Nothing Special   »   [go: up one dir, main page]

VEGASON 62 Level Sensor VEGASON Ultrasonic Level Sensor - Operating Instructions - 4 20mAHART

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

Tel: +44 (0)191 490 1547

Fax: +44 (0)191 477 5371


Email: northernsales@thorneandderrick.co.uk
Website: www.heattracing.co.uk
www.thorneanderrick.co.uk

Operating Instructions
Ultrasonic sensor for continuous level
measurement

VEGASON 62
4 … 20 mA/HART - two-wire

Document ID: 28776


Contents

Contents
1 About this document
1.1 Function............................................................................................................................ 4
1.2 Target group...................................................................................................................... 4
1.3 Symbolism used................................................................................................................ 4
2 For your safety
2.1 Authorised personnel........................................................................................................ 5
2.2 Appropriate use................................................................................................................. 5
2.3 Warning about incorrect use.............................................................................................. 5
2.4 General safety instructions................................................................................................ 5
2.5 Safety label on the instrument........................................................................................... 5
2.6 CE conformity.................................................................................................................... 5
2.7 Fulfillment of NAMUR recommendations.......................................................................... 6
2.8 Safety instructions for Ex areas......................................................................................... 6
2.9 Environmental instructions................................................................................................ 6
3 Product description
3.1 Configuration..................................................................................................................... 7
3.2 Principle of operation........................................................................................................ 7
3.3 Operation.......................................................................................................................... 8
3.4 Packaging, transport and storage...................................................................................... 8
4 Mounting
4.1 General instructions........................................................................................................ 10
4.2 Mounting instructions...................................................................................................... 11
5 Connecting to power supply
5.1 Preparing the connection................................................................................................ 17
5.2 Connection procedure..................................................................................................... 18
5.3 Wiring plan, single chamber housing.............................................................................. 19
5.4 Wiring plan, double chamber housing............................................................................. 21
5.5 Wiring plan - version IP 66/IP 68 (1 bar).......................................................................... 23
5.6 Switch-on phase............................................................................................................. 23
6 Set up with the display and adjustment module PLICSCOM
6.1 Short description............................................................................................................. 24
6.2 Insert display and adjustment module............................................................................. 24
6.3 Adjustment system.......................................................................................................... 25
6.4 Setup steps..................................................................................................................... 26
6.5 Menu plan ultrasonic sensor........................................................................................... 31
6.10 Saving the parameter adjustment data............................................................................ 33
7 Set up with PACTware and other adjustment programs
7.1 Connect the PC via VEGACONNECT............................................................................. 34
7.2 Parameter adjustment with PACTware............................................................................. 35
7.3 Parameter adjustment with AMS™ and PDM.................................................................. 36
7.4 Saving the parameter adjustment data............................................................................ 36
28776-EN-130417

8 Maintenance and fault rectification


8.1 Maintenance................................................................................................................... 37
8.2 Rectify faults.................................................................................................................... 37
8.3 Exchanging the electronics module................................................................................. 38

2 VEGASON 62 • 4 … 20 mA/HART - two-wire


Contents

8.4 Software update.............................................................................................................. 38


8.5 Instrument repair............................................................................................................. 39
9 Dismounting
9.1 Dismounting steps.......................................................................................................... 41
9.2 Disposal.......................................................................................................................... 41
10 Supplement
10.1 Technical data................................................................................................................. 42
10.2 Dimensions..................................................................................................................... 47

Supplementary documentation
Information:
Supplementary documents appropriate to the ordered version come
with the delivery. You can find them listed in chapter "Product descrip-
tion".

Instructions manuals for accessories and replacement parts


Tip:
To ensure reliable setup and operation of your VEGASON 62, we offer
accessories and replacement parts. The corresponding documenta-
tions are:
• 27835 - Display and adjustment module PLICSCOM
28776-EN-130417

• 32628 - Interface adapter VEGACONNECT


• 27720 - External indication VEGADIS 61
• 34296 - Protective cover
• 30176 - Electronics module VEGASON series 60
Editing status: 2013-04-11

VEGASON 62 • 4 … 20 mA/HART - two-wire 3


1 About this document

1 About this document


1.1 Function
This operating instructions manual provides all the information you
need for mounting, connection and setup as well as important instruc-
tions for maintenance and fault rectification. Please read this informa-
tion before putting the instrument into operation and keep this manual
accessible in the immediate vicinity of the device.

1.2 Target group


This operating instructions manual is directed to trained specialist
personnel. The contents of this manual should be made available to
these personnel and put into practice by them.

1.3 Symbolism used


Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result.
Warning: If this warning is ignored, injury to persons and/or serious
damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons and/or
destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
• List
The dot set in front indicates a list with no implied sequence.
→ Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of bat-
teries and accumulators.
28776-EN-130417

4 VEGASON 62 • 4 … 20 mA/HART - two-wire


2 For your safety

2 For your safety


2.1 Authorised personnel
All operations described in this operating instructions manual must
be carried out only by trained specialist personnel authorised by the
plant operator.
During work on and with the device the required personal protective
equipment must always be worn.

2.2 Appropriate use


VEGASON 62 is a sensor for continuous level measurement.
You can find detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly
used according to the specifications in the operating instructions
manual as well as possible supplementary instructions.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
trary conversions or modifications are explicitly forbidden.

2.3 Warning about incorrect use


Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards, e.g. vessel overfill or damage to system
components through incorrect mounting or adjustment.

2.4 General safety instructions


This is a high-tech instrument requiring the strict observance of stand-
ard regulations and guidelines. The user must take note of the safety
instructions in this operating instructions manual, the country-specific
installation standards as well as all prevailing safety regulations and
accident prevention rules.
The instrument must only be operated in a technically flawless and
reliable condition. The operator is responsible for trouble-free opera-
tion of the instrument.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regula-
tions.

2.5 Safety label on the instrument


The safety approval markings and safety tips on the device must be
observed.
28776-EN-130417

2.6 CE conformity
This device fulfills the legal requirements of the applicable EC guide-
lines. By attaching the CE mark, VEGA provides a confirmation of

VEGASON 62 • 4 … 20 mA/HART - two-wire 5


2 For your safety

successful testing. You can find the CE conformity declaration in the


download area of "www.vega.com".

2.7 Fulfillment of NAMUR recommendations


NAMUR is the automation technology user association in the process
industry in Germany. The published NAMUR recommendations are
accepted as the standard in field instrumentation.
The device fulfills the requirements of the following NAMUR recom-
mendations:
• NE 21 – Electromagnetic compatibility of equipment
• NE 43 – Signal level for malfunction information from measuring
transducers
• NE 53 – Compatibility of field devices and display/adjustment
components
For further information see www.namur.de.

2.8 Safety instructions for Ex areas


Please note the Ex-specific safety information for installation and op-
eration in Ex areas. These safety instructions are part of the operating
instructions manual and come with the Ex-approved instruments.

