VLT HVAC Basic Quick Start Guide MG18A302
VLT HVAC Basic Quick Start Guide MG18A302
VLT HVAC Basic Quick Start Guide MG18A302
www.danfoss.com/drives
Quick Guide
VLT® HVAC Basic Drive
*MG18A302*
Contents VLT HVAC Basic Drive Quick Guide
Contents
1 Quick Guide 2
1.1 Safety 2
1.1.1 Warnings 2
1.1.2 Safety Instructions 2
1.2 Introduction 3
1.2.1 Available Literature 3
1.2.2 Approvals 3
1.2.3 IT Mains 3
1.2.4 Avoid Unintended Start 3
1.2.5 Disposal Instruction 4
1.3 Installation 4
1.3.1 Before Starting Repair Work 4
1.3.2 Side-by-Side Installation 4
1.3.3 Dimensions 5
1.3.4 Electrical Installation in General 6
1.3.5 Connecting to Mains and Motor 8
1.3.6 Fuses 14
1.3.7 EMC-Correct Electrical Installation 16
1.3.8 Control Terminals 18
1.3.9 Electrical Overview 19
1.4 Programming 20
1.4.1 Programming with the Local Control Panel (LCP) 20
1.4.3 The Start-up Wizard for Open Loop Applications 21
1.5 Parameter Overview 28
1.6 Warnings and Alarms 33
1.7 General Specifications 35
1.7.1 Mains Supply 3 x 200-240 V AC 35
1.7.2 Mains Supply 3 x 380-480 V AC 36
1.7.3 Mains Supply 3 x 380-480 V AC 38
1.7.4 Mains Supply 3 x 525-600 V AC 40
1.7.5 EMC Test Results 41
1.8 Special Conditions 44
1.8.1 Derating for Ambient Temperature and Switching Frequency 44
1.8.2 Derating for Low Air Pressure 44
1.9 Options for VLT HVAC Basic Drive FC101 44
1 1 1 Quick Guide
CAUTION
1.1 Safety Leakage Current:
The earth leakage current from the frequency converter
1.1.1 Warnings exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced
Protective Earth connection must be ensured by means of
WARNING a min. 10 mm² Cu or an additional PE wire - with the same
cable cross section as the Mains wiring - must be
High Voltage Warning terminated separately.
The voltage of the frequency converter is dangerous
Residual Current Device:
whenever it is connected to mains. Incorrect installation of
This product can cause a DC current in the protective
the motor or frequency converter may cause damage to
conductor. Where a residual current device (RCD) is used
the equipment, serious injury or death. Consequently, it is
for extra protection, only an RCD of Type B (time delayed)
essential to comply with the instructions in this manual as
shall be used on the supply side of this product. See also
well as local and national rules and safety regulations.
Danfoss Application Note on RCD, MN90GXYY.
Protective earthing of the frequency converter and the use
WARNING of RCDs must always follow national and local regulations.
Electrical Hazard
Motor thermal protection:
Touching the electrical parts may be fatal - even after the
Motor overload protection is possible by setting Parameter
equipment has been disconnected from mains. Also make
1-90 Motor thermal protection to the value Electronic
sure that other voltage inputs have been disconnected
Thermal Relay (ETR) trip.
(linkage of DC intermediate circuit). Be aware that there
may be high voltage on the DC link even when the LEDs
are turned off. Before touching any potentially live parts of WARNING
the frequency converter, wait at least as stated in the table
Installation at high altitudes
below:
For altitudes above 2 km, please contact Danfoss regarding
PELV.
Voltage (V) Power range (kW) Min. waiting time
(minutes)
3 x 200 0.25 – 3.7 4
1.1.2 Safety Instructions
3 x 200 5.5 – 11 15
3 x 400 0.37 – 7.5 4 • Make sure the frequency converter is properly
connected to earth.
3 x 400 11 – 90 15
3 x 600 2.2 – 7.5 4 • Do not remove mains connections, motor
3 x 600 11 – 90 15 connections or other power connections while
the frequency converter is connected to power.
1.2 Introduction 1 1
130BC251.10
1.2.1 Available Literature
1.2.2 Approvals
1.2.3 IT Mains
CAUTION
IT Mains Illustration 1.2 IP54 400 V 0.75-18.5 kW
Installation on isolated mains source, i.e. IT mains. 1: EMC screw
Max. supply voltage allowed when connected to mains:
440 V (3 x 380-480 V units).
On all units, set par. 14-50 RFI filter to OFF when operating
On IP20 200-240 V 0.25-11 kW and 380-480 V IP20 0.37-22 in IT mains.
kW, open the RFI switch by removing the screw on the
side of the frequency converter when at IT grid.
CAUTION
If reinserted, only use M3 x 12 screw.
130BB612.10
1 1 1.2.5 Disposal Instruction Voltage (V) Power range (kW) Min. waiting time
(minutes)
Equipment containing electrical components 3 x 200 0.25 – 3.7 4
must not be disposed of together with domestic 3 x 200 5.5 – 45 15
waste. 3 x 400 0.37 – 7.5 4
It must be separately collected with electrical 3 x 400 11 – 90 15
and electronic waste according to local and 3 x 600 2.2 – 7.5 4
currently valid legislation. 3 x 600 11 – 90 15
The frequency converter can be mounted side-by-side and requires the clearance above and below for cooling.
NOTE
With IP21/Nema Type1 option kit mounted, a distance of 50 mm between the units is required.
1.3.3 Dimensions 1 1
e
130BC246.10
e
130BC205.10
B
130BB614.10
0D
b
f
C
a
A
a
e e
Enclosure Power [kW] Height [mm] Width [mm] Depth Mounting hole [mm] Max.W
[mm] eight
Frame IP Class 3x 3x 3x A "A incl a B b C d e f Kg
200-240 V 380-480 V 525-60 Decoupling
0V Plate"
H1 IP20 0.25-1.5 0.37-1.5 195 273 183 75 56 168 9 4.5 5.3 2.1
kW kW
H2 IP20 2.2 kW 2.2-4.0 kW 227 303 212 90 65 190 11 5.5 7.4 3.4
H3 IP20 3.7 kW 5.5-7.5 kW 255 329 240 100 74 206 11 5.5 8.1 4.5
H4 IP20 5.5-7.5 kW 11-15 kW 296 359 275 135 105 241 12.6 7 8.4 7.9
H5 IP20 11 kW 18.5-22 334 402 314 150 120 255 12.6 7 8.5 9.5
kW
H6 IP20 15-18.5 30-45 kW 22-30 518 595/635(45 495 239 200 242 - 8.5 15 24.5
kW kW kW)
H7 IP20 22-30kW 55-75 kW 45-55 550 630/690(75 521 313 270 335 - 8.5 17 36
kW kW)
H8 IP20 37-45kW 90 kW 75-90 660 800 631 375 330 335 - 8.5 17 51
kW
H9 IP20 2.2-7.5 269 374 257 130 110 205 11 5.5 9 6.6
kW
H10 IP20 11-15 399 419 380 165 140 248 12 6.8 7.5 12
kW
I2 IP54 0.75-4.0 332 - 318.5 115 74 225 11 5.5 9 5.3
kW
I3 IP54 5.5-7.5 kW 368 - 354 135 89 237 12 6.5 9.5 7.2
I5 IP54 11-18.5 480 - 454 242 210 260 19 9 9 23
kW
I6 IP54 22-37 kW 650 - 624 242 210 260 19 9 9 27
I7 IP54 45-55 kW 680 - 648 308 272 310 19 9 9.8 45
I8 IP54 75-90 kW 770 - 739 370 334 335 19 9 9.8 65
The dimensions are only for the physical units, but when installing in an application it is necessary to add space for free air
passage both above and below the units. The amount of space for free air passage is listed in Table 1.1:
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors required, (75°C) recommended.
