Teldor Data Communication Cables

Table of contents

Title

Page

Introduction Pages

Twisted Pair Copper Data Cables

General Information

Category 5e Data Transmission Cables

13

Category 6 Data Transmission Cables

17

Category 6A Data Transmission Cables

21

Category 7 Data Transmission Cables

25

Category 7A Data Transmission Cables

29

Data Center Cables

33

Closing Pages

35

The Best ConnectionTM

Teldor Data Communication Cables


Introduction Pages

TELDOR CABLES & SYSTEMS Ltd.

Company Profile
TELDOR is a world-class cable manufacturer committed to innovation and excellence. We have continually lived up to
that commitment with the help of the best personnel, the latest equipment and future-oriented management. Today,
TELDOR is recognized as a leading cable manufacturer in almost all the markets where cables are sold and installed.
The company was established in 1966, with the intent of manufacturing power and telecommunication cables. Over the
years it has diversified to additional fields, always seeking the most competitive and profitable markets.
TELDOR products are sold and distributed in more than 25 countries on all 5 continents, Fifty-five percent (55%) of all
sales are exported. TELDOR cables can be found in the most prestigious cabling projects all around the world, marked
either with the TELDOR brand name or with one of the many international cabling companies to whom we provide cable
with a private label. TELDOR is a certified supplier to many companies and organizations such as Panduit, Hubbell, RIT,
Leviton, RW-Data, Israeli Air Force, Israels Department of Defense, ECI Telecom, and more.
TELDOR also anticipates the demands of future markets with progressive research and development. The company
continuously monitors and interprets industry trends, and uses state-of-the-art R&D methods to introduce innovative
new products that meet the needs of the rapidly changing market.
TELDOR utilizes the most advanced marketing methods, including a state-of-the-art Internet site at www.teldor.com.
TELDOR's engineers lecture in international seminars and training sessions all over the world. They also represent
Israel in international standardization organizations such as ISO/IEC, IEC, and IEEE.
TELDORs quality system is approved to conform to the requirements of ISO-9001:2008. In addition, many of TELDOR's
products are approved and verified by national and international certification bodies such as UL, ETL and SII .

Engineering
- Product development management (from DRD to FDR)
- Consulting (materials, processing, applications, standards)
- Custom design (technical specs., drawings, modeling, prototype)
- Product verification (test regimes, standards conformance, simulations)
- Senior engineers with expertise in polymers, conductors, strength elements, advanced transmission systems
- Technology forecasting (based on active participation in all major national and international standards organizations)
- Rapid turnover, full NDA's, ISO 9001:2008 certified

The Best ConnectionTM

Teldor Data Communication Cables


Introduction Pages

Processing
- Drawing, stranding and insulation of conductors
- Precise twinning and cabling (twist, planetary, reverse oscillating)
- Extrusion of polymers (thermoplastics, thermosets, PVC, HFFR, TPU, TPE,PEE and many more)
- Armoring and shielding (wire braid, served wire, Moisture Barrier, corrugated steel,dielectric materials)
- Polymer compounding and granulation
- Precise process control
- Winding, spooling and packaging

Testing
- Fully equipped hi-frequency lab
- OTDR and OLS-PM testing for all major optical fibers and wavelengths
- Fully equipped mechanical testing laboratory
- Fully equipped chemical and materials testing laboratory
- Electric testing laboratory (up to 50 kV)
- Environmental testing (Temperature, Permeability, UV, Flame, Aging)
- Issuing of C.O.Cs and C.O.Ts

The Best ConnectionTM

Teldor Data Communication Cables


Introduction Pages
Cable Performance Icons
Teldor Cable Catalogues use a system of easily recognizable icons to indicate cable performance. The icons that
appear in each cable family chapter indicate characteristics common or available in that particular family. Below is a
legend of the icons used throughout this catalogue and their meaning:

UV Sunlight Resistant

Rodent Resistant

Flame Retardant

Water-blocked

Oil / Fuel Resistant

Enhanced Tensile Strength

Enhanced Crush Resistance

Electromagnetically Shielded / Dielectric

Enhanced Flexibility

Armored - Direct Burial

Aerial Applications

Very Cold Environments

Very Hot Environments

Robotic / Chain Applications

Highly Impact Resistant

For Petrochemical Environments

The Best ConnectionTM

Teldor Data Communication Cables / Twisted Pair Copper Data Cables

TELDOR DATA COMMUNICATION CABLES

Twisted Pair Copper Solutions

The Best ConnectionTM

Teldor Data Communication Cables / Category 5e Data Transmission Cables


CATEGORY 5e 100 Ohm Cables

The BASIC Solution

CATEGORY 5e, 100 Ohm


100 MHz DATA TRANSMISSION CABLES
THE BASIC-Solution is a complete line of high-performance 100 Ohm cables, conforming to Category 5e in accordance
withTIA/EIA-568-C, ISO/IEC 11801, IEC 61156-5, IEC 61156-6 and CENELEC prEN 50288, supporting CLASS D (new)
Links.
The product range includes Horizontal, Working area (Patch) and Backbone Cables, available in a wide range of
constructions, including U/UTP, F/UTP, SF/UTP and S/FTP (Basic-Solution cables for Outdoor use are given in Teldor's
Outdoor Solution brochure).
TELDOR Cables & Systems guarantees that when BASIC-Solution cables are properly installed and terminated with
adequate connecting hardware, the basic link supports the application of IEEE 802.3ab 1000Base-T (better known as
"Gigabit Ethernet"). The attenuation of the BASIC-Solution cables is low enough to allow the use of patch cords having
up to 50% higher attenuation than horizontal cables, as defined in IEC 61156-5 and IEC-61156-6.
BASIC-Solution cables are constantly tested and verified to maintain all their transmission parameters after installation
and throughout the warranty period. They are officially verified by internationally recognized independent third-party
testing houses.
All cables are available with PVC, PU (Polyurethane), PE (Polyethylene) and FR-LSZH (Flame Retardant Low Smoke
Zero Halogen) jackets, in single or "Siamese twin" (FIG-8), multi-cable, or multi-core constructions.
Testing is conducted up to 160 MHz to ensure the transmission requirements of the more advanced digital
encoding schemes.

13

The Best ConnectionTM

Teldor Data Communication Cables / Category 5e Data Transmission Cables


CATEGORY 5e 100 Ohm Cables

Cat. 5e Work Area Cables*


Freq.

Attenuation 20%

Attenuation 50%

PS NEXT

NEXT

RL

PS ELFEXT

ELFEXT

MHz

(24AWG & lower)

(26AWG & higher)

Loss

Loss

dB

dB

dB

dB/100m

dB/100m

dB

dB

o
20 C

Typical

20 C

Cat. 5e

Value

Typical

Cat. 5e

Typical

Value

Cat. 5e

Value

Typical Cat. 5e Typical Cat. 5e


Value

Typical

Value

Cat. 5e

Value

Typical

Cat. 5e

Value

2.4

2.5

3.1

3.2

68.3

62.3

71.3

65.3

22.0

20.0

64.0

61.0

2.4

2.5

4.8

4.9

5.8

6.0

59.3

53.3

62.3

56.3

25.0

23.0

52.0

49.0

4.8

4.9

10

7.6

7.8

9.2

9.5

53.3

47.3

56.3

50.3

28.0

25.0

44.0

41.0

7.6

7.8

20

10.8

11.1

13.1

13.5

48.8

42.8

51.8

45.8

28.0

25.0

38.0

35.0

10.8

11.1

30

13.4

13.8

16.2

16.8

46.1

40.1

49.1

43.1

27.0

23.8

35.0

31.5

13.4

13.8

60

19.4

20.0

23.5

24.2

41.6

35.6

44.6

38.6

24.0

21.1

28.0

25.4

19.4

20.0

100

25.5

26.4

31.0

32.0

38.3

32.3

41.3

35.3

22.0

18.8

24.0

21.0

25.5

26.4

*Supplied cables meet minimum Cat. 5e transmission requirements of IEC 61156-6 Ed. 2 and ANSI/EIA/TIA 568-B.2

Cat. 5e Horizontal Cables


Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

o
20 C
Typical

Cat.