2.9 Environmental instructions


Protection of the environment is one of our most important duties.
That is why we have introduced an environment management system
with the goal of continuously improving company environmental pro-
tection. The environment management system is certified according
to DIN EN ISO 14001.
Please help us fulfill this obligation by observing the environmental
instructions in this manual:
• Chapter "Packaging, transport and storage"
• Chapter "Disposal"
28776-EN-130417

6 VEGASON 62 • 4 … 20 mA/HART - two-wire


3 Product description

3 Product description
3.1 Configuration
Scope of delivery The scope of delivery encompasses:
• VEGASON 62 ultrasonic sensor
• Documentation
–– this operating instructions manual
–– Safety Manual 28983 "VEGASON 61, 62 - 4 … 20 mA/HART"
(optional)
–– Operating instructions manual 27835 "Display and adjustment
module PLICSCOM" (optional)
–– Supplementary instructions manual 31708 "Heating for display
and adjustment module" (optional)
–– Supplementary instructions manual "Plug connector for con-
tinuously measuring sensors" (optional)
–– Ex-specific "Safety instructions" (with Ex versions)
–– Supplementary instructions manual "Plug connector" (optional)

Constituent parts The VEGASON 62 consists of the components:


• Process fitting with transducer
• Housing with electronics, optionally available with plug connector
• Housing cover, optionally available with display and adjustment
module PLICSCOM
The components are available in different versions.
1

Fig. 1: VEGASON 62 - threaded version with plastic housing


1 Housing cover with integrated PLICSCOM (optional)
2 Housing with electronics
3 Process fitting with transducer
28776-EN-130417

3.2 Principle of operation


Application area VEGASON 62 is an ultrasonic sensor for continuous level measure-
ment. It is suitable for liquids and solids in virtually all industries,
particularly in the water and waste water industry.

VEGASON 62 • 4 … 20 mA/HART - two-wire 7


3 Product description

Functional principle The transducer of the ultrasonic sensor transmits short ultrasonic
pulses to the measured product. These pulses are reflected by
product surface and received back by the transducer as echoes.
The running time of the ultrasonic pulses from emission to reception
is proportional to the distance and hence the level. The determined
level is converted into an appropriate output signal and outputted as
measured value.

Voltage supply 4 … 20 mA/HART two-wire electronics for voltage supply and meas-
ured value transmission on the same cable.
The supply voltage range can differ depending on the instrument
version.
The data for power supply are specified in chapter "Technical data".
The optional background lighting of the display and adjustment
module is powered by the sensor. A certain level of operating voltage
is required for this. You can find the exact voltage specifications in
chapter "Technical data".
The optional heating requires its own operating voltage. You can find
details in the supplementary instructions manual "Heating for display
and adjustment module".
This function is generally not available for approved instruments.

3.3 Operation
The instrument can be adjusted with the following adjustment media:
• With the display and adjustment module
• with the suitable VEGA DTM in conjunction with an adjustment
software according to the FDT/DTM standard, e.g. PACTware and
PC
• with manufacturer-specific adjustment programs AMS™ or PDM
• With a HART handheld

3.4 Packaging, transport and storage


Packaging Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
The packaging of standard instruments consists of environment-
friendly, recyclable cardboard. For special versions, PE foam or PE
foil is also used. Dispose of the packaging material via specialised
recycling companies.

Transport Transport must be carried out under consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
28776-EN-130417

Transport inspection The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or con-
cealed defects must be appropriately dealt with.

8 VEGASON 62 • 4 … 20 mA/HART - two-wire


3 Product description

Storage Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
• Not in the open
• Dry and dust free
• Not exposed to corrosive media
• Protected against solar radiation
• Avoiding mechanical shock and vibration
Storage and transport • Storage and transport temperature see chapter "Supplement -
temperature Technical data - Ambient conditions"
• Relative humidity 20 … 85 %
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 9


4 Mounting

4 Mounting
4.1 General instructions
Suitability for the process Make sure that all parts of the instrument coming in direct contact
conditions with the process, especially the sensor element, process seal and
process fitting, are suitable for the existing process conditions, such
as process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data" and on the
nameplate.

Installation position Select an installation position you can easily reach for mounting and
connecting as well as later retrofitting of a display and adjustment
module. The housing can be rotated by 330° without the use of any
tools. You can also install the display and adjustment module in four
different positions (each displaced by 90°).

Moisture Use the recommended cables (see chapter "Connecting to power


supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable entry. Rain and condensation water can thus drain off. This ap-
plies mainly to outdoor mounting as well as installation in areas where
high humidity is expected (e.g. through cleaning processes) or on
cooled or heated vessels.

Fig. 2: Measures against moisture penetration

Measuring range The reference plane for the measuring range is the lower edge of the
transducer.
Make sure that a minimum distance from the reference plane - the
so-called dead band, in which measurement is not possible - is
maintained. The exact value of the dead band is stated in chapter
"Technical data".
28776-EN-130417

10 VEGASON 62 • 4 … 20 mA/HART - two-wire


4 Mounting

2
1

Fig. 3: Minimum distance to the max. level


1 Dead band
2 Reference plane

Information:
If the medium reaches the transducer, buildup can form on it and
cause faulty measurements later on.

1 2 3
100%

0%

Fig. 4: Measuring range (operating range) and max. measuring distance


1 full
2 empty (max. measuring distance)
3 Measuring range

Pressure/Vacuum Gauge pressure in the vessel does not influence VEGASON 62. Low
pressure or vacuum does, however, damp the ultrasonic pulses. This
influences the measuring result, particularly if the level is very low.
With pressures under -0.2 bar (-20 kPa) you should use a different
measuring principle, e.g. radar or guided microwave.

4.2 Mounting instructions


Screwing in Screw VEGASON 62 into the mounting socket with an appropriate
spanner applied to the hexagon of the process fitting. Max. torque see
28776-EN-130417

chapter "Technical data".


Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.

VEGASON 62 • 4 … 20 mA/HART - two-wire 11


4 Mounting

Installation position When mounting the sensor, keep a distance of at least 200 mm
(7.874 in) to the vessel wall. If the sensor is installed in the center of
dished or round vessel tops, multiple echoes can arise. These can,
however, be suppressed by an appropriate adjustment (see chapter
"Setup").

> 200 mm

Fig. 5: Mounting on round vessel tops


1 Reference plane
2 Vessel center or symmetry axis

If you cannot keep this distance you should carry out a false echo
storage before setup. This applies mainly if buildup on the vessel wall
is expected. In this case, we recommend repeating a false echo stor-
age later with existing buildup.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the vessel bottom.

28776-EN-130417

Fig. 6: Vessel with conical bottom

Socket Socket pieces should be dimensioned so that the lower end of the
transducer protrudes at least 10 mm (0.394 in) out of the socket.

12 VEGASON 62 • 4 … 20 mA/HART - two-wire


4 Mounting

ca. 10 mm
Fig. 7: Recommended socket mounting

If the reflective properties of the medium are good, you can mount
VEGASON 62 on sockets which are higher than the length of the
transducer. You will find recommended values for socket heights in the
following illustration. The socket end should be smooth and burr-free,
if possible also rounded. Carry out a false echo storage.

d h
100 mm/4" 300 mm/12"
150 mm/6" 400 mm/16"
h

200 mm/8" 500 mm/20"

Fig. 8: Deviating socket dimensions

Sensor orientation Align the sensor in liquids as vertical as possible to the product sur-
face to achieve an optimum measurement result.

Fig. 9: Alignment in liquids

To reduce the min. distance to the medium, you can also mount VE-
GASON 62 with a beam deflector. By doing this, it is possible to fill the
vessel nearly to maximum. Such an arrangement is suitable primarily
for open vessels such as e.g. overflow basins.
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 13


4 Mounting

~4
45°

00
x4
00
~200

Fig. 10: Beam deflector

Vessel installations The ultrasonic sensor should be installed at a location where no


installations cross the ultrasonic beam.
Vessel installations such as for example, ladders, limit switches, heat-
ing spirals, struts etc. can cause false echoes that interfere with the
useful echo. Make sure when planning your measuring site that the
ultrasonic signals have a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be
carried out during setup.
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal or plastic baffles above the installations
scatter the ultrasonic signals and avoid direct false echoes.

