C264en-Cortec - EXTENSION RACK
C264en-Cortec - EXTENSION RACK
C264en-Cortec - EXTENSION RACK
MiCOM C264C/264
Disclaimer / Décharge / Descarga
Disclaimer
Our policy is one of continuous development. Accordingly the design of our products may change at any time.
Whilst every effort is made to produce up to date literature, this document should only be regarded as a guide
and is intended for information purposes only.
Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
Décharge
Nous avons une politique de développement permanent.
Par conséquent, la conception de nos produits risque de subir des modifications à tout moment.
Bien que nous nous efforcions de tenir notre documentation à jour, ce brochure ne devra être considérée
que comme guide à des fins d’information seulement.
Son contenu n’a pas titre d’offre de vente ou d’assistance technique sur l’application d’un produit mentionné.
Descarga
Nuestra política se basa en un desarrollo continuo.
Por este motivo, el diseño de nuestros productos puede experimentar cambios en cualquier momento.
Realizamos el máximo esfuerzo para producir documentación actualizada. Estas páginas sólo tienen valor informativo.
Su contenido no constituye en modo alguno una proposición de venta o asesoramiento en relación con ninguno de los productos
mencionados.
Declinamos toda responsabilidad por las decisiones que se adopten basándose en su contenido sin notificación al respecto.
MiCOM C264 CORTEC FOR C264-V3/V4, fully assembled device Version: V3_28
Variants Notes /
Order N° Ext. N°
cpu serial
biu serial
SBU200
Tropical
DIU200
DIU211
AIU201
AIU211
Voltage
Built in
Isagraf
detach
TMU
GHU
DOU
AOU
CCU
rack
lang
Soft
SW
MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application
cpu
P.S
MiCOM C 2 6 4 T 2 1 I 6 A 5 0 0 0 2 4 5 0 2 0 0 C 0 0 1 1 1 1 N 0 0
CORTEC CODE Synthesis (for export to Word Docs) :
MiCOM C264T21I6A5000240200C001111N00
Basic Model and Components
Package rack 4U (CAS2xx) + FBP2xx
1) 1)
Case 40 T for use wo. CT/VT (Compact size), IP52, pin-terminal connection, 6 slots C
1) 1)
Case 40 T for use with CT/VT (Compact size), IP52, pin-terminal connection, 4 slots S
1) 1)
Case 80 T for use without CT/VT (Medium size), IP20, pin-terminal connection, 15 slots L
1) 1)
Case 80 T for use with CT/VT (Medium size), IP20, pin-terminal connection, 14 slots M
1) 1)
Case 60 T for use without CT/VT (Medium size), IP20, pin-terminal connection, 10 slots T
1) 1)
Case 60 T for use with CT/VT (Medium size), IP20, pin-terminal connection, 9 slots U
Front panel (GHU2xx) - Schneider Electric
Front Panel Leds and L/R switch - IP52 protection - GHU210 (40TE) or GHU211(80TE) or GHU212(60TE) 0 New GHU212 60TE! Generally available
Front Panel with Leds + Graphic Display LCD + L/R switch -GHU200(40TE)or GHU201(80TE) or GHU202(60TE) - IP52 prot. 1
Simple Blind front panel : GHU220 (40TE) or GHU221(80TE) or GHU222 (60TE) 12)
2 New GHU222 60TE! Generally available
Detachable Front Panel with Graphic Display 40TE (GHU200) + Simple Blind Front panel (GHU22x) 12)
3 Select the cable lenght
Detachable Front Panel with Graphic Display 80TE (GHU201) + Simple Blind Front panel (GHU22x) 12)
4 Select cable
Detachable Front Panel with Leds 40TE (GHU210) + Simple Blind Front panel (GHU22x) 12)
5 Select cable
