwise the deterioration of quality may result.
and fire. Do not remove the air outlet of the outdoor unit.
Ask your dealer for improvement, repair, and The fan may get exposed and result in injury.
maintenance. When the air conditioner is used in combina-
Incomplete improvement, repair, and mainte- tion with burners or heaters, perform suffi-
nance may result in a water leakage, electric cient ventilation.
shock, and fire. Insufficient ventilation may result in an oxygen
Do not insert your finger, a stick, etc., into the deficiency accident.
air inlet, outlet, and fan blades. Check and make sure that foundation blocks
A fan in high-speed running may result in injury. are not damaged after a long use.
For refrigerant leakage, consult your dealer. If they are left in a damaged condition, the unit
When the air conditioner is to be installed in a may fall and result in injury.
small room, it is necessary to take proper mea- Neither place a flammable spray bottle near
sures so that the amount of any leaked refriger- the air conditioner nor perform spraying.
ant does not exceed the limiting concentration Doing so may result in a fire.
even when it leaks. If the refrigerant leaks To clean the air conditioner, stop operation,
exceeding the level of limiting concentration, an and unplug the power cord from the outlet.
oxygen deficiency accident may happen. Otherwise, an electric shock and injury may result.
English 2
Do not operate the air conditioner with a wet Water coming inside the machine may cause an
hand. electric leak or may damage the internal elec-
An electric shock may result. tronic parts.
Do not place items that might be damaged by Watch your steps at the time of air filter
water under the indoor unit. cleaning or inspection.
Water may condensate and drip if the humidity High-place work is required, to which utmost
reaches 80% or if the drain exit gets clogged. attention must be paid.
Do not place a burner or heater at a place If the scaffold is unstable, you may fall or topple
directly exposed to the wind from the air con- down, thus causing injury.
ditioner.
Incomplete combustion of the burner or heater
may result.
Do not allow a child to mount on the outdoor
unit or avoid placing any object on it. 3. OPERATION RANGE
Falling or tumbling may result in injury.
Do not expose animals and plants directly to If the temperature or the humidity is beyond the fol-
the wind. lowing conditions, safety devices may work and the
Adverse influence to animals and plants may result. air conditioner may not operate, or sometimes,
Do not wash the air conditioner with water. water may drop from the indoor unit.
Electric shock or fire may result. COOLING
Do not install the air conditioner at any place OUTDOOR
where flammable gas may leak out. INDOOR OUTDOOR
UNIT
If the gas leaks out and stays around the air con- TEMPERA-
TEMPERA- HUMID-
ditioner, a fire may break out. TURE
Execute complete drain piping for perfect RZQ71 TURE ITY
drainage. 100 D
18 to 37
Incomplete piping may result in a water leakage. 125 B 80% or D
–15 to 50
The appliance is not intended for use by young 140 W below B
12 to 28
children or infirm persons without supervision. B
Young children should be supervised to HEATING
ensure that they do not play with the appliance. OUTDOOR INDOOR OUTDOOR
Consult with installation contractor for UNIT TEMPERATURE TEMPERATURE
cleaning the inside of the air conditioner. RZQ71 D
Wrong cleaning may make the plastics parts broken –19.5 to 21
100 D B
or cause failure of water leakage or electric shock. 10 to 27
125 B W
Do not touch the air inlet or aluminium fin of –20 to 15.5
140 B
the air conditioner.
Otherwise, injury may be caused. For Australia model Only
Do not start or stop operating the air condi- COOLING
tioner with the power supply breaker turned
ON or OFF. OUTDOOR
INDOOR OUTDOOR
Otherwise, fire or water leakage may result. UNIT
TEMPERA-
Furthermore, the fan will rotate abruptly if power TEMPERA- HUMID-
TURE
failure compensation is enabled, which may TURE ITY
result in injury. D
Do not place objects in direct proximity of the RZQ71 20 to 37
B 80% or D
outdoor unit and do not let leaves and other –5 to 46
W below B
debris accumulate around the unit. 14 to 28
B
Leaves are a hotbed for small animals which can
enter the unit. Once in the unit, such animals can HEATING
cause malfunctions, smoke or fire when making OUTDOOR INDOOR OUTDOOR
contact with electrical parts. UNIT TEMPERATURE TEMPERATURE
Never touch the internal parts of the remote D
controller. –14 to 21
D B
Do not remove the front panel. Some parts RZQ71 10 to 27
B W
inside are dangerous to touch, and a machine –15 to 15.5
trouble may happen. B
For checking and adjusting the internal parts, D B: Dry bulb temperature
contact your dealer. WB: Wet bulb temperature
Avoid placing the remote controller in a spot The setting temperature range of the remote con-
splashed with water. troller is 16°C to 32°C.