130BB634.10
maximum cross-section on wires please see section
1.7 General Specifications.
1 Line
2 Earth
3 Motor
4 Relays
H6 Frame H7 Frame 1 1
IP20 380-480 V 30-45 kW IP20 380-480 V 55-75 kW
IP20 200-240 V 15-18.5 kW IP20 200-240 V 22- 30 kW
IP20 525-600 V 22-30 kW IP20 525-600 V 45-55 kW
130BB762.10
130BB763.10
03 02 01
06 05 04
L1 91 / L2
92 / L3 93
U 96 / V 97
/ W 98
95
99
1 1 2
4
2 3 4
1 Line
2 Motor 1 Line
3 Earth 2 Relays
4 Relays 3 Earth
4 Motor
1 1 H8 Frame H9 Frame
IP20 380-480 V 90 kW IP20 600 V 2.2-7.5 kW
IP20 200-240 V 37-45 kW
IP20 525-600 V 75-90 kW
130BA261.10
130BB764.10
91 95
L1 92
L1 93
L1 99
96
U 97
V 98
w
M
A
I N
S
RELAY 1 RELAY 2
95
-D
C+
DC
1 BR
-B
R+
U
4 V
W
2
- LC +
1 Line
99
2 Relays
3 Earth
4 Motor 130BA262.10
I
N
S
95
RELAY 2
RELAY 1
+D
C
BR
-
BR
+
U
V
W
1 1
130BA263.10
130BT302.12
M
A
I MOTOR
N
S
RELAY 2
95
MOTO
99 R
UVW
RELAY 1
L1
L2
91 L3
92
93
+D
C
BR
- B
R+
U
V
W
H10 Frame
130BA264.10
91 L2 N
S
92 L3
93
RELAY 2
130BA725.10
RELAY 1
+D
C
BR
- B
R+
U
99 V
W
- LC -
1 1 I2 Frame I3 Frame
IP54 380-480 V 0.75-4.0 kW IP54 380-480 V 5.5-7.5 kW
130BC299.10
130BC201.10
1
1 RS 485 1 RS 485
2 Line in 2 Line in
3 Earth 3 Earth
4 Wire clamps 4 Wire clamps
5 Motor 5 Motor
6 UDC 6 UDC
7 Relays 7 Relays
8 I/O 8 I/O
130BC203.10
130BT326.10
130BT325.10
1 1 1.3.6 Fuses
130BA215.10
REL
AY
1 Branch circuit protection
01 REL
AY
In order to protect the installation against electrical and
2
03
02
fire hazard, all branch circuits in an installation, switch
gear, machines etc., must be short-circuit and overcurrent
04
05
90
protected according to national/international regulations.
9
6
9
Overcurrent protection
Provide overload protection to avoid overheating of the
311
cables in the installation. Overcurrent protection must
always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable
of supplying a maximum of 100,000 Arms (symmetrical),
480 V maximum.
I7, I8 Frame
IP54 380-480 V 45-55 kW Non UL compliance
IP54 380-480 V 75-90 kW If UL/cUL is not to be complied with, Danfoss recommends
using the fuses mentioned in Table 1.3, which will ensure
compliance with IEC 61800-5-1:
In case of malfunction, not following the fuse recommen-
130BA248.10
95 99
1.3.7 EMC-Correct Electrical Installation high frequencies. Use the cable clamps provide-
dinstead.
General points to be observed to ensure EMC-correct • It is important to ensure good electrical contact
electrical installation. from the installation plate through the installation
screws to the metal cabinet of the frequency
• Use only screened/armoured motor cables and converter.
screened/armoured control cables.
• Use starwashers and galvanically conductive
• Connect the screen to earth at both ends. installation plates.
• Avoid installation with twisted screen ends • Do not use unscreened/unarmoured motor cables
(pigtails), since this ruins the screening effect at in the installation cabinets.
1 1
130BB761.10
PLC etc. Panel
Output con-
tactor etc.
PLC
Earthing rail
Cable insula-
tion stripped
Min. 16 mm2
Equalizing cable
Motor cable
Min. 200mm
between control
Mains-supply cable, mains cable
and between mains
L1 motor cable
L2
L3
PE Motor, 3 phases and
Reinforced protective earth
Protective earth
Illustration 1.3 EMC-correct Electrical Installation
130BC249.10
130BB622.10
130BB625.10
OFF ON
61 68 69 18 19 27 29 42 45 50 53 54
10V OUT
10V/20mA IN
10V/20mA IN
DIGI IN
DIGI IN
DIGI IN
DIGI IN
COMM. GND
P
N
130BB626.10
L1 U
L2 V
3 Phase
power L3 W
input
PE PE
Motor
UDC-
Not present on all power sizes
UDC+
0-10Vdc- 54 (A IN) 04
0/4-20 mA
55 (COM A IN/OUT) relay1
42 0/4-20mA A OUT / DIG OUT 03
240V AC 3A
45 0/4-20mA A OUT / DIG OUT 02
Bus ter. 01
12 (+24V OUT) ON=Terminated
ON
1 2
OFF=Unterminated
18 (DIGI IN)
24V (NPN)
OV (PNP)
19 (DIGI IN)
24V (NPN)
20 (COM D IN) OV (PNP)
Bus ter.
27 (DIGI IN)
24V (NPN) RS-485 (N PS-485) 69
OV (PNP) RS-485
29 (DIGI IN) Interface
24V (NPN) (P RS-485) 68
OV (PNP) Do not connect shield to
(Com RS-485 ) 61 61 on 116,117 and 118 unites
(PNP)-Source
(NPN)-Sink
NOTE
Please note there is no access to UDC- and UDC+ on the following units:
IP20 380-480 V 30-90 kW
IP20 200-240 V 15-45 kW
IP20 525-600 V 2.2-90 kW
IP54 380-480 V 22-90 kW
1.4.1 Programming with the Local Control 1 Parameter number and name.
Panel (LCP) 2 Parameter value.
3 Set-up number shows the active set-up and the edit set-
NOTE up. If the same set-up acts as both active and edit set-up,
only that set-up number is shown (factory setting). When
The frequency converter can also be programmed from a
active and edit set-up differ, both numbers are shown in
PC via RS485 com-port by installing the MCT-10 Set-up
the display (Setup 12). The number flashing, indicates the
Software. This software can either be ordered using code
edit set-up.
number 130B1000 or downloaded from the Danfoss Web
4 Motor direction is shown to the bottom left of the display
site: www.danfoss.com/BusinessAreas/DrivesSolutions/
– indicated by a small arrow pointing either clockwise or
softwaredownload
counterclockwise.
5 The triangle indicates if the LCP is in status, quick menu or
1.4.2 Local Control Panel (LCP) main menu.
The following instructions are valid for the FC101 LCP. The
B. Menu Key
LCP is divided into four functional sections.
Use the menu key to select between status, quick menu or
main menu.
A. Alphanumeric display
C. Navigation keys and indicator lights (LEDs)
B. Menu key
C. Navigation keys and indicator lights (LEDs) 6 Com led: Flashes when bus communication is communi-
cating.
D. Operation keys and indicator lights (LEDs)
7 Green LED/On: Control section is working.
130BB765.10
On OK 12
7 D. Operation keys and indicator lights (LEDs)
Warn
8 11
13 [Hand On]: Starts the motor and enables control of the
Alarm
9 frequency converter via the LCP.
A. Alpha Numeric Display 14 [Off/Reset]: Stops the motor (off). If in alarm mode the
The LCD-display is back-lit with 2 alpha-numeric lines. All alarm will be reset.
data is displayed on the LCP. 15 [Auto On]: frequency converter is controlled either via
control terminals or serial communication.
At power-up 1 1
At the first power-up the user is asked to choose preferred
language. Once selected this screen will never be shown
again in the following powerups, but language can still be
changed in 0-01 Language.
Select Language
130BB628.10
[ 0 ] English
Setup 1
FC
130BB674.10
+24V 12
DIG IN 18
DIG IN 19 Start
COM DIG IN 20
DIG IN 27
DIG IN 29
+10V 50
A IN +
53 Reference
A IN 54
COM 55 -
A OUT / D OUT 42 0-10V
A OUT / D OUT 45
01
R1
02
03
04
R2
05
06
1 1
130BC244.10
At power up the user is - the HVAC FC 101 Wizard starts
asked to choose the
prefered laguage. Select Regional Settings
[0] International 4
Setup 1
Select language Grid Type 5
[1] English 200-240V/50Hz/Delta
Setup 1
Setup 1 Asynchronous Motor
Menu Status Quick Main
1 Menu Menu
Set Motor Power
1.10 kW 7
Setup 1
Back
Hand Off
Reset
Auto Set Motor Frequency
On On
50 Hz 9
Setup 1
Power Up Screen
Set Motor Current
4.66 A 10
OK
Setup 1
On OK Setup 1
Warn Set Ramp 1 Ramp Down Time
Alarm
20 0003 s
Setup 1
Hand Off Auto
On Reset On
Active Flying start?
