P140 Apps
P140 Apps
P140 Apps
Speaker name
Speaker title
Configurable
Interface
Dual Rated Programmable
CT Inputs LEDs
Flexible
Communications
Secure Comprehensive
Recording
Programmable
Scheme Logic
Optimised Costs;
High Level of Integration
Increased Plant Availability
Comprehensive Monitoring
Post Fault Analysis Tools
Condition Based Maintenance
Adaptable to evolving systems
Flexibility
Download/monitor port
Minimal Spares Holding
Alarm viewer
Menu browser
Fixed
function
LEDs
Programmable
LEDs
Battery
back-up Download/
Monitor port
Local
communications Security seal
Fault
Analysis Tools
Comprehensive
Protection Measurements
Communications
Bay Monitoring
& Control
Self Diagnostics
& Commissioning
Tools
Protection
functionality
required is system
dependent
Solid
Resistive Petersen
coil
TPI
PPI
PRI TRI
B/S
Busbar Busbar
CB CB
Busbar Busbar
HVCB LBCB
REF CT
SBEF CT
Busbar Busbar
HVCB LVCB
REF CT
SBEF CT
HVCB LVCB
REF CT
SBEF CT
0 Current
IEC Curves
Operating Time (s)
1000 IEC SI
Four independent stages
IEC VI
IEC EI IDMT/DT stage 1 & 2
IEC LTS
100 DT on stages 3 & 4
Each stage:
Non directional
10
Directional forward
Directional reverse
1 Memory polarising
IEC & IEEE IDMT curves
0.1
1 10 100
Current (Multiples of Is)
IEEE Curves
Operating Time (s)
100 US MI
US VI
Comprehensive setting
US EI ranges
US I
US SI 8% - 400% stages 1 & 2
10 8% - 3200% stages 3 & 4
TMS range: 0.025 to 1.2
Time dial: 0.01 to 100
1 Definite time: 0 to 100s
Phase segregated
contacts/indication
0.1
Per stage starts &
1 10 100 blocking inputs
Current (Multiples of Is)
Adjustable reset time
18 > Title of presentation - Date - References 18
Application of Two IDMT Curves (1)
Busbar Busbar
CB 1 CB 3
P141 CB 5
1 3
CB 2 CB 4 P142
5
P141
2
4
Busbar Busbar
CB 1 CB 3
P141 CB 5
1 3
CB 2 CB 4 P142
5
P141
2
4
Time
Current setting
1/2 Existing practices
3/4 Sensitivity
5 Relay thermal withstand
3/4
DIR
Load current reversal
Time setting
IDMT
Definite time
IFL I3 LV I3 HV
Directional
E/F Measured Wattmetric E/F
(EF2) a,b,c
SEF
EF1
Frame to
earth Fault
(EF2) a,b,c
SEF
EF1
Frame to
earth Fault
Busbar Busbar
CB CB
P141
1 3
CB 3 Limb VT CB
P141
2
4
LV HV Busbar
CB CB
Trip
V A CB
5 Limb VT
VA
59 Residual Overvoltage
(Neutral Displacement)
VC A Phase
VB
to Earth
Fault
No external differential
IDMT DEF
connection
IDMT E/F
Different ratios permissible SBEF
200/1A
Low Z REF
Polarising options for DEF
1000/1A High Z REF
Allows 3-limb VTs
In
No
stabilising
resistor
No non
linear
resistors
28 > Title of presentation - Date - References 28
Low Impedance REF (2)
Line CT ratio
1000
I
DIFF
Operate K2
Restrain
K1
I
S1
I S2 I BIAS
100A
Load
CB 3
CB 2
CB2
CB2
CB 3
51V Voltage Controlled Overcurrent
Isubstation full load
HV LV
I1 + I2 I1 + I2 + I0
CB
I0
Earth
Fault
46 Negative sequence
overcurrent
Backtrip
Two stage
Fast reset
External initiation
Blocking scheme
Retrip
compatible
Trip
BF
INIT
Current
Severe
Marginal
For severeoverload
overload
overloads
replica
requirescurve
dominated by short
100 short timeconstant
longconstant
time time constant
Single
10 characteristic:
1 2 3 4 5 6 = 5 mins
Current (multiple of thermal setting)
CB Motor
a
b
c
Block
CB Close
Motor
47 Negative Sequence Overvoltage
CB HV LV
HV LV
BC Broken Conductor
A
B
C
Alarms
Blocking
IO
Event
& T record
VO
A
B
C
I and 2
logic
3 on load
logic Alarms
Event record
on
VTS
Blocking
energisation
logic Adaptive
setting
MCB digital
input
Benefits:
Time
No requirement to use
Energisation period
characteristic alternate setting groups
May eliminate need for earth fault
stabilising resistor
Normal load
Security /dependability on
characteristic
energisation
Energisation
current profile Potential applications:
Motor feeders
HV transformer earth fault
protection
Switch On To Fault (SOTF)
Air conditioning
Current
Resistive heating
Incomer
Established technique Block high-set
providing: element
Improved fault
clearance times CB fail backtrip
SOL
Input Start
Fault
SOL
SOL Selective Overcurrent Logic Highset
CB1
Highset
CB2 CB1
Start
CB2
Ifault
50 > Title of presentation - Date - References 50
Programmability &
Customerisation
Relay
Optos contacts
Gate Logic
Protection
& Communication
elements 1
&
Timers
Control
Fixed LEDs
scheme
logic
User programmable scheme logic
Trip
Circuit breaker
Trip 52a
Trip
coil
Opto
52b
Opto
L7 52-A
Status
Phase to Earth
Fault
PSL Programmable Scheme Logic
L7 52-A PU 1000
&
LED 1 (Unlatched)
ISEF>START
LOGIC Gate added
Busbar CB CB Busbar
Healthy
Auto
Busbar CB CB Busbar
Healthy
Auto