Kumpalavalee et al., 2017 - Google Patents
Condition evaluation of power transformers using dissolved gas analysis and dielectric breakdown voltage testKumpalavalee et al., 2017
- Document ID
- 9951063895392297193
- Author
- Kumpalavalee S
- Suwanasri T
- Suwanasri C
- Wattanawongpitak S
- Sooksodkiao T
- Tanprasert P
- Kaewkamthong B
- Publication year
- Publication venue
- 2017 International Electrical Engineering Congress (iEECON)
External Links
Snippet
This paper proposes the techniques for evaluating power transformer condition based on frequently updated test results. According to planned maintenance, insulation oil is regularly sampled and analyzed in laboratory to determine problems inside main tank by dissolved …
- 230000015556 catabolic process 0 title abstract description 38
Classifications
-
- G—PHYSICS
- G01—MEASURING; TESTING
- G01R—MEASURING ELECTRIC VARIABLES; MEASURING MAGNETIC VARIABLES
- G01R31/00—Arrangements for testing electric properties; Arrangements for locating electric faults; Arrangements for electrical testing characterised by what is being tested not provided for elsewhere
- G01R31/12—Testing dielectric strength or breakdown voltage; Testing or monitoring effectiveness or level of insulation, e.g. of a cable or of an apparatus, for example using partial discharge measurements; Electrostatic testing
- G01R31/1227—Testing dielectric strength or breakdown voltage; Testing or monitoring effectiveness or level of insulation, e.g. of a cable or of an apparatus, for example using partial discharge measurements; Electrostatic testing of components, parts or materials
- G01R31/1263—Testing dielectric strength or breakdown voltage; Testing or monitoring effectiveness or level of insulation, e.g. of a cable or of an apparatus, for example using partial discharge measurements; Electrostatic testing of components, parts or materials of solid or fluid materials, e.g. insulation films, bulk material; of semiconductors or LV electronic components or parts; of cable, line or wire insulation
- G01R31/1272—Testing dielectric strength or breakdown voltage; Testing or monitoring effectiveness or level of insulation, e.g. of a cable or of an apparatus, for example using partial discharge measurements; Electrostatic testing of components, parts or materials of solid or fluid materials, e.g. insulation films, bulk material; of semiconductors or LV electronic components or parts; of cable, line or wire insulation of cable, line or wire insulation, e.g. using partial discharge measurements
-
- G—PHYSICS
- G01—MEASURING; TESTING
- G01R—MEASURING ELECTRIC VARIABLES; MEASURING MAGNETIC VARIABLES
- G01R31/00—Arrangements for testing electric properties; Arrangements for locating electric faults; Arrangements for electrical testing characterised by what is being tested not provided for elsewhere
- G01R31/02—Testing of electric apparatus, lines or components, for short-circuits, discontinuities, leakage of current, or incorrect line connection
- G01R31/027—Testing of transformers
-
- G—PHYSICS
- G01—MEASURING; TESTING
- G01R—MEASURING ELECTRIC VARIABLES; MEASURING MAGNETIC VARIABLES
- G01R31/00—Arrangements for testing electric properties; Arrangements for locating electric faults; Arrangements for electrical testing characterised by what is being tested not provided for elsewhere
- G01R31/12—Testing dielectric strength or breakdown voltage; Testing or monitoring effectiveness or level of insulation, e.g. of a cable or of an apparatus, for example using partial discharge measurements; Electrostatic testing
- G01R31/1227—Testing dielectric strength or breakdown voltage; Testing or monitoring effectiveness or level of insulation, e.g. of a cable or of an apparatus, for example using partial discharge measurements; Electrostatic testing of components, parts or materials
- G01R31/1236—Testing dielectric strength or breakdown voltage; Testing or monitoring effectiveness or level of insulation, e.g. of a cable or of an apparatus, for example using partial discharge measurements; Electrostatic testing of components, parts or materials of surge arresters
-
- G—PHYSICS
- G01—MEASURING; TESTING
- G01R—MEASURING ELECTRIC VARIABLES; MEASURING MAGNETIC VARIABLES
- G01R31/00—Arrangements for testing electric properties; Arrangements for locating electric faults; Arrangements for electrical testing characterised by what is being tested not provided for elsewhere
- G01R31/327—Testing of circuit interrupters, switches or circuit-breakers
- G01R31/3271—Testing of circuit interrupters, switches or circuit-breakers of high voltage or medium voltage devices
-
- G—PHYSICS
- G01—MEASURING; TESTING
- G01R—MEASURING ELECTRIC VARIABLES; MEASURING MAGNETIC VARIABLES
- G01R31/00—Arrangements for testing electric properties; Arrangements for locating electric faults; Arrangements for electrical testing characterised by what is being tested not provided for elsewhere
- G01R31/02—Testing of electric apparatus, lines or components, for short-circuits, discontinuities, leakage of current, or incorrect line connection
- G01R31/024—Arrangements for indicating continuity or short-circuits in electric apparatus or lines, leakage or ground faults
Similar Documents
Publication | Publication Date | Title |
---|---|---|
Muhamad et al. | Comparative study and analysis of DGA methods for transformer mineral oil | |
Van Bolhuis et al. | Monitoring and diagnostic of transformer solid insulation | |
Jahromi et al. | An approach to power transformer asset management using health index | |
Singh et al. | Dissolved gas analysis technique for incipient fault diagnosis in power transformers: A bibliographic survey | |
Haema et al. | Condition assessment of the health index for power transformer | |
Brandtzæg | Health indexing of Norwegian power transformers | |
Setayeshmehr et al. | A procedure for diagnosis and condition based maintenance for power transformers | |
Braunlich et al. | Assessment of insulation condition of large power transformers by on-site electrical diagnostic methods | |
Kumpalavalee et al. | Condition evaluation of power transformers using dissolved gas analysis and dielectric breakdown voltage test | |
Hamid et al. | Dissolved gas analysis (DGA) of vegetable oils under electrical stress | |
Suwanasri et al. | Failure statistics and power transformer condition evaluation by dissolved gas analysis technique | |
Shanker et al. | Case studies on transformer fault diagnosis using dissolved gas analysis | |
Chitnavis et al. | Review of critical analysis for life estimation of power transformer | |
Ding et al. | Learning from success and failure in transformer fault gas analysis and interpretation | |
Jagers et al. | Transformer reliability and condition assessment in a south african utility | |
Chaidee et al. | Failure statistics and condition evaluation for power transformer maintenance | |
Furqaranda et al. | Analysis Oil Condition of Transformer PT-8801-A by Using the Method TDCG, Rogers Ratio, Key Gas, and Duval Triangle: A Case Study at PT. Perta Arun Gas | |
Uchida et al. | Estimating the remaining life of water-treed XLPE cable by VLF voltage withstand tests | |
Steed | Condition monitoring applied to power transformers-an REC experience | |
Dmitriev et al. | Fuzzy dynamic model of power equipment state assessment | |
Okubo et al. | Electrical insulation diagnostic method and maintenance criteria for oil-immersed power transformers | |
Angkapiyasiri et al. | Condition evaluation of power transformer by analysis of insulating oil tests | |
Arshad et al. | Power transformer critical diagnostics for reliability and life extension | |
Arora | Innovative way of Understanding Test Results Obtained by DGA Test of power Transformers based on iEEE & iEC Standards | |
Arshad et al. | Power transformer insulation response and risk assessment |