3 English
• Operating procedure varies with heat pump type
4. INSTALLATION SITE and cooling only type. Contact your Daikin dealer
Regarding places for installation to confirm your system type.
• Is the air conditioner installed at a well-ventilated • To protect the unit, turn on the main power switch
place where there are no obstacles around? 6 hours before operation.
• Do not use the air conditioner in the following • If the main power supply is turned off during oper-
places. ation, operation will restart automatically after the
a. Filled with much mineral oil such as cutting oil power turns back on again.
b. Where there is much salt such as a beach area
c. Where sulfured gas exists such as a hot-spring AIR FLOW DIRECTION ADJUST
resort
d. Where there are considerable voltage fluctua-
tions such as a factory or plant Press the AIR FLOW DIRECTION button to adjust
e. Vehicles and vessels the air flow angle.
f. Where there is much spray of oil and vapor
such as a cookery, etc.
g. Where there are machines generating electro-
magnetic waves
h. Filled with acid and/or alkaline steam or vapor
• Is a snow protection measure taken?
For details, consult your dealer. Up and down adjustment
Regarding wiring • The movable limit of the flap is changeable.
• All wiring must be performed by an authorized Contact your Daikin dealer for details.
electrician.
To do wiring, ask your dealer. Never do it by yourself.
Press the AIR FLOW DIRECTION ADJUST but-
• Make sure that a separate power supply circuit
ton to select the air direction as shown below.
is provided for this air conditioner and that all
electrical work is carried out by qualified per- The AIR FLOW FLAP display
sonnel according to local laws and regulations. swings as shown below and the
Pay attention to running noises, too air flow direction continuously
• Are the following places selected? swing
varies. (Automatic swing setting)
a. A place that can sufficiently withstand the
weight of the air conditioner with less running Press AIR FLOW DIRECTION
noises and vibrations. ADJUST button to select the air
b. A place where the hot wind discharged from the air direction of your choice.
outlet of the outdoor unit and the running noises.
• Are you sure that there are no obstacles near The AIR FLOW FLAP display
the air outlet of the outdoor unit?
stops swinging and the air flow
Such obstacles may result in declined perfor-
direction is fixed (Fixed air flow
mance and increased running noises.
direction setting).
• If abnormal noises occur in use, consult your dealer.
Regarding drainage of drain piping MOVEMENT OF THE AIR FLOW FLAP
• Is the drain piping executed to perform com-
plete drainage? For the following conditions, micro computer controls the
If proper drainage is not carried out from the out- air flow direction so it may be different from the display.
door drain pipes during air-conditioning operation, Operation
chances are that dust and dirt are clogged in the Cooling Heating
mode
pipe. This may result in a water leakage from the
• When operating • When room
indoor unit. Under such circumstances, stop the continuously at temperature is
operation of the air conditioner, and then consult horizontal air higher than the
your dealer or our service station. flow direction set temperature
Operation • At defrost operation
condition (Air is blown
horizontally to prevent
5. OPERATION PROCEDURE the cool air from being
blown directly onto
• Operation procedure anyone in the room.)
Read the operation manual attached to the
Operation mode includes automatic operation.
remote controller.
English 4
• Be careful with a scaffold or staging.
6. OPTIMUM OPERATION Caution must be exercised because of work at a
Observe the following precautions to ensure the high place.
system operates.
• Adjust the room temperature properly for a com- HOW TO CLEAN THE AIR FILTER
fortable environment. Avoid excessive heating or Clean the air filter when the display shows “ ”
cooling. (TIME TO CLEAN AIR FILTER).
