Ordering information for Modular Compact Bay Controller / Remote Terminal Unit (RTU)

MiCOM C264C/264
Disclaimer / Décharge / Descarga

Disclaimer
Our policy is one of continuous development. Accordingly the design of our products may change at any time.
Whilst every effort is made to produce up to date literature, this document should only be regarded as a guide
and is intended for information purposes only.
Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Décharge
Nous avons une politique de développement permanent.
Par conséquent, la conception de nos produits risque de subir des modifications à tout moment.
Bien que nous nous efforcions de tenir notre documentation à jour, ce brochure ne devra être considérée
que comme guide à des fins d’information seulement.
Son contenu n’a pas titre d’offre de vente ou d’assistance technique sur l’application d’un produit mentionné.

Descarga
Nuestra política se basa en un desarrollo continuo.
Por este motivo, el diseño de nuestros productos puede experimentar cambios en cualquier momento.
Realizamos el máximo esfuerzo para producir documentación actualizada. Estas páginas sólo tienen valor informativo.
Su contenido no constituye en modo alguno una proposición de venta o asesoramiento en relación con ninguno de los productos
mencionados.
Declinamos toda responsabilidad por las decisiones que se adopten basándose en su contenido sin notificación al respecto.
MiCOM C264 CORTEC FOR C264-V3/V4, fully assembled device Version: V3_28
Variants Notes /
Order N° Ext. N°

cpu serial
biu serial

SBU200
Tropical

DIU200
DIU211

AIU201
AIU211
Voltage

Built in
Isagraf

detach
TMU
GHU

DOU

AOU
CCU
rack

lang

Soft
SW
MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application

cpu
P.S
MiCOM C 2 6 4 T 2 1 I 6 A 5 0 0 0 2 4 5 0 2 0 0 C 0 0 1 1 1 1 N 0 0
CORTEC CODE Synthesis (for export to Word Docs) :
MiCOM C264T21I6A5000240200C001111N00
Basic Model and Components
Package rack 4U (CAS2xx) + FBP2xx
1) 1)
Case 40 T for use wo. CT/VT (Compact size), IP52, pin-terminal connection, 6 slots C
1) 1)
Case 40 T for use with CT/VT (Compact size), IP52, pin-terminal connection, 4 slots S
1) 1)
Case 80 T for use without CT/VT (Medium size), IP20, pin-terminal connection, 15 slots L
1) 1)
Case 80 T for use with CT/VT (Medium size), IP20, pin-terminal connection, 14 slots M
1) 1)
Case 60 T for use without CT/VT (Medium size), IP20, pin-terminal connection, 10 slots T
1) 1)
Case 60 T for use with CT/VT (Medium size), IP20, pin-terminal connection, 9 slots U
Front panel (GHU2xx) - Schneider Electric
Front Panel Leds and L/R switch - IP52 protection - GHU210 (40TE) or GHU211(80TE) or GHU212(60TE) 0 New GHU212 60TE! Generally available
Front Panel with Leds + Graphic Display LCD + L/R switch -GHU200(40TE)or GHU201(80TE) or GHU202(60TE) - IP52 prot. 1
Simple Blind front panel : GHU220 (40TE) or GHU221(80TE) or GHU222 (60TE) 12)
2 New GHU222 60TE! Generally available
Detachable Front Panel with Graphic Display 40TE (GHU200) + Simple Blind Front panel (GHU22x) 12)
3 Select the cable lenght
Detachable Front Panel with Graphic Display 80TE (GHU201) + Simple Blind Front panel (GHU22x) 12)
4 Select cable
Detachable Front Panel with Leds 40TE (GHU210) + Simple Blind Front panel (GHU22x) 12)
5 Select cable
Detachable Front Panel with Leds 80TE (GHU211) + Simple Blind Front panel (GHU22x) 12)
6 Select cable
8)
Language (including: Front panel labels, HMI)
French ( English) 0
English (English) 1
Spanish (English) 2
German (English) 3
Power supply and legacy ports (BIUxxx)
about BIU241: Vn +/- 20% - 2 DI/2DO - 2*serial Ports (port n°1 and port n°2 )
BIU241-A01 : VA,nom: 24 VDC / Nominal voltage for 2DI: 24 V DC A
BIU241-A02 : VA,nom: 48 to 60 VDC / Nominal voltage for 2DI: 48/60 V DC E
BIU241-A03 :VA,nom: 110 to 125 VDC / Nominal voltage for 2 DI: 110/125 V DC I
BIU241 A04 : VA,nom: 220 VDC and 115 to 230VAC / Nominal voltage for 2 DI: 220 V DC M
about BIU261: Redundant/Double SOURCE (+/- 20%) - 2 DI/2DO - 1 *serial Port only
BIU261-A02 : VA,nom: 48-60VDC / Nominal voltage for 2DI: 48-60 V DC N Warning : only 1 serial port (n°2)
BIU261-A03 : VA,nom: 110-125 VDC / Nominal voltage for 2DI: 110-125 V DC P Warning : only 1 serial port (n°2)
BIU261-A04 :VA,nom: 220VDC / Nominal voltage for 2 DI: 220 V DC Q Warning : only 1 serial port (n°2)
about the BIU100 : only to be interfaced to the Redunded Power supply rack : RPS280
15)
BIU100 : 12V auxiliary voltage, 2 non isolated serial links R Consult Mkg
8)
Factory setted legacy ports: port n°1 and n°2 on BIU241 board, only port n°2 on BIU261
Definition : Port N°2:RS232or RS422 or RS485 ; Port N°1: RS232or RS485
Port N°2: RS232 ; Port N°1: RS232 1
Port N°2: RS232 ; Port N°1: RS485 (BIU241 only) - Not allowed on BIU261 2 Not applicable for BIU261
Port N°2: RS485 ; Port N°1: RS485 6
CPU and Base Communications (CPU2x0)
14)
Power PC processor board with Ethernet port(s) , 2 serial links, IRIGB input- CPU260-based
CPU260(Type2) , with 1 Ethernet RJ45, IRIG-B input, 2 Serial links (Ref CPU2 = 45196300 A5) 5 Consult Mkg
CPU260(Type2)-based with Pack 2 = IRIG-B input +2 serial links+ 100BaseFL MultiMode Ethernet 6 Consult Mkg
CPU270(Type3) , with 2*Ethernet RJ45, 64Mb FlashMemory, 1 ppm Oscillator accuracy (Ref CPU270 = 2071590A02 ) 8 Available w Mkg autorisation (delivery time)
CPU270(Type3) , with 2*Ethernet RJ45, 64Mb FlashMemory, 128Mb SDRAM, 50ppm Oscillator (Ref CPU270 = 2071590A01 ) 9
CPU275 (Type 4) , with 2*Ethernet RJ45, 128Mb FlashMem, 256Mb SDRAM, 50 ppm Oscill (Ref CPU275 =2072282A01) A Generally Available
CPU275 (Type 4), with 2*Ethernet RJ45, 128Mb FlashMem, 256Mb SDRAM, 1 ppm Oscill (Ref CPU275 =2072282A02) B Generally Available
8)
For CPU with 2 serial links: Factory setted legacy ports N°3/4
Configuration of the legacy Ports N°3/4 :RS232 (non isolated), RS485, Optical settable no serial link
Port N°3:RS232 (non isolated) ; Port N°4: RS232 (non isolated) 1
Port N°3: RS485(ECU201) ; Port N°4: RS485(ECU201) 5
Port N°3: Optical(ECU200) ; Port N°4: Optical(ECU200) 9
Inputs / outputs boards and Ethernet-based switch boards
Manufacturing process 0)
Automatic affectation (as standard) of the I/O modules in the basic rack 0
Preferred affectation (customized with extra cost) of the I/O modules in the basic rack 1 consult us

