ELSSG03
ELSSG03
ELSSG03
PIP ELSSG03
Design and Fabrication of Medium Voltage
Metal-Enclosed Load Interrupter Switchgear
PRINTING HISTORY
October 2009
Issued
Not printed with State funds
October 2009
PIP ELSSG03
Design and Fabrication of Medium Voltage
Metal-Enclosed Load Interrupter Switchgear
Table of Contents
1. Introduction..................................2
1.1
1.2
Purpose..........................................2
Scope.............................................2
2. References...................................2
2.1
2.2
3. Definitions....................................3
4. Requirements..............................3
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8.
Service Conditions..........................3
Ratings...........................................3
Basic Construction..........................3
Bus and Bus Supports....................5
Ground Bus....................................6
Grounding to Confirm
De-Energized Status......................6
Arc-Resistant Switchgear...............6
Load Interrupter Switch..................8
10
Page 1 of 17
4.15
4.16
4.17
4.18
4.19
4.20
4.21
4.22
4.23
4.24
Potential Transformers.................12
Current Transformers...................12
Instruments, Meters, Control Devices and Indicating Lights
Space Heaters..............................13
Paint.............................................14
Test and Inspection.......................14
Nameplates and Labels................15
Documentation.............................15
Shipment......................................16
Conflict Resolution........................17
13
October 2009
1.
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
Introduction
1.1
Purpose
This Practice provides requirements for medium voltage metal-enclosed load
interrupter switchgear.
1.2
Scope
This Practice describes the requirements for design, fabrication, inspection,
testing, and shipment of medium voltage metal-enclosed load interrupter
switchgear for installation in non-classified areas. This Practice covers
assemblies for medium voltage application for nominal 2.4 kV to 38 kV, 60 Hertz
systems.
This Practice does not include no-load interrupter switches.
2.
References
Applicable parts of the following Practices, industry codes and standards, and references
shall be considered an integral part of this Practice. The edition in effect on the date of
contract award shall be used, except as otherwise noted. Short titles are used herein where
appropriate.
2.1
2.2
Page 3 of 17
3.
Definitions
owner: The party who owns the facility wherein the load interrupter switchgear will be
used
purchaser: The party who awards the contract to the supplier. The purchaser may be the
owner or the owners authorized agent.
supplier: The party responsible for furnishing the load interrupter switchgear
4.
Requirements
4.1
Service Conditions
Equipment shall be designed to perform satisfactorily under the ambient
conditions specified on purchasers PIP ELSSG03D Data Sheet.
4.2
4.3
Ratings
4.2.1
The ratings of the switchgear assemblies and the system parameters shall
be as specified on purchasers PIP ELSSG03D Data Sheet.
4.2.2
Basic Construction
4.3.1
4.3.2
4.3.3
4.3.4
Main front and rear doors if any shall have door stops that can hold the
door in the full open position until released.
4.3.5
Front doors shall be provided with hand operated latches and shall have
provisions for padlocking.
4.3.6
4.3.7
October 2009
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
4.3.9
4.3.10 If specified on purchasers PIP ELSSG03D Data Sheet, a 120 VAC light
with an on-off switch that is externally accessible or mounted in the low
voltage compartment shall be provided for each cubicle containing an
interrupter switch.
4.3.11 If specified on purchasers PIP ELSSG03D Data Sheet, switchgear shall
be designed for expansion on the ends, and the enclosures shall be of
modular design so that additional units may be safely and readily
installed. Provisions for expansion shall include, but not limited to,
predrilled buses, terminal blocks for secondary wiring, and removable
enclosure end covers secured by captive hardware on the structure.
4.3.12 Front doors on vertical sections of enclosures containing load interrupter
switches shall be interlocked with the switch to prevent the door from
being opened if the switch is not in the fully opened position. Also, the
interlock shall prevent the switch from being closed if the door is not
fully closed.
4.3.13 If specified on the purchasers PIP ELSSG03D Data Sheet, full height
and width grounded metal barriers shall be installed between front switch
enclosures and rear cable or bus areas. Through bushings shall be
provided to isolate the front and rear compartments.
4.3.14 The switchgear base shall be constructed of either of the following as
specified on purchasers PIP ELSSG03D Data Sheet:
a. G90 Galvanized steel, 1.5 inches (3.8 cm) high
b. 4-inch (10.6 cm) minimum channel
4.3.15 Full height, grounded metal barriers shall be provided between adjacent
vertical sections.
4.3.16 Bushings shall be provided for bus penetration between cable and switch
compartment and between adjacent vertical units.