Typical

Cat.

Typical

Cat.

Typical

Cat.

Typical

Cat.

Typical

Cat.

Value

5e

Value

5e

Value

5e

Value

5e

Value

5e

Value

5e

2.0

2.1

68.3

62.3

71.3

65.3

22.0

20.0

64.0

61.0

67.0

64.0

3.9

4.1

59.3

53.3

62.3

56.3

25.0

23.0

52.0

49.0

55.0

52.0

10

6.2

6.5

53.3

47.3

56.3

50.3

28.0

25.0

44.0

41.0

47.0

44.0

20

8.8

9.3

48.8

42.8

51.8

45.8

28.0

25.0

38.0

35.0

41.0

38.0

30

10.9

11.5

46.1

40.1

49.1

43.1

27.0

23.8

35.0

31.5

38.0

34.5

60

15.8

16.6

41.6

35.6

44.6

38.6

24.0

21.1

28.0

25.4

31.0

28.4

100

21.0

22.0

38.3

32.3

41.3

35.3

22.0

18.8

24.0

21.0

27.0

24.0

*Supplied cables meet minimum Cat. 5e transmission requirements of IEC 61156-5 Ed. 2 and ANSI/EIA/TIA 568-B.2

14

The Best ConnectionTM

Teldor Data Communication Cables / Category 5e Data Transmission Cables


CATEGORY 5e 100 Ohm Cables

Category 5e Data Transmission Cables


Teldor P/N

Product Description

Computer & LAN


Applications

Outer
Jacket
Material

4T00080101 Cat. 5e 4x2x24/1 AWG U/F/UTP + 17 AWG CCS


Fig-8 Double Jacket Outdoor UL1581-VW1/CMX
Jacket Outdoor UL1581-VW1/CMX

Outdoor installations

UV resistant 7.9
FR-PVC

8393204xxx

Cat. 5e 4x2x24/1 AWG F/UTP Outdoor PVC/PVC


UL (1581 VW 1) (UL) LISTED E211498

Outdoor installations

UV resistant 7.9
FR-PVC

7272604xxx

Cat. 5e 4x2x26/7 AWG Work Area U/UTP PVC

Indoor use, fixed or


portable installations

FR-PVC

4.9

8272626xxx

Cat. 5e 4x2x26/7 AWG F/UTP Work Area PVC

Work area cabling

FR-PVC

5.70

9292604xxx

Cat. 5 4x2x26/7 AWG SF/UTP Work Area PVC

Work area cabling

FR-PVC

5.3

7562004xxx

Cat. 5e 4x2x24/1 AWG U/UTP PVC

Indoor use, fixed


installations

FR-PVC

5.0

7568204xxx

Cat. 5e 2x(4x2x24/1 AWG) FIG-8 U/UTP PVC P


FIG-8

Indoor use, fixed


installations

FR-PVC

5.1

8371204xxx

Cat. 5e 4x2x24/1 AWG F/UTP PVC

Indoor use, fixed


installations

FR-PVC

6.1

8391304xxx

Cat. 5e 4x2x24/1 AWG F/UTP Outdoor Low


Temperatures PVC peratures

Indoor/Outdoor use,
fixed installations

UV resistant 7.2
FR-PVC

8371804xxx

Cat. 5e 2x(4x2x24/1 AWG) FIG-8 F/UTP PVC

Trunking

FR-PVC

6.1

8371406xxx

Cat. 5e 6x(4x2x24 AWG F/UTP) Multi-Cable PVC

Indoor use, fixed


installations

FR-PVC

20

8371412xxx

Cat. 5e 12x(4x2x24 AWG F/UTP) Multi-Cable PVC Indoor use, fixed


installations

FR-PVC

27.6

8371425xxx

Cat. 5 25x(4x2x24 AWG F/UTP) Multi-Cable PVC

FR-PVC

35.5

15

Trunk Cable for Local


Area Networks

Outer
Diameter (mm
nom.)

The Best ConnectionTM

Teldor Data Communication Cables / Category 6 Data Transmission Cables


250 MHz 100 Ohm Data Transmission Cables

The GIGA-STAR Solution

CATEGORY 6, 100 Ohm


250 MHz DATA TRANSMISSION CABLES
The GIGA-STAR Solution is a complete line of data-transmission cables horizontal and work area types, designed for Cat.
6 and Cat. 5e for use in CLASS D and CLASS E cabling systems.
GIGA-STAR cables are tested up to 300 MHz, and are fully compatible with ISO/IEC 11801, IEC 61156-5, IEC 61156-6,
and TIA/EIA 568C.
The GIGA-STAR Solution is consists of the following three groups:
U/UTP cables, where high NEXT and FEXT loss values are achieved by mechanical pair separation
U/FTP cables, where high NEXT and FEXT loss values are achieved by individual pair shielding
S/FTP cables, where an additional overall braid shield provides outstanding EMC performance
Our customers have the option of selecting a true Category 6 cable that meets all the transmission parameters required to
support the advanced applications with 3 different levels of EMC performance:
U/UTP cables: 50 dB coupling attenuation
U/FTP cables: 75 dB coupling attenuation
S/FTP cables: 85 dB coupling attenuation
All GIGA-STAR cables feature high values of PS-ACR and PS-ELFEXT, and a stable 100 Ohm characteristic impedance
ensuring very low Return-Loss, making The GIGA-STAR Solution ideal for GIGABIT-Ethernet applications. All cables are
available with a PVC or Flame Retardant Low-Smoke Zero-Halogen (FR-LSZH \ HFFR) jacket and in a single or "Siamese
twin" (FIG-8) construction.

17

The Best ConnectionTM

Teldor Data Communication Cables / Category 6 Data Transmission Cables


250 MHz 100 Ohm Data Transmission Cables
Cat. 6 Screened-Pair Work Area Cables
Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