Varnish I/O boards for installations demanding tropicalized conditions


No 0
Yes 1 consult us

Transducerless Measurements Unit - Direct measuring value acquisition: 4 CT + 5 VT 3) 5) S=1 2)


Without 0
9)
with TMU220 ( measurement 4*I + 5*U) , I nom: 1 A / 5A, Vnom: 50 to 250 VAC - and DSP200 Board S -M 1
17)
With TMU210 A01 (& DSP210) : Vnom: 57 to 130 VAC, Iph=1A, Ion=1A, Io operating range= 0,1-40Ion S -M 2 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A01 (& DSP210) : Vnom: 57 to 130 VAC, Iph=1A, Ion=5A, Io operating range= 0,1-40Ion S -M 3 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A01 (& DSP210) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range= 0,1-40Ion S -M 4 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A01 (& DSP210) : Vnom: 57 to 130 VAC, Iph=5A, Ion=1A, Io operating range= 0,1-40Ion S -M 5 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A02 (& DSP210) : Vnom: 57 to 130 VAC, Iph=1A, Ion=1A, Io operating range= 0,01-8Ion S -M 6 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A02 (& DSP210) : Vnom: 57 to 130 VAC, Iph=1A, Ion=5A, Io operating range= 0,01-8Ion S -M 7 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A02 (& DSP210) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range=0,01-8Ion S -M 8 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A02 (& DSP210) : Vnom: 57 to 130 VAC, Iph=5A, Ion=1A, Io operating range= 0,01-8Ion S -M 9 DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A03 (& DSP210) : Vnom: 57 to 130 VAC, Iph=1A, Ion=1A, Io operating range=0,002-1Ion S -M A DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A03 (& DSP210) : Vnom: 57 to 130 VAC, Iph=1A, Ion=5A, Io operating range=0,002-1Ion S -M B DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A03 (& DSP210) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range=0,002-1Ion S -M C DSP210 (common contacts) , Refer to note 20)
17)
With TMU210 A03 (& DSP210) : Vnom: 57 to 130 VAC, Iph=5A, Ion=1A, Io operating range=0,002-1Ion S -M D DSP210 (common contacts) , Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED


17)
With TMU210 A01 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=1A, Io operating range= 0,1-40Ion S -M G Refer to note 20)

17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A01 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=5A, Io operating range= 0,1-40Ion S -M H Refer to note 20)

17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A01 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range= 0,1-40Ion S -M J Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED


17)
With TMU210 A01 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=1A, Io operating range= 0,1-40Ion S -M K Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED


17)
With TMU210 A02 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=1A, Io operating range= 0,01-8Ion S -M L Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED


17)
With TMU210 A02 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=5A, Io operating range= 0,01-8Ion S -M M Refer to note 20)

17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A02 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range=0,01-8Ion S -M N Refer to note 20)

17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A02 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=1A, Io operating range= 0,01-8Ion S -M P Refer to note 20)

17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A03 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=1A, Io operating range=0,002-1Ion S -M Q Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED


17)
With TMU210 A03 (& DSP211) : Vnom: 57 to 130 VAC, Iph=1A, Ion=5A, Io operating range=0,002-1Ion S -M R Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED


17)
With TMU210 A03 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=5A, Io operating range=0,002-1Ion S -M S Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED


17)
With TMU210 A03 (& DSP211) : Vnom: 57 to 130 VAC, Iph=5A, Ion=1A, Io operating range=0,002-1Ion S -M T Refer to note 20)

DSP211(independant Trip contacts)= TO BE PREFERED - for


17)
PCCN only
With TMU210 A04 (& DSP211) : Vnom: 57 to 130 VAC, 4* Ion=5A, Io operating range =0,01-8Ion S -M U Refer to note 20)

17)
DSP211(independant Trip contacts)= TO BE PREFERED
With TMU210 A04 (& DSP211) : Vnom: 57 to 130 VAC, 4*Ion=1A, Io operating range =0,01-8Ion S -M V Refer to note 20)

