Section 204: Dead Loads
Section 204: Dead Loads
Section 204: Dead Loads
DEAD LOADS
204.1 General
Dead loads consists of the weight of all
materials of construction incorporated into
the building or other structure, including but
not limited to walls, floors, roofs, ceilings,
stairways, built-in partitions, finishes,
cladding and other similarly incorporated
architectural and structural items, and fixed
service equipment, including the weight of
cranes.
Exception:
Access floor systems shall be designed to
support, in addition to all other loads, a
uniformly distributed dead load not less than
0.5kPa.
SECTION 205
LIVE LOADS 205.3.2 Concentrated Loads
Floor shall be designed to support safely the
uniformly distributed live loads given in
205.1 General Table 205-1 whichever produces the greatest
load effects. Unless otherwise specified the
Live loads shall be the maximum loads indicated concentration shall be assumed to
expected by the intended use or occupancy be uniformly distributed over an area 750-
but in no case shall be less than the loads mm square and shall be located so as to
required by this section. produce the maximum load effects in the
structural member.
For those conditions where light-page metal 205.5. Reduction of Live Loads
performed structural sheets serve as the
The design live load determined using the
support and finish of roofs, roof structural
unit live loads as set forth in Table 205-1 for
members arranged to create continuity shall
roofs may be reduced on any member
be considered adequate if designed for full
supporting more than 15 m2, including flat
dead loads on all spans in combination with
slabs, except for floors in places of public
the most critical one of the following
superimposed loads: assembly and for live loads greater than 4.8
kPa, in accordance with the following
equation:
1. The uniform roof live load, L, set R=r(A-15) (205-1)
forth in Table 205-3 on all spans.
The reduction shall not exceed 40 percent for
2. A concentrated gravity load, L, of 9
members receiving load from one level, 60
kN placed on any span supporting a
percent for other members or R, as
tributary area greater than 18m2 to
determined by the following equation:
create maximum stresses in the
number, whenever this loading R= 23.1(1+ D/L) (205-2)
creates greater stresses than those
caused by the uniform live load. The where
concentrated load shall be placed on A = area of floor or roof supported by the
the member over a length of 0.75 m member, m2
along the span. The concentrated load
need not be applied to more than one D = dead load per square meter of area
span simultaneously. supported by the member, kPa
3. Water accumulation as prescribed in L = unit live load per square meter of area
Section 206.7. supported by the member, kPa
R = reduction in percentage.
r = rate of reduction equal to 0.08 for floors.
See table 205-3 for roofs.
For storage loads exceeding 4.8 kPa, no
reduction shall be made, except that design
live loads on columns may be reduced 20
percent.
The live load reduction shall not exceed 40
percent in garages for the storage of private
pleasure cars having a capacity of not more
than nine passengers per vehicle.
1
L = L0 [0.25 + 4.57 ( )] (205-3)
√𝐴1
where
A1 = influence area, m2
L = reduced design live load per square meter
of area supported by the member
L0 = unreduced design live load per square
meter of area supported by the member
(Table 205-1)
qp = velocity pressure at top parapet, in N/m2 𝛆̅ = integral length scale power law exponent
in Equation 27A.9.9 from Table 207A.9-1
qr = velocity pressure evaluated at height z
above ground, in N/m2 λ = adjustment factor for building height and
exposure from Figures. 207C.-1 and 207E.51
R = resonant response factor from Equation
207A.9-12 ὴ = value send I Equation 207A9-15
Rh, RL = values from Equations 207A.9-15 θ = angel of plane of roof from horizontal, in
degrees.