21 [0] Disable
Wizard Screen Setup 1
Select Terminal 53 Mode
Back
if Current 22 Voltage
[0] Voltage
Setup 1
On OK 27 0016 Hz
Setup 1
Warn
Alarm Set Maximum Reference
28 0050 Hz
Hand Off Auto Setup 1
On Reset On
Do AMA
Wizard completed Auto Motor Tuning OK AMA running AMA Failed
35 Press OK to accept 34 Press OK 32 ----- 33
Setup 1 Setup 1 Setup 1
0.0 Hz
36 0.0 kW
Setup 1 AMA OK AMA failed
130BC245.10
0-03 Regional Settings
1 [0] International
Motor Set-up 1 1
The Quick Menu Motor Set-up guides through the needed Changes Made
motor parameters. Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
No & Name Range Default Function are listed in changes made.
0-03 Regional [0] Interna- 0
If the parameters value is changed back to factory setting's
Settings tional
value from another different value, the parameter will NOT
[1] US
be listed in Changes Made.
0-06 Grid [0]-[132] please Size selected Select operating
Type see start-up mode for restart 1. Press [Menu] key to enter the Quick Menu until
wizard for upon indicator in display is placed above Quick Menu.
open loop reconnection of 2. Press [▲] [▼] to select either FC101 wizard, closed
application the frequency loop setup, motor setup or changes made, then
converter to press [OK].
mains voltage
after power 3. Press [▲] [▼] to browse through the parameters
down in the Quick Menu.
1-20 Motor 0.12-110 kW/ Size related Enter motor 4. Press [OK] to select a parameter.
power 0.16-150 Hp power from
5. Press [▲] [▼] to change the value of a parameter
nameplate data
setting.
1-22 Motor 50.0 - 1000.0 V Size related Enter motor
Voltage voltage from 6. Press [OK] to accept the change.
nameplate data 7. Press either [Back] twice to enter “Status”, or
1-23 Motor 20.0 - 400.0 Hz Size related Enter motor press [Menu] once to enter “Main Menu”.
Frequency frequency from
The Main Menu accesses all parameters.
nameplate data
1-24 Motor 0.01 - 10000.00 Size related Enter motor
Current A current from 1. Press [Menu] key until indicator in display is
nameplate data placed above “Main Menu”.
1-25 Motor 100.0 - 9999.0 Size related Enter motor 2. Use [▲] [▼] to browse through the parameter
Nominal RPM nominal speed groups.
Speed from nameplate
3. Press [OK] to select a parameter group.
data
4-12 Motor 0.0 - 400 Hz 0.0 Hz Enter the 4. Use [▲] [▼] to browse through the parameters in
Speed Low minimum limit the specific group.
Limit [Hz] for low speed 5. Press [OK] to select the parameter.
4-14 Motor 0-400 Hz 65 Enter the
Speed High maximum limit
6. Use [▲] [▼] to set/change the parameter value.
Limit [Hz] for high speed
3-41 Ramp 1 0.05 - 3600.0 s Size related Ramp up time
Ramp up Time from 0 to rated
motor frequency
1-23 Motor
Frequency
3-42 Ramp 1 0.05 - 3600.0 s Size related Ramp down time
Ramp Down from rated motor
Time frequency
1-23 Motor
Frequency to 0
1-73 Flying [0] Disabled 0 Select Enable to
Start [1] Enabled enable the
frequency
converter to
catch a spinning
motor
Parameter Overview 1 1
1-63 Slip Compensation Time 3-1* References 0.00 - 194.00 A, * 0.00 [54] Auto start
Constant 3-10 Preset Reference 4-51 Warning Current High [60] Counter A (up)
0.05 - 5.00 s, * 0.10 -100.00 - 100.00 %, * 0.00 0.00 - 194.00 A, * 194.00 [61] Counter A (down)
1-64 Resonance Dampening 3-11 Jog Speed [Hz] 4-54 Warning Reference Low [62] Reset Counter A
0 - 500%, * 100 0.0 - 400.0 Hz, * 5.0 -4999.000 - 4999.000, *-4999.000 [63] Counter B (up)
1-65 Resonance Dampening Time 3-14 Preset Relative Reference 4-55 Warning Reference High [64] Counter B (down)
Constant -100.00 - 100.00, * 0.00 -4999.000 - 4999.000, *4999.000 [65] Reset Counter B
0.001 - 0.050 s, * 0.005 3-15 Reference Resource 1 4-56 Warning Feedback Low 5-11 Terminal 19 Digital Input
1-7* Start Adjustments [0] No function -4999.000 - 4999.000, *-4999.000 See par. 5-10, *[0] No operation
1-71 Start Delay *[1] Analog in 53 4-57 Warning Feedback High 5-12 Terminal 27 Digital Input
0.0 - 10.0 s, * 0.0 [2] Analog in 54 -4999.000 - 4999.000, *4999.000 See par. 5-10, *[2] Coast inverse
1-72 Start Function [11] Local bus reference 4-58 Missing Motor Phase 5-13 Terminal 29 Digital Input
[0] DC Hold/delay time 3-16 Reference 2 Resource Function See par. 5-10, *[14 Jog]
*[2] Coast/delay time [0] No function [0] Off 5-3* Digital Outputs
1-73 Flying Start [1] Analog in 53 *[1] On 5-34 On Delay, Digital Output
*[0] Disabled *[2] Analog in 54 4-6* Speed Bypass 0.00 - 600.00 s, *0.01 s
[1] Enabled [11] Local bus reference 4-61 Bypass Speed From [Hz] 5-35 Off Delay, Digital Output
1-8* Stop Adjustments 3-17 Reference 3 Resource 0.0 - 400.0, * 0.0 0.00 - 600.00 s, *0.01 s
1-80 Function at Stop [0] No function 4-63 Bypass Speed To [Hz] 5-4* Relays
*[0] Coast [1] Analog in 53 0.0 - 400.0, * 0.0 5-40 Function Relay
[1] DC hold/MotorPreheat [2] Analog in 54 4-64 Semi-Auto Bypass Set-up *[0] No operation
1-82 Min Speed for Function at *[11] Local bus reference *[0] Off [1] Control ready
Stop [Hz] 3-4* Ramp 1 [1] Enable [2] Drive ready
0.0 - 20.0 Hz, * 0.0 3-41 Ramp 1 Ramp up Time 5-** Digital In/Out [3] Drive ready/remote control
1-9* Motor Temperature 0.05 - 3600.00 s, *Size related 5-0* Digital I/O mode [4] Enable / no warning
1-90 Motor Thermal Protection 3-42 Ramp 1 Ramp Down Time 5-00 Digital Input Mode [5] VLT running
*[0] No protection 0.05 - 3600.00 s, *Size related *[0] PNP [6] Running / no warning
[1] Thermistor warning 3-5* Ramp 2 [1] NPN [7] Run in range/no warning
[2] Thermistor trip 3-51 Ramp 2 Ramp up Time 5-03 Digital Input 29 Mode [8] Run on ref/no warning
[3] ETR warning 1 0.05 - 3600.00 s, *Size related *[0] PNP [9] Alarm
[4] ETR trip 1 3-52 Ramp 2 Ramp down Time [1] NPN [10] Alarm or warning
1-93 Thermistor Resource 0.05 - 3600.00 s, *Size related 5-1* Digital Inputs [12] Out of current range
*[0] None 3-8* Other Ramps 5-10 Terminal 18 Digital Input [13] Below current, low
[1] Analog input 53 3-80 Jog Ramp Time [0] No operation [14] Above current, high
[6] Digital input 29 0.05 - 3600.00 s, *Size related [1] Reset [16] Below frequency, low
2-** Brakes 3-81 Quick Stop Ramp Time [2] Coast inverse [17] Above frequency, high
2-0* DC-Brake 0.05 - 3600.00 s, *Size related [3] Coast and reset inverse [19] Below feedback, low
