SIEMENS-7SA522 Setting Calculation

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 20

Addr.

Setting Title Setting Options Set Value

Configuration File

103 Group Change OPTION Disabled Disabled


Enabled

110 Trip Mode 3pole only 1 & 3 pole


1-/3pole

112 Phase Distance Quadrilateral Quadrilateral


MHO
Disabled

113 Earth Distance Quadrilateral Quadrilateral


MHO
Disabled

120 Power Swing Disabled Enabled


Enabled

121 Teleprot. Dist. PUTT PUTT


POTT
UNBLOCKING
BLOCKING
Disabled

122 DTT Direct Trip Disabled Disabled


Enabled

124 SOTF Overcurr. Disabled Enabled


Enabled

125 Weak infeed Disabled Disabled


Enabled

126 Back-Up O/C Disabled Disabled


TOC IEC
TOC ANSI

131 Earth Fault O/C Disabled TOC IEC


TOC IEC
TOC ANSI
TOC Logarithm.
Definite Time

132 Teleprot. E/F Dir. Comp. Pickup Disabled


UNBLOCKING
BLOCKING
Disabled

133 Auto Reclose Disabled Disabled


1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT

134 AR Control Mode Pickup w/Tact Pickup w/Tact


Pickup w/o Tact
Trip w/Tact
Trip w/o Tact

135 Synchro-Check Disabled Disabled


Enabled

137 Overvoltage Disabled Disabled


Enabled

138 Fault Locator Disabled Enabled


Enabled

139 BREAKER FAILURE Disabled Disabled


Enabled

140 Trip Circ. Superv Disabled Disabled


1 trip circuit
2 trip circuit
3 trip circuit

Power System Data

201 CT Starpoint Towards Line Towards Line


towards Busbar

203 Unom PRIMARY 1.0.1200.0 KV 220

204 Unom SECONDARY 80.125 V 110

205 CT PRIMARY 10.5000 A 800

206 CT SECONDARY 1A 1
5A

210 U4 transformer not connected Not connected


Udelta transformer
Usync transformer
Ux reference transformer

211 Uph/Udelta 0.10.9.99 1.73

212 Usync connect L1-E L1-E


L2-E
L3-E
L1-L2
L2-L3
L3-L1

214 Usync-Uline 0.36 0

215 U-line / Usync 0.80.1.20 1

220 14 transformer Not connected Neutral Current of


Neutral Current (of the parallel line
the protected line)
Neutral Current of
the parallel line
Starpoint Curr.of earthed
power transf.

221 I4/Iph CT 0.010.5.000 1

230 Rated Frequency 50 Hz 50 Hz


60 Hz

235 PHASE SEQ L1L2L3 L1L2L3


L1L3L2

236 Distance Unit km km


miles

237 Format Z0/Z1 Zero seq. comp.factors Zero seq. comp.


RE/RL and XE/XL factors RE/RL and XE/XL
Zero seq.comp. Factor KO
and angle(KO)

239 T-CB close 0.01..0.60 sec 0.05 sec ( Not required )

240 Tmin TRIP CMD 0.02..30.00 sec 0.10 sec

241 Tmax CLS CMD 0.01..30.00 sec 0.10 sec ( Not required )

242 T-CB test-dead 0.00..30.00 sec 1.0 Second

302 CHANGE Group A Group A


Group B
Group C
Group D
Binary Input
Protocol

D R Settings

402A WAVE FORM CAPTURE Save with Pickup Save With Pick Up
Save with TRIP
Start with TRIP

403A SCOPE OF WAVE FORM DATA Fault event Power System Fault
Power System fault

410 MAX LENGTH 0.30..5.00 sec 3.00 sec

411 PRE. TRING. TIME 0.05..5.00 sec 0.2

412 POST REC. TIME 0.05..5.00 sec 2

415 Binin CAPT.TIME 0.10..5.00 sec 1.0 seconds

610 Flt Disp. LED/LCD DIsplay Targets on every Display Targets on every
Pickup Pickup
Display Targets on TROP
only

Line Parametrs ( In ohms/perkm/per phase primary ohms )

