ELECTRONIC CONTROLLER WITH DELTA P
200 SERIES – INSTRUCTION MANUAL
INDEX
1. MAIN FEATURES Page 2
2. TECHNICAL FEATURES Page 3
3. INSTALLATION GUIDELINES Page 4
4. PRELIMINARY CHECKS Page 5
5. ELECTRICAL CONNECTIONS Page 5
6. FILTERED PRESSURE TAPS Page 5
6.1 FILTERED PRESSURE TAPS: INSTALLATION Page 5
6.2 FILTERED PRESSURE TAPS: CONNECTION Page 6
6.3 DRAWING1: FILTERED PRESSURE TAPS Page 6
7. SETTINGS Page 7
7.1 SETTINGS: VOLTAGE SELECTION Page 7
7.2 MANUAL AND AUTOMATIC MODE OPERATION Page 8
7.2.1 MANUAL MODE OPERATION Page 8
7.2.2 AUTOMATIC MODE OPERATION Page 8
7.2.3 REMOTE SWITCHING Page 8
7.3 SETTINGS: PARAMETERS SELECTION Page 9
8. SHUT DOWN CLEANING Page 10
9. CODES AND ALARMS Page 10
9.1 LEDS Page 10
9.2 LED OK Page 11
9.3 CODE “– – –” ON THE DISPLAY Page 11
9.4 LED ALARM Page 11
10. DELTA-P / VALVES BUTTON Page 12
11. LOW PRESSURE ( Stand-by ) FUNCTION Page 12
12. ∆P VALUE PLAYBACK (option) Page 12
12.1 4÷20 mA CONNECTION Page 12
12.2 4÷20 mA ASSEMBLED CARD Page 13
12.3 FULL-SCALE 4÷20 mA SETTING Page 14
13. FACTORY PRESETTINGS Page 14
14. TROUBLESHOOTING Page 15
15. FUSES TABLE Page 15
16. LEGEND Page 16
17. 200-SERIES FRONT PANEL Page 17
18. 200-SERIES 4 – 32 GENERAL ASSEMBLY Page 18
19. 200-SERIES 36 – 64 GENERAL ASSEMBLY Page 19
20. 200-SERIES 68 – 128 GENERAL ASSEMBLY Page 20
NOTE: figures shown inside square brackets […] refer to positions on drawing pages 17.
CAUTION: before use, read the instructions thoroughly to acquire sufficient knowledge of the
product. For your convenience, keep this sheet as a quick reference.
1. MAIN FEATURES
The 200-SERIES completely controls the GOYEN diaphragm valves, on the dust collector filters, with
pneumatic cleaning procedures (pulse-jet). The main features of the 200-SERIES are:
– Automatic regulation of cleaning, according to the level of filter clogging (∆P).
– Operating mode selection (MANUAL Mode or AUTOMATIC Mode).
– Automatic identification of connected valves (disconnected outlets are automatically skipped).
– Shut Down Cleaning, with programmable number of cycles.
– Low Pressure or stand-by function.
– Remote commutation of position (MANUAL or AUTOMATIC).
– ∆P value playback (option).
2
2. TECHNICAL FEATURES
WEEE
The device should be disposed of in accordance with current European regulations
3
3. INSTALLATION GUIDELINES
• Do not expose the MCS to direct sunlight in order to avoid overheating of the circuit board.
• Connect MCS to a continually powered line to allow SHUT-DOWN CLEANING when the
fan stops and to have maximum precision in the ∆P measurements.
• Protect MCS from rain, water infiltration and humidity. Incomplete closing of the cover may
cause infiltration which can seriously damage the circuit board.
• The initial length of conduit which holds the electric cables which run to the MCS, should be
turned upwards or interrupted before the appliance. This will stop any water or condensate
entering the MCS.
• Use Only cable gland with protection grade IP65 and of proper size ( according to the cable
used )
• A disconnecting switch has to be installed on the power line before the MCS
• All wiring should be carried out by a qualified electrician to avoid risk of fire and electrical
shocks
• MCS wiring has to be performed in order to separate the different types of cables , ( power ,
relay’s contact, valve output , 4-20ma output) and in order not to pass close to the PCB.
• Before opening the unit , be sure that ,MCS is switched off (switch on/off (1) on 0 and wires on
clamps (4) disconnected , including connection to alarm / signal relays .
• All MCS electrical connections , including solenoid valves have to use separate paths in
respect to the other loads .
• Voltage selectors jumpers have o be positioned only by skilled personnel and following the
instructions.
• A wrong Voltage selectors jumpers positioning may cause potential danger to the personnel
safety .