• Prevent direct sunlight from entering a room dur-
It will display that it will operate for a set amount of time.
ing cooling operation by using curtains or blinds.
Increase the frequency of cleaning if the unit is
• Ventilate the room regularly.
installed in a room where the air is extremely contami-
Using the unit for long periods of time requires
nated.
attentive ventilation of the room.
If the dirt becomes impossible to clean, change the air
• Keep doors and windows closed. If the doors and
filter. (For changing air filter, please contact your
windows remain open, room air will flow out and
dealer.)
cause to decrease the effect of cooling and heating.
• Do not place other heaters directly below the 1. Open the suction grille.
indoor unit. Pull it downward slowly while pressing the
They may deform due to the heat. buttons provided on two spots.
• Never place objects near the air inlet and the air (Do the same procedure for closing.)
outlet of the unit. It may cause deterioration in the
effect or stop in the operation. Fig. 1
• Turn off the main power supply switch when it is
not used for long periods of time. When the main
power switch is turned on, some watts of electricity
is being used even if the system is not operating.
Turn off the main power supply switch for saving
energy. When reoperating, turn on the main power
supply switch 6hours before operation for smooth
running (Refer to MAINTENANCE). 2. Remove the air filters.
• When the display shows “ ” (TIME TO CLEAN Pull the hook of the air filter out diagonally
AIR FILTER), ask a qualified service person to downward, and remove the filter.
clean the filter (Refer to MAINTENANCE).
• Fully use the function of air flow direction adjust. Fig. 2
Cold air gathers on the floor, and warm air gathers
in the ceiling.
Set the air flow direction parallel during cooling or
dry operation, and set it downwards during heat-
ing operation.
Do not let the air blow directly to a person.
5 English
NOTE Fig. 4
• Do not wash the air conditioner with hot water of
more than 50°C, as doing so may result in discol-
oration and/or deformation.
• Do not expose it to fire, as doing so may result in
burning.
HOW TO CLEAN THE SUCTION GRILLE Clean the air filter and outside panels.
1. Open the suction grille. • After cleaning the air filter, make sure to attach it.
Push it downward slowly while pressing the but-
tons provided on two spots. (Follow the same Turn on the main power supply switch.
procedure for closing.) • The display on the remote controller will be shown
when the power is turned on.
English 6
• To protect the unit, turn on the main power switch • The system does not start immediately after
at least 6 hours before operation. the power supply is turned on.
Wait one minute until the micro computer is pre-
WHAT TO DO WHEN STOPPING THE SYS- pared for operation.
TEM FOR A LONG PERIOD
Turn on FAN OPERATION for a half day and dry II. WHITE MIST COMES OUT OF A UNIT
the unit. • When humidity is high during cooling opera-
• Read the operation manual attached to the tion. (In oily or dusty places)
remote controller. If the inside of an indoor unit is extremely con-
taminated, the temperature distribution inside a
Cut off the power supply. room becomes uneven. It is necessary to clean
• When the main power switch is turned on, some the inside of the indoor unit. Ask your Daikin
watts of electricity is being used even if the sys- dealer for details on cleaning the unit. This oper-
tem is not operating. ation requires a qualified service person.
Turn off the main power supply switch for saving • When the system is changed over to HEATING
energy. OPERATION after DEFROST OPERATION.
• The display on the remote controller will vanish Moisture generated by DEFROST becomes
when the main power switch is turned off. steam and exists.
Clean the air filter and the exterior. III. NOISE OF AIR CONDITIONERS
• Be sure to replace the air filter to its original place A ringing sound after the unit is started.
after cleaning. Refer to “MAINTENANCE”. This sound is generated by the temperature reg-
ulator working.
It will quiet down after about a minute.
• A continuous flow “Shuh” sound is heard
8. NOT MALFUNCTION OF THE AIR when the systems is in COOLING or
CONDITIONER DEFROST OPERATION.
