Two Way Slab Example
Two Way Slab Example
Two Way Slab Example
ports are so low that the stiffness ratio IXhas a value close to 0.2, gradually approachin
the condition of a flat plate. It is not applicable when IX=O.If it is to be used in the lau g
condition, however, we can assume that part of the slab in the column region acts aser
beam. Thickness h cannot be less than the following values:
a
Slabs without beams or drop panels
Slabs without beams, but with drop panels
Slabs with beams on all four edges with a value of IXfrn
at least equal to 2.0
5in.
4in.
3.5in.
h also has to be increased by at least 10% for flat-plate floors if the end panels have no
edge beams and by 45 % for comer panels.
In addition, in the equations above,
IX= ratio of flexural stiffnessof beam sectionto flexural stiffnessof a widthof slab
bounded laterally by the center line of the adjacent panel (if any) on each side
of the beam
IXfrn
= average value of IXfor all beams on edges of a panel
~ = ratio of clear spans in long to short direction of ~o-way slabs
It has to be emphasized that a deflection check is critital for the construction load.
ing condition. Shoring and reshoring patterns can result in dead-load deflection in excess
of the normal service-load state at a time when the concrete has only a 7-day strength or
less and not the normal design 28-day strength. The stiffness' El in such a state is less than
the design value. Flexural cracking lowers further the stiffness values of the two-way slab
or plate, with a possible increase in long-term deflection several times the anticipated design deflection. Consequently, reinforced concrete two-way slabs and plates have to be
constructed with a camber onin. in lO-ft span or more and crack control exercised as in
Section 11.9 in order to counter the effects of excessive deflection at the construction
loading stage. An analysis for the construction load stresses and deflections is important
in most cases.
'\
the use of Ir
= 7.5Vjj for
the modulus of rupture in computing the cracking moment, Me,. it is advisable that a-lower value than 7.5 in the expression for f, be used, such as 4.Q.-4.5.In this manner, the
possibility is avoided of unanticipated deflection of a two-way slab larger than what the
ACI deflection tables present.
11.5 DESIGN AND ANALYSIS PROCEDURE: DIRECT DESIGN METHOD
. -
459
Carry out the geometry check for use of direct design method;
observe the limitation of the direct design method
listed in Section 11.3.1
1.2Wo + 1.6WL
No.
Assumed section satisfies shear requirements
For flat plates, check the shear requiremenu taking into account
the moment to be transferred by shear to the column face
No
Shear requiremenu
are satisfied
alcu1ation~"
reasonabJel
of reinforcement
;1
average of:
the critical
shown foj:'
)wing:
Figure 11.9 Flowchart for design sequence in two-way slabs and plates by the
direct design method.
460
Chapter 11
,.;i
6. Distribute the factored equivalent frame moments from step 5 to the colllInn and
middle strips.
7. Determine whether the trial slab thickness chosen is adequate for moment-shear
transfer in the case of flat plates at the column junction computing that portion of
the moment transferred by shear and the properties of the critical shear section at
distance d/2 from column face.
8. Design the flexural reinforcement to resist the factored moments in step 6.
9. Select the size and spacing of the reinforcement to fulfill the requirements for crack
control, bar development lengths, and shrinkage and temperature stresses.
+
N
I).
Edgeof
building'
0I
24 ft
(7.32m)
I""'"o'i
I
r-24ft
-T-~
0
-,
::
(9I
~~~
I
co
1
CD
1E
II
_",
co....
I
i
I
461
f~ =
f, =
The building is not subject to earthquake; consider gravity loads only. Design the end panel
and the size and spacing of the reinforcement needed. Consider flooring weight to be 10 psf
in addition to the floor self-weight.
Solution:
(a) Ratio longer span/shorter span =24/18 =1.33 < 2.0, hence two-way action
(b) More than three spans in each direction and successive spans in each direction the
same and columns are not offset.
(c) Assume a thickness of 9 in. and flooring of 10 psf.
9
Wd = 10 + 12 X 150 = 122.5psf
WI = 70 psf
< 2Wd
2Wd
= 245 psf
O.K.
ln2 = 18 X 12
~ - ~ = 269in. (6.83m)
~O
- 2; = 196in. (4.98m)
~~: = 1.37
Minimum preliminary thickness h from Table 11.3 for a flat plate without edge beams or
drop panels using f, = 60,OOO-psi
steel is h = lj30, to be increased by at least 10% when no
edge beam is used.
E-W:
In = 269in.
269
h="3OXl.l=.
986
'
m.
Try a slab thickness h = 10 in. This thickness is larger than the absolute mirtimum
thickness of 5 in. required in the code for flat plates; hence O.K. Assume that d = h - 1 in. =
9 in.
10
new Wd = 10 + 12 X 150
= 135.0 psf
Therefore,
2Wd = 270psf
O.K.
= 274psf (13.12kPa)
Interior column:The controllingcriticalplane of maximumperimetric shear stress is at
a distance d/2 from the columnfaces;hence, the net factored perimetric shear force is
462
Chapter 11
Vu = [(ll x [2)-
+ d)(C2+ d)]wu
(CI
Vn =
116,768
= 155,6911b
~ = 0:75
From Figure 11.11, the perimeter of the critical shear failure surface is
bo = 2(cl + d + C2+ d) = 2(cl + C2+ 2d)
= 2 x 9.0(20+ 20 + 18)
= 116 x 9 = 1044in.2(673,400mm2)
Since moments are not known at this stage, only a preliminary check for shear can be made.