R1 = 0.0795
X1 = 0.398

Ro = 0.27
Xo = 1.29

RoM = 0.159
XoM = 0.62

Zone Reaches ( In percentage )

Z1 = 80.00%
Z1B = 150.00%
Z2 = 150.00%
Z3 = 223.00%
Z4 = 223.00%
Z5 (R,F) = 22.30%

Station Name
Line Name
General Protection Data

1103 Full Scale Volt. 1.0.001200 kV 220

1104 Full Scale Curr. 10..5000 A 800

1105 Line Angle 30..89 79

1110 x' 0.005..6.500 Ohm/km 0.15920

1111 Line Length 1.0..1000.0 km 25.600

1112 x' 0.005..10.500 Ohm/mile NA

1113 Line Length 0.6..650.0 Miles NA

1116 RE/RL(Z1) -33.7 0.80

1117 XE/XL(Z1) -33.7 0.75

1118 RE/RL(Z1B..Z5) -33.7 0.80

1119 XE/XL(Z1B..Z5) -33.7 0.75

1120 K0(Z1) 0.000.4.00 0.75

1121 Angle KO(Z1) -135.00135 -0.76

1122 KO(Z1) 0.000.4.000 0.75

1123 Angle KO(>Z1) -135.00135 -0.76

1126 RM/RL Paraline 0.00..8.00 0.67

1127 XM/XL Para Line 0.00..8.00 0.52

1128 RATIO Par. Comp 50.95% 85%

1130 Pole Open Current 0.05..1.00 A 0.1 Amps

1131 Pole Open Voltage 2.70 A 30 V

1132 Sl Time all Cl. 0.01..30.00 0.2 seconds


Minimal time for line open before
1133 0.05.30.00 0.25 sec
SOTF
1134 Line Closure Manual Close B1 only
Current OR voltage or
Manual close B1
Cbaux OR Current or Man- Cbaux OR Current or Man-
ual close B1 ual close B1
Current flow or Manual close
B1
1135 Reset Trip CMD with Pole Open Current with Cbaux AND Pole
Threshold only Open Current
with Cbaux AND Pole
Open Current

