98 Contents
Contents
4 INSTALLATION................................................................................................ 4-1
5 CONNECTING-UP............................................................................................ 5-1
9 CERTIFICATES................................................................................................ 9-1
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 1
10.98 Definitions and Warnings
DANGER For the purpose of this documentation and the product warning labels,
"Danger" indicates death, severe personal injury or substantial property
damage will result if proper precautions are not taken.
WARNING For the purpose of this documentation and the product warning labels,
"Warning" indicates death, severe personal injury or property damage
can result if proper precautions are not taken.
CAUTION For the purpose of this documentation and the product warning labels,
"Caution" indicates that minor personal injury or material damage can
result if proper precautions are not taken.
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 1-1
Definitions and Warnings 10.98
NOTE This documentation does not purport to cover all details on all types of
the product, nor to provide for every possible contingency to be met in
connection with installation, operation or maintenance.
Should further information be desired or should particular problems
arise which are not covered sufficiently for the purchaser’s purposes,
the matter should be referred to the local SIEMENS sales office.
The contents of this documentation shall not become part of or modify
any prior or existing agreement, commitment or relationship. The sales
contract contains the entire obligation of SIEMENS AG. The warranty
contained in the contract between the parties is the sole warranty of
SIEMENS AG. Any statements contained herein do not create new
warranties or modify the existing warranty.
6SE7087-6NP87-2DD0 Siemens AG
1-2 Operating Instructions SIMOVERT MASTERDRIVES
10.98 Definitions and Warnings
1. General 4. Installation
In operation, drive converters, depending on their degree The installation and cooling of the appliances shall be in
of protection, may have live, uninsulated, and possibly accordance with the specifications in the pertinent
also moving or rotating parts, as well as hot surfaces. documentation.
In case of inadmissible removal of the required covers, of The drive converters shall be protected against
improper use, wrong installation or maloperation, there is excessive strains. In particular, no components must be
the danger of serious personal injury and damage to bent and/or isolating distances altered in the course of
property. transportation or handling. No contact shall be made with
For further information, see documentation. electronic components and contacts.
All operations serving transport, installation and Drive converters contain electrostatic sensitive
commissioning as well as maintenance are to be carried components which are liable to damage through
out by skilled technical personnel (observe IEC 364 or improper use. Electronic components must not be
CENELEC HD 384 or DIN VDE 0100 and IEC Report mechanically damaged or destroyed (potential health
664 or DIN VDE 0110 and national accident prevention risks).
rules). 5. Electrical connection
For the purposes of these basic safety instructions, When working on live drive converters, the applicable
"skilled technical personnel" means persons who are national accident prevention rules (e.g. VBG 4) must be
familiar with the installation, mounting, commissioning complied with.
and operation of the product and have the qualifications
needed for the performance of their functions. The electrical installation shall be carried out in
accordance with the relevant requirements (e.g. cross-
2. Intended use sectional areas of conductors, fusing, PE connection).
Drive converters are components designed for inclusion For further information, see documentation.
in electrical installations or machinery. Instructions for the installation in accordance with EMC
In case of installation in machinery, commissioning of the requirements, such as screening, grounding, location of
drive converter (i.e. the starting of normal operation) is filters and wiring, are contained in the drive converter
prohibited until the machinery has been proved to documentation. They must always be complied with, also
conform to the provisions of the EC directive 89/392/EEC for drive converters bearing a CE marking. Observance
(Machinery Safety Directive - MSD). Account is to be of the limit values required by the EMC law is the
taken of EN 60204. responsibility of the manufacturer of the installation or
machine.
Commissioning (i.e. the start of normal operation) is
admissible only where conformity with the EMC directive 6. Operation
(89/336/EEC) has been established. Installations which include drive converters shall be
The drive converters meet the requirements of the low- equipped with additional monitoring and protective
voltage directive 73/23/EEC. They are subject to the devices in accordance with the relevant applicable safety
harmonized standards of the series prEN 50178/DIN requirements, e.g. Act respecting technical equipment,
VDE 0160 in conjunction with EN 60439-1/DIN VDE accident prevention rules, etc. Changes to the drive
0660 Part 500 and EN 60146/DIN VDE 0558. converters by means of the operating software are
permissible.
The technical data as well as information concerning the
supply conditions shall be taken from the rating plate and After disconnection of the drive converters from the
from the documentation and shall be strictly observed. voltage supply, live appliance parts and power terminals
must not be touched immediately because of possibly
3. Transport, storage energized capacitors. In this regard, the corresponding
signs and markings on the drive converter must be
The instructions for transport, storage and proper use
respected.
shall be complied with.
During operation, all covers and doors shall be kept
The climatic conditions shall be in conformity with prEN
closed.
50178.
7. Maintenance and servicing
The manufacturer’s documentation shall be followed.
Keep these safety instructions in a safe place!
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 1-3
10.98 Description
2 Description
Range of application The capacitor module is essentially made up of capacitors. It is
connected to the DC link and is used for short-time storage of energy
which is fed back into the DC link when the drives are decelerated. This
energy is then available for subsequent accelerations. The capacitor
module limits the rise of the DC link voltage and smooths it additionally.
