06 DCPD6 Product Manual - V1.01
06 DCPD6 Product Manual - V1.01
06 DCPD6 Product Manual - V1.01
Product Overview
DC Power Distributor 6 (DCPD6) has the following functions:
1) Provides one channel of -48V DC power input and supports a current of not more than
100A;
2) Provides nine channels of DC power output, each of which is controlled by an independent
hydraulic breaker to support a current of not more than 20A;
3) Provides lightning protection and surge protection for the power output through a built-in
lightning protection board;
4)
Specifications
The specifications of DCPD6 are described in Table 2-1.
Table 2-1 DCPD6 Specifications
Characteristics
Specifications
Model
DCPD6
Name
DC Power Distributor 6
Description
Dimension (W*H*D) mm
Weight
<5kg
Surge
Waterproof/dustproof level
IP20
Operating temperature
-20 ~55
Storage temperature
-40 ~70
Relative humidity
5%-95%
Typical Application
DCPD6 applies to distributed base station systems, in which it powers BBU and RRU. The power
cable of RRU should be shielded and the shielded layer must be connected to the outdoor
grounding bar before being connected into the cabinet or equipment room.
Figure 3-1 DCPD6 Power Distribution
Outdoor
DC Power input
Indoor