Earthquake Resisting System Class Notes
Earthquake Resisting System Class Notes
Earthquake Resisting System Class Notes
1- Bearing wall systems consist of vertical load carrying walls located along exterior wall lines and at
interior locations as necessary. Many of these bearing walls are also used to resist lateral forces and are
then called shear walls. Bearing wall systems do not contain complete vertical load carrying space
frames but may use some columns to support floor and roof vertical loads.
2- Building frame systems use a complete three dimensional space frame to support vertical loads, but
use either shear walls or braced frames to resist lateral forces. A building frame system with shear walls
is shown in Figure
3- Moment-resisting frame systems, shown in Figure. provide a complete space frame throughout the
building to carry vertical loads, and they use some of those same frame elements to resist lateral forces.
4. A dual system is a structural system in which an essentially complete frame provides support for
gravity loads, and resistance to lateral loads is provided by a specially detailed moment-resisting frame
and shear walls or braced frames. The moment-resisting frame must be capable of resisting at least 25
percent of the base shear, and the two systems must be designed to resist the total lateral load in
proportion to their relative rigidities. This system, which provides good redundancy, is suitable for
medium-to-high rise buildings where perimeter frames are used in conjunction with central shear wall
core. Concrete intermediate frames cannot be used in seismic zones 3 or 4.
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
3-2Lateral-Force-Resisting Elements
Lateral-force-resisting elements must be provided in every structure to brace it against wind and seismic
forces. The three principal types of resisting elements are shear walls, braced frames, and moment-
resisting frames.
the shear walls are oriented in one direction, so only lateral forces in this direction can be resisted. The
roof serves as the horizontal diaphragm and must also be designed to resist the lateral loads and transfer
them to the shear walls. Fig. also shows an important aspect of shear walls in particular and vertical
elements in general. This is the aspect of symmetry that has a bearing on whether torsional effects will
be produced. The shear walls in Fig. show the shear walls symmetrical in the plane of loading.
Fig. illustrates a common use of shear walls at the interior of a multistory building. Because walls
enclosing stairways, elevator shafts, and mechanical shafts are mostly solid and run the entire height of
the building, they are often used for shear walls. Although not as efficient from a strictly structural point
of view, interior shear walls do leave the exterior of the building open for windows. Notice that in Fig.
(3.3.b) there are shear walls in both directions, which is a more realistic situation because both wind and
earthquake forces need to be resisted in both directions. In this diagram, the two shear walls are
symmetrical in one direction, but the single shear wall produces a nonsymmetrical condition in the other
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
since it is off center. Shear walls do not need to be symmetrical in a building, but symmetry is preferred
to avoid torsional effects. Shear walls, when used a lone, are suitable for medium rise buildings up to 20
stories high. Shear walls may have openings in them, but the calculations are more difficult and their
ability to resist lateral loads is reduced depending on the percentage of open area.
Shear walls in buildings must be symmetrically located in plan to reduce ill effects of twist in buildings.
They could be placed symmetrically along one or both directions in plan. Shear walls are more effective
when located along exterior perimeter of the building – such a layout increases resistance of the building
to twisting
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
Ductile Design of ShearWalls:
Just like reinforced concrete beams and columns, reinforced concrete shear walls also perform much
better if designed to be ductile. Overall geometric proportions of the wall, types and amount of
reinforcement, and connection with remaining elements in the building help in improving the ductility of
walls.
Overall Geometry of Walls:
Shear walls are rectangular in cross-section, i.e., one dimension of the cross-section is much larger than
the other. While rectangular cross-section is common, L- and U-shaped sections are also used (Fig. 3.6).
Thin-walled hollow reinforced concrete shafts around the elevator core of buildings also act as shear
walls, and should be taken advantage of to resist earthquake forces.
Braced Frames:
A braced frame is a truss system of the concentric or eccentric type in which the lateral forces are
resisted through axial stresses in the members. Just as with a truss, the braced frame depends on
diagonal members to provide a load path for lateral forces from each building element to the foundation.
