Operator's Manual: Line Distance Protection IED REL 670
Operator's Manual: Line Distance Protection IED REL 670
Operator's Manual: Line Distance Protection IED REL 670
WE RESERVE ALL RIGHTS TO THIS DOCUMENT, EVEN IN THE EVENT THAT A PATENT IS
ISSUED AND A DIFFERENT COMMERCIAL PROPRIETARY RIGHT IS REGISTERED. IMPROPER
USE, IN PARTICULAR REPRODUCTION AND DISSEMINATION TO THIRD PARTIES, IS NOT
PERMITTED.
THIS DOCUMENT HAS BEEN CAREFULLY CHECKED. HOWEVER, IN CASE ANY ERRORS ARE
DETECTED, THE READER IS KINDLY REQUESTED TO NOTIFY THE MANUFACTURER AT THE
ADDRESS BELOW.
THE DATA CONTAINED IN THIS MANUAL IS INTENDED SOLELY FOR THE CONCEPT OR
PRODUCT DESCRIPTION AND IS NOT TO BE DEEMED TO BE A STATEMENT OF GUARAN-
TEED PROPERTIES. IN THE INTERESTS OF OUR CUSTOMERS, WE CONSTANTLY SEEK TO
ENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATEST TECHNOLOGICAL STAN-
DARDS. AS A RESULT, IT IS POSSIBLE THAT THERE MAY BE SOME DIFFERENCES BETWEEN
THE HW/SW PRODUCT AND THIS INFORMATION PRODUCT.
Manufacturer:
ABB Power Technologies AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Contents
Chapter Page
Warnings.............................................................................................. 8
Overview............................................................................................ 14
Keypad............................................................................................... 15
Key activated screens........................................................................ 17
The Help screen ........................................................................... 17
The Reset screen ......................................................................... 17
LCD.................................................................................................... 18
Small............................................................................................. 18
Medium ......................................................................................... 18
LED.................................................................................................... 19
Status indication LEDs ................................................................. 19
Indication LEDs ............................................................................ 19
How to navigate ................................................................................. 21
Read ............................................................................................. 21
Change ........................................................................................ 21
Control .......................................................................................... 21
Overview............................................................................................ 24
Contents
Overview ............................................................................................ 28
View analog primary values ............................................................... 29
Overview....................................................................................... 29
View analog secondary values .......................................................... 30
Overview....................................................................................... 30
........................................................................................................... 31
...................................................................................................... 31
mA input module (MIM) ........................................................... 31
Signal matrix for mA inputs (SMMI) ......................................... 31
View monitoring values ...................................................................... 32
...................................................................................................... 32
Voltage phasors............................................................................ 32
Current sequence component ...................................................... 32
Voltage sequence component ...................................................... 32
Three phase busbar protection (zone A) ...................................... 32
Three phase busbar protection (Zone B)...................................... 33
Single phase busbar protection (Zone A) ..................................... 33
Single phase busbar protection (Zone B) ..................................... 33
View metering values......................................................................... 34
Identify a disturbance......................................................................... 38
View disturbance record details ......................................................... 39
View general information .............................................................. 39
View disturbance indications ........................................................ 39
View event recordings .................................................................. 39
View trip values............................................................................. 39
Recalculate distance to fault......................................................... 39
Trigger a disturbance report manually ............................................... 40
TimeSynchDSTEnd ................................................................. 42
TimeZone ................................................................................ 43
General settings................................................................................. 44
Power system ............................................................................... 44
Overview.................................................................................. 44
Identifiers ................................................................................. 44
Primary values......................................................................... 44
Three phase analog group ...................................................... 44
Three phase analog summation group.................................... 44
Communication............................................................................. 44
Overview.................................................................................. 44
TCP-IP .................................................................................... 45
SPA, LON and IEC 60870–5–103 settings.............................. 45
LDCM ...................................................................................... 46
Station communication ............................................................ 47
Analog modules ............................................................................ 48
Overview.................................................................................. 48
Analog modules....................................................................... 48
I/O modules ............................................................................. 48
HMI ............................................................................................... 48
Overview.................................................................................. 48
LEDs........................................................................................ 49
Screen .................................................................................... 49
Functions ................................................................................. 49
Reference channel service values........................................... 49
Change lock............................................................................. 49
Control .......................................................................................... 49
Overview.................................................................................. 49
Bay control (QCBAY)............................................................... 49
Reservation input (RESIN) ...................................................... 50
Bay reserve (QCRSV) ............................................................. 50
Switch controller (SCSWI) ....................................................... 50
Circuit breaker (SXCBR) ......................................................... 50
Circuit switch (SXSWI) ............................................................ 50
Local/Remote switch (LocalRemote, LocRemControl)............ 50
Control commands ....................................................................... 51
Single command...................................................................... 51
Selector switch (GGIO)............................................................ 51
Monitoring ..................................................................................... 51
Overview.................................................................................. 51
Current phasors....................................................................... 51
Voltage phasors....................................................................... 51
Current sequence components (MSQI)................................... 51
Voltage sequence components (MSQI)................................... 52
Disturbance report (RDRE) ..................................................... 52
Binary signals .......................................................................... 52
Analog signals ......................................................................... 52
Fault locator (RFLO)................................................................ 52
Generic measured value ......................................................... 52
Event function.......................................................................... 53
Binary signal status report ....................................................... 53
IEC 60870–5–103.................................................................... 53
Metering........................................................................................ 53
Contents
Overview.................................................................................. 53
Pulse counter logic (GGIO)...................................................... 53
Setting group N .................................................................................. 54
Overview....................................................................................... 54
Differential protection.................................................................... 54
Overview.................................................................................. 54
High impedance differential protection (PDIF, 87X) ................ 54
Distance protection ....................................................................... 54
Overview.................................................................................. 54
Distance protection zones (PDIS, 21)...................................... 54
Phase selection with load encroachment (PDIS, 21)............... 54
Directional impedance (RDIR) ................................................. 55
Power swing detection (RPSB, 78).......................................... 55
Automatic switch onto fault logic (PSOF) ................................ 55
Current protection ......................................................................... 55
Overview.................................................................................. 55
Instantaneous phase overcurrent protection (PIOC, 50) ......... 55
Four step phase overcurrent protection (POCM, 51/67).......... 55
Instantaneous residual overcurrent protection (PIOC, 50N).... 56
Four step residual overcurrent protection (PEFM, 51N/67N) .. 56
Thermal overload protection,
one time constant (PTTR, 26) ........................................ 56
Breaker failure protection (RBRF, 50BF)................................. 56
Stub protection (PTOC, 50STB) .............................................. 56
Pole discordance protection (RPLD, 52PD) ............................ 56
Voltage protection......................................................................... 57
Overview.................................................................................. 57
Two step undervoltage protection (PUVM, 27)........................ 57
Two step overvoltage protection (POVM, 59).......................... 57
Two step residual overvoltage protection (POVM, 59N).......... 57
Frequency protection .................................................................... 57
Overview.................................................................................. 57
Underfrequency protection (PTUF, 81).................................... 57
Overfrequency protection (PTOF, 81) ..................................... 58
Rate-of-change frequency protection (PFRC, 81) ................... 58
Multipurpose protection ................................................................ 58
Overview.................................................................................. 58
General current and voltage protection (PGPF) ...................... 58
Secondary system supervision ..................................................... 58
Overview.................................................................................. 58
Current circuit supervision (RDIF) ........................................... 58
Fuse failure supervision (RFUF).............................................. 59
Control .......................................................................................... 59
Overview.................................................................................. 59
Synchrocheck and energizing check (RSYN, 25).................... 59
Autorecloser (RREC, 79) ......................................................... 59
Selector switch (SSGGIO) ....................................................... 59
Scheme communication ............................................................... 59
Overview.................................................................................. 59
Scheme communication logic
for distance protection (PSCH, 85) ....................................... 60
Current reversal and weak-end infeed logic
for distance protection (PSCH, 85) .......................................... 60
Contents
Overview............................................................................................ 68
IED test mode .................................................................................... 70
View binary input values .................................................................... 71
Overview....................................................................................... 71
Binary Input Module (BIM)....................................................... 71
Signal matrix for binary input (SMBI)....................................... 71
View binary output values.................................................................. 72
Overview....................................................................................... 72
Binary Output Module (BOM) .................................................. 72
Signal matrix for binary outputs (SMBO) ................................. 72
Function test modes .......................................................................... 73
Distance protection ....................................................................... 73
Current protection ......................................................................... 73
Scheme communication ............................................................... 73
Voltage communication ................................................................ 73
Frequency protection .................................................................... 73
Multipurpose protection ................................................................ 73
Secondary system protection ....................................................... 74
Control .......................................................................................... 74
Control .......................................................................................... 74
Logic ............................................................................................. 74
Function status .................................................................................. 75
Overview....................................................................................... 75
View differential protection values ................................................ 75
Contents
Overview............................................................................................ 92
Read measured values and check apparatus status.................... 92
Locating and using the single line diagram................................... 92
Control screen messages ............................................................. 94
Reset guide........................................................................................ 96
Reset LEDs................................................................................... 96
Start and trip LEDs .................................................................. 96
All indication LEDs................................................................... 96
Reset lockout ................................................................................ 96
Reset counters.............................................................................. 96
Reset autorecloser .................................................................. 96
Circuit breaker ......................................................................... 96
Circuit switch ........................................................................... 97
Event counter .......................................................................... 97
Reset pulse counter................................................................. 97
LDCM clear counters ............................................................... 97
Reset temperature functions......................................................... 97
Glossary........................................................................................... 104
About this chapter Chapter 1
Introduction
Chapter 1 Introduction
1
Introduction to the operator’s manual Chapter 1
Introduction
en06000097.vsd
The Application Manual (AM) contains application descriptions, setting guidelines and setting
parameters sorted per function. The application manual should be used to find out when and for
what purpose a typical protection function could be used. The manual should also be used when
calculating settings.