4.3.17 Unless otherwise specified on purchasers PIP ELSSG03D Data Sheet,
control power shall be furnished by the purchaser. Supplier shall wire
control power circuit to terminal blocks for connection by purchaser.
4.3.18 Unless otherwise specified on purchasers PIP ELSSG03D Data Sheet,
space heater and lighting power shall be furnished by the purchaser.
Supplier shall wire space heater and lighting circuits to terminal blocks
for connection by purchaser.
Page 5 of 17
4.3.19 In any front or rear access switch compartment having a full height door,
and containing high-voltage parts which may remain energized after the
door is open, metal screen gates shall be provided behind all hinged
doors or panels covering primary voltage bare live parts.
4.3.19.1 The gates shall be provided with hinges and captive bolt
closing fastenings.
4.3.19.2 The metal gate screen shall be designed to resist collapse if a
person falls against the gate.
4.3.19.3 The metal gate screen shall be constructed of expanded or
punched 16 gage (1.31 mm2) minimum steel, with openings
not greater than 1 inch (2.54 cm).
4.3.19.4 Gates shall have warning signs that contain the following
information or equivalent: Danger High Voltage Keep Out
Qualified Persons Only.
4.4
4.4.2
4.4.3
Bus Insulation
4.4.3.1 Unless otherwise specified on the purchasers PIP ELSSG03D
Data Sheet, phase bus shall be covered with a flame-retardant,
track-resistant, non-hygroscopic insulation.
4.4.3.2 Bus insulation, except at the joints, shall be bonded to the bus
bar and shall be either liquid dipped or fluidized bed epoxy.
4.4.3.3 If specified on the purchasers PIP ELSSG03D Data Sheet,
sleeve type or heat shrink tubing type insulating systems may be
provided.
4.4.4
4.4.5
4.4.6
Air gaps around the bus and inserts shall not be permitted.
4.4.7
October 2009
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
4.4.8
4.4.9
Cable shall not be used as a power, ground, or neutral bus except for load
side connections from fuse or switch to transformer primary connections
where bracing is adequate for the cables.
4.4.10 The continuous current carrying capability of the bus shall not be less
than the continuous current rating of any associated interrupter switch.
4.4.11 Bus insulators shall be wet process porcelain or cycloaliphatic epoxy as
specified on purchasers PIP ELSSG03D Data Sheet, and shall be braced
for the maximum short circuit current specified on purchasers
PIP ELSSG03D Data Sheet.
4.5
4.6
4.7
Ground Bus
4.5.1
A tin-plated copper ground bus, minimum 2 inches (5.1 cm) by 1/4 inch
(0.6 cm), shall extend throughout the length of the switchgear.
4.5.2
NEMA spaced holes (i.e., 9/16 inch (1.4 cm) diameter, spaced 1-3/4 inch
(4.4 cm) center to center) for two-hole lugs at each end of the bus shall
be provided.
4.5.3
For cubicles with cable terminations or bus duct entry in both front and
rear compartments, the ground bus shall be extended into both
compartments.
4.5.4
For each cubicle, the ground bus shall be extended toward the incoming
power cable termination points to allow easy access for safety ground
connection of a portable grounding clamp device.
4.6.2
Arc-Resistant Switchgear
4.7.1
4.7.2
4.7.3
Testing
4.7.3.1 Arc-resistant switchgear shall be tested in accordance with
IEEE C37.20.7.
Page 7 of 17
4.7.5
4.7.6
The front and rear compartment doors shall be designed to withstand the
effects of an internal arcing fault.
4.7.7
4.7.8
4.7.9
Openings intended to close on initiation of a fault to preserve arcresistant construction shall be provided with the necessary guards on top
and sides to prevent dropping of any foreign material that can prevent
openings from closing.
4.7.10 Design and construction of the switchgear shall prevent effects of any
fault in the high voltage compartment from entering the low voltage or
instrument compartment.
4.7.11 Opening cover plates provided to preserve arc-resistant contruction shall
be accessible for inspection.
4.7.12 If rear doors interlocks are specified on the purchasers PIP ELSSG03D
Data Sheet, a means shall be provided to defeat the interlocks by a
deliberate act that is not considered part of a normal operating procedure
for maintenance purposes. The interlock shall be reset by closing the
door after the interlock has been circumvented.
4.7.13 A single-handle latch system with position labeling and provision for
padlocking shall be provided on each door such that arc-resistant
integrity is maintained if the latch is in closed position. Additional tie
down bolts or latches shall not be required on the doors to maintain arcresistant construction.
4.7.14 Plenum System
4.7.14.1 Personnel shall be protected from arc products and noise
expelled from the switchgear enclosure. Unless specified
otherwise on the purchasers PIP ELSSG03D Data Sheet,
a plenum system shall be provided.