o
20 C
Typical Value

Cat. 6

Typical Value

Cat. 6

Typical

Cat. 6

Value

Typical

Cat. 6

Value

Typical

Cat. 6

Value

Typical

Cat. 6

Value

3.0

3.1

90.0

72.3

93.0

75.3

22.0

20.0

90.0

65.0

93.0

68.0

5.6

5.8

85.0

63.3

88.0

66.3

25.0

23.0

90.0

53.0

93.0

56.0

10

8.7

9.0

85.0

57.3

88.0

60.4

28.0

25.0

80.0

45.0

83.0

48.0

20

12.4

12.8

85.0

52.8

88.0

55.8

28.0

25.0

80.0

39.0

83.0

42.0

30

15.3

15.8

85.0

50.1

88.0

53.1

27.0

23.8

70.0

35.5

73.0

38.5

100

29.0

29.9

80.0

42.3

83.0

45.3

24.0

21.1

63.0

25.0

66.0

28.0

150

36.2

37.4

80.0

39.7

83.0

42.7

22.0

18.8

60.0

21.5

63.0

24.5

200

42.5

43.8

80.0

37.8

83.0

40.8

21.0

18.0

58.0

19.0

61.0

22.0

250

48.2

49.7

77.0

36.3

80.0

39.3

20.0

17.3

55.0

17.0

58.0

20.0

Cat. 6 Screened-Pair Horizontal Cables


Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

20 C
Typical

Cat. 6

Typical

Cat. 6

Value

Value

Typical

Cat. 6

Typical

Cat. 6

Typical

Cat. 6

Typical

Cat. 6

Value

Value

Value

Value

2.0

2.8

90.0

72.3

93.0

75.3

22.0

20.0

90.0

65.0

93.0

68.0

3.7

3.8

85.0

63.3

88.0

66.3

25.0

23.0

90.0

53.0

93.0

56.0

10

5.7

6.0

85.0

57.3

88.0

60.4

28.0

25.0

80.0

45.0

83.0

48.0

20

8.1

8.5

85.0

52.8

88.0

55.8

28.0

25.0

80.0

39.0

83.0

42.0

30

10.0

10.5

85.0

50.1

88.0

53.1

27.0

23.8

70.0

35.5

73.0

38.5

100

19.0

19.9

80.0

42.3

83.0

45.3

24.0

21.1

63.0

25.0

66.0

28.0

150

23.6

24.9

80.0

39.7

83.0

42.7

22.0

18.8

60.0

21.5

63.0

24.5

200

27.7

29.1

80.0

37.8

83.0

40.8

21.0

18.0

58.0

19.0

61.0

22.0

250

31.4

33.0

77.0

36.3

80.0

39.3

20.0

17.3

55.0

17.0

58.0

20.0

18

The Best ConnectionTM

Teldor Data Communication Cables / Category 6 Data Transmission Cables


250 MHz 100 Ohm Data Transmission Cables

Category 6 Data Transmission Cables


Teldor P/N

Product Description

Computer & LAN


Applications

Outer Jacket
Material

Outer Diameter
(mm nom.)

720KZ04xxx

Cat. 6 4x2x24/7 AWG U/UTP Work


Area PVC

High bandwidth digital


applications with low BER

FR-PVC

6.5

9828022xxx

Cat. 6 4x2x26/7 AWG U/FTP Work


Area PVC

High bandwidth digital


applications with low BER

FR-PVC

6.3

9828026xxx

Cat. 6 4x2x26/7 AWG S/FTP Work


Area PVC

High bandwidth digital


applications with low BER

FR-PVC

6.4

750AZ04xxx

Cat. 6 4x2x23/1 AWG U/UTP PVC

Indoor use, fixed installations

FR-PVC

6.7

750BZ04xxx

Cat. 6 4x2x23/1 AWG U/UTP FRLSZH

Data-Centers/SANs

FR-LSZH

6.6

750BZR4101 Cat. 6 4x2x23/1 AWG U/UTP SWA


Outdoor Direct Burial LSZH

Trunk Cable for Local Area


Networks

UV resistant PO
compound

12.7

750UZ04xxx

Cat. 6 4x2x23/1 AWG U/UTP


Indoor/Outdoor FR-LSZH/FR-LSZH

Low temperature
Indoor/Outdoor applications

FR-LSZH

8.3

8300204xxx

Cat. 6 4x2x23/1 AWG U/FTP FRLSZH

Indoor use, fixed installations

FR-LSZH

7.3

8300804xxx

Cat. 6 2x(4x2x23/1 AWG) FIG-8


U/FTP FR-LSZH

Trunk Cable for Local Area


Networks

FR-LSZH

7.6

8300904101

Cat. 6 4x2x23/1 AWG U/FTP


Outdoor LSZH

Indoor/Outdoor use, fixed


installations

FR-LSZH

9.6

8300C04101 Cat. 6 4x2x23/1 AWG U/FTP CSA


FR-LSZH/PE

Outdoor and direct burial


installations

UV Resistant FR 13.2
-PO

830D104xxx

Trunk Cable for Local Area


Networks

UV resistant FR- 7.4


PVC

Cat. 6 4x2x23/1 AWG U/FTP Drop


PVC

19

The Best ConnectionTM

Teldor Data Communication Cables / Category 6A Data Transmission Cables


500 MHz Data Transmission Cables

The GIGA-TEN Solution


CATEGORY 6A, 100 Ohm
500 MHz DATA TRANSMISSION CABLES
Teldor's Giga-Ten Solution cables is a complete line of data-transmission horizontal and work area cables, designed for
state-of-the-art cabling systems including Class EA of ISO/IEC 11801 and Cat. 6A of IEC 61156-5/6.
These cables are tested up to 650 MHz, and are fully compatible with the ISO/IEC 11801, IEC 61156-5, IEC 61156-6,
and TIA/EIA 568C.
Teldor's Cat. 6A cables come in the following designs:
U/FTP cables grounded, where high AXT, NEXT and FEXT attenuation values are achieved by individual pair
shielding
U/FTP cables ungrounded, where high AXT, NEXT and FEXT attenuation values are achieved by individual pair
shielding. These cables may be terminated with non-shielded connecting hardware with out any performance or
EMC issues. (Detailed technical information about this unique design can be found at the following link -

http://www.teldor.com/files.php?actions=show&id=1117).
F/FTP cables, where high AXT, NEXT and FEXT attenuation values are achieved by both overall and individual pair
aluminum foil shields
S/FTP cables,where high AXT, NEXT and FEXT attenuation values are achieved by both overall copper braid and
individual pair aluminum foil shields. This structure is recommended for PoE (Power over Ethernet) applications
Giga-Ten Cat. 6A Solution cables have Coupling Attenuation complying with Type II and Type I (depending on shield
design) requirements per IEC 61156-5/6 therefore AXT performance is proven by design.
The cable's high values of PS-ACR and PS-ELFEXT attenuation, and a stable 100 Ohm characteristic impedance
ensuring very low Return-Loss, make it ideal for 1 and 10 GIGABIT-Ethernet applications.
All cables are available with a PVC or Flame Retardant Low-Smoke Zero-Halogen (FR-LSZH \ HFFR) jackets as well as
other compounds, and in single or "Siamese twin" (FIG-8) constructions.

