Genset 79-102-125 kVA
Genset 79-102-125 kVA
Genset 79-102-125 kVA
MODEL |GSW110-170
DEUTZ Diesel engine.
Water cooling system with radiator.
Internal residential silencer.
Central lifting eye.
Complete with engine and battery liquids.
Manual oil draining pump.
Leak proof tray.
Rental kit as option (POWER ON RENT).
Noise level attenuation panel as option (noise reducion 2/3dBA).
TECHNICAL CHARACTERISTICS NOT IMPEGNATIVE RESERVATION OF MODIFICATIONS FOR INNOVATION OF THE PRODUCT
CODE (SINGLE)
PRIME POWER PRP kVA (kW) 79 (79) 102 (102) 125 (125)
EMERGENCY POWER LTP kVA (kW) 83 (83) 107 (107) 132 (132)
Voltage Volt 240 240 240
Frequency Hz 60 60 60
Fuel capacity l (gal) 320 (70.4) 320 (70.4) 320 (70.4)
Autonomy (100% load PRP) h 14.4 11.0 9.8
Acoustic power LWA 96 97 98
Acoustic pressure level at 7m dB(A) 71 72 73
3.000x1.150x1.570 3.500x1.250x1.910 3.500x1.250x1.910
Dimensions (LxWxH) mm (in)
TECHNICAL FEATURES
Protections with Engine protections: low fuel level, low oil pressure, high engine temperature.
alarm Genset protections: over-frequency, battery voltage out of limits.
Manual control panel mounted on
the genset, complete with digital Engine protections: low fuel level, low oil pressure, high engine temperature.
control unit BE23 for monitoring, Protections with Genset protections: under/over voltage, over-load, under/over frequency.
control and protection of the shutdown Circuit breaker protection: III poles. (optional)
generating set. Differential protection. (optional)
Rev.00 Pag. 1 of 2
GENERATING SET TECHNICAL GUIDE GSW105-160 Soundproof
Hours-counter.
Engine speed r.p.m.
Fuel level (%).
Engine temperature.
Selector switch with six positions: Automatic test - Automatic starting - Engine locked - Mains contactor forced -
Manual starting - Genset contactor forced.
Push-buttons: start/stop, up/down selection, reset.
Commands and
Emergency stop button.
others
Remote starting availability.
Acoustic alarm.
Automatic battery charger.
Automatic control panel mounted
Engine protections: low fuel level, low oil pressure, high engine temperature.
on the genset, complete with Protections with
Genset protections: under/over voltage, overload, under/over frequency, starting failure, under/over battery
digital control unit AC01 for alarm
voltage, battery charger failure.
monitoring, control and
protection of the generating set.
Engine protections: low fuel level, low oil pressure, high engine temperature,
Protections with Genset protection: under/over voltage, overload, under/over battery voltage, battery charger failure.
shutdown Circuit breaker protection: III poles. (optional)
Differential protection. (optional)
KRT: RENTAL KIT. Not allowed with PHS or AFP. Complete of:
Battery switch.
Fuel filter water separator.
Three way valve.
Leak proof tray.
Earth rod.
RCG: REMOTE CONTROL BY GSM KIT (kit for genset management and control by remote
PC; comunication available by means of RS232 directly to PC or through GSM modem).
Available only on the automatic versions.
STR: SITE TRAILER. Single axle for GSW105 and double axle for GSW135-160.
Rev.00 Pag. 2 of 2