4.7.14.2 Plenum system shall exhaust arc products from the switchgear
room.
4.7.14.3 Exhaust outlet shall be weatherproof and directed to an area
October 2009
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
4.8.2
Switch Configuration
4.8.2.1
4.8.2.2
4.8.2.3
4.8.2.4
4.8.2.5
4.8.2.6
4.8.2.7
Design of the switch shall not permit moving the switch into
an intermediate position under normal operation.
4.8.3
4.8.4
4.8.5
4.8.6
4.8.7
4.8.8
Page 9 of 17
4.8.9
4.8.10 If specified on the purchasers PIP ELSSG03D Data Sheet, two normally
open (NO) and two normally closed (NC) (DPDT) auxiliary contacts that
indicate fully open and closed switch positions shall be provided and
wired to a terminal block for purchaser use. The terminal block shall be
located in a low voltage compartment.
4.8.11 If specified on the purchasers PIP ELSSG03D Data Sheet and/or the
single-line diagram, key interlocks shall be provided between specified
switches or specified switches and external equipment.
4.8.12 If specified on the purchasers PIP ELSSG03D Data Sheet, one of the
following options shall apply:
a. All three phases of each switch shall be grounded when the switches
are in the full open position.
b. A separate grounding switch shall be provided.
4.9
4.10
4.11
4.12
Surge Protection
If specified on purchasers single-line diagram or purchasers PIP ELSSG03D
Data Sheet, surge protection shall be provided.
4.13
October 2009
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
4.13.2 Cable
4.13.2.1 Unless otherwise specified on purchasers PIP ELSSG03D Data
Sheet, cable lugs shall be furnished by purchaser.
4.13.2.2 Type of cable termination used by the purchaser shall be shown
on purchasers PIP ELSSG03D Data Sheet.
4.13.2.3 Switchgear cable termination compartment space shall facilitate
bringing cables to line or load terminals with a minimum of
cable bending.
4.13.2.4 Unless otherwise specified on the purchasers PIP ELSSG03D
Data Sheet, cable penetrations shall be from the bottom.
4.13.3 If bus duct or cable bus is specified on purchasers PIP ELSSG03D Data
Sheet, bus duct and bus duct terminations or cable bus and cable bus
terminations shall be in accordance with PIP ELSBD01 and
PIP ELSBD01D or PIP ELSBD02 and PIP ELSBD02D.
4.13.4 Transformer Close Coupled
4.13.4.1 Switchgear shall be cable or bus connected to the transformer
bushings as specified on the purchasers PIP ELSSG03D Data
Sheet.
4.13.4.2 If a cable connection is specified, the cable for the connection
to the transformer shall be provided.
4.13.4.3 If a cable connection is specified, the cable shall be supported
by wet process porcelain or cycloaliphatic epoxy standoff
insulators and inserts where the cable passes through barriers.
4.14
Page 11 of 17
October 2009
4.15
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
Potential Transformers
4.15.1 Unless specified as drawout or tiltout type on purchasers
PIP ELSSG03D Data Sheet, potential transformers (PT) shall be fixed
mounted.
4.15.2 Drawout PTs shall be mounted on a tilt-out or draw-out type carriage
with two handles. Means shall be provided to ground the primary of the
PT in the fully drawn out position and to isolate the primary
disconnecting devices from the operator when the PT is withdrawn.
4.15.3 PT rating shall be as shown on purchasers PIP ELSSG03D Data Sheet or
single-line diagram.
4.15.4 The PT BIL rating shall be coordinated with the switchgear BIL rating.
4.15.5 PT primaries shall be protected with current limiting fuses.
4.15.6 Secondary circuits shall be protected with fuses.
4.15.7 Means shall be provided to pad lock the draw-out or tilt-out PTs when in
disconnected position.
4.15.8 Wye-Wye PTs shall be provided with secondary loading resistors to
prevent primary fuse blowing from ferroresonance.
4.15.9 Fuse holders shall be labeled to show the size and type of fuses required.
4.16
Current Transformers
4.16.1 Current transformers (CT) shall be window type and installed in a
manner that provides for ease of maintenance or replacement.
4.16.2 CTs shall be designed to mechanically and thermally withstand the shortcircuit stresses imposed by the rating of the associated interrupter switch
for one second.
4.16.3 Except for zero sequence CTs, CTs shall have the following
characteristics:
a. 5 ampere secondary winding rating
b. Voltage rated insulation
c. ANSI metering and relaying accuracy classification in accordance
with the system ratio and class shown on purchasers
PIP ELSSG03D Data Sheet
d. CT accuracy class ratings in accordance with, IEEE C37.20.2-1999,
Table 4
4.16.4 CTs shall be sized to prevent saturation during maximum system faults.
4.16.5 CT polarity markings shall be visible when access doors or barriers are
opened or removed.
