Nuggets
Nuggets
Nuggets
1 2 3 4 5 6
7 GENERATOR GENERATOR MOTOR GENERATOR GENERATOR GENERATOR
NO. 1 NO. 2 NO. 3 NO. 4 NO. 5
ORIGINAL READINGS
BRG. 1 BRG 2 BRG 3 BRG 4 BRG 5 BRG 6 BRG 10
H 7.8 45 DEG 5.4 45 DEG .8 80 DEG 1.5 220 DEG 1.7 253 DEG 2.1 245 DEG 2.6 260 DEG
V 10.3 50 9.1 50 9.7 45 8.6 47 5.6 63 2.5 107 5.1 180
BALANCE SHOT ADDED TO No. 1 GENERATOR 8.25 OZ at 310 DEGREES
H 5.9 37 3.9 35 .6 45 .8 270 .9 270 .8 270 1.1 45
V 11.0 45 9.6 45 10.1 36 8.8 40 5.4 45 1.1 117 5.9 200
installed,Horizontals went
UNCOUPLED GENERATORS 1 & 2 FROM MOTOR
H 6.8 25 4.5 34 1.0 350 1.6 270 1.8 270 2.0 243 2.7 236
V 7.9 68 6.5 63 6.6 45 5.9 45 3.8 45 1.9 45 1.8 270
CASE HISTORY: A STATIC BALANCE SHOT IN THE END PLANES WAS INSTALLED
ON A HIGH PRESSURE TURBINE ROTOR WITH A BOW. 18 OZ WERE ADDED IN
EACH END, WITH ALMOST NO EFFECT. WHEN WEIGHT WAS ADDED IN THE MID
SPAN, THE ROTOR WAS EASILLY BALANCED.
3: When balancing 2 pole
motors which are above 1000
HP, beware of thermal
vectors. This class of rotor will
operate well uncoupled, but
will often have high levels of
vibration when pulling full
current. This is because the
rotor can bow as a function of
heating by the current flow.
Corpoven Refinery
Venezuela
4: During a startup, if a high speed compressor
has low response as it passes through its
critical, but the level increases steadily with
RPM, without much of a phase shift, then
suspect unbalance in the coupling. On a polar
plot, the response line will point straight outward
because the amplitude increases without any
shift in phase.
COMPRESSOR WITH UNBALANCE IN COUPLING
PROBE
45 315
COUPLING IS OVERHUNG
PHASE
90 270
UNBALANCE IN COUPLING AFTER BEFORE
MAGNITUDE
135 225
1 2 3 4 5 6
7 GENERATOR GENERATOR MOTOR GENERATOR GENERATOR GENERATOR
NO. 1 NO. 2 NO. 3 NO. 4 NO. 5
ORIGINAL READINGS
BRG. 1 BRG 2 BRG 3 BRG 4 BRG 5 BRG 6 BRG 10
H 7.8 45 DEG 5.4 45 DEG .8 80 DEG 1.5 220 DEG 1.7 253 DEG 2.1 245 DEG 2.6 260 DEG
V 10.3 50 9.1 50 9.7 45 8.6 47 5.6 63 2.5 107 5.1 180
BALANCE SHOT ADDED TO No. 1 GENERATOR 8.25 OZ at 310 DEGREES
H 5.9 37 3.9 35 .6 45 .8 270 .9 270 .8 270 1.1 45
V 11.0 45 9.6 45 10.1 36 8.8 40 5.4 45 1.1 117 5.9 200
NOTE !- LEVELS WENT DOWN IN THE HORIZONTAL DIRECTION, BUT UP IN THE VERTICAL DIRECTION
UNCOUPLED GENERATORS 1 & 2 FROM MOTOR
H 6.8 25 4.5 34 1.0 350 1.6 270 1.8 270 2.0 243 2.7 236
V 7.9 68 6.5 63 6.6 45 5.9 45 3.8 45 1.9 45 1.8 270
NOTE THAT EVEN UNCOUPLED, GENERATOR NO. 1 IS OPERATING WITH ALMOST 8 MILS OF VIBRATION
PERFORMED RESONANCE TEST- STRUCTURE FOUND TO BE OPERATING NEAR RESONANCE
ADDED 50 OZ BALANCE WEIGHT TO MOTOR , ALL LEVELS DROPPED TO BELOW 3 MILS.