The Technical Reference Manual (TRM) contains application and functionality descriptions
and it lists function blocks, logic diagrams, input and output signals, setting parameters and tech-
nical data sorted per function. The technical reference manual should be used as a technical ref-
erence during the engineering phase, installation and commissioning phase, and during normal
service.
The Installation and Commissioning Manual (ICM) contains instructions on how to install
and commission the protection IED. The manual can also be used as a reference during periodic
testing. The manual covers procedures for mechanical and electrical installation, energizing and
checking of external circuitry, setting and configuration as well as verifying settings and per-
forming directional tests. The chapters are organized in the chronological order (indicated by
chapter/section numbers) in which the protection IED should be installed and commissioned.
The Operator’s Manual (OM) contains instructions on how to operate the protection IED dur-
ing normal service once it has been commissioned. The operator’s manual can be used to find
out how to handle disturbances or how to view calculated and measured network data in order
to determine the cause of a fault.
The IED 670 engineering guide (EG) contains instructions on how to engineer the IED 670
products. The manual guides to use the different tool components for IED 670 engineering. It
also guides how to handle the tool component available to read disturbance files from the IEDs
on the basis of the IEC 61850 definitions. The third part is an introduction about the diagnostic
tool components available for IED 670 products and the PCM 600 tool.
2
Introduction to the operator’s manual Chapter 1
Introduction
• The chapter “Safety information” presents warnings and notices, which the user
should pay attention to.
• The chapter “Overview” describes operations an operator may perform on a daily
basis or when the need arises.
• The chapter “Understand the local human-machine interface” describes how to
use the human-machine interface.
• The chapter “Understand the HMI tree” describes the different menu trees.
• The chapter “Read measured values” describes how to locate and identify avail-
able measurement data.
• The chapter “Event list” describes the location and nature of recorded events.
• The chapter “Handle disturbances” describes how to retrieve disturbance infor-
mation and reset alarms.
• The chapter “Read and change settings” describes how to locate, and change set-
tings and parameters.
• The chapter “Diagnose IED status” describes the location and use of available
diagnostic tools.
• The chapter “Test the IED” describes the tests applicable to the IED.
• The chapter “Control and supervise the bay” describes how to use the Single
Line Diagram to open and close primary apparatuses.
• The chapter “Reset” describes resetting procedures.
• The chapter “Authorization”describes user categories and password procedures.
• The chapter “Glossary” describes words and acronyms used in the literature de-
scribing the IED.
This manual does not contain any instructions for commissioning or testing.
1.3.2 Requirement
The operator must be trained in and have a basic knowledge of how to operate protection equip-
ment. The manual contains terms and expressions commonly used to describe this kind of equip-
ment.
3
Introduction to the operator’s manual Chapter 1
Introduction
4
Introduction to the operator’s manual Chapter 1
Introduction
Revision Description
A First revision, addition of SPA protocol, LON protocol, IEC 60870-5-103 protocol,
authorization feature, name changes and menu reorganization.
5
Introduction to the operator’s manual Chapter 1
Introduction
6
About this chapter Chapter 2
Safety information
7
Warnings Chapter 2
Safety information
1 Warnings
Warning!
Do not touch circuitry during operation. Potentially lethal voltages and currents are present.
Warning!
Always connect the IED to protective earth, regardless of the operating conditions. This also
applies to special occasions such as bench testing, demonstrations and off-site configuration.
Operating the IED without proper earthing may damage both IED and measuring circuitry and
may cause injuries in the event of an accident.
Warning!
Never remove any screw from a powered IED or from a IED connected to powered circuitry.
Potentially lethal voltages and currents are present.
Warning!
Always avoid touching the circuitry when the cover is removed. The product contains electronic
circuitries which can be damaged if exposed to static electricity (ESD). The electronic circuit-
ries also contain high voltage which is lethal to humans.
8
About this chapter Chapter 3
Overview
Chapter 3 Overview
9
Operator overview Chapter 3
Overview
1 Operator overview
The Human machine interface (HMI) on the IED provides an ideal mechanism for the day to day
operation and even advanced use of the IED. The keypad, LCD and LEDs on the front of the
IED are what constitute the HMI. Troubleshooting, apparatus control, monitoring, setting and
configuring are all possible via this interface. Through the screens and menu elements available,
as well as the keypad, the user is able to navigate throughout the menu structure and move from
screen to screen. This document is, to a great extent, arranged in the same way as the IED soft-
ware is structured and describes all aspects of operation via the HMI.
The operator can document disturbances so that their causes can be analyzed and evaluated for
future reference. For example, the fault currents and voltages at the time of the fault can be doc-
umented. The operator can also retrieve data about protected objects, providing further informa-
tion for fault analysis. This implies viewing the mean value of current, voltage, power and
frequency or primary and secondary measured phasors. The operator can check the IED status
at any time.
In some cases the operator may need to change the way the IED operates. This might include
changing the active setting group or a parameter value. This must always be done strictly accord-
ing to applicable regulations because un-authorized changes may lead to severe damage of the
protected object especially if a fault is not properly disconnected.
10
Identify the IED Chapter 3
Overview
The type of IED, the main function type, its serial number, ordering number and production date
are found here.
11
Identify the IED Chapter 3
Overview
12
About this chapter Chapter 4
Understand the local
human-machine interface
13
Overview Chapter 4
Understand the local
human-machine interface
1 Overview
The human machine interface is used to monitor and to some extent control the way the IED op-
erates. The configuration designer can add functions that alert to events requiring the attention
of the operator.
Figure 1: 1/2 x 19” case and 1/1 x 19” case with small and medium LCDs
14
Keypad Chapter 4
Understand the local
human-machine interface
2 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look and feel in
all IEDs in the IED 670 series. LCD screens and other details may differ but the way the keys
function is identical. The keypad is illustrated in figure 2.
The keys used to operate the IED are described below in table 1.
The help key brings up two submenus. Key operation and IED information.
Opens the main menu, and used to move to the default screen.
15
Keypad Chapter 4
Understand the local
human-machine interface
Key Function
The Local/Remote key is used to set the IED in local or remote control mode.
The E key starts editing mode and confirms setting changes when in editing mode.
The right arrow key navigates forward between screens and moves right in editing mode.
The left arrow key navigates backwards between screens and moves left in editing mode.
The up arrow key is used to move up in the single line diagram and in menu tree.
The down arrow key is used to move down in the single line diagram and in menu tree.
16
Key activated screens Chapter 4
Understand the local
human-machine interface
• General operation
The General Operation submenu provides information about the IED keypad.
The I an O keys are used to open (OFF) and close (ON) breakers and disconnectors when using
the Single Line Diagram (SLD) in direct control situations.
• Reset LEDs
• Reset counters
• Reset BBP trip
• Reset BBP open CT
The Reset LEDs submenu consists of two lower level menus which are the “Start and trip LEDs”
and “All indication LEDs” submenus. To reset a counter, the actual counter must first be select-
ed. The submenus and the their structures are discussed in the “Reset” chapter of this document.
17
LCD Chapter 4
Understand the local
human-machine interface
4 LCD
4.1 Small
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19” case. The LCD on the small HMI
measures 32 x 90 mm and displays 7 lines with up to 40 characters per line. The first line dis-
plays the product name and the last line displays date and time. The remaining 5 lines are dy-
namic. This LCD has no graphic display potential.
4.2 Medium
The 1/2, 3/4 and 1/1 x 19” cases can be equipped with the medium size LCD. This is a fully
graphical monochrome LCD which measures 120 x 90 mm. It has 28 lines with up to 40 char-
acters per line. To display the single line diagram, this LCD is required.
18
LED Chapter 4
Understand the local
human-machine interface
5 LED
The LED module is a unidirectional means of communicating. This means that events may occur
that activate a LED in order to draw the operators attention to something that has occurred and
needs some sort of action.
There are alarm indication LEDs and hardware associated LEDs on the right hand side of the
front panel. The alarm LEDs are found to the right of the LCD screen. They can show steady or
flashing light. Flashing would normally indicate an alarm. The alarm LEDs are configurable us-
ing the PCM 600 tool. This is because they are dependent on the binary input logic and can there-
fore not be configured locally on the HMI. Some typical alarm examples follow:
The RJ45 port has a yellow LED indicating that communication has been established between
the IED and a computer.