This is the sound of refrigerant gas flowing
The following symptoms do not indicate air condi- through both indoor and outdoor units.
tioner malfunction • A “Shuh” sound which is heard at the start or
immediately after the stop of operation or
I. THE SYSTEM DOES NOT OPERATE which is heard at the start or immediately
• The system does not restart immediately after the stop of DEFROST OPERATION.
after the ON/OFF button is pressed. This is the noise of refrigerant caused by flow
If the OPERATION lamp lights, the system is in stop and flow change.
normal condition.
• A continuous low “Shah” sound is heard
It does not restart immediately because a safety
device operates to prevent overload of the sys- when the system is in COOLING OPERATION
tem. After 3 minutes, the system will turn on or at a stop.
again automatically. The noise is heard when the drain pump is in
• The system does not restart immediately when operation.
TEMPERATURE SETTING button is returned to • A “Pishi-pishi” squeaking sound is heard
the former position after pushing the button. when the system is in operation or after the
If the OPERATION lamp lights, the system is in stop of operation.
normal condition. Expansion and contraction of plastic parts
It does not restart immediately because a safety caused by temperature change makes this noise.
device operates to prevent overload of the sys-
tem. After 3 minutes, the system will turn on IV. DUST FROM THE UNITS
again automatically. • Dust may blow out from the unit after starting
• The system does not start when the display operation from long resting time.
Dust absorbed by the unit blows out.
shows “ ” (UNDER CENTRALIZED
CONTROL) and it flashes for a few seconds V. THE UNITS GIVE OFF ODORS
after pressing an operation button. The unit absorbs the smell of rooms, furniture,
This is because the system is under centralized cigarettes, etc., and then emits them.
control. Flashes on the display indicates that the
system cannot be controlled by the remote con-
troller.
7 English
VI. THE LIQUID CRYSTAL OF THE REMOTE II. If the system does not properly operate except
CONTROLLER SHOW “ ” for the above mentioned case, and none of the
• It happens immediately after the main power above mentioned malfunctions is evident,
supply switch is turned on. investigate the system according to the fol-
This shows that the remote controller is in nor- lowing procedures.
mal condition.
This continues temporary. 1. If the system does not operate at all.
• Check if there is a power failure.
Wait until power is restored. If power failure
occurs during operation, the system automati-
cally restarts immediately after the power sup-
9. TROUBLE SHOOTING ply recovers.
• Check if no fuse has blown.
I. If one of the following malfunctions occurs, Turn off the power supply.
take the measures shown below and contact • Check if the breaker is
your Daikin dealer.
blown.
Turn the power on with
The system must be repaired by a qualified service
the breaker switch in
person.
the off position.
Do not turn the power
WARNING on with the breaker switch in the trip position.
When the air conditioner is in abnormal con- (Contact your dealer.)
ditions (smell of something burning, etc),
unplug the power cord from the outlet, and 2. If the system stops operating after operating
contact your dealer the system.
Continued operation under such circumstances
• Check if the air inlet or outlet of outdoor or indoor
may result in a failure, electric shock, and fire.
unit is blocked by obstacles.
Remove the obstacle and make it well-ventilated.
• If a safety device such as a fuse, a breaker or an • Check if the air filter is clogged.
earth leakage breaker frequently actuates; Ask a qualified service person to clean the air
Measure: Do not turn on the main power switch. filters (Refer to MAINTENANCE).
• If the ON/OFF switch does not properly work;
Measure: Turn off the main power switch.
3. The system operates but it does not suffi-
• If water leaks from unit.
ciently cool or heat.
Measure: Stop the operation.
• If the air inlet or outlet of the indoor or the outdoor
• If the display “ ” (INSPECTION), “UNIT No.”, unit is blocked with obstacles.
and the OPERATION lamp flash and the “MAL- Remove the obstacle and make it well-ventilated.
FUNCTION CODE” appears. • If the air filter is clogged.
OPERATION lamp Ask a qualified service person to clean the air
filters (Refer to MAINTENANCE).
• If the set temperature is not proper.
• If the FAN SPEED button is set to LOW SPEED.
UNIT No.
• If the air flow angle is not proper (Refer to AIR
C L H FLOW DIRECTION ADJUST).
• If the doors or the windows are open. Shut doors
or windows to prevent wind from coming in.