Detachable Front Panel with Leds 80TE (GHU211) + Simple Blind Front panel (GHU22x) 12)
6 Select cable
8)
Language (including: Front panel labels, HMI)
French ( English) 0
English (English) 1
Spanish (English) 2
German (English) 3
Power supply and legacy ports (BIUxxx)
about BIU241: Vn +/- 20% - 2 DI/2DO - 2*serial Ports (port n°1 and port n°2 )
BIU241-A01 : VA,nom: 24 VDC / Nominal voltage for 2DI: 24 V DC A
BIU241-A02 : VA,nom: 48 to 60 VDC / Nominal voltage for 2DI: 48/60 V DC E
BIU241-A03 :VA,nom: 110 to 125 VDC / Nominal voltage for 2 DI: 110/125 V DC I
BIU241 A04 : VA,nom: 220 VDC and 115 to 230VAC / Nominal voltage for 2 DI: 220 V DC M
about BIU261: Redundant/Double SOURCE (+/- 20%) - 2 DI/2DO - 1 *serial Port only
BIU261-A02 : VA,nom: 48-60VDC / Nominal voltage for 2DI: 48-60 V DC N Warning : only 1 serial port (n°2)
BIU261-A03 : VA,nom: 110-125 VDC / Nominal voltage for 2DI: 110-125 V DC P Warning : only 1 serial port (n°2)
BIU261-A04 :VA,nom: 220VDC / Nominal voltage for 2 DI: 220 V DC Q Warning : only 1 serial port (n°2)
about the BIU100 : only to be interfaced to the Redunded Power supply rack : RPS280
15)
BIU100 : 12V auxiliary voltage, 2 non isolated serial links R Consult Mkg
8)
Factory setted legacy ports: port n°1 and n°2 on BIU241 board, only port n°2 on BIU261
Definition : Port N°2:RS232or RS422 or RS485 ; Port N°1: RS232or RS485
Port N°2: RS232 ; Port N°1: RS232 1
Port N°2: RS232 ; Port N°1: RS485 (BIU241 only) - Not allowed on BIU261 2 Not applicable for BIU261
Port N°2: RS485 ; Port N°1: RS485 6
CPU and Base Communications (CPU2x0)
14)
Power PC processor board with Ethernet port(s) , 2 serial links, IRIGB input- CPU260-based
CPU260(Type2) , with 1 Ethernet RJ45, IRIG-B input, 2 Serial links (Ref CPU2 = 45196300 A5) 5 Consult Mkg
CPU260(Type2)-based with Pack 2 = IRIG-B input +2 serial links+ 100BaseFL MultiMode Ethernet 6 Consult Mkg
CPU270(Type3) , with 2*Ethernet RJ45, 64Mb FlashMemory, 1 ppm Oscillator accuracy (Ref CPU270 = 2071590A02 ) 8 Available w Mkg autorisation (delivery time)
CPU270(Type3) , with 2*Ethernet RJ45, 64Mb FlashMemory, 128Mb SDRAM, 50ppm Oscillator (Ref CPU270 = 2071590A01 ) 9
CPU275 (Type 4) , with 2*Ethernet RJ45, 128Mb FlashMem, 256Mb SDRAM, 50 ppm Oscill (Ref CPU275 =2072282A01) A Generally Available
CPU275 (Type 4), with 2*Ethernet RJ45, 128Mb FlashMem, 256Mb SDRAM, 1 ppm Oscill (Ref CPU275 =2072282A02) B Generally Available
8)
For CPU with 2 serial links: Factory setted legacy ports N°3/4
Configuration of the legacy Ports N°3/4 :RS232 (non isolated), RS485, Optical settable no serial link
Port N°3:RS232 (non isolated) ; Port N°4: RS232 (non isolated) 1
Port N°3: RS485(ECU201) ; Port N°4: RS485(ECU201) 5
Port N°3: Optical(ECU200) ; Port N°4: Optical(ECU200) 9
Inputs / outputs boards and Ethernet-based switch boards
Manufacturing process 0)
Automatic affectation (as standard) of the I/O modules in the basic rack 0
Preferred affectation (customized with extra cost) of the I/O modules in the basic rack 1 consult us
17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A01 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=5A, Io operating range= 0,1-40Ion S -M H Refer to note 20)
17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A01 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range= 0,1-40Ion S -M J Refer to note 20)