Ri = reduction response factor from Equation
207A.11-1
Rn = value from Equation 207A.9-13 207A.4 General
s = vertical dimension of the solid 207A.4.1 Sign Convention
freestanding wall or solid sign from Figure
Positive pressure acts toward the surface and
207D.4-1, in m
negative pressure acts away from the surface.
r = rise-to-span ratio for arched roofs
v = height-to-width ratio solid sign
207A.4.2 Critical Load Condition
V = basic wind speed obtained from Figure
Values of external and internal pressure shall
207A.5-1A through 207A.5-IC in m/s. The
be combined algebraically to determine the
basic wind spend corresponds to a 3-s gust
most critical load.
speed at 10 m above the ground in Exposure
Category C,
Vi = unpartitioned internal volume m3 207A.4.3 wind Pressure Acting on
Opposite Faces of Each Building Surface
̅̅̅
𝑽𝒛 = mean hourly wind speed at height 𝒛̅ m/s
In the calculation of design wind loads for the
W = width of building in Figures 207E.-3 and
MWFRS and for components and cladding
207E.4-5A and 207E.4-5B and width of span
for buildings, the algebraic sum of the
in Figures 207E.4-4 and 207E.4-6
pressures acting on opposite faces of each
x = distance upwind or downwind of crest in building surface shall be taken into account.
Figure 207A.8-1, in m
z = height above ground level, in m
Commentary:
𝒛̅= equivalent height of structure, in m Section 207A.4.3 is included in the code to
ensure that internal and external pressures
acting on a building surface area taken into on several factors important to an accurate
account by determining a net pressure from wind specification.
the algebraic sum of those pressures. For
1. A strength design wind speed map brings
additional information on the application of
the wind loading approach in line with that
the net components and cladding wind
used for seismic loads in that they both
pressure acting across a multilayered
essentially eliminate the use of a load factor
building envelope system, including air-
for strength design.
permeable cladding, refer to Section
C207E.1.5. 2. Multiple maps remove inconsistencies in
the use of importance factors that actually
should vary with location and between
207A.5 Wind Hazard Map tropical cyclone-prone regions for
Occupancy Category III, IV and V structures
207A.5.1 Basic Wind Speed and acknowledge that the demarcation
The basic wind speed, V, used in the between tropical cyclone and non-tropical
determination of design wind loads on cyclone winds change with the recurrence
buildings and other structures shall be interval.
determined from Figure 207A.5-1 as follows, 3. The new maps establish uniformity in the
except as provided in Section 207A.5.2 and return period of the design-basis winds, and
207A.5.3: they more clearly convey that information.
For Occupancy Category III, IV and V 4. The new maps, by providing the design
buildings and other structures-use Figure wind speed directly, more clearly inform
207A.5-1A. owners and their consultations about the
For Occupancy Category II buildings and storm intensities for which designs are
other structures-use Figure 207A.5-1B. performed.
This edition of NSCP departs from prior To determine the return periods to be used in
editions by providing wind maps that are the new mapping approach, the task
directly applicable for determining pressures committee needed to meet with PAGASA
for strength design approaches. Rather than scientists, gather historical records and
using a single map with importance factors evaluate representative return period for
and a load factor for each building wind speeds determined in accordance with
occupancy category in this edition there are Section 207 NSCP 2010 and earlier, wherein
different maps for different categories of determination of pressures appropriate for
building occupancies. The updated maps are strength design started with mapped wind
based on a new and more complete analysis speeds, but involved multiplication by
of tropical cyclone characteristics (Vickery et importance factors and a wind load factor to
al. 2008a, 2008b and 2009) performed over achieve pressures that were appropriate for
the past 10 years. strength design. Furthermore, it was
assumed that the variability of the wind speed
The decision to move to multi-strength design dominated the calculation of the wind load
maps in conjunction with a wind load factor factor. The strength design wind load, WT, is
of 1.0 instead of using a single map used with given as:
an importance and a load factor of 1. Relied
WT, = CF,(V50 I )2 WLF (c207A.5-1)
Where CF is a building, component, or years. In the development of Equation
structure specific coefficient that includes the C207A.5-6, the term (V100 /V50) WLF replaces
effects of the things like building height, the WLF used in Equation C207A.5-5,
building geometry, terrain, and gust factor as effectively resulting in a higher load factor
computed using the procedures outlined in for Occupancy Category I, II and III
NSCP 2010. VLF is the 50-year return period structures equal to WLF(V100 /V50)2. Thus for
design win speed. WLF is the wind load occupancy Category I and II structures, the
factor, and I is the importance factor. basic wind speed is associated with a return
period of 1,700 years, or an annual
Starting with the nominal return period of 50
exceedance probability of 0.000588.