INDOOR UNIT No. in which a • If direct sunlight enters the room (when cooling).
INSPECTION malfunction occurs.
Use curtains or blinds.
display MALFUNCTION • When there are too many inhabitants in the
CODE room (when cooling).
Measure: Notify your Daikin dealer and inform Cooling effect decreases if heat gain of the
him/her of the display. room is too large.
• If the heat source of the room is excessive
(when cooling).
Cooling effect decreases if heat gain of the
room is too large.
English 8
3P184442-8B EM04A036C (0704) FS HT
00_CV_3PA60995-8V.fm Page 1 Monday, July 10, 2006 12:02 PM
OPERATION MANUAL
MODELS
Ceiling mounted cassette type (Multi flow model)
FCQ100PV4A
FCQ125PV4A
FCQ140PV4A
4 11 2 1
3
6 hr
8
C L H
hr NOT 10
5 TEST AVAILABLE
9
7 12
13 20
19
TEST
18
15 14 16 17 21
k j
a i
h
f
e g
d e
3
b
c d
e
f
hr
C
l H
2 4
3
01_EN_3PA60995-8V.fm Page 4 Monday, July 10, 2006 9:22 PM
4
01_EN_3PA60995-8V.fm Page 5 Monday, July 10, 2006 9:22 PM
The refrigerant in the air conditioner is safe and nor- The appliance is not intended for use by young chil-
mally does not leak. If the refrigerant leaks inside the dren or infirm persons without supervision.
room, the contact with a fire of a burner, a heater or a Young children should be supervised to ensure that
cooker may result in a harmful gas. they do not play with the appliance.
Do not use the air conditioner until when a service person Consult with installation contractor for cleaning the
confirms to finish repairing the portion where the refriger- inside of the air conditioner.
ant leaks. Wrong cleaning may make the plastics parts broken or
Do not use any fuse with improper capacity. cause failure of water leakage or electric shock.
The use of a piece of wire and whatnot may result in a fail- Do not touch the air inlet or aluminium fin of the air
ure and fire. conditioner.
Be sure to establish an earth. Otherwise, injury may be caused.
Do not earth the unit to a utility pipe, arrester, or tele- Do not place objects in direct proximity of the out-
phone earth. door unit and do not let leaves and other debris
Incomplete earth may cause electrical shock, or fire. accumulate around the unit.
A high surge current from lightning or other sources may Leaves are a hotbed for small animals which can enter the
cause damage to the air conditioner. unit. Once in the unit, such animals can cause malfunc-
Be sure to install an earth leakage breaker. tions, smoke or fire when making contact with electrical
Failure to install an earth leakage breaker may result in parts.
electric shocks, or fire.
OPERATION RANGE
CAUTION
If the temperature or the humidity is beyond the following con-
Do not use the air conditioner for other purposes. ditions, safety devices may work and the air conditioner may
Do not use the air conditioner for a special application such not operate, or sometimes, water may drop from the indoor
as the storage of foods, animals and plants, precision unit.
machines, and art objects as otherwise the deterioration of
Cooling
quality may result.
Do not remove the air outlet of the outdoor unit. INDOOR OUTDOOR
The fan may get exposed and result in injury. TEMPERATURE HUMIDITY TEMPERATURE
When the air conditioner is used in combination with 80% or below
burners or heaters, perform sufficient ventilation. DB 21 to 32 °C (Long time operation in a
Insufficient ventilation may result in an oxygen deficiency humidity over 80% may DB –5 to 46 °C
accident.
Check and make sure that foundation blocks are not WB 14 to 25 °C cause condensation on
the unit and dripping.)
damaged after a long use.
If they are left in a damaged condition, the unit may fall and Heating
result in injury. INDOOR OUTDOOR
Neither place a flammable spray bottle near the air TEMPERATURE TEMPERATURE
conditioner nor perform spraying.
Doing so may result in a fire. DB –20 to 21 °C**
To clean the air conditioner, stop operation, and DB 15 to 27 °C
unplug the power cord from the outlet.
Otherwise, an electric shock and injury may result. WB –20 to 15.5 °C**
Do not operate the air conditioner with a wet hand.
