ASCO SIL Certificate

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Certificate / Certificat

Zertifikat /
ASC 1205106 C001
exida hereby confirms that the:

The manufacturer
may use the mark:

Redundant Control System


ASCO Valve, Inc.
Florham Park, NJ - USA
Has been assessed per the relevant requirements of:

IEC 61508 : 2010 Parts 1-7


and meets requirements providing a level of integrity to:

Systematic Capability: SC 3 (SIL 3 Capable)


Random Capability: Type A, Route 2H Device
Valid until July 1, 2018
Revision 1.1 June 26, 2015

PFDAVG and Architecture Constraints


must be verified for each application
Safety Function:
The Redundant Control System will move to the safe state,
normally open or normally closed, within the specified safety
time when de-energized.
Application Restrictions:
The unit must be properly designed into a Safety Instrumented
Function per the Safety Manual requirements.

Place embossed
seal here for
originals, lining it
up at the bottom

ANSI Accredited Program

Evaluating Assessor

Certifying Assessor

PRODUCT CERTIFICATION
#1004

Page 1 of 2

Certificate / Certificat / Zertifikat /


ASC 1205106 C001
Systematic Capability: SC 3 (SIL 3 Capable)
Random Capability: Type A, Route 2H Device
PFDAVG and Architecture Constraints
must be verified for each application
Systematic Capability :

Redundant Control
System

The product has met manufacturer design process requirements of Safety


Integrity Level (SIL) 3. These are intended to achieve sufficient integrity
against systematic errors of design by the manufacturer.
A Safety Instrumented Function (SIF) designed with this product must not
be used at a SIL level higher than stated.
Random Capability:
The SIL limit imposed by the Architectural Constraints must be met for
each element. This device meets exida criteria for Route 2H.

IEC 61508 Failure Rates in FIT*


Failure Rates Redundant Control System with Automated Diagnostic Tests

Device
Solenoid Valve
Bypass Valve
Pressure Switch

lsd
594 FIT
57 FIT
444 FIT

lsu
261 FIT
88 FIT
5 FIT

ldd
502 FIT
7 FIT
0 FIT

ldu
10 FIT
0 FIT
0 FIT

Failure Rates Redundant Control System with Manually Initiated Diagnostic


Tests

Device
Solenoid Valve
Bypass Valve
Pressure Switch

lsd
0 FIT
0 FIT
0 FIT

lsu
855 FIT
145 FIT
449 FIT

ldd
0 FIT
0 FIT
0 FIT

ldu
512 FIT
7 FIT
0 FIT

* FIT = 1 failure / 109 hours


PVST = Partial Valve Stroke Test of a final element Device
SIL Verification:
The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
must be verified via a calculation of PFDavg considering redundant architectures,
proof test interval, proof test effectiveness, any automatic diagnostics, average
repair time and the specific failure rates of all products included in the SIF. Each
element must be checked to assure compliance with minimum hardware fault
tolerance (HFT) requirements.
The following documents are a mandatory part of certification:
64 N Main St
Sellersville, PA 18960

Assessment Report: ASC 12-05-106 R001 V1R3


Safety Manual: SM V9535; R2; 02/11

T-061, V1R7

Page 2 of 2