Omron E5CWL PDF
Omron E5CWL PDF
Omron E5CWL PDF
E5CSL/E5CWL
The Simple and New Temperature
Controller is Released that Easily
Achieves the Temperature
Control.
Easy to Read (Character Height E5CSL: 21.7 mm
E5CWL: 16.2 mm (PV)).
Depth beyond front panel: Only 60 mm.
Fewer parameters for simple setup.
Faster sampling at 250 ms.
48 48 mm
E5CSL
48 48 mm
E5CWL
4-digit Display
Alarm Outputs
One
*E5CWL only
Control Output 1
Relay output
Voltage output (for driving SSR)
E5CSL-@@
E5CWL-@1@
1 2
1. Control Output
R: Relay output: 250 VAC, 3 A
Q: Voltage output (for driving SSR): 12 VDC, 21 mA
2. Sensor type
TC: Thermocouple (K, J, T, R, or S)
P: Platinum resistance thermometer (Pt100)
1 2 3
1. Control Output
R: Relay output: 250 VAC, 3 A
Q: Voltage output (for driving SSR): 12 VDC, 21 mA
2. Alarm (E5CWL only)
1: Relay output: 250 VAC, 1 A (resistive load)
3. Sensor type
TC: Thermocouple (K, J, T, R, or S)
P: Platinum resistance thermometer (Pt100)
E5CSL/E5CWL
Ordering Information
Single Display
Size
Input type
Alarm output
Thermocouple
1/16 DIN
48 48 60
(W H D)
Control output
Relay output
Resistance thermometer
None
Thermocouple
Voltage output
(for driving SSR)
Resistance thermometer
Model
E5CSL-RTC
E5CSL-RP
E5CSL-QTC
E5CSL-QP
Dual Display
Size
Input type
Alarm output
Thermocouple
1/16 DIN
48 48 60
(W H D)
Control output
Relay output
Resistance thermometer
Thermocouple
Voltage output
(for driving SSR)
Resistance thermometer
New model
E5CWL-R1TC
E5CWL-R1P
E5CWL-Q1TC
E5CWL-Q1P
Adapter
E53-COV19
Front Panel
Model
E53-COV20
Note: 1. This Front Panel accessory is required to attach the Y92A48B or Y92A-48D.
2. This Front Panel accessory is only the frame.
It does not include the plastic cover.
Model
Y92F-45
Note: 1. Use this Adapter when the Front Panel has already been
prepared for the E5B@.
2. Only black is available.
Specifications
Ratings
Power supply voltage
Power consumption
E5CSL
E5CWL
3.5 VA
Models with thermocouple inputs
Thermocouple: K, J, T, R, or S
Sensor input
Control
output
3.5 VA
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA
Voltage output
(for driving
Output voltage: 12 VDC +25%/15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
SSR)
Alarm output
SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA
Control method
Setting method
Indication method
Other functions
Ambient operating
temperature
25% to 85%
Storage temperature
E5CSL/E5CWL
Input Ranges
Models with Thermocouple Inputs
Model
(temperature input)
Set value
Input type
1
2
TC input
Range
C
200 to 1,300
300 to 2,300
20.0 to 500.0
0.0 to 900.0
100 to 850
100 to 1500
20.0 to 400.0
0.0 to 750.0
200 to 400
300 to 700
199.9 to 400.0
199.9 to 700.0
0 to 1,700
0 to 3,000
0 to 1,700
0 to 3,000
Default setting: 0
Applicable standards (K, J, T, R, S): JIS C1602-1995 and IEC 60584-1
Set value
Input type
Pt input
Pt100
Range
C
-200 to 850
-300 to 1500
-199.9 to 500.0
-199.9 to 900.0
Default setting: 8
Applicable standards (Pt100): JIS C1604-1997 and IEC 60751
Alarm Types
Select alarm types out of the 11 alarm types listed in the following
table.
Setting
Positive alarm
value (X)
No alarm
Deviation upper/
lower limit
ON
OFF
Deviation upper
limit
ON
OFF
Deviation lower
limit
ON
OFF
Deviation upper/
lower range
ON
OFF
5
(See
note.)