4
4. PRELIMINARY CHECKS
1) Check that the 200-SERIES has no power (switch on/off [1] on 0 and terminals [4] disconnected).
2) Check that the value of power supply, registered on the yellow label [22] is the same as the one of the
available power supply of grid.
3) Check that the outlet voltage (valves), registered on the yellow label [22] is the same as the voltage
of the solenoid valves.
5. ELECTRICAL CONNECTIONS
1) Check that the 200-SERIES has no power (switch on/off [1] on 0 and terminals [4] disconnected).
2) Unscrew and open the terminal cover [20].
3) Pull out the extractable terminals [2].
4) Check that the connections to the valves are correct and insulated respect to the ground. Therefore
testing the insulation between ground [3] and common (C) with outlets connector disconnected.
5) Connect the valves to the terminals [2], between common (C) and numbered terminals of the outlets
· The grounding [3] of the valves is necessary if the outlets voltage is greater or equal to 48V.
· Never connect the commons (C) or the outlets to ground [3].
· The commons (C) are connected between them on the printed circuitry. Carry out a common to
each valve or group together the commons in one wire.
· The outlets are of static type, with “zero-crossing” command, to prevent electrical noises.
6) Put back the extractable terminals [2].
7) Power the 200- a) With 230 V of grid (L = phase, N = neutral)
SERIES [4]:
b) With 115 V from auxiliary transformer (solenoids, control switches,
etc.). It is necessary to connect to the ground one of two terminals of
secondary and to connect it to the N [4].
c) – Special realization 24/48 V: it is necessary to connect to the ground
one of two terminals of secondary and to connect it to the N [4].
– Special realization 24 V DC: the terminals [4] are this: + –
8) Close and screw the terminal cover [20].
The ∆P into the filter is measured by an internal probe, connected to the filter by 2 filtered pressure taps.
The filtered pressure taps avoid that the process powders block the tubes connecting probe and filter.
For the depressurised filters install on the filter wall both the filtered pressure taps, one on the dusty air
plenum and one on the clean air plenum. For the pressurised filters, install only one filtered pressure tap
on the dusty air plenum. For each filtered pressure taps refer to the instructions below: (Drawing 6.3):
1) Drill, on the filter wall, the 4 fixing holes for the tap (∅ 3,75 mm., inter axial distance 39 mm.).
2) At the centre of the 4 fixing holes, make 3-5 pressure intake holes, all in a circle with radius of 10
mm. The ∅ of the holes must be 4 mm.
3) Position the rubber seal. If the support surface is irregular, you must fill with silicon
4) Position the filtered pressure tap, with the tube connection turned upside.
5) Fix the filtered pressure tap with the self-tapping screws (∅ 4,25 mm.).
5
6.2. FILTERED PRESSURE TAPS: CONNECTION
Connect the 2 tubes of the filtered pressure taps to nipples [13]. Connect the tube of the tap of the filtered
air to the “-” inlet. Connect the tube of the tap of the dusty air to “+” inlet.
Note: – Install the pressure taps so that neither condensate nor powder can precipitated.
– The 2 tubes (∅ 6/4) that connect the filtered taps to nipples [13], must be lead upwards in the
first part of the circuit. This avoids that into the tubes precipitated condensation. In damp
processes, where condensation is likely, for each tube there must be a drainpipe.
– If the pressure taps are correctly installed and connected to nipples [13], the display [7] shows
positive values of ∆P. If the display shows negative values of ∆P, the connections of 2
pressure taps are reversed.
– If the ∆P goes below –0,14 kPa, on the display [7] appears “– – –”. In this case, reverse the
tubes of 2 filtered taps. If the problem persists, use the regulation [15] to reset the indication
at 0 kPa.
6.3 DRAWING1: FILTERED TAPS
Pressure Holes
Fori presa pressione Positioned
(3÷5 Ø 4 central)
(3÷5 Ø 4 al centro, Upward
Otherwise 1entro
hole Øun20
Ø mm)
di 20 mm)
Filter wall
Seal
Ø 20
25 45
39
39 Wad
50
4 fixing holes
Ø 3,75 Con superfici irregolari,
With irregular surfaces, silicon the
siliconare abbondantemente
seal well before joining the parts.
50 25 la guarnizione prima di
Self-tapping screws
Ø 4,25
–
Filtered air
Fan
+
Dusty air
inlet
Bag filter
200-
SERIES
6
7. SETTINGS
Check that the 200-SERIES is not powered (switch on/off [1] on 0 and terminals [4] disconnected).
Check: 1) That the power supply voltage, registered on the yellow label [22] is the same as the one
of the available power supply.