21

The Best ConnectionTM

Teldor Data Communication Cables / Category 6A Data Transmission Cables


500 MHz Data Transmission Cables

Cat. 6A Screened-pair Work Area Cables


Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ANEXT

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

dB

o
20 C
Typical

Cat. 6

Value

Typical

Cat. 6

Value

Typical Cat. 6
Value

Typical Cat. 6
Value

Typical

Cat. 6

Value

Typical

Cat. 6

Value

Typical

Cat. 6

3.0

3.1

95.0

72.3

98.0

75.3

22.0

20.0

70.0

67.0

85.0

65.0

88.0

68.0

5.6

5.8

95.0

63.3

98.0

66.3

25.0

23.0

70.0

67.0

73.0

53.0

76.0

56.0

10

8.7

9.0

95.0

57.3

98.0

60.3

28.0

25.0

70.0

67.0

65.0

45.0

68.0

48.0

20

12.4

12.8

90.0

52.8

93.0

55.8

28.0

25.0

70.0

67.0

59.0

39.0

62.0

42.0

30

15.3

15.8

85.0

50.1

88.0

53.1

27.0

23.8

70.0

67.0

55.4

35.4

58.4

38.4

100

29.0

29.9

80.0

42.3

83.0

45.3

24.0

21.1

67.0

62.5

45.0

25.0

48.0

28.0

150

36.2

37.4

78.0

39.7

81.0

42.7

22.0

18.8

66.0

59.8

41.5

21.5

44.5

24.5

200

42.5

43.8

78.0

37.8

81.0

40.8

21.0

18.0

65.0

58.0

49.0

19.0

52.0

22.0

250

48.2

49.7

75.0

36.3

78.0

39.3

20.0

17.3

63.0

56.5

37.0

17.0

40.0

20.0

300

53.4

55.1

75.0

35.1

78.0

38.1

19.0

17.3

62.0

55.3

35.5

15.5

38.5

18.5

400

63.1

65.1

70.0

33.3

73.0

36.3

19.0

17.3

61.0

53.4

33.0

13.0

36.0

16.0

500

71.9

74.0

70.0

31.8

73.0

34.8

19.0

17.3

59.0

52.0

31.0

11.0

34.0

14.0

22

Value

The Best ConnectionTM

Teldor Data Communication Cables / Category 6A Data Transmission Cables


500 MHz Data Transmission Cables

Cat. 6A Screened-pair Horizontal Cables*


Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ANEXT

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

dB

o
20 C
Typical

Cat. 6A

Typical

Cat. 6A

Typical

Cat. 6A Typical Cat. 6


A

Typical

Value

Value

Value

Cat. 6A

Typical

Cat. 6A

Typical

Cat. 6A

Value
Value

Value

Value

2.0

2.0

95.0

72.3

98.0

75.3

22.0

20.0

70.0

67.0

85.0

65.0

88.0

68.0

3.7

3.8

95.0

63.3

98.0

66.3

25.0

23.0

70.0

67.0

73.0

53.0

76.0

56.0

10

5.6

5.9

95.0

57.3

98.0

60.3

28.0

25.0

70.0

67.0

65.0

45.0

68.0

48.0

20

7.9

8.4

90.0

52.8

93.0

55.8

28.0

25.0

70.0

67.0

59.0

39.0

62.0

42.0

30

9.7

10.3

85.0

50.1

88.0

53.1

27.0

23.8

70.0

67.0

55.4

35.4

58.4

38.4

100

18.0

19.1

80.0

42.3

83.0

45.3

24.0

21.1

67.0

62.5

45.0

25.0

48.0

28.0

150

22.4

23.6

78.0

39.7

81.0

42.7

22.0

18.8

66.0

59.8

41.5

21.5

44.5

24.5

200

26.0

27.6

78.0

37.8

81.0

40.8

21.0

18.0

65.0

58.0

49.0

19.0

52.0

22.0

250

29.4

31.0

75.0

36.3

78.0

39.3

20.0

17.3

63.0

56.5

37.0

17.0

40.0

20.0

300

32.5

34.3

75.0

35.1

78.0

38.1

19.0

17.3

62.0

55.3

35.5

15.5

38.5

18.5

400

38.0

40.0

70.0

33.3

73.0

36.3

19.0

17.3

61.0

53.4

33.0

13.0

36.0

16.0

500

43.0

45.2

70.0

31.8

73.0

34.8

19.0

17.3

59.0

52.0

31.0

11.0

34.0

14.0

*Supplied cables meet the minimum Cat. 6A transmission requirements as per IEC 61156-5 Ed. 2

23

The Best ConnectionTM

Teldor Data Communication Cables / Category 6A Data Transmission Cables


500 MHz Data Transmission Cables

Category 6A Cables
Teldor P/N

Product Description

Computer & LAN


Applications

Outer Jacket
Material

Outer Diameter
(mm nom.)

9828U22xxx

Cat. 6A 4x2x26/7 AWG U/FTP


Ungrounded U/UTP use Workarea FRLSZH

High bandwidth digital


applications with low BER

FR-LSZH

6.1

9828U61xxx

Cat. 6A 4x(2x24/1 AWG) U/FTP


ungrounded FR-LSZH

Indoor use, fixed


installations

FR-LSZH

6.4

9828U71xxx

Cat. 6A 4x(2x24/1 AWG) U/FTP


ungrounded FR-PVC

Indoor use, fixed


installations

FR-PVC

6.4

9828G22xxx

Cat. 6A 4x2x26/7 AWG U/FTP Work Area High bandwidth digital


FR-LSZH
applications with low BER

FR-LSZH

6.0

9828G24xxx

Cat. 6A 4x2x0.45/1 mm U/FTP Workarea


FR-LSZH

High bandwidth digital


applications with low BER

FR-LSZH

6.3

83U0204xxx

Cat. 6A 4x2x23/1 AWG U/FTP


Ungrounded U/UTP use FR-LSZH

Indoor use, fixed


installations

FR-LSZH

7.4

83UM204xxx Cat. 6A 4x2x23/1 AWG U/FTP


Ungrounded U/UTP use FR-LSZH IEC
60332-3

Indoor use, fixed


installations

FR-LSZH

8.0

83G0204xxx

Cat. 6A 4x2x23/1 AWG U/FTP FR-LSZH

Indoor use, fixed


installations

FR-LSZH

7.3

83G0208xxx

Cat. 6A 2x(4x2x23/1 AWG) FIG-8 U/FTP


FR-LSZH

Indoor use, fixed


installations

FR-LSZH

7.3

Indoor/Outdoor use, fixed


installations

FRZH-PU

9.0

83GU204xxx Cat. 6A 4x2x23/1 AWG U/FTP


Indoor/Outdoor FR-LSZH/HFFR-PU

24

The Best ConnectionTM

Teldor Data Communication Cables / Category 7 Data Transmission Cables


600 MHz Data Transmission Cables

The GIGA-DOR Solution

CATEGORY 7, 100 Ohm


600 MHz DATA TRANSMISSION CABLES

The GIGA-DOR Solution is a complete line of high-performance Cat. 7 horizontal and work area data cables, designed for
CLASS F links and for advanced high data-rate networks, available in a wide range of constructions.
TELDOR's GIGA-DOR Solution cables conform to the ISO/IEC 11801 requirements for Cat. 7 cables as specified in IEC
61156-5 and 61156-6. These cables are composed of balanced twisted pairs having a nominal 100 Ohm characteristic
impedance up to 600 MHz, with a very high NEXT loss.
The high NEXT loss, achieved by individual aluminum foil pair shields, provides a typical margin of 60 dB ACR over U/UTP
cables, making GIGA-Solution cables ideal for multiple high-frequency services.
GIGA-DOR & GIGA-DOR Jr. S/FTP horizontal cables and GIGA-Patch 4 pair S/FTP 26 AWG work area (patch) cables are
overall shielded with a tin-coated copper braid. When properly grounded, this copper braid and the individual aluminum foil
shields provide exceptional EMC performance, having a minimum coupling attenuation of 90 dB.
All cables are available with flame-retardant PVC or halogen-free (HFFR) jackets, in a range of colors, in single or
"Siamese" twin (FIG-8) constructions.