Deviation upper/
lower limit standby
sequence ON
ON
OFF
6
(See
note.)
Deviation upper
limit standby
sequence ON
ON
OFF
7
(See
note.)
Deviation lower
limit standby
sequence ON
ON
OFF
Absolute value
upper limit
ON
OFF
Absolute value
lower limit
ON
OFF
10
(See
note.)
Absolute value
upper limit standby
sequence ON
ON
OFF
11
(See
note.)
Absolute value
lower limit standby
sequence ON
ON
OFF
12
Do not set.
Alarm type
Negative alarm
value (X)
Alarm value
Output OFF
X
Process value
Time
Always ON
SP
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
The standby sequence is cleared when the alarm OFF condition has
been met.
The standby sequence is started again when any of the following
conditions is met.
Operation is started (power is turned ON or operation is switched
from stop to run).
The alarm value is changed.
The temperature input offset is changed.
The set point is changed.
X
SP
Always OFF
SP
X
Always OFF
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
X
SP
X
SP
X
0
X
0
X
0
X
0
E5CSL/E5CWL
Characteristics
Thermocouple: (See note 1.)
(0.5% of indicated value or 1C, whichever is greater) 1 digit max.
Platinum resistance thermometer:
(0.5% of indicated value or 1C, whichever is greater) 1 digit max.
Indication accuracy
Influence of temperature
Influence of voltage
Hysteresis
Control period
Sampling period
250 ms
Insulation resistance
Dielectric strength
Vibration resistance
Shock
resistance
Malfunction
Destruction
Malfunction
Destruction
Weight
Degree of protection
Memory protection
Conformed standards
EMC
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
Immunity Surge:
Immunity Voltage Dip/Interrupting:
Note: 1. The indication accuracy of K and T thermocouples at a temperature of 100C max. is 2C 1 digit maximum. The indication accuracy
of the R and S thermocouples at a temperature of 200C max. is 3C 1 digit max.
2. R, and S sensors: 0.2C/ max. (100 max.)
10
5
3
1
0
E5CSL/E5CWL
External Connections
A voltage output (control output 1) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect
any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured
temperature values as a result of leakage current.
E5CWL
E5CSL
Control Output
Relay output: 250 VAC, 3 A (resistive load)
Voltage output (for driving SSR): 12 VDC, 21 mA
Control Output
Relay output: 250 VAC, 3 A (resistive load)
Voltage output (for driving SSR): 12 VDC, 21 mA
2
DO NOT
USE
10
Pt input
Control output
Control output
10
Pt input
TC input
DO NOT
USE
Alarm Output
Relay output: 250 VAC, 1 A
(resistive load)
Input power supply:
100 to 240 VAC,
50/60 Hz
TC input
Nomenclature
E5CSL
E5CWL
(1)
(1)
(5)
(3)
(7)
(2)
(6)
(4)
(6)
(9)
(10) (9)
(11)
(8)
(12)
(7)
(8)
(12)
E5CWL
(14)
(11)
(13)
E5CSL
(1) Display No. 1
(10)
(4) SP
(5) ALM
(6) OUT
Lit while the set point is displayed on display No. 1 (E5CSL only).
Lit while the alarm is ON. Not lit while the alarm is OFF.
Lit while the control output is ON. Not lit while the control output is
OFF.
(7) STOP
(8) O
(9) M
(13)
(14)
(10) D
(11) U
(12) O+M
Press these keys for at least 3 seconds in Operation Level or Adjustment Level to go to Protect Level.
(13) M+D
Press these keys for at least 1 second in Protect Level to return to Operation Level.
Press these keys for at least 2 seconds to start or stop autotuning.*1
(14) M+U
*1: These keys are disabled when starting and stopping autotuning has been disabled with operation control
key protection.
*2: These keys are disabled when starting and stopping operation has been disabled with operation control
key protection.
Dimensions
4848
4
64
60
44.844.8
Panel Cutout
Individual Mounting
Group Mounting
+1.0
0
58
45 +0.6
0
60 min.
