Laboratory Test Report On Plate Load Bearing: (ASTM D 1194)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

LABORATORY TEST REPORT ON PLATE LOAD BEARING

( ASTM D 1194 )

DATE : March 07, 2018


LAB. NO. :

CUSTOMER/ CLIENT SHIMIZU PHILIPPINE CONTRACTORS, INC.


PROJECT EPP 1 FACTORY RENOVATION WORKS ( INK BOTTLE EXPANSION)
LOCATION Lima Technology Center, Lipa Batangas DEAD WT. OF EQUIPMENT, kN : 0.3716
DATE TESTED February 28, 2018 CALIBRATION, kN. : 1.4892
TEST PIT NUMBER TP-1 ( GL Y11' to GL X6) PLATE DIAMETER, cm. : 30.775
TEST DEPTH 1FL -0.3 meters AREA, m² : 0.0745
TYPE OF SOIL Silty Sand w/ Gravel WEATHER : Cloudy
TESTED BY ETC MTCI Personnel MOISTURE CONDITION : Wet

PLATE LOAD BEARING TEST DATA


Adjusted Time Displacement (Per Division) Total Pressure
Cycle Load (kN) Time Average
Load (min.) Strain A Strain B Strain C Settlement (mm) (kPa)

1 4 5.8608 0 2:45 PM 40 45 0 28 78.668


1 2:46 PM 40 45 0 28
2 2:48 PM 41 45 0 29
3 2:51 PM 41 45 0 29
3 2:54 PM 41 45 0 29
3 2:57 PM 41 45 0 29
3 3:00 PM 41 45 0 29 0.2867
2 8 9.8608 0 3:00 PM 75 92 21 63 132.36
1 3:01 PM 76 92 22 63
2 3:03 PM 77 92 22 64
3 3:06 PM 78 92 22 64
3 3:09 PM 78 92 22 64
3 3:12 PM 78 92 22 64
3 3:15 PM 78 92 22 64 0.6400
3 12 13.8608 0 3:15 PM 98 115 36 83 186.05
1 3:16 PM 101 118 37 85
2 3:18 PM 102 119 38 86
3 3:21 PM 103 120 38 87
3 3:24 PM 103 120 38 87
3 3:27 PM 103 120 38 87
3 3:30 PM 103 120 38 87 0.8700
Remarks : This report is the result of test performed on the sample tested on site.

Witnessed By:
F. Ariban
Shimizu Representative - P.E.

Tested by: Checked by: Certified by:

Eduard Zamora/Ronel Rodela/Dexter M. Copino Engr. Raul Leslie S. Banzon Jeffrey C. Reyes
Laboratory Technicians Laboratory Head Managing Director
LABORATORY TEST REPORT ON PLATE LOAD BEARING
( ASTM D 1194 )

DATE : March 07, 2018


LAB. NO. :

CUSTOMER/ CLIENT SHIMIZU PHILIPPINE CONTRACTORS, INC.


PROJECT EPP 1 FACTORY RENOVATION WORKS ( INK BOTTLE EXPANSION)
LOCATION Lima Technology Center, Lipa Batangas DEAD WT. OF EQUIPMENT, kN : 0.3716
DATE TESTED February 28, 2018 CALIBRATION, kN. : 1.4892
TEST PIT NUMBER TP-1 ( GL Y11' to GL X6) PLATE DIAMETER, cm. : 30.775
TEST DEPTH 1FL -0.3 meters AREA, m² : 0.0745
TYPE OF SOIL Silty Sand w/ Gravel WEATHER : Cloudy
TESTED BY ETC MTCI Personnel MOISTURE CONDITION : Wet

PLATE LOAD BEARING TEST DATA


Adjusted Time Displacement (Per Division) Total Pressure
Cycle Load (kN) Time Average
Load (min.) Strain A Strain B Strain C Settlement (mm) (kPa)
4 16 17.8608 0 3:30 PM 106 127 48 94 239.74
1 3:31 PM 108 129 49 95
2 3:33 PM 108 129 49 95
3 3:36 PM 108 129 49 95
3 3:39 PM 108 129 49 95
3 3:42 PM 108 129 49 95
Release 3 3:45 PM 108 129 49 95 0.9533
5 11 12.8608 0 3:45 PM 108 129 49 95 172.63
1 3:46 PM 108 129 49 95
2 3:48 PM 108 129 49 95
3 3:51 PM 108 129 49 95
3 3:54 PM 108 129 49 95
3 3:57 PM 108 129 49 95
3 4:00 PM 108 129 49 95 0.9533
6 6 7.8608 0 4:00 PM 108 128 43 93 105.51
1 4:01 PM 108 128 43 93
2 4:03 PM 108 128 43 93
3 4:06 PM 108 128 43 93
3 4:09 PM 108 128 43 93
3 4:12 PM 108 128 43 93
3 4:15 PM 108 128 43 93 0.9300
Remarks : This report is the result of test performed on the sample tested on site.

Witnessed By:
F. Ariban
Shimizu Representative - P.E.

Tested by: Checked by: Certified by:

Eduard Zamora/Ronel Rodela/Dexter M. Copino Engr. Raul Leslie S. Banzon Jeffrey C. Reyes
Laboratory Technicians Laboratory Head Managing Director
LABORATORY TEST REPORT ON PLATE LOAD BEARING
( ASTM D 1194 )

DATE : March 07, 2018


LAB. NO. :

CUSTOMER/ CLIENT SHIMIZU PHILIPPINE CONTRACTORS, INC.


PROJECT EPP 1 FACTORY RENOVATION WORKS ( INK BOTTLE EXPANSION)
LOCATION Lima Technology Center, Lipa Batangas DEAD WT. OF EQUIPMENT, kN : 0.3716
DATE TESTED February 28, 2018 CALIBRATION, kN. : 1.4892
TEST PIT NUMBER TP-1 ( GL Y11' to GL X6) PLATE DIAMETER, cm. : 30.775
TEST DEPTH 1FL -0.3 meters AREA, m² : 0.0745
TYPE OF SOIL Silty Sand w/ Gravel WEATHER : Cloudy
TESTED BY ETC MTCI Personnel MOISTURE CONDITION : Wet

PLATE LOAD BEARING TEST DATA


Adjusted Time Displacement (Per Division) Total Pressure
Cycle Load (kN) Time Average
Load (min.) Strain A Strain B Strain C Settlement (mm) (kPa)
7 0 1.8608 0 4:15 PM 78 99 12 63 24.98
1 4:16 PM 77 98 12 62
2 4:18 PM 76 97 12 62
3 4:21 PM 76 97 12 62
3 4:24 PM 76 97 12 62
3 4:27 PM 76 97 12 62
3 4:30 PM 76 97 12 62 0.6167

Remarks : This report is the result of test performed on the sample tested on site.

Witnessed By:
F. Ariban
Shimizu Representative - P.E.

Tested by: Checked by: Certified by:

Eduard Zamora/Ronel Rodela/Dexter M. Copino Engr. Raul Leslie S. Banzon Jeffrey C. Reyes
Laboratory Technicians Laboratory Head Managing Director