An electric shock may result. **–20~–15°CWB: Range for operation
Do not place items which might be damaged by –15~15.5°CWB: Range for continuous operation
moisture under the indoor unit which may be dam- DB: Dry bulb temperature WB: Wet bulb temperature
aged by water. The setting temperature range of the remote controller is
Condensation may form if the humidity is above 80%, if the 16°C to 32°C.
drain outlet gets blocked or the filter is polluted.
Do not place a burner or heater at a place directly Tips for saving energy
exposed to the wind from the air conditioner. • Be careful not to cool (heat) the room too much.
Incomplete combustion of the burner or heater may result. Keeping the temperature setting at a moderate level
Do not allow a child to mount on the outdoor unit or helps save energy.
avoid placing any object on it. • Cover windows with a blind or a curtain.
Falling or tumbling may result in injury. Blocking sunlight and air from outdoors increases the
Do not expose animals and plants directly to the cooling (heating) effect.
wind. Recommended temperature setting
Adverse influence to animals and plants may result.
For cooling 26 to 28 °C
Do not wash the air conditioner with water.
Electric shock or fire may result. For heating 20 to 24 °C
Do not install the air conditioner at any place where
flammable gas may leak out.
If the gas leaks out and stays around the air conditioner, a
fire may break out.
Execute complete drain piping for perfect drainage.
Incomplete piping may result in a water leakage.
5
01_EN_3PA60995-8V.fm Page 6 Monday, July 10, 2006 9:22 PM
• Make sure that a separate power supply circuit is pro- DISPLAY “ L H ” (FAN SPEED)
vided for this air conditioner and that all electrical 8
work is carried out by qualified personnel according The display shows the fan speed: “LOW” or “HIGH”.
to local laws and regulations.
DISPLAY “ ” (AIR FLOW FLAP)
9
Pay attention to running noises, too Refer to page 8.
• Are the following places selected?
a. A place that can sufficiently withstand the weight of the DISPLAY “ ” (TIME TO CLEAN AIR FILTER)
10
air conditioner with less running noises and vibrations. Refer to page 9.
b. A place where the hot wind discharged from the air
outlet of the outdoor unit and the running noises. DISPLAY “ ” (DEFROST/HOT START)
• Are you sure that there are no obstacles near the air 11 Refer to page 7.
outlet of the outdoor unit? “ ” is not displayed when the unit is in cooling only
Such obstacles may result in declined performance and mode.
increased running noises. NON-FUNCTIONING DISPLAY
• If abnormal noises occur in use, consult your dealer.
12 If that particular function is not available, pressing the
Regarding drainage of drain pipe button may display the words “NOT AVAILABLE” for a
• Is the drain pipe executed to perform complete drain- few seconds.
age? TIMER MODE START/STOP button
If proper drainage is not carried out from the outdoor drain 13
Refer to page 8.
pipes during air-conditioning operation, chances are that
dust and dirt are clogged in the pipe. This may result in a TIMER ON/OFF button
14
water leakage from the indoor unit. Under such circum- Refer to page 8.
stances, stop the operation of the air conditioner, and then
INSPECTION/TEST OPERATION button
consult your dealer or our service station.
15 This button is used only by qualified service persons
NAME AND FUNCTION OF EACH SWITCH for maintenance purposes.
Do not use it in normal operation.
AND DISPLAY ON THE REMOTE CON-
PROGRAMMING TIME button
TROLLER
16 Use this button for programming “START and/or
Refer to figure 1 on page 3
STOP” time.
The illustrations in this operating manual correspond to the
remote control format BRC1C type. TEMPERATURE SETTING button
17 Use this button for SETTING TEMPERATURE of the
ON/OFF button thermostat.
1 Press the button and the system will start. Press the FILTER SIGN RESET button
button again and the system will stop. 18
Refer to page 9.
OPERATION lamp (RED)
2 FAN SPEED CONTROL button
The lamp lights up during operation.
19 Press this button to select the fan speed, LOW or
HIGH, of your choice.
6
01_EN_3PA60995-8V.fm Page 7 Monday, July 10, 2006 9:22 PM
OPERATION MODE SELECTOR button 5. Press AIR FLOW DIRECTION ADJUST button.