2-00 DC Hold/Motor Preheat 4-** Limits / Warnings [4] Quick stop inverse [20] Above feedback, high
Current 4-1* Motor Limits [5] DC-brake inverse [21] Thermal warning
0 - 160%, * 50 4-10 Motor Speed Direction [6] Stop inverse [22] Ready, no thermal warning
2-01 DC Brake Current [0] Clockwise [7] External Interlock [23] Remote, ready, no thermal
0 - 150%, * 50 *[2] Both directions *[8] Start warning
2-02 DC Braking Time 4-12 Motor Speed Low Limit [Hz] [9] Latched start [24] Ready, Voltage OK
0.0 - 60.0 s, * 10.0 0.0 - 400 Hz, * 0.0 Hz [10] Reversing [25] Reverse
2-04 DC Brake Cut In Speed 4-14 Motor Speed High Limit [11] Start reversing [26] Bus OK
0.0 - 400.0 Hz, * 0.0 [Hz] [14] Jog [35] External Interlock
2-1* Brake Energy Funct. 0.1 - 400 Hz, * 65.0 Hz [16] Preset ref bit 0 [36] Control word bit 11
2-17 Over-voltage Control 4-18 Current Limit [17] Preset ref bit 1 [37] Control word bit 12
[0] Disabled 0 - 300%, * 110 [18] Preset ref bit 2 [45] Bus Control
*[2] Enabled 4-19 Max Output Frequency [19] Freeze reference [60] Comparator 0
3-** Reference / Ramps 0.0 - 400.0 Hz, * 65.0 [20] Freeze output [61] Comparator 1
3-0* Reference Limits 4-4* Adj. Warnings 2 [21] Speed up [62] Comparator 2
3-02 Minimum Reference 4-40 Warning Freq. Low [22] Speed down [63] Comparator 3
(-4999.000) - 4999.000, * 0.000 0.0-400.0 Hz, *400.0 [23] Set-up select bit 0 [64] Comparator 4
3-03 Maximum Reference 4-41 Warning Freq. High [34] Ramp bit 0 [65] Comparator 5
(-4999.000) - 4999.000, * 50.000 0.0-400.0 Hz, *400.0 [37] Fire mode [70] Logic rule 0
4-5* Adj. Warnings [52] Run permissive 71] Logic rule 1
4-50 Warning Current Low [53] Hand Start [72] Logic rule 2
1 1 Parameter Overview
[73] Logic rule 3 [0] Current mode [26] Bus OK [4] Enable / no warning
[74] Logic rule 4 *[1] Voltage mode [35] External Interlock [5] Drive running
[75] Logic rule 5 6-2* Analog Input 54 [45] Bus Control [6] Running / no warning
[80] SL digital output A 6-20 Terminal 54 Low Voltage [60] Comparator 0 [7] Run in range/no warning
[81] SL digital output B 0.00 - 10.00V, * 0.07 [61] Comparator 1 [8] Run on ref/no warning
[82] SL digital output C 6-21 Terminal 54 High Voltage [62] Comparator 2 [9] Alarm
[83] SL digital output D 0.00 - 10.00V, * 10.00 [63] Comparator 3 [10] Alarm or warning
[160] No alarm 6-22 Terminal 54 Low Current [64] Comparator 4 [12] Out of current range
[161] Running reverse 0.00 - 20.00, * 4.00mA [65] Comparator 5 [13] Below current, low
[165] Local ref. active 6-23 Terminal 54 High Current [70] Logic rule 0 [14] Above current, high
[166] Remote ref. active 0.00 - 20.00, * 20.00mA [71] Logic rule 1 [21] Thermal warning
[167] Start command activ 6-24 Terminal 54 Low Ref./Feedb. [72] Logic rule 2 [22] Ready, no thermal warning
[168] Drive in hand mode Value [73] Logic rule 3 [23] Remote, ready, no thermal
[169] Drive in auto mode -4999.000 - 4999.000, * 0.000 [74] Logic rule 4 warning
[193] Sleep Mode 6-25 Terminal 54 High Ref./ [75] Logic rule 5 [24] Ready, Voltage OK
[194] Broken Belt Function Feedb. Value [80] SL digital output A [25] Reverse
[196] Fire Mode -4999.000 - 4999.000, * 50.000 [81] SL digital output B [26] Bus OK
[198] Drive Bypass 6-26 Terminal 54 Filter Time [82] SL digital output C [35] External Interlock
5-41 On Delay, Relay Constant [83] SL digital output D [45] Bus Control
0.00 - 600.00 s, *0.01 s 0.01 - 10.00, * 0.01 [160] No alarm [60] Comparator 0
5-42 Off Delay, Relay 6-29 Terminal 54 mode [0] [161] Running reverse [61] Comparator 1
0.00 - 600.00 s, *0.01 s Current mode [165] Local ref. active [62] Comparator 2
5-5* Pulse Input [0] Current mode [166] Remote ref. active [63] Comparator 3
5-9* Bus Controlled *[1] Voltage mode [167] Start command activ [64] Comparator 4
5-90 Digital and Relay Bus 6-7* Analog Output 45 [168] Drive in hand mode [65] Comparator 5
Control 6-70 Terminal 45 Mode [169] Drive in auto mode [70] Logic rule 0
0 - 0xFFFFFFFF, * 0 *[0] 0-20 mA [193] Sleep Mode [71] Logic rule 1
6-** Analog In/Out [1] 4-20 mA [194] Broken Belt Function [72] Logic rule 2
6-0* Analog I/O Mode [2] Digital Output [196] Fire Mode [73] Logic rule 3
6-00 Live Zero Timeout Time 6-71 Terminal 45 Analog Output [198] Bypass Mode [74] Logic rule 4
1 - 99s, * 10 *[0] No operation 6-73 Terminal 45 Output Min [75] Logic rule 5
6-01 Live Zero Timeout Function [100] Output frequency Scale [80] SL digital output A
*[0] Off [101] Reference 0.00 - 200.00%, * 0.00 [81] SL digital output B
[1] Freeze output [102] Feedback 6-74 Terminal 45 Output Max [82] SL digital output C
[2] Stop [103] Motor current Scale [83] SL digital output D
[3] Jogging [106] Power 0.00 - 200.00%, * 100.00 [160] No alarm
[4] Max. speed [139] Bus Control 6-76 Terminal 45 Output Bus [161] Running reverse
[5] Stop and trip 6-72 Terminal 45 Digital Output Control [165] Local ref. active
6-1* Analog Input 53 *[0] No operation 0.00 - 100.00%, * 0.00 [166] Remote ref. active
6-10 Terminal 53 Low Voltage [1] Control ready 6-9* Analog Output 42 [167] Start command activ
0.00 - 10.00 V, * 0.07 [2] Drive ready 6-90 Terminal 42 Mode [168] Drive in hand mode
6-11 Terminal 53 High Voltage [3] Drive ready/remote control *[0] 0-20 mA [169] Drive in auto mode
0.00 - 10.00 V, * 10.00 [4] Standby / no warning [1] 4-20 mA [193] Sleep Mode
6-12 Terminal 53 Low Current [5] Drive running [2] Digital Output [194] Broken Belt Function
0.00 - 20.00, * 4.00 mA [6] Running / no warning 6-91 Terminal 42 Analog Output [196] Fire Mode
6-13 Terminal 53 High Current [7] Run in range/no warning *[0] No operation [198] Drive Bypass
0.00 - 20.00, * 20.00 mA [8] Run on ref/no warning [100] Output frequency 6-93 Terminal 42 Output Min
6-14 Terminal 53 Low Ref./Feedb. [9] Alarm [101] Reference Scale
Value [10] Alarm or warning [102] Feedback 0.00 - 200.00%, * 0.00
-4999.000 - 4999.000, * 0.000 [12] Out of current range [103] Motor current 6-94 Terminal 42 Output Max
6-15 Terminal 53 High Ref./ [13] Below current, low [105] TorquereltoRated Scale
Feedb. Value [14] Above current, high [106] Power 0.00 - 200.00%, * 100.00
-4999.000 - 4999.000, * 50.000 [21] Thermal warning [139] Bus Control 6-96 Terminal 42 Output Bus
6-16 Terminal 53 Filter Time [22] Ready, no thermal warning 6-92 Terminal 42 Digital Output Control
Constant [23] Remote, ready, no thermal *[0] No operation 0.00 - 100.00%, * 0.00
