Description
AIR HANDLERS (With One Coil System)

Supply, installation testing and commissioning of factory built floor mounted chilled water Double skin type
horizintal/vertical air handling units made of 25mm ±2mm thick panels consisting of pre plasticized GI casing of thickness
0.8mm outside layerand 0.8mm inside layer with polyurethene foam (PUF) insulation factory injected between them by
injection moulding machine, complete with blower section with blower suitable for static pressure as required , min. 2
bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes ( tube thickness not less than 0.5
mm ) cooling coil of 6 row deep, filter section with 50 mm thick metal viscous filter /washable synthetic type air
prefilters, AHU Blower Direct driven, squirel cage induction motor (Its suitable for VFD or with plug fan) package with
TEFC drive motor of efficiency class IE3 suitable for 415±10% V, 50Hz, 3 phase AC supply suitably designed for variable
frequency drive applications, drain connections , stainless steel (18G) drain pain with PUF insulation,150 mm dia. dial
type pressure gauges (2 Nos.) and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge
valve wherever required, necessary vibration isolation arrangement etc. complete as per specification & AHU schedule
and of following capacities as :
Supply , installation testing and commissioning of Double skin floor mounted Horizontal/vertical Two pipe system (One
coil) AHUs as per the mentioned in AHU schedule. (All AHU Should Be BMS/VFD Compitable)
Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 2000 CFM / 4.0-4.5 TR, 6 row deep chilled water
coil ,pre filter, 35 mm SP WG with three phase motor.
Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 2500 CFM / 5.0 TR, 6 row deep chilled water
coil ,pre filter, 35 mm SP WG with three phase motor.
Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 3000 CFM / 6.0 TR, 6 row deep chilled water
coil ,pre filter, 35 mm SP WG with three phase motor.
Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 3500 CFM / 7.0 TR, 6 row deep chilled water
coil ,pre filter, 35 mm SP WG with three phase motor.
Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 5000 CFM / 9.5-11.5 TR, 6 row deep chilled
water coil ,pre filter, 35 mm SP WG with three phase motor.

Floor Mounted Horizontal Air Handling Units With Exh. Blower and Enthalpy Recovery Wheel (FM AHU)

Supply, Installation Testing and Commissioning of floor mounted AHU's. The AHU's shall be double skin type made of
0.60 mm thick GI sheet with 23+/-2mm for indoor application and 43+/-2 mm Thick for outdoor application PUF
insulation. The Drain Pan for AHU's shall be of SS. They shall be suitable for indoor/outdoor installation. The AHU's
selected shall be supplied with Forward / Backward direct driven/belt driven supply air Blower Fans and exh. air blower
with Ethalpy Recovery Wheel (Min. Efficiency of HRW is 75%) (ERW/HRW) suitable to deliver the undergiven CFM and
Static. The AHU's shall be chilled water coil ( complete with mixing chamber if required and electrical push buttnos.
Cooling Coil)on starting panel for operating the AHU. AHU Included VI Pads .
All AHU Should Be included Supply/Return/Fresh Air Damper & Thermal Break Profile and with three phase motor
suitable for VSD drive and BMS Compitable

Double skin floor mounted Horizontal 8-Row Depth chilled water Coil (1 Coil) with Supply Fan 5300 CFM with pre filter ,
S.P. is 65 mm & Exhaust fan 3600 CFM with Pre Filter, S.P. 50 mm , Heat Recovery Wheel (Enthalpy Wheel) AHU Coil is
14.0 TR, pre filter with mixing box . (For Common TFA)
TOTAL
Qty Unit Rate Amount

2 No.
0
3 No.
0
8 No.
0
1 No.
0
4 No.
0
0
0

1 No.
0