α
α α

α
α α

Fig. 11: Cover smooth profiles with deflectors

Agitators If there are agitators in the vessel, a false signal memory should be
carried out with the agitators in motion. This ensures that the interfer-
ing reflections from the agitators are saved with the blades in different
positions.
28776-EN-130417

14 VEGASON 62 • 4 … 20 mA/HART - two-wire


4 Mounting

Fig. 12: Agitators

Inflowing medium Do not mount the instruments in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.

Fig. 13: Inflowing liquid

Foam Through the action of filling, stirring and other processes in the vessel,
dense foams which considerably damp the emitted signals may form
on the product surface.
If foams are causing measurement errors, the sensor should be used
in a standpipe or, alternatively, the more suitable guided radar sen-
sors (TDR) should be used.
Guided wave radar is unaffected by foam generation and is particu-
larly suitable for such applications.

Air turbulences If there are strong air currents in the vessel, e.g. due to strong winds
28776-EN-130417

in outdoor installations or air turbulence, e.g. by cyclone extraction


you should mount VEGASON 62 in a standpipe or use a different
measuring principle, e.g. radar or guided radar (TDR).

VEGASON 62 • 4 … 20 mA/HART - two-wire 15


4 Mounting

Standpipe measurement By using a standpipe (surge or bypass tube), the influence of vessel
installations, foam generation and turbulence is excluded.
Standpipes must extend all the way down to the requested min. level,
as measurement is only possible within the tube.

max.

min.

Fig. 14: Standpipe in the tank


1 Vent hole: ø 5 … 10 mm (0.197 … 0.394 in)

VEGASON 62 can be used from tube diameters of 50 mm (1.969 in).


Avoid large gaps and thick welding joints when connecting the tubes.
Generally carry out a false echo storage.
Measurement in a standpipe is not recommended for extremely
adhesive products.

28776-EN-130417

16 VEGASON 62 • 4 … 20 mA/HART - two-wire


5 Connecting to power supply

5 Connecting to power supply


5.1 Preparing the connection
Safety instructions Always keep in mind the following safety instructions:
• Connect only in the complete absence of line voltage
• If overvoltage surges are expected, overvoltage arresters should
be installed

Tip:
We recommend using VEGA overvoltage arresters B63-48 and
ÜSB 62-36G.X.
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.

Voltage supply Power supply and current signal are carried on the same two-wire
cable. The voltage supply range can differ depending on the instru-
ment version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the
mains circuits according to DIN EN 61140 VDE 0140-1. The VEGA
power supply units VEGATRENN 149A Ex, VEGASTAB 690 as well
as all VEGAMETs and VEGASCANs meet this requirement.
Keep in mind the following additional factors that influence the operat-
ing voltage:
• Output voltage of the power supply unit can be lower under nomi-
nal load (with a sensor current of 20.5 mA or 22 mA in case of fault
message)
• Influence of additional instruments in the circuit (see load values in
chapter "Technical data")

Connection cable The instrument is connected with standard two-wire cable without
screen. If electromagnetic interference is expected which is above the
test values of EN 61326 for industrial areas, screened cable should
be used.
Use cable with round cross-section. A cable outer diameter of
5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.
If you are using cable with a different diameter or cross-section,
exchange the seal or use a suitable cable gland.
We generally recommend the use of screened cable for HART multi-
drop mode.

Cable gland ½ NPT On the instrument with cable entry ½ NPT and plastic housing there is
a metallic ½" threaded insert moulded into the plastic housing.
28776-EN-130417

Caution:
No grease should be used when screwing the NPT cable gland or
steel tube into the threaded insert. Standard grease can contain
additives that corrode the connection between threaded insert and

VEGASON 62 • 4 … 20 mA/HART - two-wire 17


5 Connecting to power supply

housing. This would influence the stability of the connection and the
tightness of the housing.

Cable screening and If screened cable is necessary, connect the cable screen on both
grounding ends to ground potential. In the sensor, the screen must be connected
directly to the internal ground terminal. The ground terminal on the
outside of the housing must be connected to the potential equalisa-
tion (low impedance).
If potential equalisation currents are expected, the connection on the
processing side must be made via a ceramic capacitor (e. g. 1 nF,
1500 V). The low-frequency potential equalisation currents are thus
suppressed, but the protective effect against high frequency interfer-
ence signals remains.
Warning:
Considerable potential differences exist inside galvanic plants as well
as vessels with cathodic corrosion protection. Very large equalisa-
tion currents can flow through the cable screen when the screen
is grounded on both ends. To avoid this, the cable screen must be
connected to ground potential only on one end (inside the switch-
ing cabinet) in such applications. The cable screen must not be
connected to the internal ground terminal in the sensor and the outer
ground terminal on the housing not to potential equalisation!
Information:
The metallic parts of the instrument (transmitter, process fitting, etc.)
are conductively connected with the inner and outer ground terminal
on the housing. This connection exists either as a direct metallic
contact or via the shielding of the special connection cable on instru-
ments with external electronics. You can find specifications on the po-
tential connections within the instrument in chapter "Technical data".
Take note of the corresponding installation regulations for Ex applica-
tions. In particular, make sure that no potential equalisation currents
flow over the cable screen. In case of grounding on both sides this
can be achieved by the use of a capacitor or a separate potential
equalisation.

5.2 Connection procedure


Proceed as follows:
1. Unscrew the housing cover
2. If a display and adjustment module is installed, remove it by turn-
ing it to the left.
3. Loosen compression nut of the cable entry
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
5. Insert the cable into the sensor through the cable entry
28776-EN-130417

6. Lift the opening levers of the terminals with a screwdriver (see


following illustration)
7. Insert the wire ends into the open terminals according to the wir-
ing plan

18 VEGASON 62 • 4 … 20 mA/HART - two-wire


5 Connecting to power supply

Fig. 15: Connection steps 6 and 7

8. Press down the opening levers of the terminals, you will hear the
terminal spring closing
9. Check the hold of the wires in the terminals by lightly pulling on
them
10. Connect the screen to the internal ground terminal, connect the
outer ground terminal to potential equalisation
11. Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
12. Screw the housing cover back on
The electrical connection is hence finished.