6: Do not attempt to balance when the phase
is moving. This is a sign that there is a rub.
Machines that operate below a critical tend
to bow into the rub and the rub gets worse
with time. Machines that operate above a
critical can bow away from the rub causing
the phase angle to continually move against
rotation. Note that if a above critical
machine has a light rub, it can be a bad idea
to shut it down, because then it will have to
coast down through its critical speed.
7: When the horizontal and vertical
phase are the same or 180 degrees
out, then look for rocking or a loose
base. Another thing to consider is that
if a machine is operating between a
vertical and horizontal natural
frequency then his can also cause
unusual phase relationships between
the vertical and horizontal directions.
6 CASES OF LOOSENESS
Case History 1- The phase on a turbine bearing
was identical in the vertical and axial directions
with the axial vibration being very high. It was
discovered that one of the hold down bolts was
broken off beneath the surface of the concrete
allowing the bearing to rock.
Case 2- On a large fan, the horizontal and vertical vibration phase
angles were identical. The base bolts were loose allowing the bearing to
rock. The maintenance manager did not believe it so a cup of water was
poured on the base next to the bearing. When the water alternately shot
out from between the bearing housing and the base plate, he agreed to
have the bolts tightened. The horizontal vibration dropped from 12 mils
to less than 2 mils.
CASE 3- A power plant had spent $30000 on a mill motor trying to
get the vibration levels reduced. The rotor had been balanced
several times, but the amplitude was still high.
APPARENT COUPLE UNBALANCE IN A
FAN THAT OPERATES BELOW 1st
NATURAL FREQUENCY
POSSIBLE CAUSES
DISSIMILAR PEDESTAL STIFFNESES
– WRONG PLACEMENT OF VIBRATION PICKUPS
– LOOSE BASE BOLTS
– PHASE REVERSAL WITHIN ONE PICKUP
Vectors showed
what appeared
to be a large
amount of
couple
unbalance
SOLUTION
• The large couple component raised the level of
suspicion.
• The results of a previous balance person showed
the response to be highly non-linear
• The base bolt tightness was therefore checked
and all the bolts were all found to be significantly
loose.
• The bolts were tightened, the couple component
disappeared and the levels dropped to 1/4th their
original values.
• Following bolt tightening, the fan was then easily
balanced.
PLUNGER BOLT HOLDS BEARING TIGHT WITHIN HOUSING.
Loose fit
between bowl
and drive shaft
LARGE POWER
GENERATION GAS
TURBINES
• A different sort of an animal
• Balancing Cross effects are often
much larger than direct influence.
DIRECT AND CROSS
EFFECT
WESTINGHOUSE 100
MW 501 GT
Exhaust End Shot on Exhaust End 18.6 oz/mil 25 Degree lag
Exhaust End Shot on Compressor End 4.7 oz/mil 46 degree lag
CONDENSER
VIBRATION SPECTRUM
MAP PLOT
16 MIL
DIFFERENTIAL
DISCUSSION
VACUUM DRAW DOWN COMBINED WITH THERMAL
DIFFERENTIAL GROWTH UNLOADED BEARING CAUSING
IT TO GO UNSTABLE. WHEN BOTH WERE COLD,
IT WOULD BE STABLE. WHEN BOTH WERE HOT,
IT WOULD BE STABLE. THE PROBLEM OCCURRED
AFTER A TRIP, WHEN THE THINNER LP SECTION
WOULD COOL DOWN QUICKER THAN THE THICK
HP SECTION. THIS DIFFERENTIAL ADDED TO THE
VACUUM DRAW DOWN WAS TOO MUCH.
BEARING METAL TEMPERATURE
CONFIRMED THIS FINDING.
SOLUTION
TILT PAD
BEARING
FINAL RESULTS
. Case 2- Two boiler feed pumps were having vibration problems and
wearing out their gear couplings. When dynamic alignment was
performed between the turbines and pumps, it was discovered that
when vacuum was pulled on the turbines that they dropped .020”
relative to the pumps.
COUPLINGS BEING DESTROYED ON STEAM
GENERATOR FEED PUMP AT NUCLEAR
STATION
VIBRATION SPECTRUM
5.8 Mils of 2X
VIBRATION
ORBIT DISPLAY
PROBLEM-ALIGNMENT
SPEC. WAS WRONG
• Vacuum draw down was 20 mils
• Even though pump was center
mounted, it was growing.