Package Contents
Temperature Controller
Adapter
Instruction Manual
Adapter
45 +0.6
0
45 +0.6
0
E5CSL/E5CWL
Accessories (Order Separately)
Terminal Cover
Front Panel
E53-COV19
E53-COV20
4
43.3
48 48
4.8
43.8
1.2
Adapter
Note: 1. Use this Adapter when the panel has already been prepared for the E5B@.
2. Only black is available.
Y92F-45
Fixture (Accessory)
76
4.7
69.6 to 77.6
72 72
67 67 87
Panel (1to8mm)
72 x 72
2.7
87
48 x 48
Mounted to E5CWL
62.8
78
E5CSL/E5CWL
Safety Precautions
!CAUTION
Do not touch the terminals while power is being
supplied.
Doing so may occasionally result in minor injury due to
electric shock.
Do not allow pieces of metal, wire clippings, or fine
metallic shavings or filings from installation to enter the
product. Doing so may occasionally result in electric
shock, fire, or malfunction.
Do not use the product where subject to flammable or
explosive gas. Otherwise, minor injury from explosion
may occasionally occur.
Never disassemble, modify, or repair the product or
touch any of the internal parts. Minor electric shock, fire,
or malfunction may occasionally occur.
If the output relays are used past their life expectancy,
contact fusing or burning may occasionally occur.
Always consider the application conditions and use the
output relays within their rated load and electrical life
expectancy.
The life expectancy of output relays varies considerably
with the output load and switching conditions.
Tighten the terminal screws to between 0.74 and 0.90
Nm. Loose screws may occasionally result in fire.
Set the parameters of the product so that they are
suitable for the system being controlled. If they are not
suitable, unexpected operation may occasionally result
in property damage or accidents.
A malfunction in the Temperature Controller may
occasionally make control operations impossible or
prevent alarm outputs, resulting in property damage. To
maintain safety in the event of malfunction of the
Temperature Controller, take appropriate safety
measures, such as installing a monitoring device on a
separate line.
9. Make sure that the rated voltage is attained within two seconds of
turning ON the power using a switch or relay contact. If the voltage
is applied gradually, the power may not be reset or output
malfunctions may occur.
10.Make sure that the Controller has 30 minutes or more to warm up
after turning ON the power before starting actual control
operations to ensure the correct temperature display.
11.A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the
operator, and must be marked as a disconnecting means for this
unit.
12.Do not use paint thinner or similar chemical to clean with. Use
standard grade alcohol.
13.Design system (control panel, etc) considering the 2 second of
delay that the controllers output to be set after power ON.
14.The output may turn OFF when shifting to certain levels. Take this
into consideration when performing control.
15.The number of non-volatile memory write operations is limited.
E5CSL/E5CWL
Precautions for Correct Use
Mounting
Service Life
Mounting to a Panel
Measurement Accuracy
Make sure that the rib on the E53-COV19 Terminal Cover to lower
side, and then attach the this cover to E5CSL/E5CWL.
Waterproofing
The degree of protection is as shown below. Sections without any
specification on their degree of protection or those with IP@0 are not
waterproof.
Front panel: IP50
Rear case: IP20, Terminal section: IP00
Operating Precautions
1. It takes approximately two seconds for the outputs to turn ON from
after the power supply is turned ON. Due consideration must be
given to this time when incorporating Temperature Controllers in a
sequence circuit.
2. When starting operation after the Temperature Controller has
warmed up, turn OFF the power and then turn it ON again at the
same time as turning ON power for the load. (Instead of turning the
Temperature Controller OFF and ON again, switching from STOP
mode to RUN mode can also be used.)
3. Avoid using the Controller in places near a radio, television set, or
wireless installing. These devices can cause radio disturbances
which adversely affect the performance of the Controller.
Terminal Cover
E53-COV19
(Order separately)
Adapter
Panel
7.2 mm max.
7.2 mm max.
E5CSL/E5CWL
E5CSL/E5CWL
10
E5CSL/E5CWL
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
11
OMRON Corporation
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388