5.3 Wiring plan, single chamber housing


The following illustrations apply to the non-Ex as well as to the Ex-ia
version.
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 19


5 Connecting to power supply

Housing overview

5 5 5

1 2 3

5
4

Fig. 16: Material versions, single chamber housing


1 Plastic
2 Aluminium
3 Stainless steel, investment casting
4 Stainless steel, electro-polished
5 Filter element for air pressure compensation of all material versions. Blind
plug with version IP 66/IP 68, 1 bar for Aluminium and stainless steel

Electronics and connec-


tion compartment

Display
I²C 1

1 2 5 6 7 8
4 2

Fig. 17: Electronics and connection compartment, single chamber housing


1 Plug connector for VEGACONNECT (I²C interface)
2 Spring-loaded terminals for connection of the external indication VEGADIS
61
3 Ground terminal for connection of the cable screen
4 Spring-loaded terminals for voltage supply
28776-EN-130417

20 VEGASON 62 • 4 … 20 mA/HART - two-wire


5 Connecting to power supply

Wiring plan

Display
I2C

1 2 5 6 7 8

Fig. 18: Wiring plan, single chamber housing


1 Voltage supply, signal output

5.4 Wiring plan, double chamber housing


The following illustrations apply to the non-Ex as well as to the Ex-ia
version.
Housing overview
1 2 3

4 5

Fig. 19: Double chamber housing


1 Housing cover, connection compartment
2 Blind plug or plug M12 x 1 for VEGADIS 61 (optional)
3 Housing cover, electronics compartment
4 Filter element for air pressure compensation
5 Cable gland
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 21


5 Connecting to power supply

Electronics compartment

Display
1
I2C

1 2 5 6 7 8

3 2

Fig. 20: Electronics compartment, double chamber housing


1 Plug connector for VEGACONNECT (I²C interface)
2 Internal connection cable to the connection compartment
3 Terminals for VEGADIS 61

Connection compartment Display

1 2 I2C

Fig. 21: Connection compartment, double chamber housing


1 Spring-loaded terminals for voltage supply
2 Plug connector for VEGACONNECT (I²C interface)
3 Ground terminal for connection of the cable screen
28776-EN-130417

22 VEGASON 62 • 4 … 20 mA/HART - two-wire


5 Connecting to power supply

Wiring plan

I2C

1 2

Fig. 22: Wiring plan, double chamber housing


1 Voltage supply, signal output

5.5 Wiring plan - version IP 66/IP 68 (1 bar)


Wire assignment, con-
nection cable
1

2
Fig. 23: Wire assignment, connection cable
1 brown (+) and blue (-) to power supply or to the processing system
2 Shielding

5.6 Switch-on phase


Switch-on phase After connecting VEGASON 62 to power supply or after a voltage
recurrence, the instrument carries out a self-check for approx. 30
seconds:
• Internal check of the electronics
• Indication of the instrument type, the firmware as well as the sen-
sor TAGs (sensor designation)
• Output signal jumps briefly (approx. 10 seconds) to the set fault
current
Then the corresponding current is outputted to the cable (the value
corresponds to the actual level as well as the settings already carried
out, e.g. factory setting).
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 23


6 Set up with the display and adjustment module PLICSCOM

6 Set up with the display and adjustment


module PLICSCOM
6.1 Short description
Function/Configuration The display and adjustment module is used for measured value
display, adjustment and diagnosis. It can be mounted in the following
housing versions and instruments:
• All sensors of the plics® instrument family, in the single as well as
in the double chamber housing (optionally in the electronics or
connection compartment)
• External display and adjustment unit VEGADIS 61
From a hardware version …- 01 or higher of the display and adjust-
ment module resp. …- 03 or higher of the corresponding sensor elec-
tronics, an integrated backlight can be switched on via the adjustment
menu. The hardware version is stated on the type label of the display
and adjustment module or the sensor electronics.
Note:
You can find detailed information on the adjustment in the operating
instructions manual "Display and adjustment module".

6.2 Insert display and adjustment module


Mount/Dismount display The display and adjustment module can be inserted into the sensor
and adjustment module and removed again at any time. It is not necessary to interrupt the
power supply.
Proceed as follows:
1. Unscrew the housing cover
2. Place the display and adjustment module in the desired position
on the electronics (you can choose any one of four different posi-
tions - each displaced by 90°)
3. Press the display and adjustment module onto the electronics
and turn it to the right until it snaps in.
4. Screw housing cover with inspection window tightly back on
Removal is carried out in reverse order.
The display and adjustment module is powered by the sensor, an ad-
ditional connection is not necessary.
28776-EN-130417

24 VEGASON 62 • 4 … 20 mA/HART - two-wire


6 Set up with the display and adjustment module PLICSCOM

Fig. 24: Insert display and adjustment module

Note:
If you intend to retrofit the instrument with a display and adjustment
module for continuous measured value indication, a higher cover with
an inspection glass is required.

6.3 Adjustment system

1 2

1.1

Fig. 25: Display and adjustment elements


1 LC display
2 Indication of the menu item number
3 Adjustment keys
28776-EN-130417

Key functions • [OK] key:


–– Move to the menu overview
–– Confirm selected menu
–– Edit parameter

VEGASON 62 • 4 … 20 mA/HART - two-wire 25


6 Set up with the display and adjustment module PLICSCOM

–– Save value

• [->] key to select:


–– Menu change
–– Select list entry
–– Select editing position

• [+] key:
–– Change value of the parameter

• [ESC] key:
–– interrupt input
–– Jump to next higher menu

Adjustment system The sensor is adjusted via the four keys of the display and adjust-
ment module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration.
Approx. 10 minutes after the last pressing of a key, an automatic reset
to measured value indication is triggered. Any values not confirmed
with [OK] will not be saved.

6.4 Setup steps


Address setting HART In HART-Multidrop mode (several sensors on one input) the address
multidrop must be set before continuing with the parameter adjustment. You
will find a detailed description in the operating instructions manual
"Display and adjustment module" or in the online help of PACTware
or DTM.
HART mode

Standard
Address 0

Parameter adjustment As VEGASON 62 is a distance measuring instrument, the distance


from the sensor to the product surface is measured. To have the real
product level displayed, an allocation of the measured distance to the
percentage height must be made. To carry out this adjustment, the
distance is entered with full and empty vessel. If these values are not
known, an adjustment with the distance values, e.g. 10 % and 90 %
is also possible. Starting point for these distance specifications is
always the lower side of the flange, with all other versions the lower
side of the transducer.
The actual level is then calculated on the basis of these entered
values. At the same time, the operating range of the sensor is limited
from maximum range to the requested range.
The real product level during this adjustment is not important, be-
cause the min./max. adjustment is always carried out without chang-
ing the product level. These settings can be made ahead of time
28776-EN-130417

without the instrument having to be installed.


In the main menu item "Basic adjustment", the individual submenu
items should be selected one after the other and provided with the
correct parameter values.

26 VEGASON 62 • 4 … 20 mA/HART - two-wire


6 Set up with the display and adjustment module PLICSCOM

Start your parameter adjustment with the following menu items of the
basic adjustment:

Carry out min. adjustment Proceed as follows:


1. Move from the measured value display to the main menu by
pushing [OK].
▶ Basic adjustment
Display
Diagnostics
Service
Info

2. Select the menu item "Basic adjustment" with [->] and confirm
with [OK]. Now the menu item "Min. adjustment" is displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)

3. Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4. Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5. Save the settings with [OK] and move to "Max. adjustment" with
[->].

Carry out max. adjust- Proceed as follows:


ment
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)

1. Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3. Save the settings with [OK] and move to "Medium selection" with
[->].

Medium selection Each product has different reflective properties. In addition, there
are various interfering factors which have to be taken into account:
28776-EN-130417

agitated product surfaces and foam generation (with liquids); dust


generation, material cones and echoes from the vessel wall (with
solids). To adapt the sensor to these different conditions, you should
first select "Liquid" or "Solid".