• Turbine was growing unevenly
TURBINE
CHILLER
MONITORING OF
ALIGNMENT
MACHINE LAYOUT
COMPRESSOR
TURBINE
EXPANSION JOINT
TEST RESULTS
COMPRESSOR
TURBINE
EXPANSION JOINT
DIAL INDICATORS SHOWED THAT
THERE WAS NO MOVEMENT
ACROSS JOINT
ACTUAL PROBLEM
LASER
MOUNTED ON
BEAM When compressor started up,
this pipe cooled down causing
LASER compressor to rock back. This
MOUNTED ON
made turbine appear to drop
COMPRESSOR
down relative to compressor.
TURBINE
3: If a machine operates well for a few weeks following an overhaul,
then 2X running speed shows up in the proximity probe spectrum,
suspect a locked coupling. The amount of misalignment may not have
changed. The problem is that either the coupling grease has broken
down or escaped from the coupling.
PUMPS
LOMAKIN EFFECT
N0=.0914, N10=.027
Time decay in g’s. Note
PSI=1/10*1/(2*PI)*ln(.0914/.027)=.0194
the presence of higher
Q=1/(2*.0194)= 25.7 frequency in time plot.
AMPLIFICATION FACTOR CALCULATION USING LOG
DEC APPROACH WITH ANALOG INTEGRATION
Time plot is in
displacement. Note that
no high frequencies are
present.
6: Long time samples are useful when low
frequency beats are present.
4.55
ROUTE SPECTRUM
3.5 components
23-JUN-99to phase
4.40
13:11:40
3.0
2.5
together so worse
OVRALL= 4.15 D-DG
P-P = 4.13
2.0 case can
LOAD =be
100.0seen.
4.71
4.94
RPM = 360.
5.07
1.5
RPS = 6.00
1.0
0.5
0
2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5
Frequency in Hz
Displacement in Mils
6
ROUTE WAVEFORM
4 23-JUN-99 13:11:40
P-P = 4.31
2
PK(+) = 3.93
0 PK(-) = 3.96
CRESTF= 2.60
-2
-4
-6
Time: 8.848
0 2 4 6 8 10 12 14 16 18 20 Ampl: 3.931
Time in Seconds
9: If a signal is clipped, then this effectively introduces a DC shift
into the data. This can prove disastrous if the data is then
integrated. Example:
A high output accelerometer was used to measure vibration on a
pump. The signal was integrated into velocity. Unfortunately, the
pump cavitated. The cavitation overloaded the accelerometer’s
electronics introducing a DC shift. The overall output of the pump
then fictitiously read several inches per second and all the alarms
went off. Source: Jack Frarey
10: When trying to separate two closely spaced
signals, remember that the frequency resolution is not
the number of lines divided by Fmax. It is not even
the number of lines divided by Fmax X the weighting
window factor. It is actually the number of lines
divided by Fmax X the widow factor X 2. If the factor
of 2 is not included, then the modulating effect of the
window function can create false sidebands that are
mistaken for actual frequencies. Source: Jack Frarey
A BEAT THAT COMPLETES ONE CYCLE DURING TIME BLOCK-
CENTERED IN BUFFER
Amplitude .6 units.
Note false resolution
caused by Hanning
Window.
11: When viewing a spectrum and time plot, there
are often times when things do not seem to add up.
For instance, the spectrum may show low levels
and generate no concern. On the other hand, the
time plot might show very high amplitudes. One
reason for this is the fact that the time based data
was sampled at a frequency that is equivalent to
2.56 Fmax. According to the Nyquist sampling law,
this is sufficient to pick up frequencies at 1.28
Fmax. This means that the time data can see
higher frequencies than are displayed in the
spectral plot. Example: When viewing data from a
motor, the spectrum showed nothing over .03
in/sec. In the acceleration time plot levels as high
as 8 g’s were observed. The maximum frequency
was set at 1000 HZ. The actual problem was that
the 1750 RPM motor had rotor bars generating a
signal just above 1000 HZ . The vibration was
visible in the time plot, but was beyond the 1000 Hz
Fmax, so it was not seen in the spectrum.