25

The Best ConnectionTM

Teldor Data Communication Cables / Category 7 Data Transmission Cables


600 MHz Data Transmission Cables

Cat. 7 Work Area Cables


Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ANEXT

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

dB

o
20 C
Typical

Cat. 7

Typical

Cat. 7

Typical

Cat. 7

Typical

Cat. 7

Typical

Cat. 7

Typical

Cat. 7

Typical

Cat. 7

Value
Value

Value

Value

Value

Value

Value

2.9

3.0

105.0

99.4

108.0

102.4

22.0

20.0

68.0

N/A

95.0

75.0

98.0

78.0

5.4

5.6

98.0

90.4

101.0

93.4

25.0

23.0

68.0

N/A

90.0

75.0

93.0

78.0

10

8.5

8.8

95.0

84.4

98.0

87.4

28.0

25.0

68.0

N/A

86.0

71.0

89.0

74.0

20

12.1

12.4

90.0

80.0

93.0

83.0

28.0

25.0

68.0

N/A

80.0

65.0

83.0

68.0

30

14.8

15.3

85.0

77.2

88.0

80.2

27.0

23.8

68.0

N/A

76.0

61.5

79.0

64.5

100

27.7

28.5

80.0

69.4

83.0

72.4

24.0

21.1

68.0

N/A

66.0

51.0

69.0

54.0

150

34.3

35.3

78.0

66.7

81.0

69.7

22.0

18.8

65.0

N/A

63.0

47.5

66.0

50.5

200

40.0

41.2

78.0

65.0

81.0

68.0

21.0

18.0

65.0

N/A

60.0

45.0

63.0

48.0

250

45.1

46.5

75.0

63.4

78.0

66.4

20.0

17.3

62.0

N/A

58.0

43.0

61.0

46.0

300

49.7

51.3

75.0

62.2

78.0

65.2

19.0

17.3

62.0

N/A

52.0

41.5

55.0

44.5

400

58.2

60.0

70.0

60.4

73.0

63.4

19.0

17.3

62.0

N/A

49.0

38.9

52.0

41.9

500

65.8

67.9

70.0

58.9

73.0

61.9

19.0

17.3

62.0

N/A

47.0

37.0

50.0

40.0

600

72.9

75.1

70.0

57.7

73.0

60.7

19.0

17.3

62.0

N/A

45.0

35.4

48.0

38.4

26

The Best ConnectionTM

Teldor Data Communication Cables / Category 7 Data Transmission Cables


600 MHz Data Transmission Cables

Cat. 7 Horizontal Cables


Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ANEXT

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

dB

o
20 C
Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

2.0

2.0

105.0

75.0

108.0

78.0

22.0

20.0

68.0

N/A

95.0

75.0

98.0

78.0

3.6

3.7

98.0

75.0

101.0

78.0

25.0

23.0

68.0

N/A

90.0

75.0

93.0

78.0

10

5.6

5.8

95.0

75.0

98.0

78.0

28.0

25.0

68.0

N/A

86.0

71.0

89.0

74.0

20

7.9

8.3

90.0

75.0

93.0

78.0

28.0

25.0

68.0

N/A

80.0

65.0

83.0

68.0

30

9.7

10.2

85.0

75.0

88.0

78.0

27.0

23.8

68.0

N/A

76.0

61.5

79.0

64.5

100

18.0

19.0

80.0

69.4

83.0

72.4

24.0

21.1

68.0

N/A

66.0

51.0

69.0

54.0

150

22.4

23.6

78.0

66.7

81.0

69.7

22.0

18.8

65.0

N/A

63.0

47.5

66.0

50.5

200

26.0

27.5

78.0

65.0

81.0

68.0

21.0

18.0

65.0

N/A

60.0

45.0

63.0

48.0

250

29.4

31.0

75.0

63.4

78.0

66.4

20.0

17.3

62.0

N/A

58.0

43.0

61.0

46.0

300

32.5

34.2

75.0

62.2

78.0

65.2

19.0

17.3

62.0

N/A

52.0

41.5

55.0

44.5

400

38.0

40.0

70.0

60.4

73.0

63.4

19.0

17.3

62.0

N/A

49.0

38.9

52.0

41.9

500

43.0

45.2

70.0

58.9

73.0

61.9

19.0

17.3

62.0

N/A

47.0

37.0

50.0

40.0

600

47.6

50.1

70.0

57.7

73.0

60.7

19.0

17.3

62.0

N/A

45.0

35.4

48.0

38.4

27

The Best ConnectionTM

Teldor Data Communication Cables / Category 7 Data Transmission Cables


600 MHz Data Transmission Cables

Category 7 Cables
Teldor P/N

Product Description

Computer & LAN


Applications

Outer Jacket
Material

Outer Diameter
(mm nom.)

9928244xxx Cat. 7 4x2x26/7 AWG S/FTP Work


Area FR-LSZH

High data rates

FR-LSZH

6.4

9928264xxx Cat. 7 4x2x26/7 AWG S/FTP Work


Area PU

Outdoor installations

PU

6.5

9928312xxx Cat. 7 12x(4x2x26/7 AWG S/FTP)


Multi-Cable Work Area FR-LSZH

Indoor Backbone

FR-LSZH

27.8

9827A54xxx Cat. 7 4x2x23/1 AWG F/FTP FRLSZH

Indoor use, fixed


installations

FR-LSZH

7.4

9928675xxx Cat. 7 1000 MHz 4x2x23/1 AWG


S/FTP FR-LSZH

Indoor use, fixed


installations

FR-LSZH

7.5

9928654xxx Cat. 7 4x2x23/1 AWG S/FTP FRLSZH

Data-Centers/SANs

FR-LSZH

8.0

9928554xxx Cat. 7 4x2x22/1 AWG S/FTP FRLSZH

Indoor use, fixed


installations

FR-LSZH

8.2

9928692xxx Cat. 7 2x(4x2x23/1 AWG) FIG-8


S/FTP FR-LSZH

Data-Centers/SANs

FR-LSZH

8.0

9928604xxx Cat. 7 4x2x23/1 AWG S/FTP FR-PVC

Indoor use, fixed


installations

FR-PVC

7.8

9928659xxx Cat. 7 4x2x23/1 AWG S/FTP CSA


Direct Burial PE

Outdoor and direct burial


installations

PE

12.0

28

The Best ConnectionTM

Teldor Data Communication Cables / Category 7A Data Transmission Cables


1000 MHz Data Transmission Cables

The GIGA-DOR Solution


CATEGORY 7A, 100 Ohm
1000 MHZ DATA TRANSMISSION CABLES

Teldor's Giga-Ten Solution cables are a complete line of horizontal and work area data-transmission cables, designed
for state-of-the-art cabling systems including IEEE 802.3ae, ISO/IEC 11801 otherwise known as 10 GBaseT.
These cables are tested up to 1200 MHz, and are fully compatible with the ISO/IEC 11801, IEC 61156-5, and IEC
61156-6 with the highest coupling attenuation level Type I, which makes the application to be defined as "Alien
Crosstalk proven by design".
Giga-Ten Solution cables come in S/FTP shielding structure where very high NEXT and FEXT values and outstanding
EMC performance are achieved.
Giga-Ten Solution cables have Coupling Attenuation complying with Type I requirements as per IEC 61156 therefor the
AXT requirements are achieved by design, and feature high values of PS-ACR and PS-ELFEXT attenuations together
with a stable 100 Ohm characteristic impedance ensuring high Return-Loss attenuation, making them ideal for very high
bandwidth applications as 10 GBase-T.
Giga-Ten horizontal and work area cables are compatible with shielded RJ45 connecting hardware, allowing use in
variety of communication application including Video Over Ethernet and IEEE 802.3af (Power over Ethernet) and IEEE
802.3at (Power over Ethernet Plus).
The cables are available with a FR-PVC or Flame Retardant Low-Smoke Zero-Halogen (FR-LSZH \ HFFR) jacket and in
single or "Siamese twin" (FIG-8) constructions.

29

The Best ConnectionTM

Teldor Data Communication Cables / Category 7A Data Transmission Cables


1000 MHz Data Transmission Cables

Cat. 7A Work Area Cables


Freq.