19
LED Chapter 4
Understand the local
human-machine interface
The Local/Remote key on the front panel has two LEDs indicating whether local or remote con-
trol of the IED is active.
20
How to navigate Chapter 4
Understand the local
human-machine interface
6 How to navigate
6.1 Read
To read values and access information about the objects being monitored the operator must nav-
igate the menu tree using the arrow keys. The active submenu or value is highlighted.
Navigation is as follows:
6.2 Change
To change a parameter setting the following steps should be followed:
6.3 Control
The HMI offers the operator the opportunity to exercise direct local control over breakers and
other apparatuses in the bay using the graphic display and designated keys on the front panel of
the IED.
By pressing the L/R key until the uppermost of the two LEDs next to the key lights up, local
operator control can be exercised from the HMI.
An apparatus is selected using the up and down arrow keys. The active apparatus is highlighted
in the display.
21
How to navigate Chapter 4
Understand the local
human-machine interface
22
About this chapter Chapter 5
Understand the HMI tree
23
Overview Chapter 5
Understand the HMI tree
1 Overview
The root of the HMI tree is the main menu and consists of the following submenus:
• Control
• Measurements
• Events
• Disturbance records
• Settings
• Diagnostics
• Test
• Reset
• Authorization
• Language
Each submenu is in turn made up of several other submenus. The overall structure is illustrated
in figure 3.
24
Overview Chapter 5
Understand the HMI tree
Main Menu
IED Test
Mode
Analog
Primary Time Reset LEDs
Disturbance LED Test
Values
1
General
IED Status Display
Analog Settings Reset
Station Disturbance Test English
Secondary counters Admin.
Matrix 2 Internal
Values Event List Group N
Events Binary Optional
Settings Reset BBP User
Commands Disturbance Output Test Lang.
trip
n
Activate
Function
Monitoring Setting Reset BBP
Manual Trig Status
Group open CT
Function
Test Modes
Single Monitoring
Command
Function
Selector Current Status
General
Switch Phasors
Information IED Status
Diff.Prot.
General Group N
BBPBay
Indications Settings General Settings
3 Phase BBPZoneA
Setting
3ph Current
Event Protection, Product Protection, Group
BBPBay
Recording control and Identifiers control and Selection
1 Phase BBPZoneB
monitoring monitoring
3ph Control
Trip Values functions Installed functions
Switchgear
HW
Status BBPZoneA Monitor
1ph
etc.
BBPZoneB
1ph
en06000140.vsd
25
Overview Chapter 5
Understand the HMI tree
26
About this chapter Chapter 6
Read measured values
27
Overview Chapter 6
Read measured values
1 Overview
The measurement menu contains primarily analog measurement data. External signals can also
be viewed as they are or as they appear in the Signal Matrix Tool (SMT). These signals are a
virtual representation of the hard wired signals on the various inputs and outputs. The SMT is
only accessible via the PCM and is intended to simplify the configuration of the IED. It allows
hardware changes to made without having to reconfigure the internal logic. Signals that can be
used in the SMT are indicated with the Suffix SMT.
1. Analog primary values are the quantities measured on the primary side of the cur-
rent and voltage transformers (CTs and VTs).
2. Analog secondary values are the quantities measured on the secondary side of the
current and voltage transformers. These are the quantities measured on the Trans-
former module (TRM) inputs.
3. Analog mean values are the quantities measured at the inputs of the milliampere
module (MIM).
4. Under Monitoring a number of submenus are available. These include Service
values, Current phasors, Voltage phasors, Current sequence components and
Voltage sequence components.
5. Metering displays the pulse counter function. The measurements available here
show pulse counter status data.
All measurement descriptions in this document reflect the maximum number of hardware units
possible in any application. In reality the hardware in the IED will be chosen according to a par-
ticular application. For example, it is possible to equip a 1/1 x 19” case IED with 14 I/O modules.
In reality fewer I/O modules may be installed. In the measurements menu the operator will only
see data from the hardware and software installed.
28
View analog primary values Chapter 6
Read measured values
2.1 Overview
The analog primary values are analog quantities measured on the primary side of the TRM and
reflect the actual current or voltage on the primary side of the VTs and CTs. The ratio is adjusted
under settings and also depends on the rating of the TRM. 24 primary values and phase angles
are displayed in this view.
Displays the quantities measured by the transformer module (TRM). For each channel used the
amplitude of the voltage or current and its phase angle is shown. The status of the module is al-
ways shown and channels not in use are indicated with the abbreviation NC. Data from up to
two TRMs and four LDCMs can be viewed. All currents and voltages are given in RMS values.
29
View analog secondary values Chapter 6
Read measured values
3.1 Overview
Analog secondary values shows secondary CT currents and VT voltages. These are the actual
current and voltage values at the TRM inputs.
Displays up to 24 channels with secondary CT and VT data. RMS values are shown.
30
Chapter 6
Read measured values
4.1
Measurements from the Milliampere Input Module (MIM) are found in this part of the measure-
ments menu. Data from either the hard wired mA module or the Signal Matrix Tool mA modules
are shown here.
Displays input data from the milli-ampere module which has six inputs. Each input has a range
of +/- 20 mA. The value displayed on the screen is however dependant on the settings for the
Milli-ampere Module. In the menu for settings, the range and a transformation factor can be ad-
justed to suit the application. This means that an input 3 mA may be displayed as temperature
of 45 degrees. The output values shown are without units.
Displays the input signals coming into the Milli-ampere Module. Each module has six physical
inputs with an input tolerance of +/- 20mA. The value displayed depends on the settings applied
to this board which may for example cause an input of 3mA to show a value 30. The SMT mA
modules are the virtual representation of MIMs in the Signal Matrix Tool.
31
View monitoring values Chapter 6
Read measured values
5.1
Measurement\Monitoring\ServiceValues(MMXU)\SVR
Displays up to three instances of SVR with measured values for S, P, Q, PF, U, I, ILead, ILag
and F.
Phase to phase voltages and phase angles are displayed here. Up to three sets of voltage data can
be displayed.
The current sequence component under monitoring displays the positive (I1), negative (I2) and
zero sequence (I0) current values for a three phase line, both magnitude and phase angle for each
component are displayed. These indicate how well balanced a system is. In an ideal balanced
system the zero sequence current should be zero, the positive sequence current should be equal
to the current of each phase with the same phase angle (relative to GPS) as the L1 phase signal
and the negative sequence current should be zero.
The Voltage sequence component displays the positive (U1), negative (U2) and zero (U0) se-
quence components in the system, and includes the magnitude and phase angle of each compo-
nent. Three sets of values are shown. This data indicates how well balanced the system is.
The magnitude of the three phase currents is displayed here. The differential current for each
pahse is also shown.
32
View monitoring values Chapter 6
Read measured values
Displays the magnitude of the currents and the differential currents in the three phase system.
33
View metering values Chapter 6
Read measured values
The output data generated under metering is from the pulse counter and includes data about the
status of the counter and counter values.
34
About this chapter Chapter 7
Event list
35
View events Chapter 7
Event list
1 View events
1.1 Overview
Events displays recorded events such as trips and breaker opened or closed.
Events
Displays a list of events in chronological order and where each event has a time stamp. The latest
event is at the top of the list.
36
About this chapter Chapter 8
Handle disturbances
Chapter 8 Handle
disturbances
37
Identify a disturbance Chapter 8
Handle disturbances
1 Identify a disturbance
A disturbance record can be generated manually by using the Manual Trig functionality in the
HMI menu. Other disturbance records are generated automatically in the system dependant on
the settings made. Disturbance reports generate a disturbance sequence number and are time
tagged. The fault location and fault loop are among the data generated in a fault record. Under
each fault report there are five categories of information available. These are described in the
sections that follow.
38
View disturbance record details Chapter 8
Handle disturbances
In the Recalculate distance to fault section in a disturbance record it is possible not only to view
fault data but to recalculate the distance to a fault. By taking into account peripheral influences
like the resistance and reactance of other lines in the immediate network area new distances can
be calculated. The reactance and resistance in the forward direction have the suffix B and in the
reverse direction they have the suffix A.
Recalculation may be necessary in cases where the data from a different fault loop needs to be
calculated. In three phase faults only one loop is shown in the disturbance record. When recal-
culating, a different fault loop can be selected. The path in the HMI is shown below.
39
Trigger a disturbance report manually Chapter 8
Handle disturbances
40
About this chapter Chapter 9
Read and change settings
41
System time and synchronization Chapter 9
Read and change settings
Under System time, the system clock date and time are set.
1.2.2 TimeSynch
Settings\Time\Synchronization\TimeSynch
Here the parameters FineSyncSource, CourseSyncSrc and SyncMaster are switched on or off.
1.2.3 TimeSynchBIN
Settings\Time\Synchronization\TimeSynchBIN
Binary input synchronization settings available here are the position of the of the module, the
number of the binary input and the detection mode.
1.2.4 TimeSynchSNTP
Settings\Time\Synchronization\TimeSynchSNTP
Here the IP addresses for the Simple Network Time Protocol servers are set.