Nominal wetting voltage for digital inputs (DIU200 or DIU211 or CCU200 or DSP21x(-) 18)
) S=12)
VA,nom: 24 V DC (- to common) DIU200-A01 board or CCU200-A01 board or DSP21x-A01 0
VA,nom: 48/60 V DC (- to common) - DIU200-A02 board or CCU200-A02 board or DSP21x-A02 1
VA,nom: 110/125 V DC (- to common) - DIU200-A03 board or CCU200-A03 board or DSP21x-A03 2
VA,nom: 220 V DC (- to common) : DIU200-A04 board or CCU200-A04 board or DSP21x-A04 3

VA,nom: 110-125 VDC (- to common) - DIU200-A03 board or CCU200-A07 board


(input setted if >68%*Vn) or DSP210-A03 6 consult us
VA,nom: 48 V DC (+ to common) -DIU220-A02 (+ to common) or CCU200-A02 (- to common) board or DSP21x-A02 (- to common) 9 consult us
VA,nom: 110-125V DC (+ to common) -DIU220-A03 (+ to common) or CCU200-A03 (- to common) board or DSP21x-A03 (- to common) A consult us
Selection of "voltage" for DIU200, DSP21x and multi-voltage CCU211 or DSP21x(-) 18)
)

CCU211 : Multivoltage 24Vdc-> 250Vdc ; preset threshold : 17.4 VDC; also for DIU200-A02 and DSP21x-A02 (VA,nom:
48/60Vdc) C in case CCU211 is needed

CCU211 : Multivoltage 24Vdc-> 250Vdc ; preset threshold : 50 VDC; also for DIU200-A03 and DSP21x-A03 (VA,nom:
110/125 VDC) D in case CCU211 is needed

CCU211 : Multivoltage 24Vdc-> 250Vdc ; preset threshold : 86 VDC ; also for DIU200-A04 and DSP21x-A04 (VA,nom: 220
VDC) E in case CCU211 is needed
Digital inputs (16 DI) module, each with 16 digital inputs (DIU200A0x) 3) 22)
S=12)
16 optically insulated inputs in 8 isolated groups
DIU200 quantity = 0 to 4 or 6 for 40TE racks, 0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks X
Multi tension-peak-current Digital inputs (16 DI) module, each with 16 digital inputs DIU211 3) 13) 22)
S=12)
16 optically insulated inputs in 8 isolated groups ; preset threshold= 17.4Vdc
check 13) for thresholds and quantities
DIU211 quantity = 0 to 4 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks X
Digital outputs (10 DO) module, each with 10 digital outputs (DOU201) 3) S=12)
8 outputs NO contacts and 2 outputs NO/NC contacts
DOU quantity = 0 to 4 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 14 or 15 slots in 80TE racks X
Mixed (8 DI + 4 DO) module each with 8 digital inputs and, 4 digital outputs4) (CCU200 or CCU211-Ref.2071732 ) 3) S=12)
8 optically insulated inputs (in 4 isolated groups) and 4 direct command relays (2 NO contacts) CCU211:, only with voltage codes : C, D or E
CCU quantity = 0 to 3 or 6 for 40TE racks, =0 to 9,A,B,C,D,E or F for 13 or 15 slots in 80TE racks 19) X Consult us for CCU-A07

DC 4 Analog inputs module (C or V transducer connection) each with 4 analogue inputs (AIU201) 3)

560477127.xlsx
C264 CORTEC Page 3
11/29/2021
MiCOM C264 CORTEC FOR C264-V3/V4, fully assembled device Version: V3_28
Variants Notes /
Order N° Ext. N°

cpu serial
biu serial

SBU200
Tropical

DIU200
DIU211

AIU201
AIU211
Voltage

Built in
Isagraf

detach
TMU
GHU

DOU

AOU
CCU
rack

lang

Soft
SW
MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application

cpu
P.S
MiCOM C 2 6 4 T 2 1 I 6 A 5 0 0 0 2 4 5 0 2 0 0 C 0 0 1 1 1 1 N 0 0
4 DC Analog Inputs in current or voltage (4 isolated groups) - Maximum of 6*AIU2xx in one case
AIU201 quantity = 0 to 4 or 6 for 40TE racks , =0 to 6 for 80TE racks X S=12)
3), 23)
DC 8 Analog inputs module (Current),with 8 analogue inputs (AIU211)
8 DC Analog Inputs in current (AIU211: 8 isolated channels) - Maximum of 6*AIU2xx in one case
AIU21x quantity = code 0 (=0 board) or code "A" to "F" for 1 to 6*AIU211 (code "1" to "6" for AIU210) X S=12), 24) Consult Mkg
3), 16)
Analog output module (Currents) ,with 4 analogue ouputs (AOU200)
4 Analog Outputs (PACIS V4.5.5 or upper, and RTUs applications)
AOU200 quantity = 0 to 4 for 40TE racks , 0 to 4 for 80TE racks x S=12)
Ethernet-based Switch Unit (SWU20x) 3) S=12)
Without 0
SWU200 - With four 10/100BaseT Ethernet ports (RJ45) 1
SWU202- With two 100BaseF MultiMode Ethernet ports (ST) and four 10/100BaseT Ethernet ports (RJ45) 3
SWU204- With two 100BaseF MonoMode Ethernet ports (SC) and four 10/100BaseT Ethernet ports (RJ45) 5
Ethernet-based Switch Redundant Unit (SWR20x) 3) -
For Ethernet Redunded Ring S=12)
SWR212 -With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45) 6 refer note 21)

SWR 214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45) 7 refer note 21)

Ethernet-based Switch Dual Humming Unit (SWD20x) 3)


S=12)
SWD212 - With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45) A refer note 21)

SWD214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45) B refer note 21)

Ethernet-based Switch RSTP Compatible Unit (SWS20x) 3)