Attenuation

PS NEXT Loss

NEXT Loss

RL

PS ANEXT

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

dB

20 C
Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

2.9

3.0

96.0

75.0

99.0

78.0

22.0

20.0

78.0

67.0

90.0

70.0

93.0

N/A

5.4

5.6

96.0

75.0

99.0

78.0

25.0

23.0

78.0

67.0

90.0

70.0

93.0

N/A

10

8.5

8.7

96.0

75.0

99.0

78.0

28.0

25.0

78.0

67.0

86.0

70.0

89.0

N/A

20

12.1

12.3

94.0

75.0

97.0

78.0

28.0

25.0

78.0

67.0

80.0

65.0

85.0

N/A

30

14.8

15.0

90.0

75.0

93.0

78.0

27.0

23.8

78.0

67.0

76.0

61.5

80.0

N/A

100

27.0

27.8

85.0

75.0

88.0

78.0

24.0

21.1

78.0

67.0

66.0

51.0

70.0

N/A

200

38.3

39.7

85.0

71.0

88.0

74.0

21.0

18.0

78.0

67.0

60.0

45.0

65.0

N/A

300

46.9

49.0

85.0

68.2

88.0

71.2

21.0

15.6

78.0

67.0

52.0

41.5

57.0

N/A

600

66.3

70.6

80.0

63.7

83.0

66.7

20.0

15.6

75.0

64.0

45.0

35.5

52.0

N/A

700

71.7

76.7

80.0

62.7

83.0

65.4

19.0

15.6

73.0

63.0

45.0

34.0

52.0

N/A

900

81.3

87.7

80.0

61.1

83.0

64.1

19.0

15.6

73.0

61.0

45.0

32.0

52.0

N/A

1000

85.0

92.9

78.0

60.4

81.0

63.4

19.0

15.6

73.0

60.0

45.0

31.0

50.0

N/A

1100

89.8

N/A

78.0

N/A

81.0

N/A

18.0

N/A

73.0

N/A

45.0

N/A

50.0

N/A

1200

93.8

N/A

78.0

N/A

81.0

N/A

18.0

N/A

73.0

N/A

45.0

N/A

50.0

N/A

30

Value

The Best ConnectionTM

Teldor Data Communication Cables / Category 7A Data Transmission Cables


1000 MHz Data Transmission Cables

Cat. 7A Horizontal Cables


Freq.

Attenuation

NEXT Loss

PS-NEXT Loss

RL

PS ANEXT

PS ELFEXT

ELFEXT

MHz

dB/100m

dB

dB

dB

dB

dB

dB

o
20 C
Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

Value

Typical

Cat. 7

1.8

2.0

103.0

78.0

100.0

75.0

31.0

20.0

100.0

67.0

108.0

75.0

110.0

78.0

3.2

3.8

103.0

78.0

100.0

75.0

31.0

23.0

100.0

67.0

105.0

75.0

108.0

78.0

10

4.9

5.8

103.0

78.0

100.0

75.0

31.0

25.0

100.0

67.0

100.0

71.0

103.0

74.0

20

7.0

8.2

103.0

78.0

100.0

75.0

31.0

25.0

100.0

67.0

90.0

65.0

93.0

68.0

30

8.6

10.1

103.0

78.0

100.0

75.0

31.0

23.8

100.0

67.0

90.0

61.5

93.0

64.5

100

15.7

18.5

103.0

78.0

100.0

75.0

31.0

21.1

100.0

62.5

85.0

51.0

88.0

54.0

150

19.4

22.8

103.0

78.0

100.0

75.0

26.0

18.8

95.0

59.8

84.0

47.5

87.0

50.5

200

22.5

26.5

98.0

76.8

95.0

73.8

26.0

18.0

95.0

58.0

80.0

45.0

83.0

48.0

250

25.3

29.7

96.0

75.4

93.0

72.4

25.0

17.3

92.0

56.5

78.0

43.0

81.0

46.0

300

27.8

32.7

95.0

74.2

92.0

71.2

25.0

17.3

92.0

55.3

75.0

41.5

78.0

44.5

400

32.3

38.0

94.0

72.3

91.0

69.3

23.0

17.3

92.0

53.4

70.0

38.9

73.0

41.9

500

36.3

42.7

93.0

70.9

90.0

67.9

23.0

17.3

90.0

52.0

69.0

37.0

72.0

40.0

600

40.0

47.1

92.0

69.7

89.0

66.7

23.0

17.3

90.0

50.8

68.0

35.4

71.0

38.4

1000

52.7

62.0

88.0

66.4

85.0

63.4

21.0

17.3

90.0

47.5

67.0

31.0

70.0

34.0

31

Value

The Best ConnectionTM

Teldor Data Communication Cables / Category 7A Data Transmission Cables


1000 MHz Data Transmission Cables

Category 7A Data Transmission Cables


Teldor P/N

Product Description

Computer & LAN Applications Outer Jacket


Material

Outer Diameter
(mm nom.)

992G244xxx

Cat. 7A 4x2x26/7 AWG S/FTP


Work Area FR-LSZH

High bandwidth digital


applications with low BER

FR-LSZH

6.3

99XG504xxx

Cat. 7A 4x2x23/1 AWG S/FTP FR- Data-Centers/SANs


LSZH

FR-LSZH

8.1

99XG508xxx

Cat. 7A 2x(4x2x23/1 AWG) FIG-8


S/FTP FR-LZSH

FR-LSZH

8.1

99XG254xxx

Cat. 7A 4x2x22/1 AWG S/FTP FR- Indoor use, fixed installations


LSZH

FR-LSZH

8.7

99XG258xxx

Cat. 7A 2x(4x2x22/1 AWG) FIG-8


S/FTP FR-LSZH

FR-LSZH

8.7

99XG524xxx

Cat. 7A 4x2x23/1 AWG S/FTP ND Indoor use, fixed installations


FR-LSZH IEC60332-3

FR-LSZH

8.4

99XG954xxx

Cat. 7A 4x2x22/1 AWG S/FTP


OUTDOOR PVC

Outdoor installations

UV resistant
FR-PVC

10.4

99XGM07xxx Cat. 7A 7x(4x2x23/1 AWG)


S/FTP) Multi-Cable FR-LSZH

Indoor Backbone

FR-LSZH

27.5

99XGM12xxx Cat. 7A 12x(4x2x23/1 AWG)


S/FTP) Multi-Cable FR-LSZH

Indoor Backbone

FR-LSZH

35
8.0

Data-Centers/SANs

Indoor Backbone

99XG544xxx

Cat. 7A 4x2x23/1 AWG S/FTP FR- Data-Centers/SANs


LSZH

FR-LSZH

99XG548xxx

Cat. 7A 2x(4x2x23/1 AWG) FIG-8


S/FTP FR-LZSH

FR-LSZH

99XG854xxx

Cat. 7A 4x2x23/1 AWG S/FTP FR- Data-Centers/SANs


LSZH/PVC

Data-Centers/SANs

32

FR-PVC

10.4

The Best ConnectionTM

Teldor Data Communication Cables / Data Center Cables


Multi-Pair/Core/Cable Data Transmission Cables

DATA CENTER CABLES


We

at Teldor know that your Data Center is much more than a space that houses servers and network equipment. In the

IT world we live in today, the Data Center has become the most critical asset and a crucial investment for nearly
every organization. It is truly the operations center of every business: housing all the critical applications, equipment and
systems needed to run the business - to enable every transaction, communication and task; providing the
communication links to customers and business partners and suppliers around the world; and even controlling building
environmental, security and life safety systems.
Faced with today's fundamental importance of the Data Center and the need to provide for daily increasing applications,
transmission speeds and data storage, businesses are investing in the amount of equipment their Data Centers must
support. Consequently, IT managers must design scalable Data Centers to support their future growth and potentially
new technologies, while ensuring the best performance.
TELDOR Data-Center cables consist of Cat.5e to Cat.7A multi-cable, multi-pair and multi-core structures solid and
matched work area cables.
All cables are fully compatible with the standard connecting hardware (i.e. RJ-45)
All products are available with FR-LSZH, PVC, PU and PE jackets combined with different optional shielding
structures such as S/FTP, SF/UTP, F/UTP, U/FTP.
The cables are designed with optimized lay lengths, size, transmission performance and structures to enable peak
high density data-center cabling.
High-density cabling creates less congestion in pathways which means better cooling conditions in particular for PoE
and PoE+ applications, lower installation time, minimizes down time, accelerates recovery time, minimizes site
access by non-essential personnel, and allows place-and-plug modular installation for Gigabit and up to 10 Gigabit
applications.
Teldor Meets Your Cabling System Needs
As your Data Center partner, Teldor offers an in-depth knowledge of structured cabling, Data Centers and the
interaction between them. Teldor understands the needs and design challenges and has leveraged its expertise in the
design of highly-flexible, end-to-end structured cabling systems that are unique in their ability to provide optimal system
performance, while simultaneously solving your density and manageability issues both now and in the future.