4.17
Page 13 of 17
Space Heaters
4.18.1 The interrupter switchgear assembly shall be equipped with space heaters
to minimize condensation.
4.18.2 Space heaters shall be powered as shown on purchasers wiring
diagrams.
4.18.3 Each vertical switchgear assembly shall be provided with a space heater
rated at 240 volts.
4.18.4 Space heaters shall be sized to provide the required heat output if
operated on a 120 volt system.
4.18.5 Space heaters shall be provided with high temperature wiring within 6
inches (152 mm) of the heater terminals.
4.18.6 Space heaters shall be mounted on a stand-off insulator and provided
with means for personnel protection from thermal burns.
4.18.7 A caution nameplate, as shown in Figure 1, shall be provided on the door
of each cubicle that contains space heaters.
OBSERVE CAUTION EXTERNAL POWER SOURCE
Figure 1
4.18.8 An over-current protection and disconnect for each space heater circuit
shall be provided in each vertical switchgear assembly.
4.18.9 If specified on purchasers PIP ELSSG03D Data Sheet, each space heater
in the vertical switchgear assemblies shall be controlled by a humidistat
or thermostat. The humidistat or thermostat shall be equipped with an
ammeter and a bypass switch as specified.
October 2009
4.19
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
Paint
4.19.1 The switchgear enclosures shall be cleaned and treated for rust
resistance.
4.19.2 The inside of the switchgear control compartment shall be painted as
specified on purchasers PIP ELSSG03D Data Sheet.
4.19.3 Unless otherwise specified on purchasers PIP ELSSG03D Data Sheet,
exterior finish color for switchgear shall be ANSI No. 61, light gray.
4.19.4 One quart of touch-up paint shall be provided for each five vertical
switchgear assemblies and for each paint color used.
4.20
4.21
Page 15 of 17
Documentation
4.22.1 One reproducible set of drawings shall be provided plus the specified
number of copies of all documentation and operating manuals as
specified on purchasers PIP ELSSG03D Data Sheet.
4.22.2 Unless otherwise specified on purchasers PIP ELSSG03D Data Sheet,
format for reproducible drawings shall be CAD convertible .dxf
electronic format.
4.22.3 Drawings and data requirements shall be as shown in Table 1.
Table 1. Documentation Requirements
A
With
Bid
B
For
Review
X
C
Final
Certified
X
D
As
Built
X
X
X
X
X
X
X(1)
X
X
X
X
X
X
Description
Bill of materials giving schematic identification, quantity,
make, rating, model, and manufacturer of component
Extended warranty information
Proposed layout of equipment, showing estimated
dimensions and weights
Equipment drawings, showing floor plans, front view
elevations, relay and control device panel layouts, typical
sectional views. Drawings shall show all locations of all
equipment and devices.
Installation drawings, showing dimensions and weights of
all shipping sections and location and type of all
interconnections between shipping splits
Connection wiring diagrams for all electrical equipment
3-line, and control schematic diagrams
Certified Test Reports
Installation, Operation, and Maintenance Manual
Complete parts list
Recommended spare parts list with pricing
Notes:
A. These documents shall be provided with the proposal.
B. These documents shall be provided for the purchasers review and authorization to proceed
before fabrication.
C. These documents shall be provided as part of the final certified document submittal.
(1) Equipment shall be shipped with one set of installation, operation, and maintenance
manuals.
D. The final as-built documents shall be provided within 2 weeks following shipment.
October 2009
4.23
PIP ELSSG03
Design and Fabrication of Medium Voltage Metal-Enclosed Load Interrupter Switchgear
Shipment
4.23.1 Details on shipping requirements shall be furnished by purchaser in the
contract documents.
4.23.2 Yellow tags, marked TO BE REMOVED BEFORE EQUIPMENT IS
PLACED IN SERVICE, shall be attached to all temporary shipping
braces.
4.23.3 Instructions for storage of equipment shall be attached to the equipment.
4.23.4 Equipment shall be protected from weather elements during shipping.
4.23.5 One set of installation, operation, and maintenance manuals shall be
shipped with the equipment.
4.24
Conflict Resolution
Any conflicts between the referenced documents shall be identified in writing to
the purchaser for resolution. If resolving conflicts, the following order of
precedence shall apply:
a. Purchase order
b. One line diagram and associated documents
c. Purchasers PIP ELSSG03D Data Sheet
d. This Practice
e. Referenced standards
Page 17 of 17