1.2.5 TimeSynchDSTBegin
Settings\Time\Synchonization\TimeSynchDSTBegin
1.2.6 TimeSynchDSTEnd
Setttings\Time\Synchronization\TimeSynchDSTEnd
42
System time and synchronization Chapter 9
Read and change settings
1.2.7 TimeZone
Settings\Time\Synchronization\TimeSynchZone
The time zone according to Coordinated Universal Time (UTC) is set here.
43
General settings Chapter 9
Read and change settings
2 General settings
Parameters under General settings that are changed will cause the IED to restart. This occurs au-
tomatically and requires no manual intervention.
2.1.2 Identifiers
Settings\General Settings\Power System\Identifiers
Displays list with Station Name, Station Number, Object Name, Object Number, Unit Name and
Unit Number.
Here, settings for the Fourier filters, the minimum system voltage required to measure frequen-
cy, the item designation of CTs or VTs, and the system voltage are set. These settings are re-
quired by the preprocessing blocks and are usually only adjusted during the initial engineering
phase.
Here is where the settings for the summation block are done. The summation type, fourier filter
reference frequency, minimum voltage for frequency measurement and the system voltage are
some of the parameters that can be set here.
2.2 Communication
2.2.1 Overview
The parameter settings for communications are found under General Settings\Communications.
Communication settings cover network interfaces, protocol, remote communication and recep-
tion of interlocking information.
44
General settings Chapter 9
Read and change settings
2.2.2 TCP-IP
Settings\General settings\Communication\TCP-IP configuration\Front port
The IP Address and IP mask for the ethernet port on the front panel of the IED are set here. These
are generally used when connecting a PC directly to the IED. Remember that this is a static IP
address and that the appropriate network settings must also be made in the PC.
The IP address, IP mask and Link for the Optical Ethernet card at the rear of the IED are set here.
The same as the above but with different IP address if a second port is used.
If a gateway is used to access the system the address to that gateway is entered here.
In the General submenu there are three settings. These are for the Subnet address, the Node ad-
dress and the NeuronID.
Settings\General settings\Communication\SLM\
Rear optical LON port\ServicePinMessage
In this submenu a Service pin message can be generated. This is similar to a “ping” in traditional
networks. This sends a signal to another node in the system which is then made aware of the
Neuron ID of LON port and can respond to that port.
The Application Data Event (ADE) menu is where operation of LON is set on or off and where
the data exchange speed can be set. If LON is used primarily to send event data then the appro-
priate setting is slow. Should LON be used, for example, as a channel for TRIP signals then the
setting fast would be appropriate.
45
General settings Chapter 9
Read and change settings
Settings for SPA over LON are made here. The operation setting is used to switch the function
on or off and the slave address setting is where the slave address is entered.
Settings\General settings\Communication\SLM\
Rear optical LON port\Horizontal communication
In this submenu SPA or IEC is chosen and the necessary settings for the respective communica-
tion protocols are made.
SPA and IEC cannot run at the same time and in this submenu one of the options is chosen.
When SPA is chosen the baud rate and slave address are set here.
When IEC 60870–5–103 is used the settings Slave address, Baud rate, RevPolarity and Cyc-
MeasRepTime are done here.
2.2.4 LDCM
Settings\General settings\Communication\LDCM configuration
Four identical sets of settings for Remote Binary Communication (CRB) and four for Remote
Multi Communication (CRM). The multi communication block can send both binary and analog
data whereas the binary can only send binary data.
Each instance of CRB has seven settable parameters where the channel mode can be set on or
off, terminal numbers can be entered, synchronization can be set to master or slave and opto
power can be set high or low.
46
General settings Chapter 9
Read and change settings
Each instance of CRM has 17 settable parameters. These include those above and others such as
transmission delay and transmission current.
Multicommand send
Settings\General settings\Communication\Station communication\Multicommand-
Send
The up to ten instances of MulticommandSend settings allow the user to adjust the maximum
and minimum cycle time.
Multicommand receive
Settings\General settings\Communication\Station communicationj\Multicommand
receive
The up to 60 instances of MulticommandReceive settings available here allow the user to adjust
the maximum and minimum cycle time, the pulse duration and mode of operation. The mode of
operation is either steady or pulsed.
IEC61850–8–1
Settings\General Settings\Communication\Station communication\IEC61850–8–1
Includes settings for the IED name, operation (on/off) and GOOSE.
There are up to ten sets of settings here with one parameter (GB 01– GB10) per setting. The set-
ting is Operation ON or OFF.
47
General settings Chapter 9
Read and change settings
The settings for binary inputs and outputs even include the milliampere input modules. A mix
of up to 14 instances of BIM, BOM and IOM is possible depending on the physical configuration
of the IED. Operation ON or OFF can be set for all of these and for the BIMs oscillation release
and oscillation block settings are available. These settings are on board level and apply to all bi-
nary inputs or outputs on a board.
Displays all variations of analog input modules with parameters. The analog input modules have
different combinations of current and voltage inputs. Each channel has parameters where the
type of channel is set, the primary and secondary values from VTs and CTs and for Current
Transformers the star point location (line side or busbar side) is set.
Settings for binary inputs and outputs (BIM, BOM, IOM), and under each binary module there
are one or more adjustable parameters. In the I/O modules folder there is also a “reconfigure”
setting that starts a dialog box prompting the user to confirm or cancel the command. Since only
I/O modules installed in the IED are shown, the parameters available for setting depend on the
physical configuration of the IED. All I/O modules include the operation parameter which en-
ables the operator to switch the module on or off.
The milliampere modules (MIMs) are also found in the I/O Modules folder. Parameters possible
to set here are dead band settings and various current threshold values.
2.4 HMI
2.4.1 Overview
Under HMI in General settings there are submenus for LEDs, Screen, Functions, Reference
channel service values and the Change lock function. In the LED submenu there are settings for
operation, illumination times, and sequence types for the LEDs on the IED front panel. In the
Screen submenu Contrast level, Default screen, Auto repeat and Timeout display can be set. In
the Functions submenu the Event list sorting order and Distance presentation can be set.
48
General settings Chapter 9
Read and change settings
2.4.2 LEDs
Settings\General settings\HMI\LEDs\xxx
Parameters such as Operation, tRstart, tMax and 15 instances of SeqTypeLED can be set here.
The SeqTypeLED offers several options for the type of illumination sequence the LEDs should
follow.
2.4.3 Screen
Settings\General Settings\HMI\Screen
Local HMI setting parameters such as Language, Contrast level and Default menu can be set
here.
2.4.4 Functions
Settings\General Settings\HMI\Functions
The settings here are used to determine the way information is presented in the HMI. The two
parameters available here allow the user to choose between miles and kilometers for the presen-
tation of distance and to determine the order in which events are presented in the Event list.
The operation of the Change lock function can be activated or deactivated here.
2.5 Control
2.5.1 Overview
Under Control in General settings, parameters for Apparatus control can be adjusted. These are
the parameters for among others Bay control, Switch controller, Reservation input, Circuit
breakers and Circuit switches. The parameters include delay times, dependencies, pulse times
and characteristics.
Displays up to six instances of the bay control function (CB) with a setting that gives the local
operator priority over the remote operator or vice versa.
49
General settings Chapter 9
Read and change settings
Displays 60 instances of the Reservation input function (RE) with one settable parameter per
function for future use.
Displays up to four instances of the bay reserve function (CR) with nine parameter settings. The
first is for setting the supervision time to cancel a reservation and the other eight are for the res-
ervation of the own bay only at the selection of an apparatus.
Displays instances of the switch controller function (CS) with eight settable parameters. These
are settings for the control model, position dependency and various threshold times.
Displays 18 instances of the circuit breaker function with parameter settings for various time
limits and pulse lengths. For example, different circuit breakers may require different pulse
lengths to react. The setting tOpenPulse is used to set the length of the pulse required to open a
breaker.
Displays up to 24 instances of the circuit switch function (XS) with six settable parameters per
instance for time and pulse settings, output reset and switch type.
Displays six instances of the local/remote function (LR) that permit the user to set the control
mode.
50
General settings Chapter 9
Read and change settings
A number of selector switches (LRS) can be configured in the system. These are substitutes for
rotating physical switches. There is only one parameter setting per switch. This is StopAt Ex-
tremes which is used to disable or enable the end position of the switch.
2.7 Monitoring
2.7.1 Overview
Under monitoring there are parameters for setting Service values, current phasors, Voltage pha-
sors, Disturbance reports, Fault locator and the Measured value expander block.
Displays ten instances of the current phasor function (CP) with output regarding current ampli-
tude, current range, phase angle, zero sequence current magnitude and negative sequence current
magnitude.
Displays 5 instances of the voltage phasor function (VP) with output data for phase to phase volt-
age, voltage range, residual, zero sequence and negative sequence voltage.
The current sequence components part of the HMI under settings is where the user sets the limits
and deadband settings for current sequence components. The designation for zero sequence cur-
rent is 3I0, for positive sequence current it is I1 and for negative sequence current it is I2.
