Nothing Special   »   [go: up one dir, main page]

Nakakita Temp Controller

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 13
At a glance
Powered by AI
The key takeaways from the document are the different types of controllers like proportional, integral, derivative and PID controllers and their working along with the maintenance required for a pressure controller.

The different types of controllers discussed are proportional, integral, derivative, PID, step, on-off and sequential controllers.

The components of a PID controller are the proportional, integral and derivative terms which are represented by Kp, Ki and Kd respectively along with the set point, process variable, error, comparator and controller output.

C/E Mahesh Patil

Elstan Fernandez
Revise Terminology
Understanding P I D controller theory
Valve Positioner and Actuator working
Adjustments and system tuning
Practical / Demonstration

Total duration 120 minutes


Open Loop system
Closed Loop System
Measured value (mv)
Actual value (av)
Error (mv - av)
Desired Value (dv)
Comparator
Deviation (mv - dv)
Offset(Droop)(mv dv)
Dead Band
Proportional band
Settling Time
Set Point
STEP CONTROL
ON OFF CONTROL

SEQUENCIAL CONTROL
PROPORTIONAL CONTROL
P + DERIVATIVE CONTROL
P + INTEGRAL CONTROL
P + I + D CONTROL
Proportional

Set Point Error Controller Output


- KP + t
e(t)
Kpe(t) + Ki e(t)t + Kd
t
Integral 0

Process
Variable Ki +

Derivative

d
Kd t

PROPORTIONAL - (m)controller o/p is proportional to deviation { e(t)}

m = - Kp * e(t)

INTEGRAL - Rate of change of (m)controller o/p is proportional to deviation { e(t)}

dm / dt = Ki * e(t)

i.e m = - Ki e(t) * dt

DERIVATIVE - (m)Controller o/p is proportional to rate of change of deviation { e(t)}

m = - Kd * de(t) / dt
Initial
Condition
Step Input Final Condition

Process
Time

P Control
Proportional Action

Desired value
Time
Offset
I Control
Proportional + Integral Action

Desired value
D Control Time

Proportional + Integral + Derivative Action

Desired value
Time
Restrictor
Nozzle Flapper arrangement
Nozzle
uncovered 3 Psi
Acts as a transducer or an signal amplifier

Supply Air Pr 1.5 bar


Pressure Gauge
Control air output pr range 3 ~ 15 psi
Nozzle
In mid position
9 Psi Flapper Movement(X1, X2) approx 20
microns
Flapper

Orifice Dia 0.25 mm


Nozzle
covered Nozzle Dia 0.40 mm
15 Psi
Output signal to Actuator

Measured Value Desired Value

(Reset Time) (Rate adjustment)


Periodic calibration and cleaning of measuring devices/sensors (e.g. RTD probe in the FO purifier heater line, M/E
JCW line etc.)

Replacement of polyurethane tubes inside the controller every 24 months, as tubes tend to damage due to heat, oil
and vibration.

Quarterly cleaning of nozzle with a thin SS wire (<0.25 mm)

Weekly cleaning of orifice by depressing the push button.

Bellows and linkages must be checked for their intactness.

Watch out for signs of air leakages inside the controller box

Leakages in signal transmission lines from controller to regulating valve.

Valve condition and integrity of valve packing/seals, moving surface of valve spindles.

And most important, cleanliness of supply air. Correct working of filters and Pressure reducers settings.
THANK YOU

You might also like