Solution: When this type of situation is
encountered, then increase the Fmax.
12: A similar discrepancy can occur when analog
overall levels are compared to spectral data or overall
values computed from the spectral data. The analog
overall value includes energy all the way out to say
20000 Hz. The digital overall value only includes those
components that are in the calculated spectrum. If there
is a discrepancy, then as stated in the previous topic,
increase the Fmax to determine what is causing the
difference.
RESONANCE
1: When performing a resonance test,
if a peak shows up at the frequency of
interest, but the phase shift is small,
then this is an indication that there is
a resonant component that may be
located some distance from where the
test is being performed. For instance
if a section of pipe is tested for a
resonance and there is a peak, but a
small phase shift, then there might be
for example a nearby control valve
that is resonant. If the control valve
itself is tested, then the normal 180
degree phase shift would be present
when its natural frequency is excited.
RESONANCE TEST ON VERTICAL PUMP WHERE
PUMP IS RESONANT AT RUNNING SPEED AND
RESPONSE WAS MEASURED ON MOTOR
3600 CPM
RESONANCE
2: When anchor bolts or rebar break under the
surface of concrete, this reduction in stiffness
can alter the natural frequency and result in
resonance problems. Case History- Three
identical pumps were installed. On one pump,
the 120HZ vibration on the motor was several
times higher than on the other two. When the
motor positions were swapped, the problem
always occurred in the same location, indicating
that problem was location related instead of
motor related. A resonance test showed that
there was a resonance near 120 Hz at the
location with the high levels, but not at the other
two locations. When the foundation was broken
up, it was discovered that the re-bar was broken
in the foundation that had the problem.
3. When doing impact tests, beware of
trying to get too much resolution. For
instance, if you have a vertical pump that
has a suspected resonance at 10 HZ and
you choose a 100 HZ Fmax with 800 lines of
resolution, then the sample time is 8
seconds. If the response decays away in 1
second, then there will be 7 seconds of
noise present versus 1 second of good data.
The phase shift will look rough and the
coherence will be low. If on the other hand a
500 Hz Fmax and 400 lines of resolution are
chosen, then the sample time will be .8
seconds. In this instance, the data will be
much cleaner.
4: The opposite situation could also be
true. If a lightly damped component is
excited then it may continue to ring clear to
the end of the time block. This can cause
problems when the FFT is performed
because a discontinuity is introduced. In
this case an exponential weighting factor
may need to be introduced to drive the
response to zero and eliminate the
discontinuity. It has to be noted that if a
log decrement calculation is made on data
that has been modified by an exponential
weighting factor that the answers will be
wrong.
Solution- Use exponential weighting factor
when viewing spectrum, but shut it off
when viewing the time domain.
5: A convenient way to locate support beams in a floor is to perform an
impact test and look for a reversal in the direction of the imaginary
components.
INDUCTION MOTOR CURRENT
TESTING
1: When taking spectrum of the current, measure the
ratio of the lower number of poles times slip frequency
side band in dB to the level of the line frequency current
in dB . If there are no other recommendations, then use
the 54-45dB rule. If the side band is more than 54 dB
below the line frequency signal, then the rotor is
probably OK. If the side band is less than 45 dB below
the line frequency, then the rotor is probably bad.
NOTE DATE IS
1982
2: Beware of cast aluminum
rotors. Cast aluminum rotors
will sometimes have voids
that will cause false positives
of the above described side
band test. When in doubt,
test the motor over several
starting cycles to determine if
the level is stable or getting
worse.
3: Pole modulation- If the number of spiders in
the rotor equals the number of poles, the current
will modulate and look just like a broken rotor bar
is present. The way to tell if this is the case is to vary the load
on the motor. If it is pole modulation, then the side band ratio will
be higher at low load. If there is an actual broken bar problem, the
opposite will be true. When a broken bar is present the degree of
modulation will increase at higher loads. Case History- A power
plant had 8 pole motors on its FD fans. Every year a current
spectrum test was performed to identify broken rotor bars. It was
noted both FD fan motors had indications of what appeared to be
broken rotor bars. The interesting thing was that the modulation
was less at high loads than at low loads. The cause of the
modulation turned out to be pole modulation. The motors ran for
many years and never had any problems, even though an expert
system program kept calling them out as having broken rotor
bars.