0.01 - 10.00 s, * 0.01 warning [1] Control ready 8-** Comm. and Options
6-19 Terminal 53 mode [24] Ready, Voltage OK [2] Drive ready 8-0* Comm. General Settings
[25] Reverse [3] Drive ready/remote control 8-01 Control Site
Parameter Overview 1 1
*[0] Digital and ctrl.word *[3] Logic OR 13-0* SLC Settings [12] Analog in 53
[1] Digital only 8-52 DC Brake Select 13-00 SL Controller Mode [13] Analog in 54
[2] Controlword only [0] Digital input *[0] Off [20] Alarm number
8-02 Control Source [1] Bus [1] On [30] Counter A
[0] None [2] Logic AND 13-01 Start Event [31] Counter B
*[1] FC Port *[3] Logic OR [0] False 13-11 Comparator Operator
8-03 Control Timeout Time 8-53 Start Select [1] True [0] Less Than
0.1 - 6500.0s, * 1.0 [0] Digital input [2] Running *[1] Approx. Equal
8-04 Control Timeout Function [1] Bus [3] In range [2] GreaterThan
*[0] Off [2] Logic AND [4] On reference 13-12 Comparator Value
[1] Freeze output *[3] Logic OR [7] Out of current range -9999.0 - 9999.0, * 0.0
[2] Stop 8-54 Reversing Select [8] Below Ilow 13-2* Timers
[3] Jogging [0] Digital input [9] Above Ihigh 13-20 SL Controller Timer
[4] Max. speed [1] Bus [16] Thermal warning 0.00 - 3600.00, * 0.00
[5] Stop and trip [2] Logic AND [17] Mains out of range 13-4* Logic Rules
[20] N2 Override Release *[3] Logic OR [18] Reversing 13-40 Logic Rule Boolean 1
8-06 Reset Control Word Timeout 8-55 Set-up Select [19] Warning See par. 13-01, *[0] False
*[0] No function [0] Digital input [20] Alarm (trip) 13-41 Logic Rule Operator 1
[1] Do reset [1] Bus [21] Alarm (trip lock) *[0] Disabled
8-3* FC Port Settings [2] Logic AND [22] Comparator 0 [1] AND
8-30 Protocol *[3] Logic OR [23] Comparator 1 [2] OR
*[0] FC 8-56 Preset Reference Select [24] Comparator 2 [3] AND NOT
[2] Modbus RTU [0] Digital input [25] Comparator 3 [4] OR NOT
[3] Metasys N2 [1] Bus [26] Logic rule 0 [5] NOT AND
[4] FLN [2] Logic AND [27] Logic rule 1 [6] NOT OR
[5] BACNet *[3] Logic OR [28] Logic rule 2 [7] NOT AND NOT
8-31 Address 8-7* Bacnet [29] Logic rule 3 [8] NOT OR NOT
1 - 247 , * 1 8-70 BACnet Device Instance [33] Digital input 18 13-42 Logic Rule Boolean 2
8-32 FC Port Baud Rate 0 - 0x400000UL [34] Digital input 19 See par. 13-01, *[0] False
[0] 2400 Baud *1 [35] Digital input 27 13-43 Logic Rule Operator 2
[1] 4800 Baud 8-72 MS/TP Maxmaster [36] Digital input 29 See par. 13-41, *[0] Disabled
*[2] 9600 Baud 0 - 127, * 127 *[39] Start command 13-44 Logic Rule Boolean 3
[3] 19200 Baud 8-73 MS/TP Max Info Frames [40] Drive stopped See par. 13-01, *[0] False
[4] 38400 Baud 1 - 65534, * 1 [41] Reset trip 13-5* States
[5] 57600 Baud 8-74 "I am" Service [42] Auto reset trip 13-51 SL Controller Event
[6] 76800 Baud *[0] Send at power-up [43] Key Ok See par. 13-01, *[0] False
[7] 115200 Baud [1] Continuously [44] Key Reset 13-52 SL Controller Action
8-33 FC Port Parity 8-75 Intialisation Password [47] Key Up *[0] Disabled
*[0] Even Parity, 1 Stop Bit 8-8* FC Port Diagnostics [48] Key Down [1] No action
[1] Odd Parity, 1 Stop Bit 8-80 Bus Message Count [50] Comparator 4 [2] Select set-up 1
[2] No Parity, 1 Stop Bit 0 - 65536, * 0 [51] Comparator 5 [3] Select set-up 2
[3] No Parity, 2 Stop Bits 8-81 Bus Error Count [60] Logic rule 4 [10] Select preset ref 0
8-35 Minimum Response Delay 0 - 65536, * 0 [83] Broken belt [11] Select preset ref 1
0.001 - 0.500s, * 0.010 8-82 Slave Message Rcvd 13-02 Stop Event [12] Select preset ref 2
8-36 Max Response Delay 0 - 65536, * 0 See par. 13-02, *[40] Drive stopped [13] Select preset ref 3
0.100 - 10.000s, *5.000 8-83 Slave Error Count 13-03 Reset SLC [14] Select preset ref 4
8-37 Max Inter-char delay 0 - 65536, * 0 *[0] Do not reset [15] Select preset ref 5
0.025 - 0.025s, * 0.025 8-84 Slave Message Sent [1] Reset SLC [16] Select preset ref 6
8-5* Digital/Bus 0 - 65536, * 0 13-1* Comparators [17] Select preset ref 7
8-50 Coasting Select 8-85 Slave Timeout Errors 13-10 Comparator Operand [18] Select ramp 1
[0] Digital input 0 - 65536, * 0 *[0] Disabled [19] Select ramp 2
[1] Bus 8-88 Reset FC port Diagnostics [1] Reference [22] Run
[2] Logic AND *[0] Do not reset [2] Feedback [23] Run reverse
*[3] Logic OR [1] Reset counter [3] Motor speed [24] Stop
8-51 Quick Stop Select 8-9* Bus Feedback [4] Motor current [25] Qstop
[0] Digital input 8-94 Bus feedback 1 [6] Motor power [26] DC Brake
[1] Bus -32768 - 32767, * 0 [7] Motor voltage [27] Coast
[2] Logic AND 13-** Smart Logic [8] DC-link voltage [28] Freeze output
1 1 Parameter Overview
[29] Start timer 0 [11] Automatic reset x 15 15-05 Over Volt's 16-38 SL Controller State
[30] Start timer 1 [12] Automatic reset x 20 0 - 65535, * 0 0 - 255, * 0
[31] Start timer 2 [13] Infinite auto reset 15-06 Reset kWh Counter 16-5* Ref. and Feedb.
[32] Set digital out A low 14-21 Automatic Restart Time *[0] Do not reset 16-50 External Reference
[33] Set digital out B low 0 - 600s, * 10 [1] Reset counter -200.0 - 200.0%, * 0.0
[34] Set digital out C low 14-22 Operation Mode 15-07 Reset Running Hours 16-52 Feedback
[35] Set digital out D low *[0] Normal operation Counter -4999.000 - 4999.000, * 0.000
[38] Set digital out A high [2] Initialisation *[0] Do not reset 16-6* Inputs and Outputs
[39] Set digital out B high 14-27 Action At Inverter Fault [1] Reset counter 16-60 Digital input
[40] Set digital out C high [0] Off 15-3* Fault Log 0 - 65535, * 0
[41] Set digital out D high *[1] On 15-30 Fault Log: 16-61 Terminal 53 Setting
[60] Reset Counter A 14-28 Production Settings Error Code 0 - 255, * 0 *[0] Current mode
[61] Reset Counter B *[0] No action 15-4* Drive Identification [1] Voltage mode
[70] Start timer 3 [1] Service reset 15-40 FC Type 16-62 Analog Input 53
[71] Start timer 4 [3] Software Reset 15-41 Power Section 0.00 - 10.00, * 1.00
[72] Start timer 5 14-29 Service Code 15-42 Voltage 16-63 Terminal 54 Setting
[73] Start timer 6 0 - 0x7FFFFFFF, * 0 15-43 Software Version *[0] Current mode
[74] Start timer 7 14-3* Current Limit Ctrl. 15-44 OrderedTypeCode [1] Voltage mode
[100] Reset Alarm 14-4* Energy Optimising 15-46 Frequency Converter 16-64 Analog Input 54
14-** Special Functions 14-40 VT Level Ordering No 0.00 - 20.00, * 1.00
14-0* Inverter Switching 40 - 90%, * 90% 15-47 Power Card Ordering No 16-65 Analog Output 42 [mA]