S=12)
SWS212 - With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45) Ref.=2071988A01 S refer note 21)

SWS214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45) Ref.=2071988A02 T refer note 21)

Ethernet-based Redundant Ethernet Unit PRP/HSR (REU2xx) 3)


S=12)
REU202- Multimode : with 2*100BaseF MultiMode Eth. ports +1*10/100BaseT Eth. port (RJ45) Ref.=2072062A01 U
REU203 - Mixt : with 1*100BaseF SingleMode +1*100BaseF MultiMode Eth. ports +1*10/100BaseT Eth.ports (RJ45) Ref.=2072062A03 V
REU204 - SingleMode: with 2* 100BaseF SingleMode Eth. ports+ 1*10/100BaseT Ethernet ports (RJ45) Ref.:2072062A02 W
Communications
Ethernet-based SCADA communication protocol ( to upper levels SCADA, DCS, Master Station, ...)
Without 0
IEC 60870-5-104 1
10)
Legacy serial SCADA communication protocols (to upper levels: SCADA, DCS, Master station, etc)
Without 0
Up to two SCADA links in: IEC 60870-5-101, DNP3, Modbus 1
Legacy protocols / Decentralised Smart Terminal Block Interface 11)
None 0
Up to 4 IEDs links - No acquisition from STBs 1
with Comm to IEDs+ SBU200 boards number (code A to I (A:1board --> I :9 boards) Acquisition from Smart terminal Blocks DI&DO 25)
X New ! Only for 60TE racks without TMU
PLC Automation
User applications 6)
Disabled 0
Enabled ISaGRAF run-time for Programmable Logic, Automation, etc. 1
Softwares version
11)
Specific software version
No Software loaded N
Option CD3: No Software loaded, delivered with one CD-ROM including the C264 software (PACIS V3) C
Option CD4 : No Software loaded, delivered with one CD-ROM including the C264 software (PACIS V4) D
Option V4 : With the C264 current Software version loaded (for PACIS V4.xx) -No CD delivered R Consult Mkg
Option V3 : With the C264 current Software version loaded (for PACIS V3.xx) -No CD delivered S
6)
Built in applications
Disabled 0
Synchrocheck/Autorecloser enabled L 1
iAVR Voltage regulation - Standard application (in 40T rack) - application loaded on CPU270 S New !
iAVR Voltage regulation - Premium application (in 60T rack) - application loaded on CPU270 P New !
iAVR Voltage regulation - "Elite" application (To be Defined) - application loaded on CPU270 E Consult Marketing
Cable Lenght for Detachable front Panel
No cable 0
Cable For Detachable Front Panel : 3 m 3

Associated equipments, Accesories, Softwares and Manuals


Equipments :
Fitting a 19" mounting rack FXOO21101
Wall Mounted Adaptater - for 40TE Racks (WMA 40TE) Ref = A00043409100031 Consult us
Wall Mounted Adaptater - for 80TE Racks - (under validation - Consult us) Consult us
Serial printer (80 columns) - 115/230 V AC Consult us
Power supply inverter 48 V DC / 115/230 VAC Consult us
Power supply inverter 125 V DC / 115/230 VAC Consult us
Ethernet cable (crossed-Blue) for PC connection - 2m 9565933
Ethernet cable (direct-Yellow) for Switch/Hub connection - 20cm 9565934
Ethernet cable (direct-Yellow) for Switch/Hub connection - 2m 9565935
Ethernet cable (direct-Yellow) for Switch/Hub connection - 3m 9565936

RS232 cable for PC<-> Front panel connection (3m) 9565996


Cable for Detachable front Panel (3 m) 2071098A04
Cable for direct connection of front Panel (30 cm) 2071098A01

Clock synchoniser - DIN rail model / IRIG-B output Consult us


Clock synchoniser - 19" mounting rack / IRIG-B output Consult us

Boards extractor 2070860


Cache for empty I/O slots 2071038

I/Os connectors (24 points) 9565869

Connectors (3 points) 9566235

Softwares :
6)
C264 Standalone Configuration tool - SCT Consult us

PACIS SCE Configuration tool 6) Consult us

ISaGRAF software PLC Editor 6) Consult us


6)
PACIS SMT System Management tool Consult us

Manuals :

Technical and Operation guides in English Consult us


Technical and Operation guides in French Consult us

Technical and Operation guides in Spanish Consult us


Technical and Operation guides in German Consult us

CD-ROM documentation:

Technical and Operation guides - multilingual pdf documentations (English, French, Spanish and German) Consult us

Remind of the CORTEC Code Synthesis : for export to Word documents :


MiCOM C264T21I6A5000240200C001111N00
Legend:
No commercial availability - consult us for more info.

0)

-C264 rack : with "Switch SWxxx" board or full of I/O boards :


Automatic affectation of slots : from "C" to "P" slot : SWX20x, AIU201, AIU211, DOU201, AOU200, free slots if any, CCU2xx, DIU211or DIU200, TMU220
Warning : the Slot C remain free of board for C264 rack without switch and not full of I/Os.
-C264P rack (with TMU210 Protection ) : The Slot C is dedicated to the DSP21x Board.
Automatic affectation of slots : from "D" to "P" slot : SWX20x, AIU201, AIU211, DOU201, AOU200, free slots if any, CCU2xx, DIU211 or DIU200, TMU210

1) Different racks exist depending of user-selected CT/VT(TMU) & basic case size : N= nb of slots

Remark : C264 with 60 TE rack is only availabla with the Front Panel GHU202 (with LCD screen + Leds)

2) Module slot size


3) The sum of slots (S) to receive modules must not exceed the maximum value N (available slots), indicated for each case separately
4) Output relays (2-pole) for switchgear operation
5) Required for Synchrocheck, disturbance recorder and direct measurements
6) According to specification
7) Voltage regulation needs UCA2 Ethernet-based communication

8) User-selected (factory setting underlined).


