Project: Date:: Short-Circuit Summary Report

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Project: ETAP Page: 1

12.6.0H
Location: Date: 19-11-2017
Contract: SN:
Engineer: Revision: Resetting
Study Case: SC
Filename: Bismillah Config.: Normal

Short-Circuit Summary Report

30 Cycle - 3-Phase, LG, LL, & LLG Fault Currents

Prefault Voltage = 100 % of the Bus Nominal Voltage

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV Real Imag. Mag. Real Imag. Mag. Real Imag. Mag. Real Imag. Mag.

4.0% 20.00 0.000 -10.054 10.054 0.001 -10.054 10.054 8.707 0.000 8.707 -8.708 5.027 10.055

4.10% 20.00 0.883 -6.931 6.987 0.692 -4.892 4.941 6.003 0.765 6.051 -6.285 1.125 3,780

4.20% 20.00 1.024 -5.220 5.320 0.603 -3.205 3.262 4.521 0.887 4.607 4.307 2.043 2,332

4.30% 20.00 0.996 -4.168 4.285 0.503 -2.380 2.432 3.609 0.863 3.711 3.442 1.695 1,676

4.40% 20.00 0.929 -3.461 3.584 0.426 -1.891 1.939 2.998 0.805 3.104 2.861 1.455 1,321

4.50% 20.00 0.857 -2.957 3.079 0.368 -1.569 1.612 2.561 0.742 2.666 2.446 1.276 1,086

4.60% 20.00 0.790 -2.579 2.698 0.323 -1.340 1.379 2.234 0.684 2.336 2.135 1.136 0,921

4.70% 20.00 0.729 -2.286 2.400 0.288 -1.170 1.205 1.980 0.632 2.078 1.893 1.024 0,801

4.80% 20.00 0.676 -2.053 2.161 0.260 -1.038 1.070 1.778 0.585 1.872 1.700 0.932 0,708

4.90% 20.00 0.629 -1.862 1.966 0.236 -0.933 0.962 1.613 0.545 1.702 1.543 0.855 0,634

4.100% 20.00 0.588 -1.704 1.803 0.216 -0.847 0.874 1.476 0.509 1.561 1.412 0.790 0,575

Bus recloser bdn4 20.00 0.978 -3.922 4.042 0.477 -2.205 2.256 3.397 0.847 3.501 3.241 1.613 1,551

All fault currents are symmetrical momentary (30 Cycle network) values in rms kA

* LLG fault current is the larger of the two faulted line currents