20 Refer to page 8 for details.
Press this button to select OPERATION MODE.
AIR FLOW DIRECTION ADJUST button STOPPING THE SYSTEM
21 6. Press ON/OFF button once again.
Refer to page 8.
• OPERATION lamp goes off, and the system stops
NOTE OPERATION.
• For the sake of explanation, all indications are shown on • The fan may keep on running for about 1 minute after
the display in figure 1 on page 3 contrary to actual run- the heating operation stops.
ning situations. (To start the next operation smoothly.)
ATTENTION:
OPERATION PROCEDURE • Do not turn OFF power immediately after the unit stops.
Refer to figure 1 on page 3 Then, wait no less than 5 minutes. Water is leaking or
• To protect the unit, turn on the main power supply switch 6 there is something else wrong with the unit.
hours before operation. • When the operation is started again immediately after
• If the main power supply switch is turned off during opera- being stopped, when the operation mode is changed over,
tion, operation will restart automatically after the power or when the TEMPERATURE SETTING button is pressed
turns back on again. then returned soon, the air conditioner will start the oper-
ation automatically about 5 minutes later (because the air
COOLING · HEATING · AUTOMATIC · FAN AND conditioner is controlled so that excessive load is not
PROGRAM DRY Operation applied).
Operate in the following order.
Characteristics of the heating operation
1. Press OPERATION MODE SELECTOR button several
times and select the OPERATION MODE of your choice (1) DEFROST OPERATION
as follows. • As the frost on the coil of an outdoor unit increase,
heating effect decreases and the system goes into
COOLING Operation ................................ “ ”
DEFROST OPERATION.
HEATING Operation ................................. “ ” • The indoor unit fan stops and the remote controller dis-
AUTOMATIC Operation ............................ “ ” plays shows “ ” (DEFROST/HOT START).
• In this operation mode, COOL/HEAT changeover is • After 6 to 8 minutes (maximum 10 minutes) of
automatically conducted. DEFROST OPERATION, the system returns to HEAT-
FAN Operation ...........................................“ ” ING OPERATION.
DRY Operation ..........................................“ ” (2) HOT START
• The function of this program is to decrease the • In order to prevent cold air from blowing out of an
humidity in your room with the minimum temperature indoor unit at the start of heating operation, the indoor
decrease. fan is automatically stopped. The display of the remote
• Micro computer automatically determines TEMPER- controller shows “ ” (DEFROST/HOT START).
ATURE and FAN SPEED. (3) OPERATION START
• This system does not go into operation if the room • For ordinary heating, it will take longer for the room
temperature is below 16°C. temperature to reach the set temperature than with
Refer to figure 3 on page 3 cooling. We therefore recommend starting the unit
2. Press ON/OFF button. ahead of time using the timer operation.
OPERATION lamp lights up and the system starts
OPERATION. ADJUSTING THE AIR FLOW DIRECTION
ADJUSTMENT • Press the AIR FLOW DIRECTION button to adjust the air
flow angle.
3. Press TEMPERATURE SETTING button and program
the setting temperature.
Each time this button is pressed, setting temper-
ature rises 1°C.
Each time this button is pressed, setting temper-
ature lowers 1°C.
NOTE
• Set the temperature within the operation range shown in
the table on page 5.
• The temperature cannot be set in the fan operation.
4. Press FAN SPEED CONTROL button. Up and down adjustment
High or Low fan speed can be selected.
NOTE
• In the heating operation, the fan stops during defrosting or
at startup. It does not indicate any abnormality.
7
01_EN_3PA60995-8V.fm Page 8 Monday, July 10, 2006 9:22 PM
1. Press the AIR FLOW DIRECTION ADJUST button to 2. Press the PROGRAMMING TIME button and set the
select the air direction as shown below. time for stopping or starting the system.
When this button is pressed, the time advances
The AIR FLOW FLAP display swings
by 1 hour.
as shown left and the air flow direction
When this button is pressed, the time goes
continuously varies.
backward by 1 hour.
swing (Automatic swing setting)
3. Press the TIMER ON/OFF button.
Press AIR FLOW DIRECTION The timer setting procedure ends.