For BIU261 ( Dual Source) serial port, only the CORTEC CODE "1" or "6" are allowed ( code "2" Not applicable) .
9) Includes the DSP200 daughter board plugged in the CPU270/275 module

- The DSP200 is based on the TMS320C6711, Floating-Point Digital Signal Processor (DSP)
10) The sum of communication links (legacy SCADA and IEDs) must not exceed the maximum communication ports available.

11) For Specific Software version complete the Software CORTEC (sheet C264 SOFT)
For C264-R multirack applications, Select " No software loaded"
12) For Detachable Front panel, define the lenght of the required cable ; the Blind panel size depend on the Rack size.
13)

- DIU211 is delivered in C264 racks in replacement of DIU210 from 08/2009 : With DIU211, the board number limitation (due to DIU210 consumption)is not applicable.
- DIU211, when used in replacement of the DIU210, is configured with the following preset threshold : input is set for V> 17.4V ; (jumper on the "48V" indication, and
usable with nominal voltages between 24Vdc and 220Vdc)

14) for CPU260: consult Marketing

15) BIU100 : commercialisation Stopped


(was only in association to RPS280 ,
Do not exist for tropicalised /Varnished version
Warning : specific EMC levels for this power supply - consult Marketing before use)

560477127.xlsx
C264 CORTEC Page 4
11/29/2021
MiCOM C264 REFERENCES FOR C264-V3/V4 BOARDS and Parts Version: V3_28
PROJECT :

MiCOM C264C/C264 - Modular Computer for Bay Controller, RTU, PLC application

Quanti
Short designation Designation Order Code ty Comments/Special
Package rack 4U (CAS2xx) + FBP2xx
1)
Case 40 TE for use wo. CT/VT (Compact size), IP52, pin-terminal connection, 6 slots 45196526A2 consult us
1)
Case 40 TE for use with CT/VT (Compact size), IP52, pin-terminal connection, 4 slots 45196526A1 consult us
1)
Case 80 TE for use without CT/VT (Medium size), IP20, pin-terminal connection, 15 slots 2070790A02 consult us
1)
Case 80 TE for use with CT/VT (Medium size), IP20, pin-terminal connection, 14 slots 2070790A01 consult us
1)
Case 60 TE for use without CT/VT (Medium size), IP20, pin-terminal connection, 10 slots consult us
1)
Case 60 TE for use with CT/VT (Medium size), IP20, pin-terminal connection, 9 slots consult us
Front Back Plane FBP2xx
FPB242 Front Back Plane BUS Case 40 TE CPU260 consult us
FPB243 Front Back Plane BUS Case 40 TE CPU270 consult us
FPB282 Front Back Plane BUS Case 80 TE CPU260 consult us
FPB283 Front Back Plane BUS Case 80 TE CPU270 consult us
Front panels in Base rack
GHU200 Front Panel with Leds + Graphic Display LCD +L/R switch -GHU200(40TE) 2071004
GHU201 Front Panel with Leds + Graphic Display LCD +L/R switch -GHU201 (80TE) 2070962
GHU202 Front Panel with Leds + Graphic Display LCD +L/R switch - GHU202 (60TE) tbd New
GHU210 Front Panel Leds and L/R switch - IP52 protection -GHU210 (40TE) 2071010
GHU211 Front Panel Leds and L/R switch - GHU211(80TE) 2070966
GHU212 Front Panel Leds and L/R switch - GHU212(60TE) 2071942 New
GHU220 Simple Blind front panel : GHU220 (40TE ) 2071174
GHU221 Simple Blind front panel : GHU 221 (80TE) 2071172
GHU222 Simple Blind front panel : GHU 221 (60TE) 2071943 New
Power supply and 2 serial ports : Port 1= RS232 ; Port2=RS232 in Base rack
BIU241-A01 VA,nom: 24 VDC / Nominal wetting voltage for 2DI: 24 V DC 2 serial ports 2070879A01
BIU241-A02 VA,nom: 48 to 60 VDC / Nominal wetting voltage for 2DI: 48/60 V DC -2 serial ports 2070879A02
BIU241-A03 VA,nom: 110 to 125 VDC / Nominal wetting voltage for 2 DI: 110/125 V DC -2 serial ports 2070879A03
BIU241-A04 VA,nom: 220 VDC and 115 to 230VAC / Nominal wetting voltage for 2 DI: 220 V DC - 2 serial ports 2070879A04
BIU261-A02 VA,nom: 48 to 60 VDC / Nominal wetting voltage for 2DI: 48/60 V DC -2 serial ports 2071864A02
BIU261-A03 VA,nom: 110 to 125 VDC / Nominal wetting voltage for 2 DI: 110/125 V DC -2 serial ports 2071864A03
BIU261-A04 VA,nom: 220 VDC / Nominal wetting voltage for 2 DI: 220 V DC - 2 serial ports 2071864A04
CPU260 with 2 RS232 serial ports + IRIGB in Base rack
CPU260-P1 CPU260-base, with Pack 1 = IRIG-B input + 2 Serial links 45196300A5 consult us
CPU260-P2 CPU260-based with Pack 2 = IRIG-B input +2 serial links+ 100BaseFL MultiMode Ethernet 45196300A6 consult us
CPU260-P3 CPU260-based with Pack 3= IRIG-B input +2 serial links+ 100BaseFL MonoMode Ethernet 45196300A7 consult us
A01: 50ppm
CPU270 -Type3 CPU270, 2 ethernet ports, IRIG-B input + 2 Serial links 2071590 A02 : 1 ppm
2071590:
index to be A01: 50ppm
CPU270 -Type4 CPU270, 2 ethernet ports, IRIG-B input + 2 Serial links (updated Netphy comp.), 128Mb SDRAM indicated A02 : 1 ppm
A01: 50ppm
CPU275 CPU275 , 2 ethernet ports, IRIG-B input + 2 Serial links, 256Mb SDRAM memory 2072282: A02 : 1 ppm