VEGASON 62 • 4 … 20 mA/HART - two-wire 27


6 Set up with the display and adjustment module PLICSCOM

Medium

Liquid

With solids, you can also choose between "Powder/Dust", "Granular/


Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted perfectly to
the product and measurement reliability, particularly in products with
poor reflective properties, is considerably increased.
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Vessel form Apart from the medium, the vessel shape can also influence the
measurement. To adapt the sensor to these measuring conditions,
this menu item offers different options depending on whether liquid
or bulk solid is selected. With "Liquids" these are "Storage tank",
"Stilling tube", "Open vessel" or "Stirred vessel", with "Solid", "Silo" or
"Bunker".
Vessel form

Storage tank

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Damping To suppress fluctuations in the measured value display, e. g. caused


by an agitated product surface, a damping can be set. This time can
be between 0 and 999 seconds. Keep in mind that the reaction time of
the entire measurement will then be longer and the sensor will react
to measured value changes with a delay. In general, a period of a few
seconds is sufficient to smooth the measured value display.
Damping

0 s

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Linearization curve A linearisation is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. in a horizontal cylindri-
cal or spherical tank - and the indication or output of the volume is
required. Corresponding linearisation curves are preprogrammed for
these vessels. They represent the correlation between the level per-
centage and vessel volume. By activating the appropriate curve, the
28776-EN-130417

volume percentage of the vessel is displayed correctly. If the volume


should not be displayed in percent but e.g. in l or kg, a scaling can be
also set in the menu item "Display".
Linearization curve

28 VEGASON 62 • 4 … 20 mA/HART - two-wire


6 Set up with the display and adjustment module PLICSCOM

Linear

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Sensor-TAG In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product des-
ignation. In digital systems and in the documentation of larger plants,
a singular designation should be entered for exact identification of
individual measuring points.
Sensor-TAG

Sensor

With this menu item, the Basic adjustment is finished and you can
now jump to the main menu with the [ESC] key.

False signal suppression High sockets or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls, cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer
taken into account for the level measurement. A false echo memory
should be created with low level so that all potential interfering reflec-
tions can be detected.
False signal suppression

Change now?

Proceed as follows:
1. Move from the measured value display to the main menu by
pushing [OK].
2. Select the menu item "Service" with [->] and confirm with [OK].
Now the menu item "False signal suppression" is displayed.
3. Confirm "False signal suppression - Change now" with [OK] and
select in the below menu "Create new". Enter the actual distance
from the sensor to the product surface. All false signals in this
area are detected by the sensor and saved after confirming with
[OK].
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
echo. The filling level would then no longer be detectable in this area.
28776-EN-130417

Extended setting/Quick The menu item "Extended setting" offers the possibility to optimise
level change VEGASON 62 for applications in which the level changes very quickly.
To do this, select the function "Quick level change > 1 m/min.".

VEGASON 62 • 4 … 20 mA/HART - two-wire 29


6 Set up with the display and adjustment module PLICSCOM

Extended setting

quick level change > 1 m/min.

Note:
Since with the function "Quick level change > 1 m/min." the genera-
tion of an average value of the signal processing is considerably
reduced, false reflections by agitators or vessel installations can
cause measured value fluctuations. A false echo memory is thus
recommended.

Copy sensor data This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:
• Measured value presentation
• Adjustment
• Medium
• Vessel form
• Damping
• Linearization curve
• Sensor-TAG
• Displayed value
• Display unit
• Scaling
• Current output
• Unit of measurement
• Language
The following safety-relevant data are not read out or written:
• HART mode
• PIN
Copy sensor data

Copy sensor data?

Reset Basic adjustment


If the function "Reset" is carried out, the sensor resets the values of
the following menu items to the reset values (see chart):1)
Function Reset value
Sensor address 126
Max. adjustment 0 m(d)
28776-EN-130417

Min. adjustment Meas. range end in m(d)2)


Medium Liquid

1)
Sensor-specific basic adjustment.
2)
Depending on the sensor type, see chapter "Technical data".

30 VEGASON 62 • 4 … 20 mA/HART - two-wire


6 Set up with the display and adjustment module PLICSCOM

Function Reset value


Vessel form not known
Damping 0 s
Linearization Linear
Sensor-TAG Sensor
Displayed value Distance
Current output - characteristics 4 … 20 mA
Current output - max. current 20 mA
Current output - min. current 4 mA
Current output - failure < 3.6 mA
Unit of measurement m(d)
The values of the following menu items are not reset to the reset
values (see chart) with "Reset":
Function Reset value
Backlight No reset
Language No reset
HART mode No reset

Default setting
Like basic adjustment, but in addition, special parameters are reset to
default values.3)

Peak value
The min. and max. distance and temperature values are reset to the
actual value.

Optional settings Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve presentation are shown in the following
menu schematic. You will find a detailed description of these menu
items in the operating instructions manual "Display and adjustment
module".

6.5 Menu plan ultrasonic sensor


Information:
Depending on the version and application, the highlighted menu
windows may not always be available.
28776-EN-130417

3)
Special parameters are parameters which are set customer-specifically on
the service level with the adjustment software PACTware.

VEGASON 62 • 4 … 20 mA/HART - two-wire 31


6 Set up with the display and adjustment module PLICSCOM

Basic adjustment

▶ Basic adjustment 1
Display
Diagnostics
Service
Info

Min. adjustment 1.1 Max. adjustment 1.2 Medium 1.3 Vessel form 1.4
0.00 % 100.00 % Liquid
= = Storage tank
4.000 m(d) 1.000 m(d)
3.000 m(d) 2.000 m(d)

Damping 1.5 Linearization curve 1.6 Sensor-TAG 1.7

0 s Linear Sensor

Display

Basic adjustment 2
▶ Display
Diagnostics
Service
Info

Displayed value 2.1 Display unit 2.2 Scaling 2.3 Backlight 2.4

Scaled Volume 0 % = 0.0 m³ Switched off ▼


m³ 100 % = 100.0 m³

Diagnostics

Basic adjustment 3
Display
▶ Diagnostics
Service
Info

Peak value 3.1 Meas. reliability 3.2 Curve selection 3.3 Echo curve 3.4
Distance min.: 0.234 m(d) 36 dB
Distance max.: 5.385 m(d) Sensor status Echo curve Presentation of the echo
T-min.: 16.5 °C OK curve
T-min.: 37.5 °C
28776-EN-130417

32 VEGASON 62 • 4 … 20 mA/HART - two-wire


6 Set up with the display and adjustment module PLICSCOM

Service

Basic adjustment 4
Display
Diagnostics
▶ Service
Info

False signal suppression 4.1 Extended setting 4.2 Current output 4.3 Simulation 4.4

Change now? None ▼ Characteristic: 4-20 mA ▼ Start simulation?

Fail.mode: < 3.6 mA ▼
Min. current: 3.8 mA ▼

Reset 4.5 Unit of measurement 4.6 Language 4.7 SIL 4.8

Select reset? m(d) ▼ Deutsch ▼ Not activated▼


select?

HART mode 4.9 Copy sensor data 4.10 PIN 4.11

Standard Copy sensor data? Enable?


Address 0

Info

Basic adjustment 5
Display
Diagnostics
Service
▶ Info

Instrument version 5.1 Date of manufacture 5.2 Last change using PC 5.3 Sensor characteristics 5.4
21. January 2009
Software version Display now?
Serial number 3.50 21. January 2009
12345678

6.10 Saving the parameter adjustment data


We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If VEGASON 62 is equipped with a display and adjustment module,
the most important data can be read out of the sensor into the display
and adjustment module. The procedure is described in the operating
instructions manual "Display and adjustment module" in the menu
item "Copy sensor data". The data remain there permanently even if
the sensor power supply fails.
28776-EN-130417

If it is necessary to exchange the sensor, the display and adjustment


module is inserted into the replacement instrument and the data are
written into the sensor under the menu item "Copy sensor data".