Fig. shows a simple one-story braced frame. At one end of the building two bays are braced, and at the
other end only one bay is braced. As with Fig., this building is only braced in one direction and uses
compression braces because the diagonal member may be either in tension or compression, depending
on which way the force is applied. Fig. (3.7.b) shows two methods of bracing a multistory building. A
single diagonal compression member in one bay can be used to brace against lateral loads coming from
either direction. Alternately, tension diagonals can be used to accomplish the same result, but they must
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
be run both ways to account for the load coming from either direction. Braced framing can be placed on
the exterior or interior of a building, and may be placed in one structural bay or several. Obviously, a
braced frame can present design problems for windows and doorways, but it is a very efficient and rigid
lateral force resisting system.
Advantages:
- Provide a potentially high-ductile system with a good degree of redundancy, which can allow freedom
in architectural planning of internal spaces and external cladding.
- Their flexibility and associated long period may serve to detune the structure from the forcing motions
on stiff soil or rock sites.
Disadvantages:
- Poorly designed, moment resisting frames have been observed to fail catastrophically in earthquakes,
mainly by formation of weak stories and failures around beam-column joints.
- Beam column joints represent an area of high stress concentration, which needs considerable skill to
design successfully.
Load Path:
The structure shall contain one complete load path for Life Safety for seismic force effects from any
horizontal direction that serves to transfer the inertial forces from the mass to the foundation. There must
be a complete lateral-force-resisting system that forms a continuous load path between the foundation,
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
all diaphragm levels, and all portions of the building for proper seismic performance The general load
path is as follows: seismic forces originating throughout the building are delivered through structural
connections to horizontal diaphragms; the diaphragms distribute these forces to vertical lateral-force
resisting elements such as shear walls and frames; the vertical elements transfer the forces into the
foundation; and the foundation transfers the forces into the supporting soil. If there is a discontinuity in
the load path, the building is unable to resist seismic forces regardless of the strength of the existing
elements. Mitigation with elements or connections needed to complete the load path is necessary to
achieve the selected performance level.
The design professional should be watchful for gaps in the load path. Examples would include a shear
wall that does not extend to the foundation, a missing shear transfer connection between a diaphragm
and vertical element, a discontinuous chord at a diaphragm notch, or a missing collector. In cases where
there is a structural discontinuity, a load path may exist but it may be a very undesirable one. At a
discontinuous shear walls, for example, the diaphragm may transfer the forces to frames not intended to
be part of the lateral-force-resisting system. While not ideal, it may be possible to show that the load
path is acceptable.
In the case of floors and roofs, the perimeter edges or boundaries are critical locations because they form
the interface between the diaphragms and the perimeter walls. The perimeter is typically the location for
vertical seismic elements, although many buildings also have shear walls or frames at interior locations.
An interior line of resistance also creates a diaphragm boundary. Boundary elements in diaphragms
usually serve as both chords and collectors, depending on the axis along which lateral loads are
considered to be applied. As shown in, the forces acting perpendicular to the boundary elements tend to
bend the diaphragm, and the chord member must resist the associated tension and compression. Similar
to a uniformly loaded beam, a diaphragm experiences the greatest bending stress and largest deflection
at or near the center of its span between vertical resisting seismic elements. The chord on the side of the
diaphragm along which the forces are being applied is in compression, and the chord on the opposite
side is in tension. These tension and compression forces reverse when the earthquake forces reverse.
Therefore, each chord must diaphragm level to resist the out-of-plane bending in the be designed for
both tension and compression. In concrete walls, reinforcing steel is placed at the wall. Collectors are
needed when an individual shear wall or frame in the story immediately below the diaphragm is not
continuous along the diaphragm boundary. This is a very common situation because shear walls are
often interrupted by openings for windows and doors, and because resisting frames are normally located
in only a few of the frame bays along a diaphragm boundary. A path must be provided to collect the
lateral forces from portions of a diaphragm located between vertical resisting seismic elements and to
deliver those forces to each individual shear wall or frame.
