MICOM P546:: Two End Line Differential CT Compensation With Two Different CT Ratios

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 1

MICOM P546:

LOCAL END REMOTE END


RED670 RED670 RELAY
RELAY
87L
CTR:
87L CTR:
1600/1 A 1500/1A

VT

TWO END LINE DIFFERENTIAL CT


COMPENSATION WITH TWO DIFFERENT CT
RATIOS

LOCAL END:

I BASE(Reference Current) : 1500A(No need to set reference current, CT Primary current whichever is minimum of two ends)

Phase Is1(Differential Min Pick up): 0.25 p.u.(Primary current considered as 400A)

Phase CT correction : 1(1600/1600)

REMOTE END:

I BASE(Reference Current) : 1500A(No need to set in the relay, CT Primary current whichever is minimum of two ends)

Id Min(Differential Min Pick up): 0.25 p.u.(Primary current considered as 400A)

Phase CT correction : 1.07(1600/1500)