33

The Best ConnectionTM

Teldor Data Communication Cables / Data Center Cables


Multi-Pair/Core/Cable Data Transmission Cables

Data Center Cables


Teldor P/N

Product Description

Frequency Range
(MHz)

Outer Jacket
Material

7564004xxx

Cat. 5e 4x(4x2x24/1 AWG) U/UTP Multi-Cable PVC

1 - 100

FR-PVC

7564012xxx

Cat. 5e 12x(4x2x24/1 AWG) U/UTP Multi-Cable PVC

1 - 100

FR-PVC

7574008xxx

Cat. 5e 8x(4x2x24/1 AWG) U/UTP Multi-Cable FR-LSZH

1 - 100

FR-LSZH

7574025xxx

Cat. 5e 25x(4x2x24/1 AWG) U/UTP Multi-Cable FR-LSZH

1 - 100

FR-LSZH

75AZM04xxx

Cat. 6 4x(4x2x23/1 AWG) U/UTP Multi-Cable PVC

1 - 250

FR-PVC

75VZM06xxx

Cat. 6 6x(4x2x23/1 AWG) U/UTP Multi-cable PVC-R

1 - 250

FR-PVC

75VZM08xxx

Cat. 6 8x(4x2x23/1 AWG) U/UTP Multi-cable PVC-R

1 - 250

FR-PVC

9928A12xxx

Cat. 6A 12x(4x2x26/7 AWG U/FTP) Multi-Cable Work Area


PVC

1 - 500

FR-PVC

9928M08xxx

Cat. 7 8x(4x2x26/7 AWG U/FTP) Multi-Cable Work Area FR- 1 - 600


LSZH IEC 60332-3

FR-LSZH

9928M16xxx

Cat. 7 16x(4x2x26/7 AWG U/FTP) Multi-Cable Work Area FR 1 - 600


-LSZH IEC 60332-3

FR-LSZH

992G244xxx

Cat. 7A 4x2x26/7 AWG S/FTP Work Area FR-LSZH

1 - 1000

FR-LSZH

99XGM03xxx Cat. 7A 3x(4x2x23/1 AWG) S/FTP Multi-Cable FR-LSZH

1 - 1000

FR-LSZH

99XGM06xxx Cat. 7A 6x[4x2x23/1 AWG S/FTP] Multi-Cable FR-LSZH

1 - 1000

FR-LSZH

99XGM07xxx Cat. 7A 7x(4x2x23/1 AWG) S/FTP Multi-Cable FR-LSZH

1 - 1000

FR-LSZH

99XGM12xxx Cat. 7A 12x(4x2x23/1 AWG S/FTP) Multi-Cable FR-LSZH

1 - 1000

FR-LSZH

34

The Best ConnectionTM

Teldor Data Communication Cables


Closing Pages

Warranty Applicable to Products Sold by Teldor Cables & Systems Ltd. (Teldor")
1. Teldor warrants that the products, under normal use, shall meet in all material respects the specifications of Teldor for such
products as reflected in the respective Teldor Data Specifications Sheet, for the following periods of time from the time of
completion of production (the Warranty Period):
A Warranty Period of 15 years shall apply to the products expressly listed below only:
Data transmission cables with 100 characteristic impedance, made of twisted pairs, designated as Category 5, Category
5e, Category 6, Category 6A, Category 7, Category 7A, or "Category 8"
Data transmission cables made of optical fibers
Instrumentation, Control and signal cables made of copper conductors
Telecom cables made of twisted pairs of copper conductors
Low voltage electric power cables
Coaxial, Twinaxial and Triaxial cables
Electronic and Audio cables for analog and/or digital transmission
Industrial Ethernet or Industrial BUS cables
A Warranty Period of one year shall apply to all products, other than those expressly listed above.
2. Teldor warrants further that at the time of delivery the products shall be adequately contained, packed and labeled and
conform in all material respects to statements made by Teldor on any container packaging or label.
3. Under no circumstances shall Teldor be liable for any repair or replacement needed in whole or in part (i) as a result of
inappropriate environment, improper storage, transportation, handling, installation, use, removal, modification, maintenance or
repair, negligence or fault, by any party other than by Teldor; or (ii) as a result of accident.
4. During the Warranty Period Teldor shall, at Teldors discretion, either repair, replace or give credit for the purchase price of,
any defective products found to fail to comply with this Warranty and returned by the Buyer to Teldor. In no event shall Teldor
be liable for damages in excess of the purchase price received by Teldor for the product. Teldor shall acquire the ownership of
all the products that have been replaced or given credited for. This Warranty shall also apply to the repaired or replacement
part during the remaining portion of the Warranty Period, if any.
5. This Warranty applies only if (i) Teldor has received a written notice from the Buyer giving details of the defective item
before the end of the Warranty Period, (ii) Teldor has been afforded a reasonable opportunity to inspect the item in question,
and (iii) the Buyer has provided at its expense all assistance and support needed by Teldor to fulfill its obligations under this
Warranty.
6. To the extent permitted by applicable law, this Warranty is exclusive and constitutes the entire warranty and liability of
Teldor with respect to the products, and all other warranties or liabilities imposed or implied by statute, law or custom are
explicitly excluded. In no circumstances shall Teldor have any liability for consequential or indirect loss or damage no matter
how arising, or of any loss arising out or in connection with the ability or inability to use the products. Teldor expressly
excludes liability for all costs associated with the installation of the replacement items, the removal of the items being
removed, and the repair of defective items other than at Teldors premises.
The full description of the terms, conditions and limitations of the Teldor warranty are agreed on a case-by-case basis.

35

The Best ConnectionTM

Teldor Data Communication Cables


Closing Pages
TELDOR CABLES & SYSTEMS LTD.

1) Governing Terms
a) These terms and conditions apply to all products sold by Teldor Cables & Systems Ltd., an Israeli corporation
(Teldor"), to the Buyer.
b) Any addition, deletion or alternation proposed by the Buyer but not expressly agreed and confirmed in writing by the
Buyer, shall not bind the parties and shall not constitute part of the contract.

2) Delivery
a) Teldor shall use reasonable efforts to adhere to the stated delivery date, but Teldor shall not be liable for any loss
resulting from any delay in delivery, nor shall the Buyer be entitled to cancel the contract by reason only of Teldor's
failure to deliver at the stated time.
b) The products shall be delivered in accordance with the provisions of the specific INCOTERMS 2000 specified.
c) Where products are delivered in installments, each installment shall be deemed a separate sale. Default of Teldor in
respect of any one or more installments shall not entitle the Buyer to repudiate the contract with regard to any other
installments.