1140 I-Ctsat. Thres. 0.2..50.0 A 5.0 Amps

1150 Sl Time Man.Cl 0.01..30.00 sec 0.2 Seconds

1151 SYN.MAN.CL with Synchronism-check No


without Synchronism-check
NO

1155 3pole coupling with Pickup With Trip


with Trip

1156 Trip2ph Flt 3 pole 3 pole


1 pole, leading phase
1 pole, lagging phase

Distance Protection data

1201 FCT Distance ON ON


OFF

1202 Minimum Iph> 0.10..4.00 A 0.25

1203 310> Threshold 0.05..4.00 A 0.08

1204 3U0> Threshold 1..100 V 15 V

1207 310>/Iphmax 0.05..0.30 0.15

1215 Paral. Line Comp NO YES


YES

1221 2Ph-E faults Blcok leading ph-e loop All loops


block lagging ph-e loop
all loops
only phase-phase loops
only phase-earth loops

1232 SOFT Zone with Pickup(non-directional) with Zone Z1B


with Zone Z1B
Inactive

1241 R load (ph-E) 0.10..250.00 Ohm 77.44

1242 Angle Load (ph-E) 20.60 degree 25.84

1243 R load (ph-ph) 0.10..250.00 Ohm 77.44


1244 Angle load (ph-ph) 20..60 degree 25.84

Distance Protection with polygonal tripping Chatracteristic

1301 Op. mode Z1 Forward Forward


Reverse
Non-directional
Inactive

1302 R(Z1) (ph-ph) 0.05..250.00 Ohm 5.00

1303 X(Z1) 0.05..250.00 Ohm 3.26

1304 RE(Z1) Ph-E 0.05..250.00 Ohm 10.00

1305 T1 - 1 phase 0.00..30.00 sec 0.100 sec

1306 T1 - multi-phase 0.00..30.00 sec 0.100 sec

1307 Zone reduction 0..30 degree 0 degree

1311 Op.mode Z2 Forward Forward


Reverse
Non-Directional
Inactive

1312 R(Z2) ( ph-ph) 0.05..250.00 Ohm 5.00

1313 X (Z2) 0.05..250.00 Ohm 6.11

1314 R(Z2) O-E 0.05..250.00 Ohm 15.00

1315 T2-1 phase 0.00 - 30.00 sec 0.3 Secs

1316 T2- multi phase 0.00 - 30.00 sec 0.3 secs

1317 Trip 1 pole Z2 NO NO


YES

1321 Op. mode Z3 Forward Forward


Reverse
Non-Directional
Inactive

1322 R(Z3) ph-ph 0.05..250.00 Ohm 5.00

1323 X(Z3) 0.05..250.00 Ohm 9.09

1324 R(Z3) ph-E 0.05..250.00 Ohm 15.00


1325 T3 DELAY 0.00..30.00 sec 1.0 secs

1325 T3 DELAY 0.00..30.00 sec 1.0 secs

1331 Op. mode Z4 Forward INACTIVE


Reverse
Non-Directional
Inactive

1341 Op. mode Z5 Forward Reverse


Reverse
Non-Directional
Inactive

1342 R(Z5) ph-ph 0.05..250.00 Ohm 5.00

1343 X ( Z5 ) 0.05..250.00 Ohm 0.91

1344 R(Z5) ph-E 0.05..250.00 Ohm 10.00

1345 T5 DELAY 0.00..30.00 sec 1.0 Secs

1346 X(Z5) - 0.05..250.00 Ohm 0.91

1351 Op. mode Z1B Forward Forward


Reverse
Non-Directional
Inactive

1352 R(Z1B) ph-ph 0.05..250.00 Ohm 5.00

1353 X(Z1B) 0.05..250.00 Ohm 6.11

1354 R(Z1B) ph-E 0.05..250.00 Ohm 15.00

1355 T1B-1 phase 0.00 - 30.00 sec 0.0 secs

1356 T1B- multi phase 0.00 - 30.00 sec 0.00 sec

1356 T1B- multi phase 0.00 - 30.00 sec 0.00 sec

1357 1st AR-> Z1B NO YES


YES

Power Swing Settings

2002 P/S Op. mode all zones blocked Z2 to Z5 blocked


Z1/Z1B blocked
Z2 to Z5 bocked
1.Z1B,Z2 blocked
2006 Power Swing trip NO NO
YES

Distance protection teleprotection Schemes

2101 FCT Telep. Dis. ON ON


YES

2102 Type of Line Two terminals Two terminals


Three terminals

2103 Send Prolong 0.00 - 30.00 sec 0.07 sec

2107 Delay for alarm 0.00 - 30.00 sec NA

2108 Release Delay 0.00 - 30.00 sec NA

2109 TrBlk Wait Time 0.00 - 30.00 sec NA

2110 TrBlk Block Time 0.00 - 30.00 sec NA

2201 FCT Direct Trip ON NO


OFF

2202 Trip time DELAY 0.00 - 30.00 sec NA

2401 FCT SOTF-O/C ON ON


OFF

2404 I>>> 0.00 - 25.00 A 2.5 Amps

Weak End Infeed

2501 FCT Weak Inteed OFF OFF


Echo only
Echo and Trip