Buffer capacitors, pre-charging resistors and a DC link fuse are
accommodated in the capacitor module. Pre-charging is effected
through an additional connection to the AC/rectifier unit and is
monitored by this unit.
The capacitor module does not require a 24 V supply.
C’
C’
Pre-charging
D’
D’
C/L+
DC link
D/L-
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 2-1
10.98 Transport, Storage, Unpacking
NOTE If the storage period of one year is exceeded, the unit must be newly
formed. See Section ”Forming".
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 3-1
10.98 Installation
4 Installation
WARNING Safe converter operation requires that the equipment is mounted and
commissioned by qualified personnel taking into account the warning
information provided in these Operating Instructions.
The general and domestic installation and safety regulations for work
on electrical power equipment (e.g. VDE) must be observed as well as
the professional handling of tools and the use of personal protective
equipment.
Death, severe bodily injury or significant material damage could result if
these instructions are not followed.
Clearances The units can be mounted flush with each other.
In order to ensure an adequate supply of cooling air, a clearance of 100
mm must be left at the top of the unit and at the bottom of the unit
respectively to components which may considerably affect the flow of
cooling air.
Requirements at the ♦ Foreign particles
point of installation The units must be protected against the ingress of foreign particles
as otherwise their function and operational safety cannot be
ensured.
♦ Dust, gases, vapors
Equipment rooms must be dry and dust-free. Ambient and cooling
air must not contain any electrically conductive gases, vapors and
dust which could diminish the functionality. If necessary, filters
should be used or other corrective measures taken.
♦ Cooling air
The units must only be operated in an ambient climate in
accordance with DIN IEC 721-3-3 Class 3K3. For cooling air
temperatures of more than 45 °C (113 °F) and installation altitudes
higher than 1000 m, derating is required.
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 4-1
Installation 10.98
Mounting
surface
100 mm
Cooling air
100 mm
Fig. 4-1 Minimum clearances for cooling
250 mm
360 mm
414 mm
45 mm
90 mm
220 mm
Front view
Side view (without front panel)
6SE7087-6NP87-2DD0 Siemens AG
4-2 Operating Instructions SIMOVERT MASTERDRIVES
10.98 Connecting-up
5 Connecting-up
WARNING If the capacitor module has been in storage for longer than one year or
has been continuously switched off, the capacitors must be newly
formed. Please refer to the section "Forming" in this regard.
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 5-1
Connecting-up 10.98
Pre-charging X7
DC link bus
X3 PE3
module
−
+
SIEMENS
6SE7087-6NP87-2DD0 Siemens AG
5-2 Operating Instructions SIMOVERT MASTERDRIVES
10.98 Connecting-up
X3 - DC link bus The DC link bus module is used to transfer energy between the
module capacitor module and the connected inverters.
Bar Designation Meaning Range
3 PE3 Protective conductor connection
2 D / L- DC link voltage - DC 510 - 650 V
1 C / L+ DC link voltage + DC 510 - 650 V
Connectable cross-section: “Electro-plated copper" 3x10 mm, rounded
off according to DIN 46433.
Bar 1 is at the front when installed.
X7 - Pre-charging The connections are used for pre-charging the buffer capacitors.
The two remaining free contacts are used for looping the pre-charging
cable to other capacitor modules.
Terminal Meaning Range
C’ C’ D’ D’
NOTES ♦ During operation, the full DC link voltage is always present at the
terminals for pre-charging the capacitor module.
♦ During pre-charging, the charging current of all connected capacitor
modules flows via the terminals.
♦ For reasons of protection, cables with 4 mm² Cu must be used at
connection X7!
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 5-3
10.98 Forming
6 Forming
If a unit has been non-operational for more than one year, the DC link
capacitors have to be newly formed. If this is not carried out, the unit
can be damaged when the line voltage is powered up.
If the unit was started-up within one year after having been
manufactured, the DC link capacitors do not have to be re-formed. The
date of manufacture of the unit can be read from the serial number.
3 AC 400 V R
C / L+
A C
D / L-
DC link DC link
Forming fuse
PE3
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 6-1
Forming 10.98
WARNING The unit has hazardous voltage levels up to 5 minutes after it has been
powered down due to the DC link capacitors. The unit or the DC link
terminals must not be worked on until at least after this delay time.
Procedure ♦ Before you form the DC link capacitors, the unit must be removed or
the front and middle DC link bus module must be taken out.
♦ Connect the required components in accordance with the circuit
example.
♦ Energize the forming circuit. The duration of forming is dependent
on the idle time of the capacitor module.