ECU converters for CPU260


ECU201 RS232/ RS485 converter for CPU260 serial ports 2071033
ECU200 RS232/ Optical converter for CPU260 serial ports 2071032
Transducerless Measurement Unit - Direct measuring value acquisition: 4 CT + 4 VT in Base rack
9)
TMU220 TMU220 ( 4*I + 5*U) 4-poles, Inom: 1 A / 5A, Vnom: 57 to 250 VAC - 2071613 consult us
TMU210A01 TMU210 9) - and Protection functions - 0,1-40Ion 2071469A01 consult us
TMU210A02 TMU210 9) - and Protection functions - 0,01-8Ion 2071469A02 consult us
TMU210A03 TMU210 9) - and Protection functions 0,002-1Ion 2071469A03 consult us
TMU210A04 TMU210 9) - and Protection functions 4* Ion in range : 0,01-8Ion 2071469A04 consult us
DSP200 DSP - to be used on TMU220 consult us
DSP210 DSPIO with common Trip Contact 2071414 consult us
DSP211 DSPIO with separated Trip Contacts 2071860 consult us
DIU - 16 Digital input boards
DIU200-A01 16 Inputs- Vnom = 24 Vdc 45196503A1
DIU200-A02 16 Inputs- Vnom = 48-60 Vdc 45196503A2
DIU200-A03 16 Inputs- Vnom = 110-125 Vdc 45196503A3
DIU200-A04 16 Inputs- Vnom = 220 Vdc 45196503A4
DIU210 16 Inputs : multi-Voltage + peak Current 24Vdc -> 250V dc 2071292
DIU211 16 Inputs : multi-voltage + peak current 24Vdc -> 250V dc, adjustable thresholds 2071669
DOU - Digital outputs module, with 10 digital outputs
DOU200 10 Digital outputs : 8 outputs NO contacts + 2 outputs NO/NC contacts 45196505
DOU201 10 Digital outputs : 8 outputs NO contacts + 2 outputs NO/NC contacts 2071730
CCU - CB Control Unit - 8 DI + 4 DO module with 8 digital inputs and, 4 digital outputs
CCU200-A01 8 Inputs- Vnom = 24 Vdc and 4 output Contacts 45196501A1
CCU200-A02 8 Inputs- Vnom = 48-60 Vdc and 4 output Contacts 45196501A2
CCU200-A03 8 Inputs- Vnom = 110-125 Vdc and 4 output Contacts 45196501A3
CCU200-A04 8 Inputs- Vnom = 220 Vdc and 4 output Contacts 45196501A4
CCU200-A07 8 Inputs- Vnom = 110 Vdc & 70% threshold commutation + and 4 output Contacts 45196501A7 consult us
CCU211 8 Inputs- multiVoltage, adjustable thresholds + and 4 output Contacts 2071732 consult us :only spare part
AIU - Analog inputs module
AIU201 4 DC Analog inputs module (Currents or dc Voltage) 2070913
AIU210 8 DC Analog inputs module (Currents) 1 common for 2 inputs 2071344
AIU211 8 DC Analog inputs module (Currents) -Isolated 2071652
AOU- Analog output module (Currents) ,with 4 analogue ouputs
AOU200 4 Analog Outputs 2071441
SBU200- Smart Block Acaquisition Unit (DI/DO)
SBU200 SBU200§ 8 ports acquisition units for Smart Terminal Blocks DI&DO NHA95359 New for PCCN
Ethernet-based Switch Unit (SWU20x) 3)
SWU200 SWU200 - With four 10/100BaseT Ethernet ports (RJ45) 2070745A01
SWU202 SWU202- With two 100BaseF MultiMode Ethernet ports (ST) and four 10/100BaseT ports (RJ45) 2070745A03
SWU204 SWU204- With two 100BaseF MonoMode Ethernet ports (SC) and four 10/100BaseT ports (RJ45) 2070745A05
Ethernet-based Switch Redundant Unit (SWR20x)
SWR212 SWR212 -With two 100BaseF MultiMode ports (ST) + 4* 10/100BaseT (RJ45) -SNMP 2071646A01
SWR214 SWR214 -With two 100BaseF MonoMode ports (SC) + 4* 10/100BaseT (RJ45) -SNMP 2071646A02
Ethernet-based Switch Dual Humming Unit (SWD20x) 3)
SWD212 SWD212 -With two 100BaseF MultiMode ports (ST) + 4* 10/100BaseT (RJ45) -SNMP 2071647A01
SWD214 SWD214 -With two 100BaseF MonoMode ports (SC) + 4* 10/100BaseT (RJ45) -SNMP 2071647A02
Ethernet-based Switch - RSTP compatible (SWS20x) 3)
SWS212 SWS212 -With two 100BaseF MultiMode ports (ST) + 4* 10/100BaseT (RJ45) -SNMP 2071988A01
SWS214 SWS214 -With two 100BaseF MonoMode ports (SC) + 4* 10/100BaseT (RJ45) -SNMP 2071988A02
Redunded Ethernet Unit- PRP/HSR (REU20x) 3)
REU202 REU202- Multimode : with 2*100BaseF MultiMode Eth.ports +1*10/100BaseT Eth.(RJ45) 2072062A01 consult us
REU203 REU203 - Mixt : with 1*100BaseF SingleMode +1*100BaseF MultiMode Eth.ports +1*10/100 Eth. (RJ45) 2072062A03 consult us
REU204 REU204 - SingleMode: with 2* 100BaseF SingleMode Eth. ports+ 1*10/100BaseT Eth.(RJ45) 2072062A02 consult us
CD ROM for C264 Software versions
C264-CD3 Option CD3: CD-ROM including the C264 software (PACIS V3) C264-CD3 consult us
C264-CD4 Option CD4 : CD-ROM including the C264 software (PACIS V4) C264-CD4 consult us
Cables and accessories
Cable For Detachable Front Panel : 3 m 2071098A04
Cable for direct connection of front Panel (30 cm) 2071098A01
Ethernet cable (crossed-Blue) for PC connection - 2m consult us
Ethernet cable (direct-Yellow) for Switch/Hub connection - 20cm 9565934
Ethernet cable (direct-Yellow) for Switch/Hub connection - 2m 9565935
Ethernet cable (direct-Yellow) for Switch/Hub connection - 3m 9565936