Back up O/C current Function Settings

2601 Operating Mode ON Only Active with Loss of


Only Active with Loss of VT sec. Circuit
VT sec. Circuit
OFF

2630 Iph> STUB 0.10..25.00 A 1.0 A

2631 T Iph STUB 0.00..30.00 sec 0.2 sec

2632 310> STUB 0.05..25.00 A 1.0 A


2633 T 310> STUB 0.00..30.00 sec 0.2 sec

2634 I -STUB Tele/B1 NO NO


YES

2635 I -STUB SOTF NO NO


YES

YES

2680 SOTF Time DELAY 0.00..30.00 sec 0.2 Secs

Supervision function Settings

2901 MEASURE SUPERV ON OFF


YES

2910 FUSE FAIL MON ON ON


OFF

2911 FFM U> (min) 10.100 V 50 Volts

2912 FFM U> (max) 0.10..1.00 A 0.2 Amps

2913 FFM U<max (3ph) 2..10 A 5V

2914 FFM ldelta (3p) 0.05..1.00 A 0.10 A

2921 T mcb 0..30 ms 0 ms

Earth Fault Overcurrent Settings

3101 FCT EarthFltO/C ON ON


OFF

3102 BLOCK for Dist. With every Pickup With every Pickup
with single-phase Pickup
with multi-phase Pickup
NO

3103 BLOCK 1pDead Tim YES YES


NO

3104 lph-STAB Slope 0- 30 % 10%

3105 31oMin Teleprot 0.01..1.00 A NA

3105 31oMin Teleprot 0.003..1.000 A NA


3110 Op. mode 310 >>> Forward Inactive
Reverse
Non-Directional
Inactive

3120 Op. mode 310>> Forward Inactive


Reverse
Non-Directional
Inactive

YES

3130 Op. mode 310> Forward Inactive


Reverse
Non-Directional
Inactive

3140 Op. mode 310p Forward Forward


Reverse
Non-Directional
Inactive

3141 310p PICKUP 0.20..25.00 A 0.25

3142 T 310p MinT DELAY 0.00..30.000 1.1

3143 310p Time Dial 0.05..3.00 sec 0.52

3144 310p Time Dial 0.50..15.00 NA

3145 310p Time Dial 0.50..15.00 sec NA

3146 T 310p MaxT DELAY 0.00..30.00 sec NA

3147 Add.T-DELAY 0.00..30.00 sec 0

3148 310p Telep/B1 NO NO


YES

3149 310p SOTF-Trip NO NO


YES

3150 310p InrushBlk NO NO


YES

3151 IEC curve Normal Inverse Normal Inverse


Very Inverse
Extremely Inverse
Long time Inverse
3152 ANSI Curve Inverse NA
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse

3153 LOG Curve Logarithmic Inverse NA

3154 310p Startpoint 1.0..4.0 NA

with U2 and I2 (negative


3160 POLARIZATION with UO and 1Y (dual sequence)
polorized)
with 1Y (transformer star
point current)
with U2 and I2 (negative
sequence)

3162 Dir. ALPHA 0..360 degree 338 degree

3163 Dir. BETA 0..360 degree 122 degree

3164 3U0> 0.5..10.0 V 2V

3165 IY> 0.05..1.00 A 0.2 A

3166 3U2> 0.5..10.0 V 5V

3167 312> 0.05..1.00 A 0.05

3170 2nd InrushRest 10..45% NA

3171 Imax InrushRest 0.50..25.00 A NA

3172 SOTF Op. Mode with Pickup (non- NA


directional)
with Pickup and direction

3173 SOTF Time DELAY 0.00..30.00 sec NA

Teleprotection for Earth fault Relay

3201 FCT Telep. E/F ON OFF


OFF

Auto reclose Function


3401 Automatic Reclosure ON / OFF OFF

Synchronism Function

3501 FCT Synchronism ON/ OFF OFF

Voltage Protection Function

3701 FCT U Phase - e OFF OFF


ALARM ONLY
ON

3702 Uph -e> 1.0-170 Volts 95.26

3703 T Uph -e > 0.00-30.00 secs 0.1

3705 T Sen - Impulse ( Uphe ) 0.05 - 0.50 secs 0.1 secs

3721 3 Uo > Staus OFF OFF


ALARM ONLY
ON

3725 T sen Impulse 3Uo 0.05-0.50secs 0.1

Fault Locator Settings

3802 START Pick Up Pick up


Trip

3805 Parallel line Compensation NO YES


YES

3806 Load Compensation NO YES


YES

Breaker Failure Function Settings

3901 FCT Breaker Failure ON OFF


OFF

Trip Circuit supervision

4001 FCT Trip Supervision ON OFF


OFF
Output is stored in the Word file 7SA522 in the same directory. However it has to copied