3) Risk

and Title

a) Risk or loss or damage to and in the products, including associated risk of hazard, shall pass to the Buyer upon
delivery.
b) The products shall remain the property of Teldor unless and until Teldor receives all payments due for the products.
Until used, the Buyer shall not remove, or obscure any label or marking which may allow the products to be identified.
When the products are incorporated into another product by the Buyer or otherwise, title to such other products shall
vest in Teldor until payment in full as aforesaid. The Buyer shall be entitled to sell such other product to a third party
before such payment, provided that all sums received by the Buyer with respect to the sale of such other product be
held in trust for the benefit of Teldor in a separate bank account until payment in full for the products.

36

The Best ConnectionTM

Teldor Data Communication Cables


Closing Pages

4) Price

and Payment

a) The purchase price to be paid for the products and the terms of payment shall be as agreed in writing between Buyer
and Seller. Teldor may at any time require the Buyer to provide security satisfactory to Teldor.
b)Unless otherwise specified overleaf, prices are exclusive of VAT, duties, taxes, levies, imposts, deposits or surcharges related to
the importation or otherwise, which shall be paid by the Buyer.
c)The Buyer may not, for any reason whatsoever, withhold any payment or claim any right of deduction or set-off against any
payment payable under the contract.
d)If the Buyer is in default in respect of the payment of any sum payable under the contract, then without prejudice to Teldor's other
rights and remedies, the Buyer shall pay Teldor cumulative interest on all overdue sums at the rate of 5% above the London Inter
Bank Rate for the currency of the contract, as certified by Teldor's bankers.

5) Claims, Warranty and Limited Liability


a) The Buyer must examine the applicable products immediately upon receipt of shipment. Claims for partial or total
non-delivery due to fault of Teldor must be made to Teldor within 10 days of receipt of shipment. In such situations,
Teldor shall have the right to examine the applicable products in their original form and the shipping records at the
Buyer's location. Failure to make a claim within said 10 days shall mean the products are deemed delivered in accurate
numbers and the full invoice shall be payable.
b) Teldor warrants that the products, under normal use, shall meet in all material respects the specifications of Teldor for
such products as reflected in the respective Teldor Data Specifications Sheet, for the following periods of time from the
time of completion of production (the Warranty Period):
A Warranty Period of 15 years shall apply to the products expressly listed below only:
Data transmission cables with 100 characteristic impedance, made of twisted pairs, designated as Category 5, Category 5e,
Category 6, Category 6A, Category 7, Category 7A, or "Category 8"

Data transmission cables made of optical fibers


Instrumentation, Control and signal cables made of copper conductors
Telecom cables made of twisted pairs of copper conductors
Low voltage electric power cables
Coaxial, Twinaxial and Triaxial cables
Electronic and Audio cables for analog and/or digital transmission
Industrial Ethernet or Industrial BUS cables

A Warranty Period of one year shall apply to all products, other than those expressly listed above.

37

The Best ConnectionTM

Teldor Data Communication Cables


Closing Pages

c) Teldor warrants further that at the time of delivery the products shall be adequately contained, packed and labeled
and conform in all material respects to statements made by Teldor on any container packaging or label.
d) Under no circumstances shall Teldor be liable for any repair or replacement needed in whole or in part (i) as a result
of inappropriate environment, improper storage, transportation, handling, installation, use, removal, modification,
maintenance or repair, negligence or fault, by any party other than by Teldor; or (ii) as a result of accident.
e) During the Warranty Period Teldor shall, at Teldors discretion, either repair, replace or give credit for the purchase
price of, any defective products found to fail to comply with this Warranty and returned by the Buyer to Teldor. In no
event shall Teldor be liable for damages in excess of the purchase price received by Teldor for the product. Teldor shall
acquire the ownership of all the products that have been replaced or given credited for. This Warranty shall also apply to
the repaired or replacement part during the remaining portion of the Warranty Period, if any.
g) This Warranty applies only if (i) Teldor has received a written notice from the Buyer giving details of the defective item
before the end of the Warranty Period, (ii) Teldor has been afforded a reasonable opportunity to inspect the item in
question, and (iii) the Buyer has provided at its expense all assistance and support needed by Teldor to fulfill its
obligations under this Warranty.
h) To the extent permitted by applicable law, this Warranty is exclusive and constitutes the entire warranty and liability of
Teldor with respect to the products, and all other warranties or liabilities imposed or implied by statute, law or custom
are explicitly excluded. In no circumstances shall Teldor have any liability for consequential or indirect loss or damage
no matter how arising, or of any loss arising out or in connection with the ability or inability to use the products. Teldor
expressly excludes liability for all costs associated with the installation of the replacement items, the removal of the
items being removed, and the repair of defective items other than at Teldors premises.

6) Buyer's

Default

a) Without prejudice to other rights and remedies available, Teldor shall be entitled to immediately terminate in whole or
in part the contract, or to immediately suspend all or any further deliveries, if:
i) any sum is due and payable under any contract between the parties and remains unpaid; or
ii) the Buyer fails to take delivery of any products under any contract between the parties; or
iii) the Buyer becomes insolvent or has a winding up resolution or order passed or made or has a receiver
appointed or suspends payments of its debts in whole or part or has proposed or entered into any composition or
arrangement with creditors or is the subject of a bankruptcy order, or any equivalent proceeding takes place
under the laws in which the Buyer is incorporated, carries on businesses or has assents.
b) Additionally, in the event of any such action, Teldor shall be entitled to require prepayment and such security, as it
may deem necessary as a condition to resuming delivery under this or any other contract with the Buyer.

38

The Best ConnectionTM

Teldor Data Communication Cables


Closing Pages
may deem necessary as a condition to resuming delivery under this or any other contract with the Buyer.

7) Intellectual

Property

a)The Buyer acknowledges Teldor's sole ownership of all present and future right, title and interest to any and all trademarks and
trade names, homologations, product registrations, patents, all applications relating to any of the know-how and other intellectual
property relating in any way to the TELDOR trade name or products. The Buyer will not impairs it's right, title, or interest to any such
intellectual property.
b)The Buyer will not use the trade name "TELDOR" and trademarks owned by Teldor in any manner or for any purpose except, to the
extent permitted by Teldor to designate products purchased by the Buyer from Teldor.

8) Force

Majeure

Seller shall not be liable for any delay or failure in the performance of its obligations, when such delay or failure results
in whole or in part from shortages or disruption in the supply of materials from normal sources, shortage of means of
transport, floods, fire, act of God, war, riot, civil insurrection, strikes, lock-outs, industrial unrest, inclement weather, acts
of civil or military authorities, or circumstances beyond Teldor's reasonable control or force majeure.

9) Notices

Notices under any contract between the parties shall be in writing and shall be deemed to have been duly given 14 days
after being mailed by prepaid registered air mail, or three days after being transmitted by facsimile or manually
delivered, addressed to the stated addresses of Teldor and the Buyer.

10) Assignment

The Buyer shall not assign the contract or any of the Buyer's rights or obligations under the contract without the prior
written consent of Teldor.

11) Governing

Law and Jurisdiction

The laws of The State of Israel shall govern the contract. All disputes in connection with the contract shall be subject to

39

The Best ConnectionTM

Teldor Data Communication Cables


Closing Pages
The laws of The State of Israel shall govern the contract. All disputes in connection with the contract shall be subject to
the exclusive jurisdiction of the competent courts of the District of Tel Aviv, unless Teldor prefers another competent
jurisdiction.

12) Entire

Agreement and Amendment

These terms and conditions contain the entire agreement between the parties with respect to the subject matter hereof;
and may not be amended other than by a written agreement signed by Teldor and the Buyer.

40

The Best ConnectionTM