17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A02 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range=0,01-8Ion S -M N Refer to note 20)
17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A02 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=1A, Io operating range= 0,01-8Ion S -M P Refer to note 20)
17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A03 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=1A, Io operating range=0,002-1Ion S -M Q Refer to note 20)
17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A04 (& DSP211) : Vnom: 57 to 130 VAC, 4*Ion=1A, Io operating range =0,01-8Ion S -M V Refer to note 20)
Nominal wetting voltage for digital inputs (DIU200 or DIU211 or CCU200 or DSP21x(-) 18)
) S=12)
VA,nom: 24 V DC (- to common) DIU200-A01 board or CCU200-A01 board or DSP21x-A01 0
VA,nom: 48/60 V DC (- to common) - DIU200-A02 board or CCU200-A02 board or DSP21x-A02 1
VA,nom: 110/125 V DC (- to common) - DIU200-A03 board or CCU200-A03 board or DSP21x-A03 2
VA,nom: 220 V DC (- to common) : DIU200-A04 board or CCU200-A04 board or DSP21x-A04 3
CCU211 : Multivoltage 24Vdc-> 250Vdc ; preset threshold : 17.4 VDC; also for DIU200-A02 and DSP21x-A02 (VA,nom:
48/60Vdc) C in case CCU211 is needed
CCU211 : Multivoltage 24Vdc-> 250Vdc ; preset threshold : 50 VDC; also for DIU200-A03 and DSP21x-A03 (VA,nom:
110/125 VDC) D in case CCU211 is needed
CCU211 : Multivoltage 24Vdc-> 250Vdc ; preset threshold : 86 VDC ; also for DIU200-A04 and DSP21x-A04 (VA,nom: 220
VDC) E in case CCU211 is needed
Digital inputs (16 DI) module, each with 16 digital inputs (DIU200A0x) 3) 22)
S=12)
16 optically insulated inputs in 8 isolated groups
DIU200 quantity = 0 to 4 or 6 for 40TE racks, 0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks X
Multi tension-peak-current Digital inputs (16 DI) module, each with 16 digital inputs DIU211 3) 13) 22)
S=12)
16 optically insulated inputs in 8 isolated groups ; preset threshold= 17.4Vdc
check 13) for thresholds and quantities
DIU211 quantity = 0 to 4 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks X
Digital outputs (10 DO) module, each with 10 digital outputs (DOU201) 3) S=12)
8 outputs NO contacts and 2 outputs NO/NC contacts
DOU quantity = 0 to 4 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks X
Mixed (8 DI + 4 DO) module each with 8 digital inputs and, 4 digital outputs4) (CCU200 or CCU211-Ref.2071732 ) 3) S=12)
8 optically insulated inputs (in 4 isolated groups) and 4 direct command relays (2 NO contacts) CCU211:, only with voltage codes : C, D or E
CCU quantity = 0 to 3 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 13 or 15 slots in 80TE racks 19) X Consult us for CCU-A07
DC 4 Analog inputs module (C or V transducer connection) each with 4 analogue inputs (AIU201) 3)
560477127.xlsx
C264 CORTEC Page 3
11/29/2021
MiCOM C264 CORTEC FOR C264-V3/V4, fully assembled device Version: V3_28
Variants Notes /
Order N° Ext. N°
cpu serial
biu serial
SBU200
Tropical
DIU200
DIU211
AIU201
AIU211
Voltage
Built in
Isagraf
detach
TMU
GHU
DOU
AOU
CCU
rack
lang
Soft
SW
MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application
cpu
P.S
MiCOM C 2 6 4 T 2 1 I 6 A 5 0 0 0 2 4 5 0 2 0 0 C 0 0 1 1 1 1 N 0 0