2) that the voltage (valves), registered on the yellow label [22] is the same as that of the
solenoid valves.
1) Unscrew to 45° anticlockwise the 2 screws [21]. Simultaneously push up and open the
transparent cover of the 200-SERIES.
2) Unscrew the 4 screws of the green panel. Lift the green panel (do not remove it as it is
connected to the base of the enclosure!).
3) Check that the power supply voltage, selectable with the jumpers [5], is the same as the power
available (example.: both 230 V).
4) If the two voltages are different, move the jumpers [5] on the position selecting the same voltage
as that available.
1) Check that the outlets voltage, selectable with the jumpers [6], is the same as that indicated on
the solenoid valves (example.: both 24 V).
2) If the two outlets voltage are different, move the jumpers [6] on the position selecting the same
outlets voltage as that on the solenoid valves.
(ATTENTION: on the jumpers [6] select the same value for outlets voltage!).
1) Check that the type of outlets voltage, selectable with the jumpers [8], is the same as that on the
solenoid valves (example.: both AC).
2) If the two type of outlets voltage are different, move the jumpers [8] on the position selecting the
voltage required .
3) Replace the front panel and tighten the 4 screws of the panel.
4) Close the transparent cover and tighten the 2 screws [21], rotating them to 45° in clockwise
direction.
CAUTION!
Never select the outlets 230 V in DC for the outlets!
7
7.2. MANUAL AND AUTOMATIC MODE OPERATION
Note: select the shortest PULSE TIME possible, between all those compatible with maximum
obtainable particle separation. This is valid both in MANUAL and AUTOMATIC Mode.
• Ideal time for “bag” filters: between 100 ms and 400 ms.
• Ideal time for “standard cartridge” filters: between 500 ms and 1 second.
• Ideal time for “rotating nozzle cartridge” filters: between 1sec and 4 seconds.
In MANUAL Mode, the 200-SERIES commands the valves with fixed PAUSE TIME. The cleaning is
not dependant on the level of the filter bags clogging. The MANUAL Mode must be only used during
the start-up phase.
When the 200-SERIES is in MANUAL Mode, the LED MANUAL [30] flashes.
In MANUAL Mode, the PAUSE TIME depends on selected Manual Pause Time.
In AUTOMATIC Mode, the cleaning is automatically adapted to the level of the filter bag clogging. The
cleaning starts when the filter ∆P exceeds the value of selected SET DELTA-P (see 7.3). The SET
DELTA-P to select depends on the structural characteristics and wear and tear of the filter and on the
type of process.
When the 200-SERIES is in AUTOMATIC Mode, the LED MANUAL [30] is off.
In AUTOMATIC Mode, the PAUSE TIME depends on the selected Automatic Pause Time.
It is possible to pass from AUTOMATIC Mode to MANUAL Mode (and vice versa) closing a remote
contact. See below:
8
7.3 SETTINGS: PARAMETERS SELECTION
Check that all electrical connections have been done as described in Point 5.
Switch on/off [1] on 1. On the display [7] appears, for a few seconds the 200-SERIES identification
code. Immediately after, on the display appears the value of the filter ∆P. If the LED OK [18] and
PAUSE [12] turn on and the LED MANUAL [30] flashes, the 200-SERIES is in MANUAL Mode.
If only the LED OK [18] turns on, the 200-SERIES is in AUTOMATIC Mode.
Attention! When the fan stops, the display [7] must indicate a filter ∆P value of 0 kPa.
Otherwise, use the regulation [15] to reset the indication at 0.
1) Press SELECT MENU [9]: on the display [7] flashes the no. 1:
with +/– buttons [10] select the PULSE TIME (0,01 ÷ 9,99 sec).
2) Press SELECT MENU [9]: on the display [7] flashes the no. 2:
with +/– buttons [10] select the MANUAL PAUSE TIME (1 ÷ 999
sec).
3) Press SELECT MENU [9]: on the display [7] flashes the no. 3:
with +/– [10] buttons select the SET DELTA-P (0,01 ÷ 9,99 kPa).
The cleaning starts every time that the filter ∆P exceeds the SET
DELTA-P. The cleaning stops every time that the filter ∆P goes
below the SET DELTA-P.
4) Press SELECT MENU [9]: on the display [7] flashes the no. 4:
with +/– buttons [10] select the AUTOMATIC PAUSE TIME.
(1-999 sec)
5) Press SELECT MENU [9]: on the display [7] flashes the no. 5:
with +/– [10] buttons select the PAUSE IN AFTER CLEANING
CYCLE (1 ÷ 99 sec).
