Project : System :

Marina View Wet Riser System (WRP 2-1 & 2-2)

Date : 12.04.09

HYDRAULIC CALCULATIONS FOR WET RISER SYSTEM


Minimum Requirement (CP29:1998 & Fire Precaution Act in Building 2002) The running pressure/flow for wet rising mains :Minimum running pressure at each landing valve : min 3.5 bar and max 5.5 bar Type of Occupancy : Mixed Occupancy Minimum Flow requirement : 57 l/s No. of rising mains : 2 nos Height from pump to Landing Valve : 1 m (Highest Landing Valve) Design Data Wet riser pipe diameter Pipe length from pump to most unfavourable landing valve No. of bends and fittings Equivalent length of bends and fittings (3m per bend) Total Equivalent Length Total Flow Rate Using Hazen-William formula: Q1.85 Pipe Frictional Loss , P = 6.05 x 107 C1.85 x d4.87 Pipe Frictional Loss = PxL Total Pressure Loss through pipe , PL Pressure Summary : Static Gain = Hx10Kpa/m Pipe Frictional Loss = PxL Minimum Running Pressure Total Pressure required Pp - LV 150 62 8 24 86 3420 0.751 64.588

d=

150

150

L= Q= P=

0 0 0 0.000 0.000

0 0 0 0.000 0.000

150 0 0 0 0 0

mm m nos. m m l/min

0.000 kPa/m 0.000 kPa 64.59 kPa

10.00 Kpa 64.59 Kpa 350.00 Kpa 424.59 Kpa

Wet Riser Pump Selected

3420 l/min @

424.59 kPa

(Minmum)