4 DC Analog Inputs in current or voltage (4 isolated groups) - Maximum of 6*AIU2xx in one case
AIU201 quantity = 0 to 4 or 6 for 40TE racks , =0 to 6 for 80TE racks X S=12)
3), 23)
DC 8 Analog inputs module (Current),with 8 analogue inputs (AIU211)
8 DC Analog Inputs in current (AIU211: 8 isolated channels) - Maximum of 6*AIU2xx in one case
AIU21x quantity = code 0 (=0 board) or code "A" to "F" for 1 to 6*AIU211 (code "1" to "6" for AIU210) X S=12), 24) Consult Mkg
3), 16)
Analog output module (Currents) ,with 4 analogue ouputs (AOU200)
4 Analog Outputs (PACIS V4.5.5 or upper, and RTUs applications)
AOU200 quantity = 0 to 4 for 40TE racks , 0 to 4 for 80TE racks x S=12)
Ethernet-based Switch Unit (SWU20x) 3) S=12)
Without 0
SWU200 - With four 10/100BaseT Ethernet ports (RJ45) 1
SWU202- With two 100BaseF MultiMode Ethernet ports (ST) and four 10/100BaseT Ethernet ports (RJ45) 3
SWU204- With two 100BaseF MonoMode Ethernet ports (SC) and four 10/100BaseT Ethernet ports (RJ45) 5
Ethernet-based Switch Redundant Unit (SWR20x) 3) -
For Ethernet Redunded Ring S=12)
SWR212 -With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45) 6 refer note 21)
SWR 214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45) 7 refer note 21)
SWD214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45) B refer note 21)
SWS214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45) Ref.=2071988A02 T refer note 21)
Softwares :
6)
C264 Standalone Configuration tool - SCT Consult us
Manuals :
CD-ROM documentation:
Technical and Operation guides - multilingual pdf documentations (English, French, Spanish and German) Consult us
0)
1) Different racks exist depending of user-selected CT/VT(TMU) & basic case size : N= nb of slots
Remark : C264 with 60 TE rack is only availabla with the Front Panel GHU202 (with LCD screen + Leds)
- The DSP200 is based on the TMS320C6711, Floating-Point Digital Signal Processor (DSP)
10) The sum of communication links (legacy SCADA and IEDs) must not exceed the maximum communication ports available.
11) For Specific Software version complete the Software CORTEC (sheet C264 SOFT)
For C264-R multirack applications, Select " No software loaded"
12) For Detachable Front panel, define the lenght of the required cable ; the Blind panel size depend on the Rack size.
13)
- DIU211 is delivered in C264 racks in replacement of DIU210 from 08/2009 : With DIU211, the board number limitation (due to DIU210 consumption)is not applicable.
- DIU211, when used in replacement of the DIU210, is configured with the following preset threshold : input is set for V> 17.4V ; (jumper on the "48V" indication, and
usable with nominal voltages between 24Vdc and 220Vdc)
560477127.xlsx
C264 CORTEC Page 4
11/29/2021
MiCOM C264 REFERENCES FOR C264-V3/V4 BOARDS and Parts Version: V3_28
PROJECT :
MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application
Quanti
Short designation Designation Order Code ty Comments/Special
Package rack 4U (CAS2xx) + FBP2xx
1)
Case 40 TE for use wo. CT/VT (Compact size), IP52, pin-terminal connection, 6 slots 45196526A2 consult us
1)
Case 40 TE for use with CT/VT (Compact size), IP52, pin-terminal connection, 4 slots 45196526A1 consult us
1)
Case 80 TE for use without CT/VT (Medium size), IP20, pin-terminal connection, 15 slots 2070790A02 consult us