VEGASON 62 • 4 … 20 mA/HART - two-wire 33


7 Set up with PACTware and other adjustment programs

7 Set up with PACTware and other


adjustment programs
7.1 Connect the PC via VEGACONNECT
VEGACONNECT directly
on the sensor 2

Fig. 26: Connection of the PC via VEGACONNECT directly to the sensor


1 USB cable to the PC
2 VEGACONNECT
3 Sensor

VEGACONNECT exter-
nally 1 2

3
TWIST
LO
EN

CK
OP

USB
4

Fig. 27: Connection via VEGACONNECT externally


1 I²C bus (com.) interface on the sensor
2 I²C connection cable of VEGACONNECT
3 VEGACONNECT
4 USB cable to the PC

Necessary components:
28776-EN-130417

• VEGASON 62
• PC with PACTware and suitable VEGA DTM
• VEGACONNECT
• Power supply unit or processing system

34 VEGASON 62 • 4 … 20 mA/HART - two-wire


7 Set up with PACTware and other adjustment programs

VEGACONNECT via HART


2 4

CK
LO
TWIST

USB
3

N
OPE
Fig. 28: Connecting the PC via HART to the signal cable
1 VEGASON 62
2 HART resistance 250 Ω (optional depending on processing)
3 Connection cable with 2 mm pins and terminals
4 Processing system/PLC/Voltage supply

Necessary components:
• VEGASON 62
• PC with PACTware and suitable VEGA DTM
• VEGACONNECT
• HART resistance approx. 250 Ω
• Power supply unit or processing system

Note:
With power supply units with integrated HART resistance (internal
resistance approx. 250 Ω), an additional external resistance is not
necessary. This applies, e. g. to the VEGA instruments VEGATRENN
149A, VEGADIS 371, VEGAMET 381. Common Ex separators are
also usually equipped with a sufficient current limitation resistance.
In such cases, VEGACONNECT 4 can be connected parallel to the
4 … 20 mA cable.

7.2 Parameter adjustment with PACTware


Further setup steps are described in the operating instructions
manual "DTM Collection/PACTware" attached to each CD and which
can also be downloaded from our homepage. A detailed description
is available in the online help of PACTware and the VEGA DTMs.
Note:
Keep in mind that for setup of VEGASON 62, DTM-Collection in the
actual version must be used.
All currently available VEGA DTMs are included as a DTM Collection
on a CD. They can be purchased for a token fee from the responsible
VEGA agency. In addition, the actual PACTware version is also avail-
able on this CD.
In addition, this DTM Collection incl. the basic version of PACTware
can be downloaded free of charge from the Internet. Move via www.
28776-EN-130417

vega.com and "Downloads" to "Software".

VEGASON 62 • 4 … 20 mA/HART - two-wire 35


7 Set up with PACTware and other adjustment programs

7.3 Parameter adjustment with AMS™ and PDM


For VEGA sensors, instrument descriptions for the adjustment
programs AMS™ and PDM are available as DD or EDD. The instru-
ment descriptions are already implemented in the current versions of
AMS™ and PDM.
For older versions of AMS™ and PDM, a free-of-charge download is
available via Internet. Move via www.vega.com and "Downloads" to
"Software".

7.4 Saving the parameter adjustment data


It is recommended to document or save the parameter adjustment
data. That way they are available for multiple use or service purposes.
The VEGA DTM Collection and PACTware in the licensed, profession-
al version provide suitable tools for systematic project documentation
and storage.

28776-EN-130417

36 VEGASON 62 • 4 … 20 mA/HART - two-wire


8 Maintenance and fault rectification

8 Maintenance and fault rectification


8.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.

8.2 Rectify faults


Reaction when malfunc- The operator of the system is responsible for taking suitable meas-
tions occur ures to rectify faults.

Failure reasons VEGASON 62 offers maximum reliability. Nevertheless, faults can oc-
cur during operation. These may be caused by the following, e.g.:
• Sensor
• Process
• Voltage supply
• Signal processing

Fault rectification The first measures to be taken are to check the output signals as well
as to evaluate the error messages via the display and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
and the faults rectified this way.

24 hour service hotline Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since
we offer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.

Check the 4 … 20 mA Connect a handmultimeter in the suitable measuring range according
signal to the wiring plan. The following table describes possible errors in the
current signal and helps to remove them:
Error Cause Rectification
4 … 20 mA signal Level fluctuations Set damping via the display and ad-
not stable justment module
4 … 20 mA signal Electrical connec- Check connection according to
missing tion faulty chapter "Connection steps" and if
necessary, correct according to chap-
ter "Wiring plan"
Voltage supply Check cables for breaks; repair if nec-
missing essary
Operating voltage Check, adapt if necessary
28776-EN-130417

too low or load re-


sistance too high

VEGASON 62 • 4 … 20 mA/HART - two-wire 37


8 Maintenance and fault rectification

Error Cause Rectification


Current sig- Electronics mod- Exchange the instrument or send it in
nal greater than ule in the sensor for repair
22 mA or less defective
than 3.6 mA
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
Error messages via the
display and adjustment Error code Cause Rectification
module E013 no measured value –– Sensor in boot phase
available –– Sensor does not find an echo, e.g.
due to faulty installation or wrong
parameter adjustment
E017 Adjustment span too –– Carry out a fresh adjustment and
small increase the distance between min.
and max. adjustment
E036 no operable sensor –– Carry out a software update or send
software instrument for repair
E041 Hardware error, elec- –– Exchange the instrument or send it
tronics defective in for repair

Reaction after fault recti- Depending on the reason for the fault and the measures taken, the
fication steps described in chapter "Set up" may have to be carried out again.

8.3 Exchanging the electronics module


If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module
with respective Ex approval may be used.
If there is no electronics module available on site, one can be ordered
from the VEGA agency serving you.

Sensor serial number The new electronics module must be loaded with the settings of the
sensor. These are the options:
• At the factory by VEGA
• Or on site by the user
In both cases, the sensor serial number is necessary. The serial num-
bers are stated on the type label of the instrument, inside the housing
or on the delivery note.
Information:
When loading on site, first of all the order data must be downloaded
from the Internet (see operating instructions manual "Electronics
module").
28776-EN-130417

Assignment The electronics modules are adapted to the respective sensor and
distinguish also in the signal output or power supply.

8.4 Software update


The software version of VEGASON 62 can be determined as follows:

38 VEGASON 62 • 4 … 20 mA/HART - two-wire


8 Maintenance and fault rectification

• on the type label of the electronics


• Via the display and adjustment module
• via PACTware
You can view all software histories on our website www.vega.com.
Make use of this advantage and get registered for update information
via e-mail.
The following components are required to update the sensor soft-
ware:
• Sensor
• Voltage supply
• VEGACONNECT
• PC with PACTware
• Current sensor software as file

Load sensor software At "www.vega.com/downloads" go to "Software". Select under "plics


to PC sensors and instruments", "Firmware updates" the respective instru-
ment series and software version. Load the zip file via the right mouse
key with "Save target as" e.g. on the desktop of your PC. Move with
the right mouse key to the folder and select "Extract all". Save the
extracted files, for example on the desktop.