Forming time
6
in hours
5
2
Off-circuit idle
1
time in years
1 2 3 4 5
Fig. 6-2 Forming time as a function of the capacitor module idle time
6SE7087-6NP87-2DD0 Siemens AG
6-2 Operating Instructions SIMOVERT MASTERDRIVES
10.98 Technical Data
7 Technical Data
EU low-voltage directives EN 50178
73/23/EEC and RL93/68/EEC
EU directive EMC 89/336/EEC EN 61800-3
EU machine directive EN 60204-1
89/392/EEC
Approval UL: E 145 153
CSA: LR 21 927
Type of cooling Air cooling with built-in fan
Permissible ambient and cooling-
medium temperature
• during operation 0° C to +45° C ( 32° F to 113° F)
• during storage -25° C to +70° C (-13° F to 158° F)
• during transport -25° C to +70° C (-13° F to 158° F)
Installation altitude ≤ 1000 m above sea level (100 % load capability)
> 1000 m to 4000 m above sea level
(for load capability. see Fig. "Derating curves")
Permissible humidity rating Relative humidity ≤ 95 % during transport and storage
≤ 85 % during operation (moisture
condensation not permissible)
Climatic class Class 3K3 to DIN IEC 721-3-3 (during operation)
Degree of pollution Pollution degree 2 to IEC 664-1 (DIN VDE 0110. Part 1).
Moisture condensation during operation is not permissible
Overvoltage category Category III to IEC 664-1 (DIN VDE 0110. Part 2)
Degree of protection IP20 EN 60529
Class of protection Class 1 to EN 536 (DIN VDE 0106. Part 1)
Shock protection to EN 60204-1 and DIN VDE 0106 Part 100 (VBG4)
Radio interference suppression to EN 61800-3
• Standard No radio interference suppression
• Options Radio interference suppression filter for Class B1 or A1 to EN 55011
Interference immunity Industrial to EN 61800-3
Paint finish For interior installation
Mechanical specifications
- Vibrations to DIN IEC 68-2-6
During stationary use:
Constant amplitude
• of deflection 0.075 mm in the frequency range 10 Hz to 58 Hz
• of acceleration 9.8 m/s² in the frequency range > 58 Hz to 500 Hz
During transport:
• of deflection 3.5 mm in the frequency range 5 Hz to 9 Hz
• of acceleration 9.8 m/s² in the frequency range > 9 Hz to 500 Hz
- Shocks to DIN IEC 68-2-27 / 08.89
30 g, 16 ms half-sine shock
- Drop and topple to DIN IEC 68-2-31 / 04.84
on a surface and on a corner
Table 7-1 General data
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 7-1
Technical Data 10.98
80
70
60
0 1000 2000 3000 m 4000
Installation altitude above sea level
6SE7087-6NP87-2DD0 Siemens AG
7-2 Operating Instructions SIMOVERT MASTERDRIVES
10.98 Environmental Friendliness
8 Environmental Friendliness
Environmental The number of components has been significantly reduced over earlier
aspects during the converter series by the use of highly integrated components and the
development modular design of the complete series. Thus, the energy requirement
during production has been reduced.
Special significance was placed on the reduction of the volume, weight
and variety of metal and plastic components.
Environmental The unit can be broken down into recyclable mechanical components
aspects for disposal as a result of easily releasable screw and snap connections.
The plastic components are to DIN 54840 and have a recycling symbol.
Units can be disposed of through certified disposal companies.
Addresses are available from your local Siemens partner.
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 8-1
10.98 Certificates
9 Certificates
Confirmation Erlangen,15.09.1998
This equipment fulfills the protection requirements against electric shock according to
DIN VDE 0106 Part 100 when the following safety rules are observed:
• Service work in operation is only permissible on a unit which is not live.
• The converter must be switched into a no-voltage condition and isolated from the
supply when replacing any part/component.
• All panels and the DC link terminals must be closed during operation.
The local operating regulations (e.g. EN 50110-1, EN 50110-2) must be observed when
operating the equipment.
A&D DS A P1
Mickal
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 9-1
Certificates 10.98
1) See rating plate for complete type designation, serial number and technical data
A&D DS A PE D P
Schlögel
6SE7087-6NP87-2DD0 Siemens AG
9-2 Operating Instructions SIMOVERT MASTERDRIVES
10.98 Certificates
Factory certificate *
regarding electromagnetic compatibility
When correctly used, the designated product fulfills all the requirements of
Directive 89/336/EEC regarding electromagnetic compatibility.
We confirm the conformance of the above designated product with the Standards:
EN 61800-3 10-1996
EN 61000-4-2 (old IEC 801-2)
EN 61000-4-4 (old IEC 801-4)
EN 61000-4-5 (old IEC 801-5)
IEC 1000-4-3 (old IEC 801-3)
Note:
These instructions relating to EMC-correct installation, correct operation,
connecting-up conditions and associated instructions in the product
documentation supplied must be observed.
1) See rating plate for complete type designation, serial number and technical data
Erlangen, 15.09.1998
H. Mickal
A&D DS A P1 *) Acc. to EN 10204 (DIN 50049)
A&S DS 4102x Copyright () SIEMENS AG 1997 All rights reserved Page 1 of 1
Siemens AG 6SE7087-6NP87-2DD0
SIMOVERT MASTERDRIVES Operating Instructions 9-3
Bisher sind folgende Ausgaben erschienen: Ausgabe interne Sachnummer
The following versions have been published so far: Version Internal item number
AA 475 903 4070 76 J AA-74
AB A5E00085346
We reserve the right to make changes to functions, technical data, standards, drawings and
parameters.