Cache for empty I/O slots 2071038


I/Os connectors (24 points) 9565869
CT/VT 28 points terminal MIDOS Connector
Connectors (3 points) 9566235

Softwares
C264 Standalone Configuration tool - SCT C264-SCT consult us
PACIS SCE Configuration tool PACIS-SCE consult us
ISaGRAF software PLC Editor consult us
PACIS SMT System Management tool PACIS-SMT consult us
Documentation and Manuals
CD ROM - Technical and Operation guides - multilingual pdf documentations
(English, French, Spanish and German) C264-CD-DOC consult us

560477127.xlsx
C264 BOARDS&PARTS
Page 5
11/29/2021
BACK BIU241 = Power Supply Board

Ref : 2070879 A0x

Ba sic In terface Unit BIU2 4 x


b oa rd

Pin n°

PIN
1
Output relays 2
1
O2 3
2 4
3 O1 5
4 Watchd og 6
5 7
6 8
7 +
VIN
+
VIN 9
- DI1 - DI2 10
8 - -
9 11
10 12
11 13
RS2 32 /
12 RXD / T+ RS4 85 Serial 14
13 G ND 15
link 1
14
0 Volt
TXD / T- 16
15
# 17
G ND
16 0 Volt RS2 32 / 18
CTS
17 RS4 22 19
RXD / T+ Serial
18 TXD / T- RS4 85 20
RTS / R+ link 2 21
19
R- (RS422 ) # 22
20 DCD
21
23
22 24
Vau x Power
23 +
24 - supp ly
-
Signal

Redundancy relay 2 - NO contact


Redundancy relay - common 1-2
Redundancy relay 1 - NO contact
Watchdog relay - NO contact
Watchdog relay - NC contact
Watchdog relay - common
Redundancy input - 1+
Redundancy input - common 1 / 2
Redundancy input - 2+

RS232: RxD RS485: B - Port 1


0 Volt - Port 1
RS232: TxD RS485: A - Port 1
0 Volt - Port 2
RS232: CTS - Port 2
RS232: RxD RS485 B RS422: TB - Port 2
RS232: TxD RS485 A RS422: TA - Port 2
RS232: RTS RS422: RB - Port 2
RS422: RA - Port 2
RS232: DCD - Port 2
Voltage input: Gnd Gnd
Voltage input: AC/DC ( + )
Voltage input: AC/DC ( ─ )
NEW !!! BIU261 = BIUR : Dual Source Power Supply

Ref : 2071864 A0x

Pin BIU261 - BIUR


1 OUT2 NO
2 OUT1 – 2 C
3 OUT1 NO
4 WD NO
5 WD NC
6 WD C
7 IN 1+
8 COMMON 1 – 2
9 IN 2+
10 Source 2 VE+
11 Source 2 VE-
12 Not Used
13 Not Used
14 Not Used
15 GND/ 0V Port 2
16 CTS Port 2
17 RxD/ T+ Port 2
18 TxD/ T- Port 2
19 RTS / R+ Port 2
20 R- (rs422) Port 2
21 DCD Port 2
22 GND
23 Source 1 VE+
24 Source 1 VE-
AIU201 AIU210- connector
CONSULT MKG
AIU211- connector
Dig ita l Outpu t U nit DO U2 0 0 DOU201
b oa rd

PIN Signa l outputs

1
2 DO 1
3
4 DO 2
5
6 DO 3
7
8 DO 4
9

10 DO 5
11
BACK
12 DO 6
13
14 DO 7
15
16 DO 8
17
18
19

20
DO 9
21
22
23
DO 1 0
24
Circu it b rea ker CCU 2 0 x and CCU211 (Ref 2071732)
Co n trol Unit
b oa rd

PIN Dig ita l Inputs


1 +
VIN
+
VIN

-
DI1 -
DI2
2 - -
3
4 VIN VIN
+ DI3 + DI4
- -
5 - -
6
7 +
VIN
+
VIN

-
DI5 -
DI6
8 - -
9
10 VIN VIN
+ DI7 + DI8
- -
11 - -
BACK
12
13
Dig ita l O utputs
14 B
CO 1
15 A
16 A
17 B CO 2
18
19
20 B
CO 3
21 A
22 A
23 B CO 4
24
Dig ita l In p ut U nit DIU2 0 x
Digital Input Unit DIU 210
b oa rd board

Signa l inputs Signal inputs


PIN PIN

1 VIN VIN
1 +
VIN
+
VIN

DI1 DI2 DI 1 DI 2
com com
2 -
-
-
-
2

3 3
4 VIN VIN
4 VIN VIN
+ DI3 + DI4 DI 3 DI 4
com com
5 - -
- - 5

6 6

7 VIN VIN 7 VIN VIN


+ + DI 5 DI 6
-
DI5 -
DI6 8
com com
8 - -
9
9
10 VIN VIN
10 VIN VIN
DI 7 DI 8
+ DI7 + DI8 com com
11 - -
- - 11
12
12
13 VIN VIN
13 VIN VIN DI 9 DI 10
+ +
-
DI9 -
DI1 0 14
com com
14 - -
15
15
16 VIN VIN
16 VIN VIN DI 11 DI 12
+ DI1 1 + DI1 2 com com
- -
17
17 - -
18
18
19 VIN VIN
19 VIN VIN DI 13 DI 14
+ + com com
-
DI1 3
-
DI1 4 20
20 - -
21
21
22 VIN VIN
22 VIN VIN DI 15 DI 16
+ DI1 5 + DI1 6 23 com com
- -
23 - -
24
24