1)
Case 80 TE for use with CT/VT (Medium size), IP20, pin-terminal connection, 14 slots 2070790A01 consult us
1)
Case 60 TE for use without CT/VT (Medium size), IP20, pin-terminal connection, 10 slots consult us
1)
Case 60 TE for use with CT/VT (Medium size), IP20, pin-terminal connection, 9 slots consult us
Front Back Plane FBP2xx
FPB242 Front Back Plane BUS Case 40 TE CPU260 consult us
FPB243 Front Back Plane BUS Case 40 TE CPU270 consult us
FPB282 Front Back Plane BUS Case 80 TE CPU260 consult us
FPB283 Front Back Plane BUS Case 80 TE CPU270 consult us
Front panels in Base rack
GHU200 Front Panel with Leds + Graphic Display LCD +L/R switch -GHU200(40TE) 2071004
GHU201 Front Panel with Leds + Graphic Display LCD +L/R switch -GHU201 (80TE) 2070962
GHU202 Front Panel with Leds + Graphic Display LCD +L/R switch - GHU202 (60TE) tbd New
GHU210 Front Panel Leds and L/R switch - IP52 protection -GHU210 (40TE) 2071010
GHU211 Front Panel Leds and L/R switch - GHU211(80TE) 2070966
GHU212 Front Panel Leds and L/R switch - GHU212(60TE) 2071942 New
GHU220 Simple Blind front panel : GHU220 (40TE ) 2071174
GHU221 Simple Blind front panel : GHU 221 (80TE) 2071172
GHU222 Simple Blind front panel : GHU 221 (60TE) 2071943 New
Power supply and 2 serial ports : Port 1= RS232 ; Port2=RS232 in Base rack
BIU241-A01 VA,nom: 24 VDC / Nominal wetting voltage for 2DI: 24 V DC 2 serial ports 2070879A01
BIU241-A02 VA,nom: 48 to 60 VDC / Nominal wetting voltage for 2DI: 48/60 V DC -2 serial ports 2070879A02
BIU241-A03 VA,nom: 110 to 125 VDC / Nominal wetting voltage for 2 DI: 110/125 V DC -2 serial ports 2070879A03
BIU241-A04 VA,nom: 220 VDC and 115 to 230VAC / Nominal wetting voltage for 2 DI: 220 V DC - 2 serial ports 2070879A04
BIU261-A02 VA,nom: 48 to 60 VDC / Nominal wetting voltage for 2DI: 48/60 V DC -2 serial ports 2071864A02
BIU261-A03 VA,nom: 110 to 125 VDC / Nominal wetting voltage for 2 DI: 110/125 V DC -2 serial ports 2071864A03
BIU261-A04 VA,nom: 220 VDC / Nominal wetting voltage for 2 DI: 220 V DC - 2 serial ports 2071864A04
CPU260 with 2 RS232 serial ports + IRIGB in Base rack
CPU260-P1 CPU260-base, with Pack 1 = IRIG-B input + 2 Serial links 45196300A5 consult us
CPU260-P2 CPU260-based with Pack 2 = IRIG-B input +2 serial links+ 100BaseFL MultiMode Ethernet 45196300A6 consult us
CPU260-P3 CPU260-based with Pack 3= IRIG-B input +2 serial links+ 100BaseFL MonoMode Ethernet 45196300A7 consult us
A01: 50ppm
CPU270 -Type3 CPU270, 2 ethernet ports, IRIG-B input + 2 Serial links 2071590 A02 : 1 ppm
2071590:
index to be A01: 50ppm
CPU270 -Type4 CPU270, 2 ethernet ports, IRIG-B input + 2 Serial links (updated Netphy comp.), 128Mb SDRAM indicated A02 : 1 ppm
A01: 50ppm
CPU275 CPU275 , 2 ethernet ports, IRIG-B input + 2 Serial links, 256Mb SDRAM memory 2072282: A02 : 1 ppm
Softwares
C264 Standalone Configuration tool - SCT C264-SCT consult us
PACIS SCE Configuration tool PACIS-SCE consult us
ISaGRAF software PLC Editor consult us
PACIS SMT System Management tool PACIS-SMT consult us
Documentation and Manuals
CD ROM - Technical and Operation guides - multilingual pdf documentations
(English, French, Spanish and German) C264-CD-DOC consult us
560477127.xlsx
C264 BOARDS&PARTS
Page 5
11/29/2021
BACK BIU241 = Power Supply Board
Pin n°
