RKR XXGTS
RKR XXGTS
RKR XXGTS
2. MAIN FUNCTIONS
7 Segment LED Display.
Automatic & Manual operations.
Capacitor power measuring.
Auto c/k adjustment.
Auto polarisation (current flow direction).
Over voltage protection via alarm output.
Adjustable capacitor switching on/off time.
Display of voltage & cos values.
Faults indications via LEDs in case of alarm occurance.
Fixed capacitor group output options from 1 step to 5; 7; 13 steps with nonrequired sequencing and adjustment
features.
Direct capacitor switching on/off upon system requirement aimed for serial compensation.
3.
4. PROGRAMMING
There are 5 menus available for programming of the device via the use of 4 buttons.
Cos : Target cos; adjustable range from 0.80-1.00.
Ton : Capacitor on delay switching: adjustable from 1-120 sec.
Toff : Capacitor off delay switching: adjustable from 1-120 sec.
Uhl : Over voltage protection limit; 240-300VAC adjustable.
Ope : Operation mode; auto/manual.
Cos
Press program button on main menu. Cos is selected via the use of Up-Down buttons and then SET button is
pressed to display the last set value. Program LED will start blinking. The required set value is entered via the use of
Up-Down buttons. Press SET to save. Use program button to exit.
Ton
Press program button on main menu. Ton is selected via the use Up-Down buttons and then SET button is
pressed to display the last set value. Program LED will start blinking. The required set value is entered via the use of
Up-Down buttons. Press SET to save. Use program button to exit.
Toff
Press program button on main menu. Toff is selected via the use of Up-Down buttons and then SET button is
pressed to display the last set value. Program LED will start blinking. The required set value is entered via the use of
Up-Down buttons. Press SET to save. Use program button to exit.
Uhl
Press program button on main menu. Uhl is selected via the use of Up-Down buttons and then SET button is
pressed to display the last set value. Program LED will start blinking. The required set value is entered via the use of
Up-Down buttons. Press SET to save. Use program button to exit.
Ope
Press program button on main menu. Ope (auto/manual) is selected via the use of Up-Down buttons and then
SET button is pressed to select. Program LED will start blinking. The required operation mode is selected via the
use of Up-Down buttons. Press SET to save. Use program button to exit.
5. CAPACITOR POWERS
Test mode must be applied to the device after the required parameters selected correctly. At the end of the test
process the device will show detected capacitors by blinking LEDs of capacitors.
6. OPERATION
6.1.TEST
The defines or corrects the Current Flow Direction during the test mode. Followingly, all capacitor steps are
swiched on and off one by one for computing capacitor power.
6.2.CONTACT TEST
It is assigned to test output contacts of the device when No Current status only is observed. Press SET button for
5 (five) sec. to shift into Contact Test Mode for testing while No Current text is displayed on the screen. Once
this modes activated, device will switch on and off all the contact one by one starting from first step to last. An autostop is to be performed after testing of the last step completed. Device shall not perform a measuring or changing of
the formerly recorded datas while Contact Test Mode status is activated.
7. ALARMS
7.1.Over Voltage Alarm
If the voltage of line exceeds the value determined by Uov for 4 seconds, device will switch off all the capacitors in a
way to protect against possible damages. While the device is in alarm the voltage will blink on the screen and then
the alarm output will be switched on. Alarm LED also will be on. If the voltage drops 10V below of Uov for 4
seconds device will go out of alarm status and will continue the operation normally.
8. TECHNICAL SPECIFICATIONS
Operating Voltage (Un)
Operating Range
Operating Frequency
Current Transformer Ratio
Line Current Range
Current Transformer Direction (Polarization)
C/k Adjustment
Stage Number
Output Contact
Alarm Output
Cooling Fan Output
Display
Operating Temperature
Plastic Material
Dimensions
Mounting Depth
Protection Class
Weight
9.
220VAC 20%
(0.8-1.2)xUn
50/60 Hz
/5A
0.02A-5.5A
Automatic
Automatic
UP TO 5; 7; 13 + Fxed Group, Automatic
250V/3A AC
250V/5A AC
250V/5A AC
3x7 Segmend Led Display
-25C + 65C
Nonflammable Synthetic Plastic as per UL-94, Class VO
144mmx144mm (DIN 43 700)
90mm Max.
Terminals IP 20, Housing IP 54
RKR-5GTS: 1000 gr., RKR-7GTS: 1015 gr.,
RKR-13GTS: 1080 gr.