Prepare update Connect the signal conditioning instrument to power supply and
provide the connection from the PC to the instrument via the interface
adapter. Start PACTware and go via the menu "Project" to the VEGA
project assistant. Select "USB" and "Set instruments online". Activate
the project assistant with "Start". The assistant establishes the con-
nection automatically and opens the parameter adjustment window
"Sensor # online parameter adjustment". Connect this parameter
adjustment window before you carry out further steps.

Load software into sen- Select with the right mouse key the sensor in the project and go to
sor "Additional function". Then click to "Software update". The window
"Sensor # software update" opens. PACTware checks now the sensor
data and displays the actual hardware and software version of the
sensor. This takes approximately 60 s.
Push the button "Update software" and select the previously extracted
hex file. Then the software update can be started. The additional files
are installed automatically. Depending on the sensor, this procedure
lasts up to 1 h. Then the message appears ""Software update suc-
cessfully executed".

8.5 Instrument repair


If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our Internet homepage
www.vega.com under: "Downloads - Forms and certificates - Repair
28776-EN-130417

form".
By doing this you help us carry out the repair quickly and without hav-
ing to call back for needed information.
• Print and fill out one form per instrument

VEGASON 62 • 4 … 20 mA/HART - two-wire 39


8 Maintenance and fault rectification

• Clean the instrument and pack it damage-proof


• Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
• Please ask the agency serving you for the address of your return
shipment. You can find the respective contact data on our website
www.vega.com under: "Company - VEGA worldwide"

28776-EN-130417

40 VEGASON 62 • 4 … 20 mA/HART - two-wire


9 Dismounting

9 Dismounting
9.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process conditions such
as e.g. pressure in the vessel, high temperatures, corrosive or toxic
products etc.
Take note of chapters "Mounting" and "Connecting to power supply"
and carry out the listed steps in reverse order.

9.2 Disposal
The instrument consists of materials which can be recycled by spe-
cialised recycling companies. We use recyclable materials and have
designed the parts to be easily separable.

WEEE directive 2002/96/EG


This instrument is not subject to the WEEE directive 2002/96/EG and
the respective national laws. Pass the instrument directly on to a spe-
cialised recycling company and do not use the municipal collecting
points. These may be used only for privately used products according
to the WEEE directive.
Correct disposal avoids negative effects on humans and the environ-
ment and ensures recycling of useful raw materials.
Materials: see chapter "Technical data"
If you have no way to dispose of the old instrument properly, please
contact us concerning return and disposal.
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 41


10 Supplement

10 Supplement
10.1 Technical data
General data
Materials, wetted parts
ƲƲ Process fitting, transducer PVDF
ƲƲ Seal transducer/process fitting EPDM, FKM (Viton)
Materials, non-wetted parts
ƲƲ Housing Plastic PBT (polyester), Alu die-casting powder-coated,
316L
ƲƲ Seal between housing and housing NBR (stainless steel housing), silicone (Alu/plastic hous-
cover ing)
ƲƲ Inspection window in housing cover Polycarbonate
ƲƲ Ground terminal 316Ti/316L
Weight 1.8 … 4 kg (4 … 8.8 lbs), depending on the process
fitting and housing
Max. torque mounting boss 25 Nm

Output variable
Output signal 4 … 20 mA/HART
HART output values
ƲƲ HART value (Primary Value) Distance to the level
ƲƲ HART value (Secondary Value) Temperature
ƲƲ HART value (3rd Value) Distance to the level - scaled
Signal resolution 1.6 µA
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Current limitation 22 mA
Load see load diagram under Power supply
Damping (63 % of the input variable) 0 … 999 s, adjustable
Met NAMUR recommendation NE 43

Input variable
Measured variable distance between lower edge of the transducer and
product surface
Measuring range
ƲƲ Liquids up to 8 m (26.25 ft)
ƲƲ Bulk solids up to 3.5 m (11.48 ft)
Dead band 0.4 m (1.312 ft)

Reference conditions to measuring accuracy (according to DIN EN 60770-1)


28776-EN-130417

Reference conditions according to DIN EN 61298-1


ƲƲ Temperature +18 … +30 °C (+64 … +86 °F)
ƲƲ Relative humidity 45 … 75 %
ƲƲ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

42 VEGASON 62 • 4 … 20 mA/HART - two-wire


10 Supplement

Other reference conditions


ƲƲ Reflector ideal reflector, e.g. metal plate 2 x 2 m (6.56 x 6.56 ft)
ƲƲ False reflections Biggest false signal, 20 dB smaller than the useful signal

Measuring characteristics
Ultrasonic frequency 55 kHz
Interval > 2 s (dependent on the parameter adjustment)
Abstrahlwinkel at -3 dB 11°
Adjustment time4) > 3 s (dependent on the parameter adjustment)

Measuring accuracy
Resolution, general max. 1 mm
Deviation5) see diagram

16 mm (0.63 in)

10 mm (0.394 in)

4 mm (0.157 in)

1m 2m 3m 4m 5m 6m 7m 8m
-4 mm (-0.157 in) (9.843 ft) (13.123 ft) (16.404 ft) (19.685 ft) (22.966 ft) (26.247 ft)
(3.28 ft) (6.562 ft)
-10 mm (-0.394 in)

-16 mm (-0.63 in)

Fig. 29: Deviation VEGASON 62

Influence of the ambient temperature to the sensor electronics6)

Average temperature coefficient of the 0.06 %/10 K


zero signal (temperature error)

Ambient conditions
Ambient, storage and transport tempera- -40 … +80 °C (-40 … +176 °F)
ture

Process conditions
Process pressure -20 … 200 kPa/-0.2 … 2 bar (-2.9 … 29 psig)
Process temperature (transducer tem- -40 … +80 °C (-40 … +176 °F)
perature)
Vibration resistance mechanical vibrations with 4 g and 5 … 100 Hz7)
28776-EN-130417

4)
Time to output the correct level (with max. 10 % deviation) after a sudden level change.
5)
Incl. non-linearity, hysteresis and non-repeatability.
6)
Relating to the nominal measuring range.
7)
Tested according to the guidelines of German Lloyd, GL directive 2.

VEGASON 62 • 4 … 20 mA/HART - two-wire 43


10 Supplement

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar


Cable entry/plug8)
ƲƲ Single chamber housing –– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5
or:
–– 1 x closing cap M20 x 1.5; 1 x blind plug M20 x 1.5
or:
–– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
–– 1␣x plug (depending on the version), 1␣x blind stopper
M20␣x␣1.5
ƲƲ Double chamber housing –– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5; 1 x blind plug M16 x 1.5 or
optionally available with 1 x plug M12 x 1 for external
display and adjustment unit
or:
–– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT, 1 x blind
plug M16 x 1.5 or optionally 1 x plug M12 x 1 for exter-
nal display and adjustment unit
or:
–– 1 x plug (depending on the version), 1 x blind plug
M20 x 1.5; 1 x blind plug M16 x 1.5 or optionally avail-
able with 1 x plug M12 x 1 for external display and
adjustment unit
Spring-loaded terminals for wire cross- < 2.5 mm² (AWG 14)
section

Electromechanical data - version IP 66/IP 68 (1 bar)


Cable entry
ƲƲ Single chamber housing 1 x IP 68 cable gland M20 x 1.5; 1 x blind plug M20 x 1.5
ƲƲ Double chamber housing 1␣x IP␣68 cable gland M20␣x␣1.5; 1␣x blind stopper
M20␣x␣1.5; 1␣x blind stopper M16␣x␣1.5
Connection cable
ƲƲ Wire cross-section 0.5 mm² (AWG 20)
ƲƲ Wire resistance < 0.036 Ω/m (0.011 Ω/ft)
ƲƲ Tensile strength < 1200 N (270 lbf)
ƲƲ Standard length 5 m (16.4 ft)
ƲƲ Max. length 1000 m (3280 ft)
ƲƲ Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F)
ƲƲ Diameter approx. 8 mm (0.315 in)
ƲƲ Colour - standard PE Black
ƲƲ Colour - standard PUR Blue
28776-EN-130417

ƲƲ Colour - Ex-version Blue

8)
Depending on the version M12 x 1, according to DIN 43650, Harting, 7/8" FF.