– The SHUT DOWN CLEANING automatically starts when the
filter ∆P goes below 0,10 kPa.
6) Press SELECT MENU [9]: on the display [7] flashes the no. 6:
with +/– buttons [10] select the NO. of CYCLES for the SHUT
DOWN CLEANING (0 ÷ 99 times).
(Select 0 to exclude the After Cleaning Cycle)
The functioning of the valve is indicated by the lighting up of the LED PULSE [11].
The pause between 2 valves firing is indicated by the lighting up of the LED PAUSE [12].
9
succession, on the display [7]. If there are no valves connected, on the display will show the
numbers of all outlets.
– During the first cycle, check that none of the connected valves are skipped.
– GOYEN presets: PULSE TIME, PAUSE TIME, SET DELTA-P, SET DELTA-P ALARM,
NO. OF CYCLES for the SHUT DOWN CLEANING and ∆P PRECOATING (see Chap. 13).
– We suggest setting 200-SERIES working parameters in order to clean the filter with the lowest
possible frequency in order to reduce dust emissions due to bag stress, to achieve a longer
lifetime of the bags and to reduce compressed air consumption.
– The PAUSE TIME must not be lower than the time necessary to recharge the pressure into the
tank!
– Press the DELTA-P/VALVES button [14] to return in E (run) from every step of SELECT
MENU. To change a parameter value immediately returning in E: a) enter SELECT MENU,
until the step of the desired parameter; b) change its value; c) press SELECT MENU; d) press
DELTA-P/VALVES button to return in E.
– During the parameters selection (SELECT MENU), after 5 minutes from the last button
pressed, the 200-SERIES automatically return in E (run).
After every utilization, it is useful to carry out one or more cycles of SHUT DOWN CLEANING, to free
the filtering elements of residual dust. The SHUT DOWN CLEANING starts when the ∆P goes below
0,10 kPa..
ATTENTION: • The SHUT DOWN CLEANING only starts if the 200-SERIES is in AUTOMATIC
Mode!
9.1 LEDS
1) LED MANUAL [30]: Flashes if the 200-SERIES is in MANUAL mode. It’s off if the 200-
SERIES is in AUTOMATIC mode.
2) LED PULSE [11]: It’s on when a valve is firing.
3) LED PAUSE [12]: It’s on between the firing of one valve and another
4) LED L. PRESS. [31]: It flashes when the 200-SERIES is in low-pressure.
10
9.2 LED OK
Incidental damages of the microprocessor are shown by the turning off of the LED OK [18]. This
problem cannot be resolved by the customer: Refer problem directly to GOYEN.
Refer to terminals WD [24]. If the 200-SERIES has no power, the contact of the relay is on N.C. When
you power the 200-SERIES, the relay is energized and the contact switches on N.O. If the contact
switches on N.C when the 200-SERIES is powered, the LED OK [18] turns off.
On the display [7] appears “– – –” if the filter ∆P goes below –0,14 kPa. If this is the case:
1) Check that the filtered pressure taps are connected to the pressure nipples [13] see chapter 6.2.
2) If the problem persists: • disconnect the connection pipes between the pressure filtered taps and
pressure nipples [13]
• use the regulation [15] to reset the indication at 0 kPa.
• reconnect [13] the connection pipes between the pressure filtered taps
and pressure nipples [13].
The LED ALARM [30] switch on if the ∆P inside the filter exceed the ∆P ALARM selected, or if there
is a short circuit on one or more outlets.
a) If on the display [7] appears the code PPP1, the filter ∆P exceeded the selected ∆P ALARM.
Operate as follows:
1) Stabilise the filter ∆P.
2) Press “–” to return in E (run).
3) Press RESET [19]: the alarm disconnects.
b) If on the display [7] appears the letter A followed by a number, the valve countermarked with
that number is in short circuit. Operate as follows:
1) Continue to press the button “+” [10], to read on the display the number of the faulty
outlets. Attention: the alarm intervention excludes the faulty valve, which is in short
circuit.
2) Repair the damages.
2) Press “–” to return in E (run).
3) Press RESET [19]: the alarm disconnects. The command of defective valves restarts.
Refers to terminals ALL [24]. If the 200-SERIES is not powered, the contact of relay is on N.C. When
you power the 200-SERIES, the relay is energized and the contact switches on N.O. If the contact of
relay switches on N.C when the 200-SERIES is powered, the LED ALARM [17] turns on.
11
10. DELTA P / VALVES BUTTON
On the LED display [7], the 200-SERIES shows the filter ∆P. Press DELTA-P/VALVES [14] to pass
from filter ∆P indication to active valve indication (and vice versa). When you turn on the 200-SERIES,
on the display automatically is visualised the filter ∆P.