14-01 Switching Frequency 14-41 AEO Minimum Magnetisation 15-48 LCP Id No 0.00 - 20.00, * 0.00
[0] Ran3 40 - 75%, * 66 15-49 Software ID Control Card 16-61 Digital Output
[1] Ran5 14-5* Environment 15-50 Software ID Power Card 16-72 Counter A
[2] 2.0 kHz 14-50 RFI Filter 15-51 Frequency Converter Serial -32768 - 32767, * 0
[3] 3.0 kHz [0] Off Number 16-73 Counter B
[4] 4.0 kHz *[1] On 15-53 Power Card Serial Number -32768 - 32767, * 0
[5] 5.0 kHz 14-51 DC-link Voltage Compen- 16-** Data Readouts 16-79 Analog output 45
[6] 6.0 kHz sation 16-0* General Status 20 - 20mA, * 0
[7] 8.0 kHz [0] Off 16-00 Control Word 16-8* Fieldbus / FC Port
[8] 10.0 kHz *[1] On 0 - 65535, * 0 16-86 FC Port REF 1
[9] 12.0kHz 14-52 Fan Control 16-01 Reference [Unit] -32768 - 32767, * 0
[10] 16.0kHz *[0] Auto -4999.000 - 4999.000, * 0.000 16-9* Diagnosis Readouts
14-03 Overmodulation [4] Auto Low temp env 16-02 Reference 16-90 Alarm Word
[0] Off 14-53 Fan Monitor % -200.0 - 200.0, * 0.0 0 - 0xFFFFFFFFUL, * 0
*[1] On [0] Disabled 16-03 Status Word 16-91 Alarm Word 2
14-08 Damping Gain Factor *[1] Warning 0 - 65535, * 0 0 - 0xFFFFFFFFUL, * 0
0 - 100-%, * 96 [2] Trip 16-05 Main Actual Value [%] 16-92 Warning Word
14-1* Mains on/off 14-55 Output Filter -200.00 - 200.00, * 0.00 0 - 0x7FFFFFFFUL, * 0
14-12 Function at Mains *[0] No Filter 16-09 Custom Readout 16-93 Warning Word 2
Imbalance [1] Sine-Wave Filter 0.00 - 9999.00, * 0.00 0 - 0x7FFFFFFFUL, * 0
*[0] Trip [3] Sine-Wave Filter with Feedback 16-1* Motor Status 16-94 Ext. Status Word
[1] Warning 14-63 Min Switch Frequency 16-10 Power [kW] 0 - 0x7FFFFFFFUL, * 0
[2] Disabled 1 - 16kHz, * 1 0.000-4.294, 967.500, *0.000 16-95 Ext. Status Word 2
[3] Derate 15-** Drive Information 16-11 Power [hp] 0 - 0x7FFFFFFFUL, * 0
14-2* Reset Functions 15-0* Operating Data 0.000 - 2.294, 967.500 *0.000 18-**Extended Motor Data
14-20 Reset Mode 15-00 Operating Hours 16-3* Drive Status 18-1* Firemode Log
*[0] Manual reset 0 - 2147483647, * 0 16-30 DC Link Voltage 18-10 Firemode log: Event
[1] Automatic reset x 1 15-01 Running Hours 0 - 65535, * 0 0-255, *0
[2] Automatic reset x 2 0 - 2147483647, * 0 16-34 Heatsink Temp. 20-** FC Closed Loop
[3] Automatic reset x 3 15-02 kWh Counter 0 - 255, * 0 20-0* Feedback
[4] Automatic reset x 4 0 - 65535, * 0 16-35 Inverter Thermal 20-00 Feedback 1 Source
[5] Automatic reset x 5 15-03 Power Up's 0 - 255%, * 0 *[0] No function
[6] Automatic reset x 6 0 - 2147483647, * 0 16-36 Inv. Nom. Current [1] Analog in 53
[7] Automatic reset x 7 15-04 Over Temp's 0.00 - 655.35, * 0.00 [2] Analog in 54
[8] Automatic reset x 8 0 - 65535, * 0 16-37 Inv. Max. Current [100] Bus Feedback 1
[9] Automatic reset x 9 0.00 - 655.35
[10] Automatic reset x 10
Parameter Overview 1 1
20-01 Feedback 1 Conversion 20-94 PI Integral Time 22-46 Maximum Boost Time *[0] Disabled
*[0] Linear 0.10 - 9999.00s, * 9999.00 0 - 600 s, * 60 [1] Enabled Run Forward
[1] Square root 20-97 Process PI Feed Forward Factor 22-47 Sleep Speed [Hz] [2] Enabled Run Reverse
20-8* PI Basic Setting 0 - 400%, * 0 0.0 - 400.0, * 0.0 [3] Enable-Coast
20-81 Process PI Normal/ Inverse 22-** Appl. functions 22-6* Broken Belt Detection [4] Enabled - Run Fwd/Rev
Control 22-4* Sleep mode 22-60 Broken Belt Detection 24-05 Fire Mode Preset Reference
*[0] Normal 22-40 Minimum Run Time *[0] Off -100 - 100%, * 0
[1] Inverse 0 - 600 s, * 10 [1] Warning 24-09 Fire Mode Alarm Handling
20-83 Process PI Start Speed[Hz] 22-41 Minimum Sleep Time [2] Trip *[1] Trip, Critical Alarms
0.0 - 200.0, * 0.0 0 - 600 s, * 10 22-61 Broken Belt Torque [2] Trip, All Alarms/Test
20-84 On Reference Bandwidth 22-43 Wake-Up Speed [Hz] 5 - 100%, * 10 24-1* Drive Bypass
0 - 200%, * 5 0.0 - 400.0, * 100.0 22-62 Broken Belt Delay 24-10 Drive Bypass Function
20-9* PI Controller 22-44 Wake-Up Ref./FB difference 0 - 600 s, * 10 *[0] Disabled
20-91 PI Anti Windup 0 - 100%, * 10 24-** Appl. functions 2 [2] Enabled (Fire Mode only)
[0] Off 22-45 Setpoint Boost 24-0* Fire mode 24-11 Bypass Delay Timer
*[1] On -100 - 100%, * 0 24-00 Fire Mode Function 0 - 600 s, * 0
20-93 PI Proportional Gain
0.00 - 10.00, * 0.01
1 1 Alarm/
Warning
Fault Bit Trip
number Number Fault text Warning Alarm locked Cause of problem
AMA
Calibration
50 failed X Contact your local Danfoss supplier.
AMA The setting of motor voltage, motor current and motor power is
51 15 Unom,Inom X presumably wrong. Check the settings.
52 AMA low Inom X The motor current is too low. Check the settings.
AMA big
53 motor X The motor is too big for the AMA to be carried out
AMA small
54 mot X The motor is too small for the AMA to be carried out
AMA par. The parameter values found from the motor are outside acceptable
55 range X range
AMA user
56 interrupt X The AMA has been interrupted by the user
Try to start the AMA again a number of times, until the AMA is
carried out. Please note that repeated runs may heat the motor to
a level where the resistance Rs and Rr are increased. In most cases,
57 AMA timeout X however, this is not critical
58 AMA internal X X Contact your local Danfoss supplier.
59 25 Current limit X The current is higher than the value in par. 4-18 Current Limit
External interlock has been activated. To resume normal operation,
apply 24 V DC to the terminal programmed for external interlock
External and reset the frequency converter (via serial communication, digital
60 44 Interlock X I/O, or by pressing reset button on keypad).
Heat sink
Temperature This warning is based on the temperature sensor in the IGBT
66 26 Low X module (Only on 400 V 30-90 kW units).
Pwr. Card The temperature sensor on the power card is either too hot or too
69 1 Temp X X X cold.
Illegal power
section config-
79 uration X X Internal fault. Contact your local Danfoss supplier.
Drive
80 29 initialised X All parameter settings are initialized to default settings.
Auto DC
87 47 Braking X The drive is auto DC braking
Torque is below the torque level set for no load, indicating a
95 40 Broken Belt X X broken belt. See parameter group 22-6.
200 Fire Mode X Fire mode has been activated
Fire Mode
Limits
202 Exceeded X Fire Mode has suppressed one or more warranty voiding alarms
The power or switch mode power supply has been exchanged.