4: Mechanical Modulation- Beware of motor current testing, if
there is a speed reduction gearbox coupled to the motor. Low
speed mechanical modulation will sometimes cause the current
to modulate thereby mimicking a rotor problem. Always
determine the motor speed to within 1 RPM, then calculate the
number of poles times slip frequency side band frequency. If
there is any variation in the calculated versus the actual
frequency, then suspect mechanical modulation. Examples:
Case 1: Coal barge unloader. The rate at which the buckets dug
into the barge of coal was exactly the number of motor poles
times the slip frequency making it impossible to perform an
accurate rotor bar analysis.
Case 2- In large coal mills, the
rate at which the rolls pass over
the rotating table is very close to
the number of poles times the
slip frequency. This has resulted
in several mill motors being
falsely called out as having bad
rotor bars.
Case 3- A coal conveyor motor was
called out as having rotor problems. It
was discovered that the speed of the
output gear was close to the number of
poles times the slip frequency. The
problem was with the gear instead of with
the motor rotor. Very accurately
determining the speed of the motor
allowed a calculation to be made that
determined that the modulating
frequency was a match with the gear
instead of the number of poles times the
slip frequency.
5: Two pole and four pole motors with broken
rotor bars will often cause number of poles times
slip frequency side bands in both the current and
vibration spectra. Higher pole lower speed
motors, particularly those driving high inertia
loads will create number of poles times slip side
bands in the current spectra, but will in many
cases not cause them to appear at all in the
vibration spectra.
INDUCTION MOTORS
VIBRATION TESTING
1: Rotor eccentricity- An eccentric rotor will of course result in
unbalance. If the rotor is balanced, there can still be a problem of a
rotating deviation in the air gap. This causes unequal pull on the
rotor as the magnetic poles pass the rotating gap deviation. This
occurs at the number of poles times the slip frequency, which is the
same frequency that is generated by a broken rotor bar. Note that
in neither case will this low (usually less than 1.5 HZ) frequency
show up in the spectrum, but they can both appear as side bands of
running speed in the vibration spectrum. The way to tell the
difference between an eccentric rotor and broken rotor bars is to
obtain a current spectrum. A broken rotor bar will generate no.
poles times slip frequency around the line frequency in the current
spectrum where as the eccentric rotor will not.
Current
sidebands are
over 60dB
down
ECCENTRIC ROTOR
Distinct No.
Poles X slip
sidebands in
vibration
spectrum
2: New high
efficiency
motors are
much more
susceptible to
soft foot than
older heavy
frame motors.
3: Large 2 pole motors that have shorted laminations can have very high
levels of thermal vectors that cause the amount of unbalance to vary with
load. Case History- A 4000 Hp motor in a power plant was overhauled.
After the overhaul, the motor vibration would increase and the bearings
would be destroyed. The plant sent the motor back to the motor shop for
balancing, but upon return, it again wiped out the bearings.
The motor was then sent to the manufacturer to be balanced in a high
speed balance pit. Upon return, it again wiped out the bearings. Solution-
Proximity probes were installed on the motor and the amplitude and
phase were monitored as the motor was loaded. The motor had an 8 mil
thermal vector. The motor was compromise balanced and ran for several
years. It was discovered that the original motor shop that overhauled the
motor had dropped the rotor and damaged some of the laminations. The
eddy current heating in the shorted laminations had caused the rotor to
bow thereby causing the large thermal vector. If this condition is
suspected, induction heating the rotor then looking at it with an infrared
camera will allow the hot spots to be seen.
DC MOTORS
1: D.C. MOTORS- The spectrum of the current to
a D.C. Motor can be used to find problems with
SCRs or firing circuits. The rectifier input supply
frequency (50 or 60 HZ) times 6 for 3 phase full
wave rectifiers will normally be present in the
current spectrum. When 1/3 or 2/3 of the firing
frequency is present, it indicates failed SCRs or
firing circuits. It is much simpler to look at the
current spectrum or current waveform than to try to
see the problem with vibration. Vibration is a
secondary effect reflecting the problem which is
actually of electrical origin.
½ HALF WAVE RECTIFIER
WHAT DOES THE
CURRENT PATTERN OF A
NORMAL DRIVER LOOK
LIKE
6 PULSES IN 1/60th OF A SECOND
WHAT DOES THE
WAVEFORM OF A BAD
DRIVE LOOK LIKE ?