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
The collector member provides that path. Collectors are commonly called drag struts or ties. Collectors
are also needed when an interior shear wall or frame is provided. In this case, the collector is placed in
the diaphragm, aligned with the wall or frame, and extends to the diaphragm edges beyond each end of
the wall or frame. Collectors can occur in spandrel beams, of concrete, that link sections of shear walls
together. The following statements contained in the 1997 UBC clearly require that a complete load path
be provided throughout a building to resist lateral forces. “All parts of a structure shall be interconnected
and connections shall be capable of transmitting the seismic force induced by the parts being connected.
“Any system or method of construction shall be based on a rational analysis... Such analysis shall result
in a system that provides a complete load path capable of transferring all loads and forces from their
point of origin to the load resisting elements.” To fulfill these requirements, connections must be
provided between every element in the load path. When a building is shaken by an earthquake, every
connection in the lateral force load path is tested. If one or more connections fail because they were not
properly designed or constructed, those remaining in parallel paths receive additional force, which may
cause them to become overstressed and to fail. If this progression of individual connection failures
continues, it can result in the failure of a complete resisting seismic element and, potentially, the entire
lateral-force resisting system. Consequently, connections are essential for providing adequate resistance
to earthquakes and must be given special attention by both designers and inspectors. Connections are
details of construction that perform the work of force transfer between the individual primary and
secondary structural elements discussed above. They include a vast array of materials, products, and
methods of Construction. In concrete construction, diaphragm-reinforcing steel resists forces in the
diaphragm and chord tension stresses, and reinforcing dowels are generally used to transfer forces from
the diaphragm boundaries to concrete walls or frames.
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
Base Isolation:
Traditionally, while designing structures to withstand vibrations due to an earthquake or wind, the basic
consideration was to make the structure resistant to vibrations by improving its strength, ductility, and
stiffness. On the other hand devices that prevent propagation of vibrations to the structures or that absorb
the energy of vibration were proposed as substitutes for the traditional design practices. It is only
recently, however, that the study in this direction has progressed and the findings have been used in
building construction. The aim of these techniques is to improve the safety of structures by damping
their response.
Response-control structures are generally made by attaching special elements to normal structural
members. In the case of base isolation technique, which is the most popular response-control structure
technique, a device having some damping properties and sufficient bearing strength is used in the
structure. In addition, especially in the case of tower-like structures, an added-mass mechanism is used.
A small mass is added to the main structure thereby converting the vibration energy of the main structure
into vibration energy of the added mass.
A damper is an important element for structures since it absorbs vibration energy developed during
earthquakes, thereby reducing vibration response. In the case of base isolation structures, which have
long fundamental periods of oscillation, dampers are generally employed to restrict the excess
deformation of base isolation devices. Even in the case of towers or similar structures such as high-rise
buildings, dampers are used to suppress the response during strong winds or small to medium
earthquakes. Dampers can be roughly classified into the following two types:
1. Viscous or viscoelastic dampers: This is a damper where the damping power is proportional to the
velocity (for example: oil damper).
2. Hysteresis-type dampers: In dampers such as steel damper, lead damper, friction damper, etc., the
vibration energy is dissipated as the hysteretic energy in the force deformation relation of damper
materials.
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
In either case the vibration energy of the structure is converted into thermal energy. In a mass-effect
mechanism, mass is added to the structure such that vibration energy of the structure is converted into
the vibration energy of the added mass. This is also referred to as damper or dynamic damper but will
not be discussed here since it is not a base isolation method.
Most of the dampers were developed for structures based on base isolation and are available in various
types. All are used for controlling the relative displacement of the structure in the horizontal direction
and are designed to move freely in the forward and backward directions. The limiting relative
displacement during the operation is about 20 to 40 cm.
