DC Power Supply Agilent
DC Power Supply Agilent
DC Power Supply Agilent
U8000 Series
Single Output DC Power Supplies
Data Sheet
02 | Keysight | U8000 Series Single Output DC Power Supplies - Data Sheet
Key Features
Work Eficiently with Get That Something Extra: Front Panel Operation
Great Features and Solid Safety and Security
An easy-to-use rotary knob and
Performance — self-guiding keypads allow you to set
The U8000 Series has been stringently
Within Budget tested according to various industrial the output at your desired resolution
safety standards: CSA (for US and without any effort. Also, both voltage
Differentiated features typically found and current levels can be set to a
CA regulatory requirements), C-tick
only in programmable power supplies maximum resolution of 10 mV/10 mA
(Australia), and CE (Europe). The
U8000 Series is fully integrated with from the front panel. In addition, you
The U8000 Series offers fully can save and recall for up to three
OVP and OCP in order to prevent
integrated over voltage protection operating states that are stored in the
damage to the DUT. The security
(OVP) and over current protection internal non-volatile memory.
features offered in the U8000 Series
(OCP) to prevent damage to the
prevent measurement errors and also
device-under-test (DUT). Using the Easy-to-use control functions:
ensure safety storage of the power
capability to save and recall three
supply. Security features such as – Enabling or disabling OVP and OCP
memory states, you can minimize
keypad locking capability preclude – Setting the OVP and OCP trip levels
errors and reduce set-up time. The
accidental front panel usage while
U8000 Series also provides security – Clearing OVP and OCP conditions
the physical lock mechanism provides
features such as keypad lock to – Setting and displaying the voltage
secure instrument storage.
prevent measurement errors due and current limit values
to accidental front panel usage.
– Operating state storage/recall
When the keypad lock is activated,
the knob and all the buttons on the – Resetting the power supply to
front panel are disabled except the power-on state
keypad lock button. The physical lock – Calibrating the power supply
mechanism found at the rear panel – Enabling or disabling the output
of the power supply provides secure
instrument storage. The LCD display
with backlight on/off options enables
brighter display for data viewing (see
Figure 2).
Physical lock
mechanism
•
Selects the knob control
function for voltage and
current adjustment
05 | Keysight | U8000 Series Single Output DC Power Supplies - Data Sheet
Performance Speciications
Electrical Speciications
Parameter U8001A U8002A
Output Ratings (at 0 °C to 40 °C) 0 to +30 V 0 to +30 V
0 to 3 A 0 to 5 A
Line and Load Regulation CV: <0.01% +2 mV
CC: <0.02% +2 mA
Ripple and Noise (25 °C ±5 °C) CV: 12 mVp-p, <1 mVrms;
CC: 3 mArms
Load Transient Response Time
(within 15 mV from full load to half load <50 µs
and from half load to full load)
Programming Accuracy1 (25 °C ±5 °C) <0.35% +20 mV
<0.35% +20 mA
Readback Accuracy1 (25 °C ±5 ° C) <0.35% +20 mV
<0.35% +20 mA
Meter Resolution Voltage: 10 mV
Current: 10 mA
Maximum Output Float Voltage ±240 Vdc
Supplemental Characteristics
Supplemental Characteristics
Parameter U8001A U8002A
Temperature Coefficient CV: <100 ppm/ °C
(for 12 months)
CC: <380 ppm/ °C CC: <300 ppm/ °C
Output Voltage Overshoot
(during turn-on or turn-off of AC power state <1 V
with the output control set to less than 1 V)
Voltage Programming Speed, to within 1% of
total excursion
Up Full Load 150 ms
No Load 100 ms
Down Full Load 30 ms
No Load 450 ms
Last Memory Setting Enabled Yes
Over Voltage Protection Response Time <1.5 ms when the trip voltage is equal to or greater than 3 V and <10 ms when the trip voltage
is less than 3 V (average time for output to drop from 90% of output voltage to 1 V after OVP
condition occurred)
Protection Features
Parameter U8001A U8002A
Over Voltage Protection Accuracy
<0.5% +0.5 V
± (% of output + offset)
Over Voltage Protection Programmable
1 V to 33 V
Range
Over Current Protection Accuracy
<0.5% +0.5 A
± (% of output + offset)
Over Current Protection Programmable 1 A to 3.3 A 1 A to 5.5 A
Range
Physical Speciications
Parameter U8001A U8002A
Dimensions (H x W x L) 88.1 mm x 212.3 mm x 394.3 mm
Weight 7.3 kg 8.3 kg
07 | Keysight | U8000 Series Single Output DC Power Supplies - Data Sheet
General Characteristics
Liquid Crystal Display (LCD) One year – Option U800xA-AUT Custom Power
On (available only upon purchase
Operating Environment Warm-up time with main model)
Power Options
– Three year for U8000 series power
supplies
Opt 0E9 90 to 110 Vac, 47 to 63 Hz
– Three months for standard shipped
Opt 0EM 104 to 126 Vac, 47 to 63 Hz
accessories
Opt 0E3 207 to 253 Vac, 47 to 63 Hz
08 | Keysight | U8000 Series Single Output DC Power Supplies - Data Sheet