Nothing Special   »   [go: up one dir, main page]

Digsi 5 Quick Notes DIGSI-5-QN0011: Using Excel To Modify Settings

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DIGSI 5 QUICK NOTES

DIGSI-5-QN0011: Using Excel to modify settings:

DIGSI 5 ‘TEA-X’ plug-in, allows DIGSI 5 device settings to be imported/exported between DIGSI 5 and
Microsoft Excel (2007 SP3 or later).

TEA-X is XML-based data (TEA-X = Totally integrated Energy Automation eXchange).

TEA-X is a feature ideal for:


 Engineers who want human readable settings in an ‘open format’ to be include in a settings reports.
 Organisations who have a standard design/settings scheme, and want others without DIGSI 5 access
to be able to review/update setting values.

The TEA-X plug-in for Excel can be downloaded from the Siemens website. Please also download the Readme
file which provides instruction on installation. Operation instructions are included within the Excel plug-in.

Using the following link, select the Downloads Tab, Software, then the version of DIGSI 5 you are using).
http://w3.siemens.com/smartgrid/global/en/products-systems-solutions/Protection/Engineering-
Evaluation-Diagnostic-Software/Pages/DIGSI-5.aspx

Note:
 Only the current setting group is transferred
 The engineering sequence supported is based on the workflow where:
1) The TEA-X file is exported from a DIGSI 5 project
2) It is imported into Excel where the settings are viewed/modified
3) The settings are exported from Excel back into the same TEA-X file (modifying it)
4) The TEA-X file is imported back into the same DIGIS 5 project, implementing the changes

QUICK GUIDE TO: Export TEA-X file from DIGSI 5

1) Select the ‘project’ if you wish to export


settings for all devices, or select the specific
‘relay’ if you wish to export just those settings
2) Right mouse click and select Export
3) Select TEA-X format and follow prompts

HV Power File: DIGSI-5-QN0011v1 Using Excel to modify settings.docx Page 1 of 2 Originator: Warwick Beech
Version 1. May 2017

HV Power Measurements & Protection Ltd Tel: +64-9- 377 2001


Unit 4, 1 Porters Ave, Eden Terrace, Auckland Fax: +64-9- 302 2142
P O Box 26-074, Epsom, Auckland 1030, New Zealand
QUICK GUIDE TO: Import TEA-X file into Excel

1) Select the TEA-X plug-in


2) Select Import
3) Select the directory where
the .teax file is located
4) Select the device from the
project to be imported (if
there is only one device in
the .teax file, this still
needs to be selected
5) Import

QUICK GUIDE TO: Export the TEA-X file from Excel

To export the TEA-X information from Excel, it must be exported back into the same TEA-X file it was
imported from (thereby updating it).

QUICK GUIDE TO: Import the TEA-X file into DIGSI 5

The TEA-X file should only be imported back into the original device setting file it was created from.

HV Power File: DIGSI-5-QN0011v1 Using Excel to modify settings.docx Page 2 of 2 Originator: Warwick Beech
Version 1. May 2017

HV Power Measurements & Protection Ltd Tel: +64-9- 377 2001


Unit 4, 1 Porters Ave, Eden Terrace, Auckland Fax: +64-9- 302 2142
P O Box 26-074, Epsom, Auckland 1030, New Zealand