BAD
BAD
SCR’S
120 HZ
GOOD
GOO
SCR’S
D
F E B R U A R Y 18, 1998
V IS Y F A N P U M P D R IV E
250 A M P LO A D
W H E N S C R ’S W E R E R E P L A C E D , T H E W A V E FO R M A N D SP E C T R U M R E T U R N E D T O
NORM AL.
1 2 0 H Z is
NOTE PRESENT
V A R IA T IO N IN A L O N G W IT H
H E IG H T O F SO M E 60H Z
PEAK S. COM PONENT
360 H Z SC R
F IR IN G
FREQUENCY
2: D.C. MOTORS- The current spectrum from a D.C.
Motor can also be used to find tuning problems with
D.C. Drives. Improperly tuned drives will produce
frequencies at the oscillation rate of the instability.
These frequencies can also appear in the vibration
spectra and are very difficult to analyze since they do
not have a mechanical origin. These oscillation
frequencies are unpredictable. They are a result of the
interaction between the rotating inertias of the
mechanical components, the torsional stiffness
of the shafts and the tuning of the electrical control
system. If a completely unexplainable frequency
appears on a drive, then it may well be due to this
complex interaction.
BAD TUNING, WHERE
SPEED IS CONSTANTLY
MOVING UP AND DOWN.
BADLY ADJUSTED NORMAL
DRIVE SPECTRUM
ONLY 360 HZ
OVERHEATING 180
DEG.
F
DRIVE INSTABILITY
AFTER TUNING
SOMETIMES THE
PROCESS CAN CAUSE THE
DRIVE TO APPEAR
UNSTABLE
3: DC MOTORS- Unknown frequencies
in the spectrum of the current going to a
DC drive can originate from other
mechanical equipment in the drive train.
Case History- The current on a couch
roll of a paper machine had an unknown
component in its spectrum. It turned out
to be the vane pass frequency of the fan
pump located several yards away in the
basement. The fan pump was causing
pressure pulsations in the head box
that caused the paper to be deposited in
varying thicknesses. As the thicker
material passed over the vacuum rolls,
this caused the tension to increase
which changed the tangential force on
the couch roll which in turn caused the
current draw to the couch roll to
modulate at that rate.
COUCH ROLL DRIVE
7 MILS OF VIBRATION
AT 240
CYCLES/MINUTE
BUILDING LAYOUT
FAN ROOM FAN ROOM
OPEN ATRIUM
VIBRATING
WINDOW
LOOSE COIL
FAN DISCHARGE TO ATRIUM
1.0
TEST - I.U. FOUNDATION BUILDING
I.U. BLDG -P01 POINT 1
Route Spectrum
FIRING
11-JAN-00 09:29:40
FREQUENCY OF
37.94
OVRALL= .9600 V-DG
0.8 PK = .9550
LOAD = 100.0
FURNACE IS 33
RPM = 3600.
PK Velocity in In/Sec RPS = 60.00
0.6
0.4
HZ
0.2
0
Freq: 37.81
0 60 120 180 240 300 Ordr: .630
Frequency
TEST in Hz
- I.U. FOUNDATION BUILDING Spec: .751
I.U. BLDG -P01 POINT 1
0.40
0.35
Analyze Spectrum
11-JAN-00 14:00:30
PK = .4147
Response of 3 foot
diameter window in
LOAD = 100.0
0.30 RPM = 3600.
RPS = 60.00
PK Velocity in In/Sec
0.25
0.20
watch tower
0.15
to impact 33 hz.
0.10
0.05
0
Freq: 32.50
0 100 200 300 400 500 600 Ordr: .542
Frequency in Hz Spec: .273
More Bad Luck
Natural frequency of large window
equals pulse frequency creating a
gigantic subwoofer 3 feet in
diameter.
INSTALLED
BETTER
MUFFLERS
TEST TECHNIQUES
1: Don’t forget to use a strobe light- In the past Strobe lights were
used frequently due to fact that they were utilized to obtain the phase
readings. Their use will almost certainly remain relevant as long as
there is rotating equipment. Strobe lights are still the best way to
looks at belts or to see if the elements in a coupling have cracked.