44 VEGASON 62 • 4 … 20 mA/HART - two-wire


10 Supplement

Display and adjustment module


Voltage supply and data transmission through the sensor
Indication LC display in dot matrix
Adjustment elements 4 keys
Protection rating
ƲƲ unassembled IP 20
ƲƲ mounted into the sensor without cover IP 40
Material
ƲƲ Housing ABS
ƲƲ Inspection window Polyester foil

Voltage supply
Operating voltage
ƲƲ Non-Ex instrument 14 … 36 V DC
ƲƲ Ex-ia instrument 14 … 30 V DC
Operating voltage with illuminated display and adjustment module
ƲƲ Non-Ex instrument 20 … 36 V DC
ƲƲ Ex-ia instrument 20 … 30 V DC
Permissible residual ripple
ƲƲ < 100 Hz Uss < 1 V
ƲƲ 100 Hz … 10 kHz Uss < 10 mV
Load see diagram


1000

750

3
500
2
1
250

4
14 16 18 20 22 24 26 28 30 32 34 36 V
Fig. 30: Voltage diagram
1 HART load
2 Voltage limit Ex-ia instrument
3 Voltage limit non-Ex instrument
4 Operating voltage

Electrical protective measures


Protection, depending on housing version
28776-EN-130417

ƲƲ Plastic housing IP 66/IP 67

VEGASON 62 • 4 … 20 mA/HART - two-wire 45


10 Supplement

ƲƲ Aluminium housing, stainless steel IP 66/IP 68 (0.2 bar)9)


housing - investment casting, stain-
less steel housing - electro-polished
ƲƲ Aluminium and stainless housing, in- IP 66/IP 68 (1 bar)
vestment casting (optionally available)
Overvoltage category III
Protection class II

Functional safety (SIL)


Functional safety is already activated on instruments with SIL qualification ex factory. On instru-
ments without SIL qualification ex factory, the functional safety must be activated by the user via
the display and adjustment module or via PACTware for applications according to SIL.

Functional safety according to IEC 61508-4


ƲƲ Single channel architecture (1oo1D) up to SIL2
ƲƲ double channel diversitary redundant up to SIL3
architecture (1oo2D)
You can find detailed information in the supplied Safety Manual of the instrument series or under
"www.vega.com", "Downloads", "Approvals".

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"
and "serial number search" as well as via "Downloads" and "Approvals".

28776-EN-130417

9)
A suitable cable is the prerequisite for maintaining the protection rating.

46 VEGASON 62 • 4 … 20 mA/HART - two-wire


10 Supplement

10.2 Dimensions

Housing in protection IP 66/IP 68 (0.2 bar)


~ 87 mm (3.43")
~ 69 mm
~ 116 mm (4.57") ø 84 mm
(2.72") ø 77 mm
ø 84 mm (3.31") (3.31")
(3.03")
M16x1,5

116 mm (4.57")
112 mm (4 13/32")

120 mm (4.72")
M20x1,5/ M20x1,5/ M20x1,5
½ NPT ½ NPT
M20x1,5/
1 2 ½ NPT 3

~ 59 mm ~ 69 mm ~ 87 mm (3.43")
(2.32") (2.72") ø 84 mm
ø 80 mm ø 77 mm
(3.15") (3.03") (3.31")

M16x1,5
117 mm (4.61")

120 mm (4.72")
112 mm (4.41")

M20x1,5/ M20x1,5/
½ NPT ½ NPT
M20x1,5/
4 5 ½ NPT 6

Fig. 31: Housing versions in protection IP 66/IP 68 (0.2 bar) - with integrated display and adjustment module the
housing is 9 mm/0.35 in higher
1 Plastic housing
2 Aluminium housing
3 Aluminium double chamber housing
4 Stainless steel housing, electropolished
5 Stainless steel housing - precision casting
6 Stainless steel double chamber housing - precision casting
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 47


10 Supplement

Housing in protection IP 66/IP 68 (1 bar)


~ 103 mm ~ 105 mm (4.13")
~ 150 mm (5.91") (4.06") ø 84 mm
ø 77 mm
ø 84 mm (3.31") (3.03") (3.31")

M16x1,5

116 mm (4.57")

117 mm (4.61")

120 mm (4.72")
M20x1,5 M20x1,5 M20x1,5

M20x1,5/
1 2 ½ NPT 3

Fig. 32: Housing versions in protection IP␣66/IP␣68 (1␣bar) - with integrated display and adjustment module the
housing is 9␣mm/0.35␣in higher
1 Aluminium housing
2 Stainless steel housing - precision casting
2 Stainless steel double chamber housing - precision casting

VEGASON 62
20mm (25/32")

60mm
153mm (6 1/32")

(2 23/64")
G2A /
2"NPT
(2 31/64")
63mm

1 2
ø 50mm
(1 31/32")
ø 74mm
(2 58/64")

Fig. 33: VEGASON 62


1 Dead zone: 0.4 m (1.312 ft)
2 Measuring range: with liquids up to 8 m (26.25 ft), with solids up to 3.5 m (11.48 ft)
28776-EN-130417

48 VEGASON 62 • 4 … 20 mA/HART - two-wire


10 Supplement

10.3 Industrial property rights


VEGA product lines are global protected by industrial property rights. Further information see
www.vega.com.
Only in U.S.A.: Further information see patent label at the sensor housing.
VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.
Nähere Informationen unter www.vega.com.
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec-
tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.
VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus-
trial. Para mayor información revise la pagina web www.vega.com.
Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную
собственность. Дальнейшую информацию смотрите на сайте www.vega.com.
VEGA系列产品在全球享有知识产权保护。
进一步信息请参见网站<www.vega.com>。

10.4 Trademark
All the brands as well as trade and company names used are property of their lawful proprietor/
originator.
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 49


Notes

28776-EN-130417

50 VEGASON 62 • 4 … 20 mA/HART - two-wire


Notes
28776-EN-130417

VEGASON 62 • 4 … 20 mA/HART - two-wire 51


Printing date:

All statements concerning scope of delivery, application, practical use and operat-
28776-EN-130417

ing conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice

© VEGA Grieshaber KG, Schiltach/Germany 2013

VEGA Grieshaber KG Phone +49 7836 50-0 Tel: +44 (0)191 490 1547
Fax: +44 (0)191 477 5371
Am Hohenstein 113 Fax +49 7836 50-201 Email: northernsales@thorneandderrick.co.uk
77761 Schiltach E-mail: info.de@vega.com Website: www.heattracing.co.uk
Germany www.vega.com www.thorneanderrick.co.uk

You might also like