MCP
MCP
MCP
Easier Installations
With a wide adjustment range, there is no need to swap devices to cover
the horsepower range of a starter. For example, the 30A MCP has an FLA
adjustment range of 1.5A to 27A, covering the entire range of NEMA size 00,
0 and 1 starters. The settings align directly with information published on the
Settings for Standard or motor nameplate. Likewise, just five MCPs cover the complete range from
Energy-Efficient Motors 1/2 hp to 200 hp at 480V.
The automatic setting on the PowerPact MCP
allows for a transient motor in-rush to safely High SCCR Ratings
clear before aligning the protection to the The PowerPact MCP also helps achieve high Short Circuit Current Rating
motor’s locked rotor current. Device settings (SCCR) needed to meet recent code changes for industrial control panels.
align directly with the various classifications They deliver up to 100kA at 480V SCCR when used in combination with
found on the motor nameplate. Square D® NEMA or Telemecanique® IEC motor starters.
Better Equipment Protection and Safety
The PowerPact MCP provides for quick and decisive tripping when your
motor exceeds its current limitations, improving the longevity of your
equipment. This eliminates a common misapplication that occurs when
instantaneous trip points are adjusted too far above the motor’s locked rotor
current to avoid nuisance tripping on high in-rush currents. The mechanism
is also designed to ensure that the handle of the breaker provides positive
indication that the contacts are in the ON, OFF or tripped position.
Ordering Information/Specifications
Based on 2005 NEC table 430.52 Based on 2005 NEC table 430.250
Maximum Rating or Setting of MCP Selection by Horsepower Ratings of Induction Type
Motor Protective Devices Squirrel-Cage and Wound Rotor Motors
Three Phase 60 Hz AC Full Load
Percentage of Full-Load Current Suffix
Type of Motor 200V 230V 460V 575V Amperes
Setting Not to Exceed^ 1/2 – 5 hp 1/2 – 7.5 hp 3/4 – 15 hp 1 – 20 hp 15 – 25 M71
A,B,C,D Standard 800% 1300% 5 – 10 5 – 15 10 – 30 15 – 40 14 – 42 M72
10 – 25 15 – 30 25 – 60 30 – 75 30 – 80 M73
Energy 20 – 40 25 – 50 50 – 100 60 – 125 58 – 130 M74
B,E 1100% 1700%
Efficient
40 – 60 50 – 75 100 – 150 125 – 200 114 – 217 M75
^ See NEC Exception No. 1 to table 430.52. Listed voltages are rated motor voltages. Corresponding system voltages are 200, 220 to 240, 440
The NEC 1300% maximum setting may be inadequate for to 480 and 550 to 600 volts. Select wire and circuit breakers on the basis of horsepower rather than
instantaneous-trip circuit breakers to withstand current surges nameplate full-load current per NEC 430.6(A) for general motor applications.
typical of the magnetization current of autotransformer type
reduced voltage starters, or open transition wye-delta starters Per NEC 430.3, part-winding motors should select two circuit breakers, each at not more than one
during transfer from “start” to “run,” constant horsepower multi- half the allowable trip setting for the horsepower rating. The two circuit breakers should be operated
speed motors, and motors labeled “high efficiency.” simultaneously as a disconnecting means per NEC 430.103.
Tested to meet NEC and UL 508A requirements for short circuit current ratings as part of an approved combination controller.
National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Quincy, MA.