There are three sets of settings with seven categories of parameter settings per set (CSQ)
51
General settings Chapter 9
Read and change settings
The voltage sequence components part of the HMI under settings is where the user sets the limits
and deadband settings for voltage sequence components. The designation for zero sequence
voltage is 3U0, for positive sequence voltage is U1 and for negative sequence voltage is U2.
There are three sets of settings with seven categories of parameter settings per set (VSQ)
There are up to six groups of 16 channels with 16 binary outputs per channel. Each channel has
four settable parameters. These are operation, trig level, indication MA and set LED.
There are four groups of 10 channels with 10 analog signals per channel. Each signal has six
settable parameters such as operation, Nominal value and trig values.
Sixteen instances of settings for the Measured Value function (MV) with 12 settable parameters.
These settings are used to define the range of values used in the function block and to set the
threshold values. This is a generic function and therefore the input values depend on the appli-
cation.
52
General settings Chapter 9
Read and change settings
The Event function menu consists of 20 sets of settable parameters (EV01–EV20) where the
SPA channel mask, LON channel mask, Event mask and minimum repetition interval can be set.
The Binary signal status report settings consist of three sets of settable parameters (SSR1–SSR3)
with one settable parameter per instance.
The IEC 60870–5–103 part of the settings menu is divided into two separate submenus. These
are Measurements and Disturbance report. In the Measurements menu there are four sets of mea-
surement settings, one with standard settings and three with user defined settings. The standard
settings include some standard service value thresholds.
In the Disturbance report menu Binary signal parameters on up to 96 channels are configured.
2.8 Metering
2.8.1 Overview
Under metering there are settings for the Pulse counter function. There are four instances of the
Pulse counter function. Each instance can be switched on or off and a number of parameters can
be adjusted.
In the Pulse counter folder there are 16 instances of the pulse counter function (PC). Each in-
stance has 1 setting and four settable parameters. The setting “operation” is used to turn the func-
tion on or off. The parameters are adjusted to change cycle times, pulse counter criteria and the
like.
53
Setting group N Chapter 9
Read and change settings
3 Setting group N
3.1 Overview
There are six default setting groups. Under general settings, parameters in these groups can be
changed to suit the needs of an application. The default settings have been chosen according to
established practice in the industry but will usually require a certain amount of adjustment to suit
the requirements of individual applications.
Displays up to three instances of HZR with settings for operation, the alarm voltage level in volts
on the CT secondary side, the time delay to activate the alarm, the operate voltage level in volts
on the secondary side of the CT and the value of the series resistor in ohms.
Displays 19 adjustable parameters. These include the ohms per phase for resistive and reactive
reach as well as the ohms per loop for phase to phase, and phase to earth faults. Zones can also
be set on or off.
Displays 19 settings including minimum operating current for both phase-phase and phase-earth
fault loops.
54
Setting group N Chapter 9
Read and change settings
Includes settings for rated current, voltage and impedance direction angles.
Includes settings for operation, reactive and resistive boundaries, various timers, base settings
for current levels and several others.
Includes five settings. These are operation, rated current (IBase), rated voltage (UBase), phase
current threshold as a percentage of IBase and the phase voltage threshold as a percentage of
UBase.
Displays three instances of IOC with five settable parameters per instance. Operation mode, op-
erate current multiplier, operation on or off, operate phase current level as a percentage of Ibase,
and Ibase itself are the settable parameters available here.
Displays three instances of TOC each with over 80 settings. The settings range from base current
and voltage settings to parameters for customer programmable curves.
55
Setting group N Chapter 9
Read and change settings
Displays three instances of IEF with four settable parameters per instance. The settable param-
eters are operation (On or Off), base setting for current magnitude, the threshold current as a per-
centage of Ibase, and the multiplier for the current threshold level.
Displays three instances of TEF with a large number of settings per instance. Typical settings
are those for harmonic restraint, minimum fundamental frequency current level, base settings for
current and voltage and several others.
Displays three instances of THL with ten settings per instance. Typical settings are the hysteresis
for start temperature, pulse length for operation, ambient temperature settings and so forth.
Displays 6 instances of BFP with 14 settings per instance. Settings include operation, base cur-
rent, function mode, operation mode of retrip logic, time delays and several others.
Displays two instances of STB with five settings per instance. These are operation, base current
settings, release mode, operate current level and time delay.
Displays two instances of PD with seven settings per instance. The settings are for operation,
base current, trip time delay, contact function selection, current function selection, asymmetrical
magnitude of current and current release threshold.
56
Setting group N Chapter 9
Read and change settings
Displays 42 settable parameters. The operation mode, the voltage as percentage of Ubase are ex-
amples of the settings available here.
Displays 34 settable parameters including settings for IDMT curves and other function related
settings.
Displays up to 33 settable parameters for setting two characteristics and many related parame-
ters.
Displays six instances of TUF with eight settings per instance. These include parameters like op-
eration, base voltage, and start frequency. To ensure the proper operation of the Underfrequency
function the Operation setting must be On. Once changes have been made to settings, it is essen-
tial that these changes are properly saved in the IED.
57
Setting group N Chapter 9
Read and change settings
Displays six instances of TOF with six settings per instance. The settings are operation, start fre-
quency, base voltage setting, internal blocking level, operate time delay and reset time delay. For
the Overfrequency function to operate correctly the Operation setting must be On. Once the pa-
rameters have been set make sure the settings are properly saved in the IED.
Displays six instances of RCF with eight settings per instance. The settings include parameters
such as operation, base voltage setting, start frequency, internal blocking level, time delay to trip
and frequency restoration.
Displays 12 instances of GF with up to 162 settable parameters per instance. These settings are
available for the user defined functions configured with the help of the Multipurpose protection
function.
Displays five instances of CCS with four settings per instance. There are settings for operation,
base current setting, blocking of function, and minimum threshold for current differential.
58
Setting group N Chapter 9
Read and change settings
Displays six instances of FS with 17 settings per instance. There are parameters for operation,
various thresholds and base values.
3.9 Control
3.9.1 Overview
Under Control in the Setting group N menu settings for Synchrocheck, Autorecloser are avail-
able. Up to five instances of settings are available meaning that the settings for up to five differ-
ent apparatuses can be made here. The synchrocheck settings include the selection of busses or
lines and the configuration parameters for circuit breakers. The autorecloser settings include the
number of shots, first shot combinations and many other useful settings.
Displays five instances of the synchrocheck function (SYN) with 29 settings per instance. There
are settings for operation, voltage differences and limits, time delays etc.
Displays five instances of the autorecloser function (AR) with 31 settable parameters per in-
stance. There are settings for operation, number of shots, open times and various threshold val-
ues.
A number of selector switches can be configured in the system. Each switch has a set of param-
eters that can be set. The selector switch application can be enabled/disabled by changing the
operation setting to ON or OFF. The number of positions up to a maximum of 32 that the switch
can take is adjusted with the NrPos setting and the pulse duration and delay time can be set here.
The mapping of switch positions to system functions is handled in the PCM configuration tool
and cannot be changed via the HMI.
59
Setting group N Chapter 9
Read and change settings
Displays five settable parameters which include scheme type, coordination time for blocking co-
ordination scheme, minimum duration of a carrier send signal and security timer for loss of car-
rier guard detection.
3.10.3 Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
Settings\Setting Group N\Scheme communication\ZCurrentReversalWEI(PSCH)
Displays nine settable parameters for setting operating modes, pickup times, time delays, rated
values etc.
Displays nine settable parameters for setting operation on or off, setting time delays, enable and
disable various functions.
3.10.5 Scheme communication logic for residual overcurrent protection (PSCH, 85)
Settings\Setting Group N\Scheme communication\EFSchemeCommunication(PSCH)
Displays setting parameters for operation, scheme type and coordination time.
Displays eight settable parameters including operation, rated values, time data and other related
settings.
3.11 Logic
3.11.1 Overview
Under Logic there are settings for Trip logic, Trip matrix, Event counter, Logic gate, Logic SR
memory and Logic timer set. Under each of these function categories there are a number of in-
stances of each parameter set.
Displays five instances of the trip logic function (TRP) with five settable parameters per in-
stance. The settable parameters include operation, tripping order, trip lockout and minimum du-
ration of trip output signal.
60
Setting group N Chapter 9
Read and change settings
Displays 12 instances of the trip logic function (TR), each with settable parameters for opera-
tion, selections, delay times, and pulse times.
3.11.4 LogicGate
Settings\Setting Group N\Logic\LogicGate
3.11.5 LogicSRMemory
Settings SettingGroup N\Logic\LogicSRMemory
3.11.6 LogicTimerSet
Settings\Setting Group N\Logic\LogicTimerSet
Displays settable parameters for operation (On or Off) and delay for settable timer.
3.12 Monitoring
3.12.1 Overview
Fault locator settings are found under Monitoring in the Setting Group N menu.