years, the ratio of the wind speed for any
Similarly, the 25-year return period wind
return period to the 50-year return period
speed associated with Occupancy Category
wind speed can be computed from Peterka
III, IV and V buildings equates to a 300-year
and Shahid (1998):
return period wind speed with a wind load
VT/V50 = [0.3+0.11n(12T)] (c207A.5-2) factor of 1.0.
where T is the return period in years and VT Wind Speed. The wind speed maps of Figure
is the T- year return period wind speed. The 207A.5-1 present basic wind speeds for the
strength design wind load, WT, occurs when: entire archipelago of the Philippines. The
wind speeds correspond to a 3-sec gust
WT = CF𝑽𝟐𝑻 = 𝐂𝐅𝑽𝟐𝟓𝟎 WLF (c207A.5-3) speeds at 1om above ground for exposure
Thus, category C.
The wind directionality factor, Kd, shall be The descriptions of the surface roughness
determined from Table 207A.-1. This categories and exposure categories in
directionality factor shall only be included in Section 207A.7 have been expressed as far as
determining wind loads when the load possible in easily understood verbal terms
combinations specified in Section 2.3 and 2.4 that are sufficiently precise for most practical
are used for the design. The effect of wind applications. Upwind surface roughness
directionality in determining wind loads in conditions required for Exposure B and D
accordance with Section 207F shall be based are shown schematically in Figures
on an analysis for wind speeds that conforms C207A.7-1 and C207.7-2, respectively. For
to the requirements of Section 207A.5.3 cases where the designer wishes to make a
more detailed assessment of the surface
roughness category and exposure category,
Commentary: the following more mathematical description
is offered for guidance (Irwin 2006). The
The wind load factor 1.3 in ASCE 7-95 ground surface roughness is best measured in
include a “wind directionality factor” of 0.85 terms of a roughness length parameter called
(Ellingwood 1981 and Ellingwood et al. z0. Each of the surface roughness categories
1982). This factor accounts for two effects: B through D correspond to a range of values
(1) The reduced probability of maximum
of this parameter, as does the even rougher contains open patches, such as highways,
category A used in previous versions of the parking lots ad playing fields. These cause
code in heavily built-up urban area but local increases in the wind speeds at their
removed in the present edition. The range of edges. By using an expose coefficient
z0 in meters (m) for each terrain category is corresponding to a lower than typical value
given in Table C207A.7-1. Exposure A has of z0. Some allowance is made for this. The
been included in C207A.7-1 as a reference alternative would be to introduce a number
that may be useful when using the Wind of exceptions to use of Exposure B in
Tunnel Procedure. Further information on suburban areas, which would add an
values of z0 in different types of terrain can be undesirable level of complexity.
found in Simiu and Scanlan (1996) and Table
The value of z0 for a particular terrain can be
C207A.7-2 based on Davenport et al. (2000)
estimated from the typical dimensions of a
and Wieringa et al. (2001). The roughness
surface roughness elements and their spacing
classifications in Table C207A.7-2 are not
on the group area using an empirical
intended to replace the use of exposure
relationship, due to Lettqu (1969), which is:
categories as required in the code for
structural design purposes. However, the 𝑺𝒐𝒃
z0 = 0.5Hob (C207A.7-1)
terrain roughness classification in Table 𝑨𝒐𝒃
C207A.7-2 may be related to ASCE 7
Hob = the average height of the roughness in
exposure categories by comparing z0 values
the upwind terrain
between Table C207A.7-1 and Table
C207A.7-2 fall within the range of z0 values Sob = the average vertical frontal area per
for Exposure C in Table C207A.7-1. obstruction presented to the wind
Similarly, the z0 values for Classes 5 and 6 in
Aob = the average area of ground occupied by
Table C207A.7-2 fall within the range of z0
each obstruction, including the open area
values for Exposure B in Table C207A.7-1.
surrounding it