PIN
1
Output relays 2
1
O2 3
2 4
3 O1 5
4 Watchd og 6
5 7
6 8
7 +
VIN
+
VIN 9
- DI1 - DI2 10
8 - -
9 11
10 12
11 13
RS2 32 /
12 RXD / T+ RS4 85 Serial 14
13 G ND 15
link 1
14
0 Volt
TXD / T- 16
15
# 17
G ND
16 0 Volt RS2 32 / 18
CTS
17 RS4 22 19
RXD / T+ Serial
18 TXD / T- RS4 85 20
RTS / R+ link 2 21
19
R- (RS422 ) # 22
20 DCD
21
23
22 24
Vau x Power
23 +
24 - supp ly
-
Signal
1
2 DO 1
3
4 DO 2
5
6 DO 3
7
8 DO 4
9
10 DO 5
11
BACK
12 DO 6
13
14 DO 7
15
16 DO 8
17
18
19
20
DO 9
21
22
23
DO 1 0
24
Circu it b rea ker CCU 2 0 x and CCU211 (Ref 2071732)
Co n trol Unit
b oa rd
-
DI1 -
DI2
2 - -
3
4 VIN VIN
+ DI3 + DI4
- -
5 - -
6
7 +
VIN
+
VIN
-
DI5 -
DI6
8 - -
9
10 VIN VIN
+ DI7 + DI8
- -
11 - -
BACK
12
13
Dig ita l O utputs
14 B
CO 1
15 A
16 A
17 B CO 2
18
19
20 B
CO 3
21 A
22 A
23 B CO 4
24
Dig ita l In p ut U nit DIU2 0 x
Digital Input Unit DIU 210
b oa rd board
1 VIN VIN
1 +
VIN
+
VIN
DI1 DI2 DI 1 DI 2
com com
2 -
-
-
-
2
3 3
4 VIN VIN
4 VIN VIN
+ DI3 + DI4 DI 3 DI 4
com com
5 - -
- - 5
6 6
C0056ENd
Tra nsdu ce rles s TMU 2 0 0 Tra nsdu cerless TMU 2 0 0
Mea su re m en t U nit Me a su rem en t U nit
1 A co nn ectio ns 5 A co nn e ctio ns
3 4 N2
3 4
C1
5 6 5 6 C2
C1
7 8 C2 7 8
B1
9 10 9 10 B2
B1
11 12 B2
11 12
A1
13 14
13 14 A2
A1
15 16 A2
15 16
-
- 8 STARTS COLD LOAD / DREC Common
9 DIST REC
10 START 9
11
10
12
13
11
14 12
15 13
16 14
17 TRIP C 15
18 16
19 TRIP B 17
20
18 Trip Phase C +
21 TRIP A
19
22
23 20 Trip Phase B +
24 21
22 Trip Phase A +
23 Trip Phase A,B,C Common -
24 Trip Phase A,B,C Common -
DSP211
Ref : 2071860 Independant Trip Contacts
NEW
PI Signal
N inputs Pin N°.
1
1 + 2
BLOCKING
IN
2 - -
3
3 +
4 -
IN
SELECTIVIT 4
+ -
5 -
IN
Y 5
-
6 + 6
IN COLD LOAD
7 + - - 7
8 -
IN
DIST REC 8
-
9
10
K5 9
11
10
12
11
13
14 12
15 K4 13
16 14
17 15
18 16
19 TRIP C
17
20
TRIP B 18
21
19
22
23 TRIP A 20
24 21
22
23
24
Signal
DI BLOCKING +
DI BLOCKING Common
DI SELECTIVITY +
Not Configurable
DI SELECTIVITY Common
COLD LOAD START +
DISTURBANCE START +
STARTS COLD LOAD / DREC Common
K5/1 + Close CB
K5/1 - Close CB
K5/2 + Close CB
K5/2 - Close CB
K4/1 + Not Configurable
K4/1 - Not Configurable
K4/2 + Not Configurable
K4/2 - Not Configurable
Not connected
Trip Phase C +
Trip Phase C -
Trip Phase B +
Trip Phase B -
Trip Phase A +
Trip Phase A -
Trip Phase A -
CPU270/ CPU272 / CPU275 Connector description :
0 Volt
0 Volt
SBU200 Connectors: 8* RJ45
Definitions:
AC Alternative Current
AIU Analog Input Unit
Commonly Voltage or Current DC signals delivered by transducers
Bay Set of LV, MV or HV plants (switchs and transformer) and devices (Protective, Measurement…).
Usually around a Circuit Breaker and controlled by a bay computer.
BIU Basic Interface Unit
DC Direct Current
DCS Digital Control System
DI Digital Inputs
DIU Digital Inputs Unit
DO Digital Outputs
DOU Digital Output Unit
DSP Floating-Point Digital Signal Processor
I Current
IED Intelligent Electronic Device
IP52 IP52 environmental protection
Protected against dust and direct sprays of water up to 15 degrees from vertical - Indoor
The number 5 means that it is especially protected against the dust
The number 2 means that it is especially protected against projections of water
PC Personnal Computer
PLC Programmable Logic Controller
PQ Power Quality
U Voltage
VT Voltage Transformer