Setting data entered here are the various measured or calculated impedances and resistances of
the protected line section. This data may be physically measured or taken from computer simu-
lation studies of the Line segment. For example the parameters R1A and X1A are the resistance
and reactance in reverse direction, the parameters R1B and X1B are the resistance and reactance
in the forward direction. These parameters along with the others found here need to be given val-
ues. For complete parameter data refer to the Technical reference manual (TRM).
61
Activate setting group Chapter 9
Read and change settings
Up to six setting groups can be configured in the PCM configuration tool. Under activate setting
group one of these setting groups can be chosen for the application at hand.
62
Language Chapter 9
Read and change settings
5 Language
Under the language part of the main menu the language options available in the HMI are located.
These vary depending on the configuration ordered.
63
Language Chapter 9
Read and change settings
64
About this chapter Chapter 10
Diagnose IED status
65
Find cause of internal failure Chapter 10
Diagnose IED status
Internal events in the diagnostics menu of the HMI tree shows a time stamped list of events.
These are events internal to the IED and can be used as reference when troubleshooting the sys-
tem.
Diagnostics\IED Status\General
Messages such as On, Ready and Fail indicate the status of each item on the list.
To identify the type of IED you are confronted with, navigate to identifiers using the keypad.
The path to identity parameters is shown below.
Under product identifiers, information about the type of IED, the IED main function, the serial
number of the IED, its order number and production date are found.
By following the menu path below the configuration of all hardware in the IED is displayed as
a list.
Diagnostics\IED Status\Installed HW
The list includes the slot number, the module name (Card) and its article number.
66
About this chapter Chapter 11
Test the IED
67
Overview Chapter 11
Test the IED
1 Overview
The test part of the tree view in the HMI has a number of submenus for test and viewing activi-
ties. When IED test mode is set to ON functions are inactivated so that no signals are transmitted
during testing. Under Function test modes individual functions can be activated. The LED test
are also activated here.
The submenus for binary inputs and outputs as well as the submenu titled Function status are
used to view data generated by the system. These categories of data are outlined below.
1. Binary output values has two submenus. These are Binary output modules
(BOM) and SMT binary outputs. Under these the status of binary outputs and
SMT outputs is displayed.
2. Binary input values has two submenus. These are Binary input modules (BIM)
and SMT binary inputs. These screens show the state of all the inputs on the Bi-
nary input modules (BIM). These are represented as digits but may also be a num-
ber if the input is being used to receive pulses for power measurement.
3. Distance protection displays a choice of functions available to the operator. Func-
tion related measurements can be viewed by navigating to the screen for each in-
dividual function.
4. Current protection displays a choice of functions. To view data related to these
functions it is necessary to choose one from the list and navigate to the screen for
the function in question.
5. Voltage protection displays a choice of functions available to the operator. Func-
tion related measurements can be viewed by navigating to the screen for each of
the four functions available. Data shown here is mainly trip and start related.
6. Frequency protection includes measurements from frequency functions. Mea-
surements show trip, start and similar data.
7. Multipurpose protection includes measurements showing data regarding trip sig-
nals, start signals, current and voltage values.
8. Secondary system supervision displays a choice of functions, Current circuit su-
pervision and Fuse failure. Current circuit measurements include fail and alarm
signals, and fuse failure measurements consist of start data.
9. Control displays the Synchrocheck, Autorecloser and Apparatus control func-
tions. The Synchrocheck and the Autorecloser functions include a number of
function related measurements such as calculated differences and number and
kind of reclosing attempts. Apparatus control includes up to 19 functions each
with their own set of measurement data regarding interlocking, breaker and iso-
lator conditions.
10. Scheme communication includes functions that display trip and other signals
used when interzone communication is deployed.
11. Logic displays a choice of functions available to the operator. These are Trip log-
ic, Event counter, Logic gate, Logic memory and Logic timer set each with their
own set of measurements.
12. Monitoring displays a choice of functions available to the operator. Function re-
lated measurements can be viewed by navigating to the screen for each individual
function. One of the submenus shows the status of the LEDs on the HMI.
13. Communication displays submenus for Remote communication and Receiving
interlock information.
68
Overview Chapter 11
Test the IED
All measurement descriptions in this document reflect the maximum number of hardware units
possible in any application. In reality the hardware in the IED will be chosen according to a par-
ticular application. For example, it is possible to equip a 1/1 x 19” case IED with 14 I/O modules.
In reality fewer I/O modules may be installed. In the measurements menu the operator will only
see data from the hardware and software installed.
69
IED test mode Chapter 11
Test the IED
Displays one setting which is used to activate and deactivate functions so that tests can be per-
formed without endangering system stability.
70
View binary input values Chapter 11
Test the IED
3.1 Overview
Binary input values display the state of each individual input in the Binary input modules (BIM).
These are indicated with a 1 or 0 depending on whether a signal is present or not. Binary input
modules with enhanced pulse counting capabilities can receive pulses used for power measure-
ment. The number of pulses received is used to measure power.
71
View binary output values Chapter 11
Test the IED
4.1 Overview
Binary output values show the status of each individual output in the Binary output module
(BOM). If the signal matrix tool is used binary outputs are depicted as virtual outputs. Note, that
only modules installed in the IED are shown in the HMI.
Displays up to 14 binary output modules (BOM). The status and name of each of the 24 binary
outputs that each module has are displayed here. The name of each output is user defined string.
The names of binary outputs are changed in the setting menu.
Displays up to 30 sets of binary output values. Each set or instance of binary outputs displays
the status of 10 individual binary outputs.
72
Function test modes Chapter 11
Test the IED
Test of switch onto fault logic, distance protection zones one to five, local acceleration logic,
power swing detection and phase selection with load encroachment.
Test of breaker failure protection and phase overcurrent protection, residual overcurrent protec-
tion, instantaneous phase overcurrent protection, pole discordance protection, instantaneous re-
sidual overcurrent protection, thermal overload protection and stub protection.
Test of scheme communication logic, for residual overcurrent protection and distance protec-
tion, as well as current reversal and weak end infeed logic, for distance protection and residual
overcurrent protection.
Test of two step overvoltage, two step undervoltage and two step residual overvoltage protec-
tion.
Test of up to twelve instances of the general current and voltage function (GF).
73
Function test modes Chapter 11
Test the IED
5.8 Control
Test\Function test modes\Control
5.9 Control
Test\Function test modes\Control\Autorecloser(RREC, 79)
5.10 Logic
Test\Function test modes\Logic
74
Function status Chapter 11
Test the IED
6 Function status
6.1 Overview
In the Function status section of the Test menu, data useful to the user in Test mode can be found.
The information available here is not limited to test applications alone and provides information
about the system as a whole.
Displays up to three instances of HZPDIF with 3 measurements per instance. These are the trip
signal, the alarm signal and the measured RMS voltage on the secondary side of the CT.
Displays one instance of PHS with 19 measurements. These measurements show faults detected
per phase as well as start conditions.
Displays up to five instances of ZM with nine measurements per instance of ZM. The output
quantities shown here indicate trip and start signal status.
Displays one instance of PSD with three measurements. These indicate a power swing and show
the measured impedances for the inner and outer impedance boundaries.
75
Function status Chapter 11
Test the IED
Displays up to three instances of IOC with four measurements per instance showing the trip sta-
tus in general and per phase.
Displays instances of POCM with 41 measurements per instance. These measurements are pri-
marily trip and start signal indications from each phase and from the various steps in the protec-
tion scheme.
Displays up to 24 instances of OCxx with trip, start and second harmonic data.
Displays up to three instances of IEF with one trip value per instance.
Displays up to three instances of TEF with 15 measurements per instance.The measurements in-
dicate trip and start signal status as well as the 2nd harmonic block signal status.
Displays up to three instances of THL with eight measurements per instance. The measurements
show temperature data, trip status, lockout and time to lockout.
76
Function status Chapter 11
Test the IED
Displays an application dependent number of instances of BFP with seven measurements per in-
stance. The measurement outputs include trip status and faulty circuit breaker alarm.
Displays one instance of STB with eight measurements that include trip and start data.
Displays up to two instances of PD with two measurements per instance which contain trip and
start data.
Displays up to 3 instances of TUV with 18 measurements per instance. The measurement data
includes operate/trip signals and start signals.
Displays up to three instances of TOV with 18 measurements per instance. The measurements
include operate/trip and start signal data.
Displays up to three instances of TRV with six measurements per instance. The measurements
include operate/trip and signal data.
77
Function status Chapter 11
Test the IED
Displays one instance of ZCOM with four measurements regarding trip output and carrier sig-
nals.
6.6.2 Current reversal and weak-end infeed logic for distance protection (PSCH, 85)
Test\Function status\Distance protection\ZCurrentReversalWEI(PSCH)\ZCAL
Displays six measurement outputs indicating trip status of weak end infeed logic.
6.6.4 Scheme communication logic for residual overcurrent protection (PSCH, 85)
Test\Function status\Current\EFSchemeCommunication(PSCH)\EFC
Displays one instance of EFC with three measurements indicating carrier and trip status.
Displays up to six instances of TUF with five measurements indicating status of trip, start, re-
store signals and showing possible blocking due to low amplitude as well as the start duration
as a percentage of the total operation time.