C0056ENd
Tra nsdu ce rles s TMU 2 0 0 Tra nsdu cerless TMU 2 0 0
Mea su re m en t U nit Me a su rem en t U nit
1 A co nn ectio ns 5 A co nn e ctio ns

Tra nsd uce rle ss Tra nsd uce rle ss


curre nt inputs curre nt inputs
PIN PIN N1
1 2 1 2 N2
N1

3 4 N2
3 4
C1
5 6 5 6 C2
C1

7 8 C2 7 8
B1
9 10 9 10 B2
B1

11 12 B2
11 12
A1
13 14
13 14 A2
A1

15 16 A2
15 16

17 18 Tra nsd uce rle ss 17 18 Tra nsd uce rle ss


volta g e inputs volta g e inputs
19 20
19 20
U1 U1
21 22 U2
21 22 U2
V1
V1
23 24 V2
23 24 V2
W1
W1
25 26 W2
25 26 W2
N1
N1
27 28 N2
27 28 N2
AOU200
DSP210
Ref : 2071414 Common Trip Contacts Contact Us
OLD

Digital Signal Processor DSPIO210


Input Output
Board

PIN Signal inputs


Pin N Signal
1 DI BLOCKING +
1
+ VIN
2 DI BLOCKING Common
2 - BLOCKING
- 3 DI SELECTIVITY +
3 VIN
+ 4 Not Configurable
4 - SELECTIVITY
- 5 DI SELECTIVITY Common
5
6 COLD LOAD 6 COLD LOAD START +
+
VIN
START
7 - 7 DISTURBANCE START +
8
- + VIN

-
- 8 STARTS COLD LOAD / DREC Common
9 DIST REC
10 START 9
11
10
12
13
11
14 12
15 13
16 14
17 TRIP C 15
18 16
19 TRIP B 17
20
18 Trip Phase C +
21 TRIP A
19
22
23 20 Trip Phase B +
24 21
22 Trip Phase A +
23 Trip Phase A,B,C Common -
24 Trip Phase A,B,C Common -
DSP211
Ref : 2071860 Independant Trip Contacts
NEW

Digital Signal Processor DSPIO211


Input Output
Board

PI Signal
N inputs Pin N°.
1
1 + 2
BLOCKING
IN

2 - -
3
3 +
4 -
IN

SELECTIVIT 4
+ -

5 -
IN
Y 5
-
6 + 6
IN COLD LOAD
7 + - - 7
8 -
IN
DIST REC 8
-
9
10
K5 9
11
10
12
11
13
14 12
15 K4 13
16 14
17 15
18 16
19 TRIP C
17
20
TRIP B 18
21
19
22
23 TRIP A 20
24 21
22
23
24
Signal
DI BLOCKING +
DI BLOCKING Common
DI SELECTIVITY +
Not Configurable
DI SELECTIVITY Common
COLD LOAD START +
DISTURBANCE START +
STARTS COLD LOAD / DREC Common

K5/1 + Close CB
K5/1 - Close CB
K5/2 + Close CB
K5/2 - Close CB
K4/1 + Not Configurable
K4/1 - Not Configurable
K4/2 + Not Configurable
K4/2 - Not Configurable
Not connected
Trip Phase C +
Trip Phase C -
Trip Phase B +
Trip Phase B -
Trip Phase A +
Trip Phase A -
Trip Phase A -
CPU270/ CPU272 / CPU275 Connector description :

0 Volt

0 Volt
SBU200 Connectors: 8* RJ45
Definitions:
AC Alternative Current
AIU Analog Input Unit
Commonly Voltage or Current DC signals delivered by transducers

Bay Set of LV, MV or HV plants (switchs and transformer) and devices (Protective, Measurement…).
Usually around a Circuit Breaker and controlled by a bay computer.
BIU Basic Interface Unit

CAS Package rack CASe


CBC Compact Bay Controller
CCU Circuit breaker Control Unit
CPU Central Processing Unit
CT Current Transformer
CT/VT Current and Voltage Transformers

DC Direct Current
DCS Digital Control System
DI Digital Inputs
DIU Digital Inputs Unit
DO Digital Outputs
DOU Digital Output Unit
DSP Floating-Point Digital Signal Processor

FBP Front Back Plane

GHU Graphic Human interface Unit

HMI Human Machine Interface

I Current
IED Intelligent Electronic Device
IP52 IP52 environmental protection
Protected against dust and direct sprays of water up to 15 degrees from vertical - Indoor
The number 5 means that it is especially protected against the dust
The number 2 means that it is especially protected against projections of water

MiCOM C MiCOM Computer series

NC Normally Closed (for a relay or a contact)


NEMA National Electrical Manufacturers Association
A group which issues standards for the manufacture of electrical equipment.
NEMA enclosure types: (abbreviated) (IEC equivalents in parenthesis)
· Type 1: General purpose - Indoor. (IP10)
· Type 5: Dusttight, drip-proof - Indoor (IP52)
· Type 12: Dusttight and driptight - Indoor (IP52)
· Type 12K: Dusttight and driptight, with knockouts - Indoor (IP52)
NO Normally Open (for a relay or a contact)

PC Personnal Computer
PLC Programmable Logic Controller
PQ Power Quality

RTU Remote Terminal Unit

SCADA Supervisory Control And Data Acquisition


ST®
SWD Ethernet-based SWitch Dual Humming unit
SWR Ethernet-based SWitch Redondant unit
SWU Ethernet-based SWitch Unit
TMU Transducerless Measurements Unit

U Voltage

VT Voltage Transformer

También podría gustarte