With the assembled board [4] is possible to broadcast to distance, on other unit, the ∆P value that is showed
on 200-SERIES display [7].Connect to the terminals 4÷20 mA POS [1] e 4÷20 mA NEG [2] see page 12.
12.1 4 ÷ 20 mA CONNECTION
12
1
4÷20 mA
POS S.B A.M RIGHT
DOWN
CORNER
OF 200-
Remote SERIES
4÷20 mA
DISPLAY NEG
2
R
SHIELDED CABLE
POWER SUPPLY
5 ÷ 30 V DC 3
6 L N
FRONT BACK
RIGHT TOP
PINS
CORNER
OF 200-SERIES
PLUGS
13
12.3 FULL-SCALE 4 ÷ 20 mA SETTING
1. Turn on the 200-SERIES (switch on/off [5] on 1) keeping pressed the RESET key until code
“PPSS” appears on the display. Release RESET key: on the display code “A 0” appears.
2. Press “– ” until compose on the display the number “A879”.
3. Press SELECT MENU: on the display appears the letter C and the number of outlets of the 200-
SERIES.
(Example: in case of a 200-SERIES32, appears “C 32” on the display).
4. Press SELECT MENU: on the display appears “ P 0 “.
SELECT
5. Leave “P 0” if you want the full-scale value of 9,99 kPa
With “+” select “P 1” if you want the full-scale value of 1,00 kPa. PPSS
With “+” select “P 2” if you want the full-scale value of 2,00 kPa.
MENU
With “+” select “P 3” if you want the full-scale value of 3,00 kPa. – +
With “+” select “P 4” if you want the full-scale value of 4,00 kPa.
With “+” select “P 5” if you want the full-scale value of 5,00 kPa. RESET
Press SELECT MENU: on the display appears the ∆P into the
Filter.
6. Press “–”: on the display appears “A 0” code.
7. With “+” compose on the display “A123” code.
8. Press SELECT MENU: on the display appears “nnnn” for 3 seconds: the cycle restarts.
GOYEN presets the parameters of every 200-SERIES (to change the preselections see 7.3).
14
14. TROUBLESHOOTING
IMPORTANT NOTE: if you use the 200-SERIES with power supply at 24V DC, check that it isn’t lower
than 24V and the power is suitable at connected load.
NB
In case of replacement you must respect the above value
15
16. LEGEND
1) On/off switch
2) Extractable terminals (outlets and commons)
3) Ground terminals for outlets
4) Power supply terminals
5) Jumper for inlet power supplies selection.
6) Jumper for voltage selection to valves
7) Display
8) Jumper for the frequency of outlet power supplies selection (A.C./D.C.).
9) SELECT MENU button
10) +/– Buttons
11) LED PULSE
12) LED PAUSE
13) Inlet pressure nozzle
14) DELTA-P/VALVES button
15) LED LOW PRESSURE
16) AUTOMATIC/MANUAL mode button
17) LED ALARM
18) LED OK
19) RESET button
20) Terminals cover
21) 2 screws of transparent cover
22) Yellow label voltage setting
23) Main Fuse
24) Relay ALL and relay WD terminals
25) Product code and registration number
26) Terminals for remote changing of the Mode
27) LOW PRESSURE or STAND-BY terminals
28) 4 ÷ 20 mA positive terminal.
29) 4 ÷ 20 mA negative terminal.
30) LED MANUAL
31) Fuse external contacts supply
32) Fuse internal +5v supply. (Micro, display)
ATTENTION!
Before you open the unit and connect the terminals, check that the
On/off [1] switch is on 0 and that the terminals [4] are
disconnected.
16
17.
200-SERIES FRONT PANEL
17
31 32 9 7 12 11 14
17
18
15
19
10
21
30
16
13
4 2 22 25
20
5 26
8
6
23
24
28
1 29
27
18
200-SERIES 36-64: GENERAL ASSEMBLY
19
PULSE CONTROLLER 200
Tel: +44 (0) 125 6817 800 (U.K)
+61 (2) 9792 0201 (Australia)
www.cleanairsystems.com
ISOLATE BEFORE REMOVING PANEL
L N L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 L15 L16 L17 L18 L19 L20 L21 L22 L23 L24 L25 L26 L27 L28 L29 L30 L31 L32 WD C N.O N.C
LINE COMMON OUTPUT 1-8 COMMON OUTPUT 9-16 COMMON OUTPUT 17-24 COMMON OUTPUT 25-32 ALL C N.O N.C