78
Function status Chapter 11
Test the IED
Displays up to six instances of TOF with 4 measurements per instance consisting of trip and start
signal status. The start duration as percentage of the total trip time and a blocking indication as
a result of low voltage.
Displays six instances of RCF with measurement data for trip and start signals. There is also a
restore signal for load restoring purposes, a start duration time and a blocking indication caused
by a drop in voltage.
Displays up to 12 instances of GFO with 26 output quantities per instance. These include error
signals from overcurrent functions, trip and start signals from overcurrent, undercurrent, over-
voltage and undervoltage. There is a block signal caused by second harmonic detection. The di-
rectional mode of OC1 and OC2 is shown as is low voltage for directional polarization. The
current and voltage as well as measured current multiplied by cos Phi and the angle between
voltage and current are also shown here.
Displays up to five instances of CCS with two measurements per instance indicating the detec-
tion of current circuit failure and alarm operation.
79
Function status Chapter 11
Test the IED
Displays up to six instances of FSO with three measurements per instance indicating start status.
6.10 Control
There are large amounts of output data from the control functions. The main categories of data
are found under Synchrocheck, Autorecloser and Apparatus control. Apparatus control has by
far the largest amount of data since this includes all the interlocking information for several dif-
ferent breaker arrangements.
Displays up to five instances of SYN with 21 measurements per instance. These include infor-
mation about which lines and buses selected, various voltage and frequency differences and
feedback on synchronization status.
Displays 30 instances of the function with an open and a close parameter for each disconnection
device. The enable open (EN_OPEN) parameter will have the output value one if an open oper-
ation is allowed and a zero output if an open operation is not allowed. The conditions for an open
operation are if the device is closed, intermediate or in a bad state as defined in IEC61850. The
enable close (EN_CLOSE) parameter is subject to similar conditions.
80
Function status Chapter 11
Test the IED
The information shown here indicates whether or not switching of the earth switch is permitted
and also indicates whether the earth switch (QC) is in the open or closed position.
Displays the interlocking conditions that apply to the various switches and breakers.
Displays conditions for CB opening and closing and the position of the disconnector.
Displays 35 measurements that indicate conditions for breakers, disconnectors and earthing
switches in the bay
Displays 19 measurements per breaker arrangement (instances of ILx). The measurements show
the states of the various disconnectors, breakers and earthing switches.
Displays 19 measurements per arrangement (instance of IM) showing conditions for breakers,
disconnectors and earthing switches in the arrangement. For example QA1CLREL with boolean
output 1 means that the closing of breaker QA1 is permitted. (REL=release, ITL=interlock, OP-
TR=opened transmission, CLTR=closed transmission)
81
Function status Chapter 11
Test the IED
The outputs from this function show when closing of disconnectors and breakers is allowed and
when it is not. It also shows whether QB1 is opened or closed and indicates the validity of its
switch status. There are 13 output values.
The outputs from this function show when closing of disconnectors and breakers is allowed and
when it is not. It also shows whether QB1 is opened or closed and indicates the validity of its
switch status. There are 13 output values.
There are three instances of this function with six outputs per instance showing whether switch-
ing of disconnectors QB9, QC3 and QC9 is permitted.
Displays six instances of the function (IF) with 28 boolean outputs per instance. These indicate
for which disconnect devices closing and switching of is allowed and also indicate the status and
validity of devices. For example, the measurement named QB12OPTR indicates whether or not
QB1 and QB2 are in the open position. If the output for this measurement is 1 then QB1 and
QB2 are in the open position. A zero indicates that they are closed.
Shows six instances of the function with 19 measurements per instance. The measurements in-
dicate which breakers and disconnectors are permitted to open and/or close, the status of the dis-
connect devices and switch status validity. For example, the measurement named VPQB2TR
indicates with output value 1 that the switch status of disconnector QB2 is valid.
Displays up to 30 instances of the function (CS) with 12 measurements per instance. Apart from
position indication and the latest value of the error indication during command, the majority of
the measurements provide boolean output data indicating the state of processes and devices.
82
Function status Chapter 11
Test the IED
Displays up to 18 instances of the function (XC) with 16 measurements per instance. Apart from
apparatus position (POSITION), truck position (TR_POS), operation counter (CNT_VAL), lat-
est value of error indication (L_CAUSE) and error indication during command (CAUSE) which
have integer values as outputs, the measurement values are boolean and provide status informa-
tion about processes and devices.
Displays up to 14 instances of the function with 15 measurements per instance. Apart from ap-
paratus position indication (POSITION), the value of the operation counter (CNT_VAL), the
latest value of the error indication during command (L_CAUSE) and error indication during
command (CAUSE) which have integer outputs, the measurement outputs have boolean values
indicating the status of processes and devices.
Displays up to four instances of the function (CR) with 12 measurements per instance. Apart
from the measurement for exchange signals between different BayRes blocks the output values
are all boolean and indicate the status of processes and devices.
Displays up to 60 instances of the function (RE) with six measurements per instance. Apart from
the exchange measurement (EXCH_OUT), the measurement outputs are all boolean and provide
information about acknowledgements from other bays, reservation requests form other bays
(RE_RQ_B) and also validity checks regarding requests (V_RE_RQ).
Displays up to six instances of the function (CB) with three measurements per instance. The op-
erator place allocation (PSTO) measurement has an integer as output data, whereas the Update
of position is blocked (UPD_BLKD) and Function is blocked for commands (CMD_BLKD)
have boolean output data.
6.14 Commands
In the commands menu it is possible to view three sets of values. These are found under the sub-
menus Single command, Selector switch and IEC60870–5–103.
83
Function status Chapter 11
Test the IED
There are three sets of 16 OUT signals under the Single command menu.
An application dependent number of switches can be displayed here. The position of each switch
is indicated here. There are up to 32 possible switch positions. The number of switches and
switch positions is determined by the configuration in the PCM configuration tool.
6.14.3 IEC60870–5–103
The path to the IEC60870–5–103 menu is:
Test\Function Status\Commands\IEC60870–5–103
Under this part of the HMI tree there are the following three submenus:
• IED Commands
• Function Commands
• User Defined Commands
Various IED, function and user defined command data can be viewed here.
6.15 Logic
Under the Logic function folder there is viewable data for trip logic (showing number of poles
that have tripped and trip signal information), event counter values, Logic gate outputs, Logic
SR memory output states and Logic timer set output states are also shown here.
Displays up to five instances of the function (TRP) with eight measurements per instance. The
output data from each measurement is boolean and indicates the existence of various trip signals.
For example, if the output from parameter TRL1 is one, this indicates that a trip signal from
phase L1 has been generated.
84
Function status Chapter 11
Test the IED
Displays up to 12 instances of the function (TRO) with 3 boolean output values per instance.
The output signals from this function block are typically connected to other logic blocks or di-
rectly to IED output contacts.
Displays 40 instances of the gate output. The output data type is an integer with a possible value
from 0 to 255.
Displays one value in boolean form indicating output from the pulse timer.
Displays 40 instances of the function (SM). There are two measurement parameters per instance,
SMnn OUT (Output) and SMnn N_OUT (Output inverted). The output data presented in the
HMI is boolean and indicates whether or not a signal is present. For example, an output of one
from SM01 OUT indicates that a signal exists on that output.
Displays 40 instances of the function (TS). Each instance has two output parameters, TSxx_ON
and TSxx_OFF where xx stands for the number of the instance. The output data type is boolean
and indicates whether the output from the timer pickup is delayed (ON) or if the drop out (OFF)
is delayed.
6.16 Monitoring
Monitoring includes large amounts of viewable data including Disturbance report data, Service
values, Current phasors, Voltage phasors, Milliampere signal level supervision, Fault locator,
Binary signal status report, Events, MVGGIO, MVExpander and LEDs.
85
Function status Chapter 11
Test the IED
Displays data about disturbance reports. The disturbance report can be switched off, a distur-
bance report that has been initiated is indicated by a boolean number, as are completed reports
and cleared reports. The parameter MEM USED indicates that more than 80% of the memory
space available for disturbance report data has been used and the need to clear the memory is
pressing. The Memory USED parameter generates an integer value showing the actual amount
of memory used by the disturbance record repository. The maximum number of incoming ana-
log channels is 40 and their Trig status is indicated here. The Fault number parameter generates
an integer indicating the number of faults recorded since the last clearing of the memory.
Displays the analog output from the GGIO block. The value shown here depends on the settings
and the logical configuration of the preprocessing blocks. The measurement displayed may be
current, voltage, frequency, phase angle etc.
Displays up to 66 instances of the function block (XP). These show the boolean values assigned
to the integer values generated by analog inputs.
6.16.4 LEDs
Test\Function status\Monitoring\LEDs\Start and trip LEDs
Shows new and accumulated indications and the status of the 15 HMI indication LEDs.
Displays the number of satellites supplying positioning and timing data to the GPS module.
Displays up to 20 instances of the event parameter (EV) showing one value for the Event status
mask (EvStatusMask) per instance.