250 New sparepart X X (Only on 400 V 30-90 kW units). Contact your local Danfoss supplier
The frequency converter has a new type code (Only on 400 V 30-90
251 New Typecode X X kW units). Contact your local Danfoss supplier.
1 1
1.7 General Specifications
1.7.1 Mains Supply 3 x 200-240 V AC
frequency converter PK2 PK3 PK7 P1K P2K2 P3K P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
5 7 5 5 7
Typical shaft output (kW) 0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0
Typical shaft output (hp) 0.33 0.5 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0
IP20 frame H1 H1 H1 H1 H2 H3 H4 H4 H5 H6 H6 H7 H7 H8 H8
Max. cable size in terminals (mains, 4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6 35/2 35/2 50/1 50/1 95/0 120/
motor) [mm2/AWG] (4/0)
Output current
40°C ambient temperature
130BB632.10
Continuous 1.5 2.2 4.2 6.8 9.6 15.2 22.0 28.0 42.0 59.4 74.8 88.0 115.0 143.0 170.0
(3 x 200-240 V)
[A]
Intermittent 1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8 46.2 65.3 82.3 96.8 126.5 157.3 187.0
(3 x 200-240 V)
[A]
RELAY 2
Continuous 1.1 1.6 2.8 5.6 8.6/7 14.1 21.0/ 28.3/ 41.0/ 52.7 65.0 76.0 103.7 127.9 153.0
(3 x 200-240 V) .2 / 18.0 24.0 38.2
[A] 12.0
Intermittent 1.2 1.8 3.1 6.2 9.5/7 15.5 23.1/ 31.1/ 45.1/ 58.0 71.5 83.7 114.1 140.7 168.3
(3 x 200-240 V) .9 / 19.8 26.4 42.0
[A] 13.2
RELAY 2
36
Frequency converter PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Quick Guide
Typical shaft output (kW) 0.37 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output (hp) 0.5 1.0 2.0 3.0 4.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.0
IP20 frame H1 H1 H1 H2 H2 H2 H3 H3 H4 H4 H5 H5 H6 H6 H6 H7 H7 H8
Max. cable size in terminals (mains, motor) 4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6 16/6 35/2 35/2 35/2 50/1 95/0 120/25
[mm2/AWG] 0MCM
Output current
40°C ambient temperature
Continuous (3 x 1.2 2.2 3.7 5.3 7.2 9.0 12.0 15.5 23.0 31.0 37.0 42.5 61.0 73.0 90.0 106.0 147.0 177.0
380-440 V)[A]
130BB632.10
Intermittent (3 1.3 2.4 4.1 5.8 7.9 9.9 13.2 17.1 25.3 34.0 40.7 46.8 67.1 80.3 99.0 116.0 161.0 194.0
x 380-440 V)
[A]
1.7.2 Mains Supply 3 x 380-480 V AC
Continuous (3 x 1.1 2.1 3.4 4.8 6.3 8.2 11.0 14.0 21.0 27.0 34.0 40.0 52.0 65.0 80.0 105.0 130.0 160.0
RELAY 2
440-480 V)[A]
Intermittent (3 1.2 2.3 3.7 5.3 6.9 9.0 12.1 15.4 23.1 29.7 37.4 44.0 57.2 71.5 88.0 115.0 143.0 176.0
x 440-480 V)
[A]
Max. input current
Continuous (3 x 1.2 2.1 3.5 4.7 6.3 8.3 11.2 15.1 22.1 29.9 35.2 41.5 57.0 70.0 84.0 103.0 140.0 166.0
380-440 V) [A]
130BB633.10
VLT HVAC Basic Drive Quick Guide
Intermittent (3 1.3 2.3 3.9 5.2 6.9 9.1 12.3 16.6 24.3 32.9 38.7 45.7 62.7 77.0 92.4 113.0 154.0 182.0
x 380-440 V)
[A]
440-480 V) [A]
Intermittent (3 1.1 2.0 3.2 4.3 5.8 7.5 10.3 13.9 20.2 27.2 32.2 38.1 54.1 66.7 79.8 97.5 132.9 157.0
x 440-480 V)
[A]
Max. mains fuses See 5.1.4 Fuses
Frequency converter PK37 PK75 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Estimated power loss [W], Best case/typical1) 13/15 16/21 46/57 46/58 66/83 95/118 104/13 159/19 248/27 353/37 412/45 475/52 780 893 1160 1130 1460 1780
1 8 4 9 6 3
Quick Guide
Weight enclosure IP20kg] 2.0 2.0 2.1 3.3 3.3 3.4 4.3 4.5 7.9 7.9 9.5 9.5 24.5 24.5 24.5 36.0 36.0 51.0
Efficiency [%], Best case/Typical 1 97.8/97. 98.0/97 97.7/97 98.3/97 98.2/97. 98.0/97. 98.4/98 98.2/9 98.1/9 98.0/9 98.1/9 98.1/9 97.8 97.9 97.1 98.3 98.3 98.3
3 .6 .2 .9 8 6 .0 7.8 7.9 7.8 7.9 7.9
Output current
50°C ambient temperature
Continuous (3 x 1.04 1.93 3.7 4.85 6.3 8.4 10.9 14.0 20.9 28.0 34.1 38.0 48.8 58.4 72.0 74.2 102.9 123.9
380-440 V) [A]
Intermittent (3 x 1.1 2.1 4.07 5.4 6.9 9.2 12.0 15.4 23.0 30.8 37.5 41.8 53.7 64.2 79.2 81.6 113.2 136.3
380-440 V) [A]
Continuous (3 x 1.0 1.8 3.4 4.4 5.5 7.5 10.0 12.6 19.1 24.0 31.3 35.0 41.6 52.0 64.0 73.5 91.0 112.0
440-480 V) [A]
Intermittent (3 x 1.1 2.0 3.7 4.8 6.1 8.3 11.0 13.9 21.0 26.4 34.4 38.5 45.8 57.2 70.4 80.9 100.1 123.2
440-480 V) [A]
VLT HVAC Basic Drive Quick Guide
38
Frequency converter PK75 P1K5 P2K2 P3K0 P4KO P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Quick Guide
Typical shaft output (kW) 0.75 1.5 2.2 3.0 4.0 5.5 7.5 11 15 18.5 22.0 30.0 37.0 45.0 55.0 75.0 90.0
Typical shaft output (hp) 1.0 2.0 3.0 4.0 5.0 7.5 10.0 15.0 20 25.0 30.0 40.0 50.0 60.0 70.0 100.0 125.0
IP54 frame I2 I2 I2 I2 I2 I3 I3 I5 I5 I5 I6 I6 I6 I7 I7 I8 I8
Max. cable size in terminals (mains, motor) 4/10 4/10 4/10 4/10 4/10 4/10 4/10 10/7 10/7 10/7 35/2 35/2 35/2 50/1 50/1 95/ 120/
[mm2/AWG] (3/0) (4/0)
Output current
40°C ambient temperature
Continuous (3 x 2.2 3.7 5.3 7.2 9.0 12.0 15.5 24 32 37.5 44.0 61.0 73.0 90.0 106.0 147.0 177.0
380-440 V) [A]
Intermittent (3 x 2.4 4.1 5.8 7.9 9.9 13.2 17.1 26.2 35.2 41.3 48.4 67.1 80.3 99.0 116.6 161.7 194.7
380-440 V) [A]
Continuous (3 x 2.1 3.4 4.8 6.3 8.2 11.0 14.0 21 27 34 40.0 52.0 65.0 80.0 105.0 130.0 160.0
1.7.3 Mains Supply 3 x 380-480 V AC
440-480 V) [A]
Intermittent (3 x 2.3 3.7 5.3 6.9 9.0 12.1 15.4 23.1 29.7 37.4 44.0 57.2 71.5 88.0 115.5 143.0 176.0
440-480 V) [A]
Max. input current
Continuous (3 x 2.1 3.5 4.7 6.3 8.3 11.2 15.1 22 29 34 41.8 57.0 70.3 84.2 102.9 140.3 165.6
380-440 V )[A]
Intermittent (3 x 2.3 3.9 5.2 6.9 9.1 12.3 16.6 24.2 31.9 37.3 46.0 62.7 77.4 92.6 113.1 154.3 182.2
380-440 V) [A]
VLT HVAC Basic Drive Quick Guide
Continuous (3 x 1.8 2.9 3.9 5.3 6.8 9.4 12.6 19 25 31 36.0 49.2 60.6 72.5 88.6 120.9 142.7
440-480 V) [A]
Intermittent (3 x 2.0 3.2 4.3 5.8 7.5 10.3 13.9 20.9 27.5 34.1 39.6 54.1 66.7 79.8 97.5 132.9 157.0
Weight enclosure IP54kg] 5.3 5.3 5.3 5.3 5.3 7.2 7.2 23 23 23 27 27 27 45 45 65 65
Efficiency [%], Best case/Typical 1 98.0/97. 97.7/97. 98.3/97. 98.2/97. 98.0/97. 98.4/98. 98.2/97. 98 98 98 98.0 97.8 98.3 98.3 98.3 98.3 98.5
6 2 9 8 6 0 8
Output current
50°C ambient temperature
Continuous (3 x 1.93 3.7 4.85 6.3 8.4 10.9 14.0 19.2 25.6 30 35.2 48.8 58.4 63.0 74.2 102.9 123.9
380-440 V) [A]
Intermittent (3 x 2.1 4.07 5.4 6.9 9.2 12.0 15.4 21.2 28.2 33 38.7 53.9 64.2 69.3 81.6 113.2 136.3
380-440 V) [A]
