DISTURBANCE FAULT RECORDER INDACTIC - 650 SEQUENTIAL EVENT RECORDER INDACTIC - 425
DFR
SOE
Products
DR Disturbance Fault Recorder Type I65/I65C Disturbance Fault Recorder Type I650
SER Sequence Of Event Recorder Type SER-600 Sequence Of Event Recorder Type I425.
High cost of stand still of generators, substations and lines Avoiding of system failure is of highest concern No equipment provides the insights as does a good disturbance recorder
Indactic as De-central System Bus Structure : Real time bus 1.5 Mbaud, coaxial or fibre optic cable
Maximum Configuration
per substation 79 units per complete network 250 acquisition stations
Acquisition UNIT (Basic unit
1/ 3
of 19 Rack)
Master, Slave, Slave
Predecessor
Indactic 65 (ABB Product 1981-1994)
ABB Transformation - Training
Modules
Case UB-10
PS-25
(prev. PS-10)
XI-11 TR-10
(prev. XI-10)
Basic Configuration
Indactic 650 Units PC Printer - Laser or InkJet Software WinCom, WinEve
Output
Hardware : 4 output relays (dry contacts) per unit SW : One file per recording with all analogue and digital signals
Tele-Communication
Central Evaluation Station (Master Station) WinCom/ WinEve Local Data Concentrators ReCo65 (or PC Anywhere) WinCom can collect data from many substations (Indactic 650 stations or
ReCo65
MS-DOS SW (also with Windows `95 & 98) currently under re-design
Remote communication
Remote structure
Bridge
Ethernet(TCP/IP)
Bridge
Color Printer
Ethernet(TCP/IP)
Modem
Bridge
Modem
local
Modem
Serial Port
GPS
I ndact ic 425
GPS/ DCF77
Serial Port
REB500 CU
Interbay-Bus
RE.316*4 RE.216 GPS
I ndact ic 425
RE.316
REB500 CU
CB 10
Indactic 650
Indactic 650
SPABus
RE.216
CB 10
Indactic 650 acquisition unit each with 9 analogue and 16 digital inputs De-central intelligence for optimised redundancy
PTs & CTs are integrated into the unit (no external components) Accuracy better than 2% of actual ( 0.5%on full scale) without any recalibration on site
Digital Inputs
Number: Input Type 16 48V to 250V or potential free
Analogue Inputs
Resolution:
16 bits
9, current or voltage
Number:
Voltage Inputs:
Accuracy (0.2 to 1.6 x Un)
Measurement range
0.5% of Un
Current Inputs:
1A or 5A
50 x In x 2 = full range 100 x In 30 1 x x
Trigger Settings
Digital-Inputs: Analog-Inputs: high or low levels high limit
low limit
Recording Duration Prefault: Postfault: Fault: 0.1 s to 0.5 s, prog. in steps of 0.1 s 0.1 s to 0.5 s, prog. in steps of 0.1 s 0.1 s to 30 s, prog. in steps of 0.1 s
optional to 600 s at the lowest sampling rates
On Board Memory
Total 4 Mbyte per unit - 200'000 samples per channel Data back-up for 6 hours
ABB Transformation - Training
ONLY ONE EVALUATION SOFTWARE FOR INDACTIC 650, REB500, RE.216, RE.316 and REVAL FORMATS
ABB Transformation - Training
ONLY ONE REMOTE SOFTWARE FOR INDACTIC 650, REB500, RE.216, RE.316 (SOFTWARE RELEASE END 2000)
ONE A/D CONVERTER PER CHANNEL = HIGH SECURITY IN CASE OF ONE A/D CONVERTER FAILURE
G
Excitation
DC 4..20mA
380 kV
Field Current Field Voltage Main Rotor Field Current Main Rotor Field Voltage
11 kV Unit B Transformer
Indactic System
Users
Data
RS-232
GPS
Coaxial cable 75
Generator unit 1
Generator unit 2
Indactic 650 Rubrik wxyz (rubrik identifies the configuration) GPS Clock & Receiver
19 Mounting Rack
WinCom/WinEve/ReCo65
Internal Office LAN
Industrial PC
M
Ethernet
Desktop PC InkJet/ Laser Printers RS232/ F-O Converters Telephone Modems TC-630 - Coax to F-O converters
Data
WinCom-Trigger setting
Fault analysis software under MS-WINDOWS 95 and NT One program covers all aspects of fault analysis Comprehensive formula editor for all relevant calculations, i.e. true RMS,
Merging of events Multi-event display User-definable layouts Reads and writes COMTRADE file formats Compatible to Indactic 65/650, RE. 216/316 & REB500 formats
Event display
Fault locator
Based on a well proven distance relay algorithm, accuracy is better than 2 % mutual and zero sequence impedance capacitance (for long lines) parallel lines
Fault locator
symmetric or asymmetric lines reduces fault resistance influence re-calculate the distance to fault i.e. with seasonal or "better" parameters.
Competitors
Alstom.