Trane Geister

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 24

W.

Ryan Geister
CenTraVac Product Manager Vertical Markets

Trane 3600 Pammel Creek Road LaCrosse WI 54601 7599 TEL 608 787 3881 FAX 608 787 2204 rgeister@trane.com
An American Standard Company

Energy First Cost Consumption

Annual Energy Cost Conventional Chilled Water System

Past ...
Chiller 73%

1980

Pumps 18%

Tower 9%

Present ...
Chiller 58%

2000
Pum ps 26%

Tower 16%

Low Flow Chilled Water Plant Design

A Paradigm Shift - New Rules of Thumb

New rules of thumb


44 41 F chilled water supply 16 F T across the evaporator

thats at 1.5 gpm/ton

15 F T across the condenser

thats at 2.0 gpm/ton

Resize the cooling tower accordingly

Low Flow Chilled Water Plant Design

What are others saying???

Kelly and Chan (Vanderweil Engineering)


HPAC January 1999: Optimizing Chilled Water Plants Chilled water T: 18 & Condenser water T: 14.2F
With the same cost chillers, at worst, the annual operating cost with lower flows be about equal to standard flows but still at a lower first cost

PG&E: CoolTools

Chilled water T: 12F to 20 F Condenser water T: 12F to 18 F (multi-stage)


kWh/ton/year
600 400 200 0 41/16 42/14 43/12 44/10 Chilled water pump Chiller

Chilled water supply temperature/DeltaT

EarthWise Chilled Water Systems:

Good for Business...

Offers lower first cost and lower operating cost. Reduced utility generated greenhouse gas emissions.

Good for the Environment:

Reduces pumping costs...

A low flow, low temp, high efficiency system


control s

Leverages todays technology

Equipment - Chillers, Controls System options

+$

$
piping, pumps

+$
chillers

Q= m cp T Fundamental Laws

Mass (capacity) varies directly with flow


>

T = Smaller Pipes & Tower P = Smaller Pumps

Pressure Drop varies with the square of the flow


<

Energy Consumption varies with the cube of the flow


Reduced

Operating Costs!

The Next Step...

How have Chillers Reacted to VPF Traditionally???


130 1,500.00 120

Capacity Control w/o Water Flow Compensation

1,300.00

110

1,100.00

100
Evaporator Water Flow

900.00

Water Temp [degF]

80

500.00

70

60

Too Fast a change can be a problem

300.00

100.00

Evap Entering Water Temp

50

-100.00

40
Chiller on
Evap Leaving Water Temp

-300.00
Chiller off Chiller off

30 0:00:00

0:10:00

0:20:00

0:30:00

0:40:00

-500.00 0:50:00

Time (hour:min:sec)

Water Flow [gpm]

90

700.00

But Newer Technology Can Eliminate all Concerns


130 1,500.00 120

Capacity Control with Water Flow Compensation

1,300.00

110

1,100.00

100

900.00

Water Temp [degF]

90

Evaporator Water Flow

700.00

80

70

Stable Chiller Response


Evap Entering Water Temp

500.00

300.00

60

100.00

50

-100.00

40
Evap Leaving Water Temp

-300.00

30 0:00:00

0:10:00

0:20:00 0:30:00 Time (hour:min:sec)

0:40:00

-500.00 0:50:00

Water Flow [gpm]

Bottom line: Chillers very capable today! & VPF Saves $$$

And... By coupling VPF Systems with SERIES Evaporators, many advantages emerge...

System Examples

Series Chillers & colder water = $ savings!

How???
CHILLED WATER RETURN CHILLED WATER SUPPLY

57 o F

49 o F
105 o F

41 o F

56 o F 64 o F

Assuming 85 Entering and 2 GPM/Ton

Run two chillers at 50% or..


41 oF

49 oF

Even better...
CHILLED WATER RETURN

Part Load Efficiency


CHILLED WATER SUPPLY

57 o F

57 o F
105 o F

41 o F

.Run your most efficient chiller

64 o F

41 o F

If applicable...
CHILLED WATER RETURN

Chilled Water Temperature Re-Set


CHILLED WATER SUPPLY

57 o F

57 o F
105 o F

44 o F

And save more $$$s!

61 o F

44 o F

If applicable...
AFD Chiller
CHILLED WATER RETURN CHILLED WATER SUPPLY

57 o F

57 o F

41 o F

And save more $$$s!*


* IF all three justify the initial capital cost of the AFD
1. Extensive hours of operation (~24/7, winter cooling) 2. Access to inexpensive cold condenser water 3. Expensive electricity (high kWh rates)

System Flexibility Options... Absorption Chiller Technology


CHILLED WATER RETURN CHILLED WATER SUPPLY

57 o F

50 o F

41 o F

System Flexibility Options... Screw Chiller Technology


CHILLED WATER RETURN CHILLED WATER SUPPLY

57 o F

50 o F

41 o F

System Flexibility Options... Existing Chiller Assets


CHILLED WATER RETURN CHILLED WATER SUPPLY

57 o F

50 o F

41 o F

Existing Chiller Assets

System Flexibility Options...


Plant Expansion
CHILLED WATER RETURN

Parallel - Primary Secondary (Decoupled)


~50 oF

57 oF

CHILLED WATER SUPPLY

41 oF

System Flexibility Options...


Plant Expansion
Parallel/Series - Variable-Primary
CHILLED WATER SUPPLY

CHILLED WATER RETURN 57 oF

~50 oF

41 oF

EarthWise Chilled Water Systems


Exploit technology! Low flow Low temperature High efficiency Leverage: Optimized Controls Variable Primary Flow Series Evaporators

First Operating Cost Cost

always, always,

Always Remember

W. Ryan Geister
CenTraVac Product Manager Vertical Markets

Trane 3600 Pammel Creek Road LaCrosse WI 54601 7599 TEL 608 787 3881 FAX 608 787 2204 rgeister@trane.com