Ferroresonance and Its Causes
Ferroresonance and Its Causes
Ferroresonance and Its Causes
1. Voltage transformer energized through grading capacitance of one (or more) open
CB(s)
2. Voltage transformers (VT) connected to an isolated neutral system
3. Transformer accidentally energized in only one or two phases
4. Voltage transformers and HV/MV transformers with isolated neutral
5. Power system earthed through a reactor
6. Transformer supplied by a highly capacitive power system with low short-circuit
power
Go back to contents
Overvoltage values may exceed normal phase- to-phase voltage under steady
state condition, and cause dielectric destruction of the electrical equipment.
Depending on the relative values of the magnetizing inductance of the VT and
the capacitance C0, ferroresonance is fundamental, subharmonic or quasi-periodic.
Go back to contents
For example the series ferroresonant circuit is made up of the connection in series of
the phase to earth capacitance (between circuit breaker and transformer) of the open
phase and the magnetizing impedance of the transformer. The modes are
Go back to contents
When an earth fault occurs on the HV side upstream from the substation transformer,
the HV neutral rises to a high potential. By capacitive effect between the primary and
secondary, overvoltages appear on the MV side, and may trigger ferroresonance of
the circuit made up of the voltage source E0, the capacitances Ce and C0 and
the magnetizing inductance of a VT (see fig. 4b ).
Figure 4 Ferroresonance of a VT between phase and earth with an isolated neutrals source
transformer
Where:
As regards LV power systems with isolated neutral, standards recommend (IEC 364)
1. HV neutral of the HV/MV transformer earthed, and HV fault flowing through the
earth conductor of the substation,
2. Iron core saturation of the HV/MV transformer,
3. Transformer design dissymmetry,
4. Natural dissymmetry of the capacitances (C 1, C2, C3 in figure 5b ) to earth.
This may result in saturation of the iron coil, thus initiating or sustaining
ferroresonance.
Go back to contents
This is the case, for example, on return to service in an MV (underground cable) urban
or industrial power networks, but also in very extended rural public MV power
networks (see figure 6 ) or where underground cables are increasingly used (reliability
and aesthetics).
In short:
This means that the insulation co-ordination procedure does not normally take into
account the overvoltage levels, and that, consequently, surge arresters (whose
residual voltage is usually higher than the overvoltages due to ferroresonance) do not
theoretically provide protection against it.
Go back to contents