86
Function status Chapter 11
Test the IED
6.17 Metering
6.17.1 Pulse counter logic (GGIO)
Test\Function status\Metering\PulseCounter\PC
Displays up to four instances of PC with measurement data. Each instance displays five data out-
puts that include pulse counter validity, reported value of complete integration cycle, generation
of new pulse counter value, pulse counter blocked and user defined string is used for the pulse
counter.
6.18 Communications
The communication output data available under Test includes remote communication and sta-
tion communication.
The Receiving Interlock information available here indicates the state of various apparatus such
as whether they are in a closed or open position and if their status is valid. Up to 59 apparatuses
can be displayed. There are also indications of reservation requests, reservation granted and the
validity of data and communication.
87
Function status Chapter 11
Test the IED
Up to ten sets of GOOSE binary signals can be viewed here. There are sixteen signal indications
per set.
MultiCommand send
Test\Function status\Communication\Station communication\MultiCommandSend
The MultiCommand Send indication is used to display data from the Local Optical network
(LON).
MultiCommand receive
Test\Function status\Communication\
Station communication\MultiCommandReceive
The MultiCommand Receive indications displayed here show up to 60 sets of output data. Each
set of output data has 16 signals. Other information displayed here shows whether there has been
a change in data and whether data is valid.
Displays the parameters ACTIVE, OUTPUT and SETTING. The ACTIVE parameter indicates
whether the IED is in test mode or not, the OUPUT parameter indicates whether test mode has
been activated by a binary input and the SETTING parameter indicates whether or not test mode
has been activated by a setting. The output data is binary (0 or 1).
88
Test LEDs Chapter 11
Test the IED
7 Test LEDs
Test\LED test
The Test LEDs menu enables the operator to activate LEDs manually. LEDs that do not light up
are defective. Defective LEDs are also logged in Disturbance records under Monitoring.
89
Test LEDs Chapter 11
Test the IED
90
About this chapter Chapter 12
Control and supervise the bay
91
Overview Chapter 12
Control and supervise the bay
1 Overview
The control menu in the HMI includes the Single line diagram, Single command and Selector
switch functions.
The Single Line Diagram (SLD) is used to control and supervise the bay by allowing the oper-
ator to close and open apparatuses using keys on the front panel of the IED. This is primarily
intended as a backup for higher level control systems. If for example MicroSCADA were to mal-
function, then bay level switches and circuit breakers can be controlled directly from the HMI.
The Single command function is used to view LON interlocking data and is only visible if LON
is configured and used in the system.
The Selector Switch function is configured in the PCM 600 tool and the switch position can be
changed in the HMI. The selector switch has the same function as a rotating switch with up to
32 positions. Each position is configured in the PCM 600 to match a certain application. Each
position number corresponds to the equivalent position of a rotating switch. It is only visible if
it has been configured in the PCM 600.
This is the path to the single line diagram from the main menu.
The symbols used in the Single Line Diagram (SLD) are described in the table below
92
Overview Chapter 12
Control and supervise the bay
Symbol Description
Autotransformer
Busbar
Capacitor
Circuit breaker
Damping Coil
Current Transformer
Earth
Feeder system
Generator
Disconnector
Junction
Motor
Reactor
93
Overview Chapter 12
Control and supervise the bay
Symbol Description
Surge arrestor
Trafo 2 windings
Trafo 3 windings
Truck
VT 2 windings
x
94
About this chapter Chapter 13
Reset
Chapter 13 Reset
95
Reset guide Chapter 13
Reset
1 Reset guide
Reset\Reset counters\Autorecloser(RREC.79)
96
Reset guide Chapter 13
Reset
Activating Reset of LDCM counters sets the counter concerned to zero. A reset can be per-
formed by affirmation in the dialog box. This is done by pressing the E key when YES is high-
lighted.
Reset\Reset temperature\ThermalOverload1TimeConstant(PTTR.25)
97
Reset guide Chapter 13
Reset
98
About this chapter Chapter 14
Authorization
Chapter 14 Authorization
99
Administrate users Chapter 14
Authorization
1 Administrate users
The Administrator submenu allows the administrator to log on, log off, edit own data, add new
users, edit users and delete users. The HMI path is as follows:
Authorization\Administrator
The users are categorized according to the level of access they are allowed in the system. The
super user is the default setting. The super user has unlimited access to the HMI. The adminis-
trator user category can create new users, change passwords, access settings but cannot exercise
direct apparatus control. The Control safeAction category of user can open and close breakers,
disconnectors and the like via the HMI but has no access to settings and cannot manoeuvre an
apparatus which is interlocked.
User access can be limited to certain places and to certain levels in the control system. This is
known as place authority. In multi-level control systems there are control points on different lev-
els in the system. It may be desirable to have a certain category of user at a remote locality such
as the network control centre (SCADA). Other users may be placed at the station operator WPL
(MICROSCADA). Both are remote in relation to the IED.
The control IED is provided with a control switch that can be set to LOCAL, REMOTE or OFF.
LOCAL means that the IED is controlled locally via the HMI or local panel (PC or similar).
REMOTE means that the IED is controlled from a higher level location such as the substation
control centre (MICROSCADA) or network control centre (SCADA). Settings can still be done
locally but all control functions are lifted to the next level in the control hierarchy.
Parameter setting can always be done at all levels. It is the capability to execute control functions
that is moved from place to place.
100
Users Chapter 14
Authorization
2 Users
Once users have been registered in the system by the administrator, they can log on and off, and
change their passwords under the User menu. The HMI path from the main menu to the user
menu is as follows:
Authorization\User
101
Users Chapter 14
Authorization
102
About this chapter Chapter 15
Glossary
Chapter 15 Glossary
103
Glossary Chapter 15
Glossary
1 Glossary
AC Alternating current
AR Autoreclosing
BS British standard
C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for serial communi-
cation
CB Circuit breaker
104
Glossary Chapter 15
Glossary
Co-directional Way of transmitting G.703 over a balanced line. Involves two twisted
pairs making it possible to transmit information in both directions
Contra-directional Way of transmitting G.703 over a balanced line. Involves four twisted
pairs of with two are used for transmitting data in both directions, and
two pairs for transmitting clock signals
CR Carrier receive
CS Carrier send
CT Current transformer
DC Direct current
DR Disturbance recorder
105
Glossary Chapter 15
Glossary
G.703 Electrical and functional description for digital lines used by local tele-
phone companies. Can be transported over balanced and unbalanced
lines
G.711 Standard for pulse code modulation of analog signals on digital lines
HDLC protocol High level data link control, protocol based on the HDLC standard
HV High voltage
IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements for pro-
tective current transformers for transient performance
IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-pair
or optical fiber cable
IEEE P1386.1 PCI Mezzanine card (PMC) standard for local bus modules. References
the CMC (IEEE P1386, also known as Common mezzanine card) stan-
dard for the mechanics and the PCI specifications from the PCI SIG
(Special Interest Group) for the electrical EMF Electro Motive Force.
Instance When several occurrences of the same function are available in the IED
they are referred to as instances of that function. One instance of a func-
tion is identical to another of the same kind but will have a different num-
ber in the IED user interfaces. The word instance is sometimes defined
as an item of information that is representative of a type. In the same
way an instance of a function in the IED is representative of a type of
function.
106
Glossary Chapter 15
Glossary
IP 1. Internet protocol. The network layer for the TCP/IP protocol suite
widely used on Ethernet networks. IP is a connectionless, best-effort
packet switching protocol. It provides packet routing, fragmentation and
re-assembly through the data link layer.
2. Ingression protection according to IEC standard
OV Over voltage
Overreach A term used to describe how the relay behaves during a fault condition.
For example a distance relay is over-reaching when the impedance pre-
sented to it is smaller than the apparent impedance to the fault applied
to the balance point, i.e. the set reach. The relay “sees” the fault but per-
haps it should not have seen it.
107
Glossary Chapter 15
Glossary
Process bus Bus or LAN used at the process level, that is, in near proximity to the
measured and/or controlled components
SA Substation Automation
TC Trip coil
108
Glossary Chapter 15
Glossary
TCP Transmission control protocol. The most common transport layer proto-
col used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. The de facto stan-
dard Ethernet protocols incorporated into 4.2BSD Unix. TCP/IP was
developed by DARPA for internet working and encompasses both net-
work layer and transport layer protocols. While TCP and IP specify two
protocols at specific protocol layers, TCP/IP is often used to refer to the
entire US Department of Defense protocol suite based upon these,
including Telnet, FTP, UDP and RDP.
Underreach A term used to describe how the relay behaves during a fault condition.
For example a distance relay is under-reaching when the impedance
presented to it is greater than the apparent impedance to the fault
applied to the balance point, i.e. the set reach. The relay does not “see”
the fault but perhaps it should have seen it. See also Overreach.
U/I-PISA Process interface components that deliver measured voltage and cur-
rent values
UV Undervoltage
V.36 CCITT interface for 4 wire data communication with a speed exceeding
48Kkbps.
VT Voltage transformer
3UO Three times the zero sequence voltage. Often referred to as the residual
voltage or the neutral point voltage
109
Glossary Chapter 15
Glossary
110