Continuous (3 x 1.8 3.4 4.4 5.5 7.5 10.0 12.6 16.8 21.6 27.2 32.0 41.6 52.0 56.0 73.5 91.0 112.0
440-480 V) [A]
Intermittent (3 x 2.0 3.7 4.8 6.1 8.3 11.0 13.9 18.5 23.8 30 35.2 45.8 57.2 61.6 80.9 100.1 123.2
440-480 V) [A]
VLT HVAC Basic Drive Quick Guide
Frequency converter P2K2 P3K0 P5K5 P7K5 P11K P15K P22K P30K P45K P55K P75K P90K
Typical shaft output (kW) 2.2 3.0 5.5 7.5 11.0 15.0 22.0 30.0 45.0 55.0 75.0 90.0
Typical shaft output (hp) 3.0 4.0 7.5 10.0 15.0 20.0 30.0 40.0 60.0 70.0 100.0 125.0
IP20 frame H9 H9 H9 H9 H10 H10 H6 H6 H7 H7 H8 H8
Max. cable size in terminals (mains, motor) [mm2/ 4/10 4/10 4/10 4/10 10/8 10/8 35/2 35/2 50/1 50/1 95/0 120/
AWG] (4/0)
Output current
40°C ambient temperature
130BB632.10
Continuous (3 x 4.1 5.2 9.5 11.5 19.0 23.0 36.0 43.0 65.0 87.0 105.0 137.0
525-550 V) [A]
Intermittent (3 x 4.5 5.7 10.5 12.7 20.9 25.3 39.6 47.3 71.5 95.7 115.5 150.7
525-550 V) [A]
Continuous (3 x 3.9 4.9 9.0 11.0 18.0 22.0 34.0 41.0 62.0 83.0 100.0 131.0
551-600 V) [A]
RELAY 2
Intermittent (3 x 4.3 5.4 9.9 12.1 19.8 24.2 37.4 45.1 68.2 91.3 110.0 144.1
551-600 V) [A]
Max. input current
130BB633.10
Continuous (3 x 3.7 5.1 8.7 11.9 16.5 22.5 33.1 45.1 66.5 81.3 109.0 130.9
525-550 V) [A]
Intermittent (3 x 4.1 5.6 9.6 13.1 18.2 24.8 36.4 49.6 73.1 89.4 119.9 143.9
525-550 V) [A]
Continuous (3 x 3.5 4.8 8.3 11.4 15.7 21.4 31.5 42.9 63.3 77.4 103.8 124.5
551-600 V) [A]
RELAY 2
Intermittent (3 x 3.9 5.3 9.2 12.5 17.3 23.6 34.6 47.2 69.6 85.1 114.2 137.0
551-600 V) [A]
Max. mains fuses
Estimated power loss [W], Best case/typical1) 8.4 112.0 178.0 239.0 360.0 503.0 607.0 820.0 972.0 1182. 1281. 1437.
0 0 0
Weight enclosure IP54 kg] 6.6 6.6 6.6 6.6 11.5 11.5 24.5 24.5 36.0 36.0 51.0 51.0
Efficiency [%], Best case/Typical 1 97.0 97.0 97.0 97.0 97.0 97.0 97.5 97.5 98.0 98.0 98.4 98.5
Output current
50°C ambient temperature
Continuous (3 x 2.9 3.6 6.7 8.1 13.3 16.1 25.2 30.1 45.5 60.9 73.5 95.9
525-550 V) [A]
Intermittent (3 x 3.2 4.0 7.4 8.9 14.6 17.7 27.7 33.1 50.0 67.0 80.9 105.5
525-550 V) [A]
Continuous (3 x 2.7 3.4 6.3 7.7 12.6 15.4 23.8 28.7 43.3 58.1 70.0 91.7
551-600 V) [A]
Intermittent (3 x 3.0 3.7 6.9 8.5 13.9 16.9 26.2 31.6 47.7 63.9 77.0 100.9
551-600 V) [A]
RFI Filter Type Conduct emission. Maximum shielded cable length (m) Radiated emission
Housing, trades and Industrial Housing, trades and
Industrial environment
light industries environment light industries
EN 55011 Class A2 EN 55011 Class A1 EN 55011 Class B EN 55011 Class A1 EN 55011 Class B
Without With Without With Without With Without With Without With
external external external external external external external external external external
filter filter filter filter filter filter filter filter filter filter
H4 RFI filter
(Class A1)
0.25-11 kW
3 x 200-240 V 25 50 20 Yes Yes -
IP20
0.37-22 kW
3 x 380-480 V 25 50 20 Yes Yes -
IP20
H2 RFI filter
(Class A2)
15-45 kW
3 x 200-240 V 25 No -
IP20
30-90 kW
3 x 380-480 V 25 No -
IP20
0.75-18.5 kW
3 x 380-480 V 25 Yes
IP54
22-90 kW
3 x 380-480 V 25 No -
IP54
H3 RFI filter
(Class A1/B)
15-45 kW
3 x 200-240 V 50 20 Yes -
IP20
30-90 kW
3 x 380-480 V 50 20 Yes -
IP20
0.75-18.5 kW
3 x 380-480 V 25 10 Yes
IP54
22-90 kW
3 x 380-480 V 50 10 Yes -
IP54
• Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature.
• If a motor phase is missing, the frequency converter trips and issues an alarm.
• If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
• Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
Analog inputs 1 1
Number of analog inputs 2
Terminal number 53, 54
Terminal 53 mode Parameter 6-19: 1 = voltage, 0 = current
Terminal 54 mode Parameter 6-29: 1 = voltage, 0= current
Voltage level 0 - 10 V
Input resistance, Ri approx. 10 kΩ
Max. voltage 20 V
Current level 0/4 to 20 mA (scalable)
Input resistance, Ri <500Ω
Max. current 29 mA
Analog output
Number of programmable analog outputs 2
Terminal number 42, 451)
Current range at analog output 0/4 - 20 mA
Max. load to common at analog output 500 Ω
Max. voltage at analog output 17 V
Accuracy on analog output Max. error: 0.4 % of full scale
Resolution on analog output 10 bit
1) Terminal 42 and 45 can also be programmed as digital outputs.
Digital output
Number of digital outputs 2
Terminal number 42, 451)
Voltage level at digital output 17 V
Max. output current at digital output 20 mA
Max. load at digital output 1 kΩ
1) Terminals 42 and 45 can also be programmed as analog output.
Relay output
Programmable relay output 2
Relay 01 and 02 01-03 (NC), 01-02 (NO), 04-06 (NC), 04-05 (NO)
Max. terminal load (AC-1)1) on 01-02/04-05 (NO) (Resistive load) 250 V AC, 3A
Max. terminal load (AC-15)1) on 01-02/04-05 (NO) (Inductive load @ cosφ 0.4) 250 V AC, 0.2A
Max. terminal load (DC-1)1) on 01-02/04-05 (NO) (Resistive load) 30 V DC, 2A
Max. terminal load (DC-13)1) on 01-02/04-05 (NO) (Inductive load) 24 V DC, 0.1A
Max. terminal load (AC-1)1) on 01-03/04-06 (NC) (Resistive load) 250 V AC, 3A
Max. terminal load (AC-15)1) on 01-03/04-06 (NC) (Inductive load @ cosφ 0.4) 250 V AC, 0.2A
Max. terminal load (DC-1)1) on 01-03/04-06 30 V DC, 2A
(NC) (Resistive load) Min. terminal load on 01-03 (NC), 01-02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
1) IEC 60947 parts 4 and 5.
Control card, 10V DC output
Terminal number 50
Output voltage 10.5 V ±0.5 V
Max. load 25 mA
1 1 All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and
other high-voltage terminals.
Surroundings
Enclosure IP20
Enclosure kit available IP21, TYPE 1
Vibration test 1.0 g
Max. relative humidity 5% - 95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60721-3-3), coated (standard) frame H1-H5 Class 3C3
Aggressive environment (IEC 60721-3-3), non-coated frame H6-H10 Class 3C2
Aggressive environment (IEC 60721-3-3), coated (optional) frame H6-H10 Class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature See max. output current at 40/50° C in the tables mains supply
Derating for high ambient temperature, see section on special conditions
www.danfoss.com/drives
Quick Guide
VLT® HVAC Basic Drive
*MG18A302*