1. Viscous and viscoelastic dampers
a. Oil Dampers
Oil dampers used for base isolation structures are basically the same as those used for an automotive
vehicle. They use the resistance encountered at the orifice when a piston moves through the cylinder
filled with oil. The damping power of oil dampers is broadly proportional to the velocity of
vibrations. Since it has almost no stiffness the base isolation effect is observed not only during large but
also during small or medium earthquakes.
2. Hysteresis-type dampers
a. Steel Dampers
A number of versions are available in steel dampers such as dampers using straight rods, steel rods
clubbed together, steel soils, steel plates shaped like an arch with a gap in-between, or steel pipes. Most
of these are used in base isolation type structures. All of these dampers use the bending deformation
properties of steel and its restoring force characteristics are mostly bi-linear. Accordingly, the base
isolation effect is minimal during small to medium earthquakes since the stiffness in this region is high.
b. Lead Dampers
In these dampers, lead is formed into a cylinder which shows uniform energy absorption properties
irrespective of the amplitude of deformation.
c. Friction Dampers
Friction dampers are also classified into two types—base-isolation-type structures and multi-storied
structures. In the former, a friction plate isinserted between two stainless steel plates and held together
by bolts. In the case of multi-storied buildings, this is in the form of a pump having an outer cylinder and
a rod. There is a friction plate between the outer cylinder and the rod.
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
RETRO-FITTING:
Retrofitting is the process of structural upgrading of an existing building to meet seismic design
standards close to or equivalent to standards expected of new buildings. Structural assessment is needed
to identify the structural problems exactly. Both structural and non-structural elements require analysis.
For example, the primary horizontal load resisting system may be very weak and prone to collapse, and
infill walls may be likely to collapse under out-of-plane-loads. During this detailed analysis, the
structural engineer will consider what elements require complete replacement or merely upgrading.
Perhaps a new structural system, like a shear wall, needs to be inserted into the existing building. In
the worst cases, new structural systems will be required to resist horizontal loads in both the X and Y-
directions. The three most common structural systems used for retrofitting are R.C Shear wall, Steel
cross bracing and R.C or Steel moment resisting frames.
Ideally, the chosen system will possess greater (or at least similar) horizontal stiffness to that of the
existing building. If the new system is too flexible, then the existing elements will be subject to large
horizontal deflections which they may not be able to sustain without collapse. For example, an
inadequately reinforced column can take only so much horizontal deflection before it loses its capacity
to withstand gravity loads.
The best retrofitting option is to use new RC shear walls. They have, by far, the best seismic
performance record of the three systems. They are therefore the most reliable. New shear walls almost
always require new foundations to prevent overturning.
Building Technology and Materials-VI
Earth Quake resisting Structures
Class notes 2018-19 BKPS CoA
The new systems must be configured in such a way as to not only resist plan orthogonal loads, but also
to resist torsion. If the black coloured walls are new shear walls, then the left-hand layout is unsuitable
because no two walls form anti-torsion couples. The middle scheme is suitable because of the couple
formed by the Y-direction walls, but the right-hand scheme is the best due to its largest possible lever-
arms between both sets of new walls contributing increased torsional resistance.
If possible it is constructionally easier if the walls can be constructed on the outside of the building.
New foundations will be much more straight forward to construct. In this situation of exterior walls,
careful attention must be paid to their architectural impacts on the existing building.
the diaphragms play crucial role of transferring horizontal loads. Their strength should be checked and
upgraded if necessary so as they can resist and transfer all the horizontal inertia loads into the new
vertical structural systems.
Sometimes it is possible to upgrade existing structural elements like columns. For example, a weak
column - strong beam frame can be improved by jacketing its columns with confining steel and adding
additional vertical reinforcing. But the problem of under-reinforced beam column joints and other
detailing defects are much more difficult to solve. Since the seismic performance of frames is so
dependant upon high quality detailing and construction, this approach has a far lower chance of being
effective than the introduction of new RC walls.