They can also be used to determine the size of a key or locate a
keway or look at balance weights. Strobes that are triggered by the
vibration signal are useful to freeze the rotating element that is
causing the vibration. Case History- A paper mill was going to
remove a roll to get it balanced. The frequency of the vibration
matched the frequency that the group of wire rolls was
vibrating at. This was determined by a calculation of the RPM
of the roll base upon the roll diameter and the product’s speed.
A strobe fired by the vibration was used to verify that the roll
was the source. To everyone’s surprise, the strobe froze a
different roll. It turned out that the drawings had incorrect
diameters. The strobe didn’t lie or care about drawings, it just froze
the correct component.
2. Phase locked loop strobes with a phase delay
are very useful for providing a once per
revolution output that can be used for balancing.
The use of a phase lock strobe can make it
unnecessary to stop a machine so that photo-
reflective tape can be installed. This can save
hours of time on a balance job, particularly when
a machine is limited to the number of starts that
is can go through.
3: Don’t forget shaft sticks- While it
would be great to have proximity probes
on every machine to measure shaft
motion, in the real world this is just not
the case. A shaft stick can measure the
absolute motion of a shaft. Note, before
using a shaft stick, use the strobe
mentioned in point 1 to make sure there
is not a keyway where the shaft stick is
to be placed against the shaft.
4: It is handy to have an analog integration box for certain tests that
allow the time waveform from an accelerometer to be viewed in
displacement. Case 1- Two large vertical pumps had resonant
frequencies near their operating speed. One of the calculations that
were needed was to determine the damping so the amplification
factor could be obtained. By using an analog integrator, the time
waveform of the low frequency response could be directly measured
and used for the log decrement calculation. Case 2- Foundries have
low frequency vibratory conveyors that move the castings throughout
the plant. These often cause vibration problems beyond the plant
boundaries that result in complaints by neighbors. These conveyors
which operate around 5 HZ move in and out of phase with one
another causing the vibration levels to vary significantly with time. If a
spectrum is taken of one snapshot in time, the overall value is hard to
obtain. It is much easier to look at the motion in the time domain over
a period of several seconds. The maximum peak to peak motions
that people offsite are feeling can them be easily determined.
If analog integration is available, then a long term time plot of the
motion in displacement is very useful in determining the maximum
levels of motion that are being experienced.
Vibratory conveyors that were shaking houses ½
mile from foundry. Calculated Peak-Peak 4.1 mils.
Actual P-P over 7 mils. People feel much higher
levels than spectrum indicates.
DALT - DINING ROOM TABLE AT RHODES
P-P Displacement in Mils
4.55
3.5 ROUTE SPECTRUM
4.40
23-JUN-99 13:11:40
3.0 OVRALL= 4.15 D-DG
2.5 P-P = 4.13
2.0 LOAD = 100.0
4.71
4.94
RPM = 360.
5.07
1.5
RPS = 6.00
1.0
0.5
0
2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5
Frequency in Hz
Displacement in Mils
6
ROUTE WAVEFORM
4 23-JUN-99 13:11:40
P-P = 4.31
2
PK(+) = 3.93
0 PK(-) = 3.96
CRESTF= 2.60
-2
-4
-6
Time: 8.848
0 2 4 6 8 10 12 14 16 18 20 Ampl: 3.931
Time in Seconds
5: A microphone with an analog output that can be used to
supply a signal to a spectrum analyzer can be very useful
in the analysis of vibrations that are transmitted by the air
rather than through solid material. Note that most
microphones have a pretty severe roll of below 20Hz, so
the true pressure pulsation amplitude may not be present
at a lower frequency. The spectral data can still however
be used to identify the problem.
6: If a temporary shaft rider is needed, then Ebelon rod
works well. Ebelon is graphite impregnated Teflon and it
will last a significant amount of time in contact with a
reasonably smooth shaft.
Some Final Thoughts
A vibration analyst must understand the
basic laws of physics (F=ma and F=kx and
that dynamic stiffness is different than
static stiffness). They must also
understand signal processing so they do
not get bad data. They must have an
appreciation for human nature so they can
get the truth out of mechanics and
operations personnel. They need to
understand how fans motors, gear boxes,
compressors, pumps and turbines work.
But most of all they must be able to put all
these things together under adverse
conditions and then be able to think clearly
and arrive at a logical conclusion.