ADJUST button to select the air The display “ or ” changes from flashing
direction of your choice. light to a constant light.
8
01_EN_3PA60995-8V.fm Page 9 Monday, July 10, 2006 9:22 PM
9
01_EN_3PA60995-8V.fm Page 10 Monday, July 10, 2006 9:22 PM
10
01_EN_3PA60995-8V.fm Page 11 Monday, July 10, 2006 9:22 PM
• A “Pishi-pishi” squeaking sound is heard when the II. If the system does not properly operate except for the
system is in operation or after the stop of operation. above mentioned case, and none of the above men-
Expansion and contraction of plastic parts caused by tem- tioned malfunctions is evident, investigate the system
perature change makes this noise. according to the following procedures.
IV. DUST FROM THE UNITS 1. If the system does not operate at all.
• Dust may blow out from the unit after starting opera- • Check if there is a power failure.
tion from long resting time. Wait until power is restored. If power failure occurs dur-
Dust absorbed by the unit blows out. ing operation, the system automatically restarts imme-
diately after the power supply recovers.
V. THE UNITS GIVE OFF ODORS • Check if a fuse has blown.
The unit absorbs the smell of rooms, furniture, cigarettes, Turn off the power supply.
etc., and then emits them. • Is the breaker blown?
VI.THE LIQUID CRYSTAL OF THE REMOTE CONTROL- Turn the power on with the breaker switch in the off
LER SHOW “ ” position.
• It happens immediately after the main power supply Do not turn the power on with the breaker switch in the
switch is turned on. trip position.
This shows that the remote controller is in normal condition. (Contact your dealer.)
This continues temporary. ON
Switch
TROUBLE SHOOTING
Trip position
I. If one of the following malfunctions occurs, take the Breaker
OFF
measures shown below and contact your dealer.
The system must be repaired by a qualified service person. 2. If the system stops operating after operating the
system.
• Check if the air inlet or outlet of outdoor or indoor unit
WARNING
is blocked by obstacles.
• When the air conditioner is in abnormal conditions Remove the obstacle and make it well-ventilated.
(smell of something burning, etc), unplug the power • Check if the air filter is clogged.
cord from the outlet, and contact your dealer Ask a qualified service person to clean the air filters
Continued operation under such circumstances may result (Refer to MAINTENANCE).
in a failure, electric shock, and fire.
3. The system operates but it does not sufficiently cool
or heat.
• If a safety device such as a fuse, a breaker or an earth
• If the air inlet or outlet of the indoor or the outdoor unit
leakage breaker frequently actuates;
is blocked with obstacles.
Measure: Do not turn on the main power supply switch.
Remove the obstacle and make it well-ventilated.
• If the ON/OFF button does not properly work;
• If the air filter is clogged.
Measure: Turn off the main power supply switch.
Ask a qualified service person to clean the air filters
• If water leaks from unit.
(Refer to MAINTENANCE).
Measure: Stop the operation.
• If the set temperature is not proper (Refer to ADJUST-
• If the display “ ” (INSPECTION), “UNIT No.”, and the
MENT).
OPERATION lamp flash and the “MALFUNCTION CODE”
• If the FAN SPEED button is set to LOW SPEED (Refer
appears.
to ADJUSTMENT).
OPERATION lamp • If the air flow angle is not proper (Refer to ADJUSTING
THE AIR FLOW DIRECTION).
• If the doors or the windows are open. Shut doors or
windows to prevent wind from coming in.
• If direct sunlight enters the room (when cooling).
Use curtains or blinds.
UNIT No. • When there are too many inhabitants in the room
C H (when cooling).
Cooling effect decreases if heat gain of the room is too
INDOOR UNIT No. in which a large.
malfunction occurs • If the heat source of the room is excessive (when cool-
ing).
INSPECTION MALFUNCTION
Cooling effect decreases if heat gain of the room is too
display CODE large.
Measure: Notify your dealer and inform him/her of the
display.
11
00_CV_3PA60995-8V.fm Page 4 Monday, July 10, 2006 12:02 PM