13
= ratio
of longer to shorter
side of columns
~~
= 1.0
= (2+ ~) Vi'cbod= (2 +
i)V
\.
4000
103 kN)
or
Vc
bo
116
X 1044
= 336,972Ib(1.5 X
103 kN)
or
Vc
Criticalplane~---l---
~I
1111
lLL
'
I -+
d/2-t
4.6 in.
~1
c\
20 in
0.,;",
'~
J~
4.6 in..
18
I---d/2
-,l
'---r---4.5 in.
29.0 in.
(c\+d)
24 ft
24 ft
Figure 11.11 Critical plane for shear moment transfer In Ex. 11.1 interior column
(line B-B, Fig. 11.10).
463
1.2 Vn applies in the case of interior columns. For end columns, a recommended multiplier for
Vn might have to be as high as 1.6-1.8, and for comer columns, a higher value is applicable.
Often, shear heads or drop panels are necessitated for comer columns to overcome too large a
required thickness of the slab. As the serviceability tabulated values in Table 11.3 for minimum
thickness of slabs apply only to the interior column zones, to be augmented by 10-15% for end
columns and almost 50% for comer columns, they indirectly take into account the above stipulations for choosing trial slab thickness based on augmenting Vc, as was done at the outset in
basing the choice of the slab thickness on augmenting the Table 11.3 value by 10 percent.
Exterior column: Include weight of exterior wall, assuming its service weight to be 270
plf. Net factored perimetric shear force is
18)
Vu
24
18
(18+
= [ 18 X (2 + 2 x 12) +
4.50)(20 + 9.0)
144
] 274
20
18 - 12
66 933
X 270 X 1.2
= 66,9331b
Vn = 0:75 = 89,244lb
Consider the line of action of Vu to be at the column face LM in Figure 11.12 for shear moment transfer to the centroidal plane c-c. This approximation is adequate since Vu acts perimetrically around the column faces and not along line AB only. From Figure 11.12,
kN)
Ac
= d(2c1 +
C2+ 2d)
= 9.0(2 X 18 + 20 + 18) = 9 x 74
= 666in.2(429,700mm2)
lIP kN)
v" = (2 +
N)
V 4000
X 666
= 235,8811b
or
Vc
Face of
building
mn
Figure 11.12 Centroidal axis for shear moment transfer in Ex. 11.1 end column
(line A-A or 1-1, Fig. 11.10).
",
464
Chapter 11
where as =
or
Vc = 4 Vt'cbod = 4 V 4000 X 666 = 168,486Ib(0.75 X lW kN)
controls
OX
N-S:
lnl
= 269in. = 22.42 ft
= --g
274 X 18(22.42)2
= 309,888ft-lb (420kN-m)
For end panel of a flat plate without end beams, the moment distribution factors as in Table 11.1are
= 0.70Mo
= 0.52Mo
- Muat exteriorface= 0.26Mo
+ Mu at midspan of panel
= 0.70 X 219,202
= 153,441 ft-Ib (208 kN-m)
+ Mu
0.52
X 219,202
= 0.26 X 219,202
= 56,993 ft-lb (75 kN-m)
Note that the smaller moment factor 0.35 could be used for the positive factored moment in
the N-S direction in this example if the exterior edge is fully restrained. For the N-S direction, panel BC12 was considered.
Moment distribution in the column and middle strips (steps 6 and 7)
At the exterior column there is no torsional edge beam; hence the torsional stiffness
ratio 13,of an edge beam to the columnsis zero. Hence al = O.From the exteriorfactoredmOments tables for the column strip in Section 11.4.2, the distribution factor for the negative
moment at the exterior support is 100%, the positive midspan moment is 60%, and the interior negative moment is 75%. Table 11.5givesthe moment valuesresulting from the moment
distributions to the column and middle strips.
N-S Direction
E-W Direction
1/11: 18/24 = 0.75
0
a,(//11):
Column strip
Mu (ft-Ib)
Distribution
factor(%)
Column strip
design moments
(ft-Ib)
Middlestrip
designmoments
(ft-Ib)
.j:o,
en
U1
Interior
negative
moment
216,922
75
Positive
midspan
moment
161,142
60
0.75 x
0.60 x
216,922
162,692
216,922
-162,692
54,230
161,142
96,685
161,142
- 96,685
64,457
24/18 = 1.33
0
Exterior
negative
moment
80,571
100
Interior
negative
moment
153,441
75
Positive
midspan
moment
113,985
60
1.0 x
0.75 x
0.60 x
153,441
115,081
153,441
-115,081
38,360
113,985
68,391
113,985
- 68,391
45,594
80,571
80,571
80,571
-80,571
---0
Exterior
negative
moment
56,993
100
1.0 x
56,993
56,993
56,993
-56,993
0
.'1
466
Chapter 11
column
supports
= 66
,933
24--
'
Vn= 60,850/0.75= 81,133Ib, assuming that the design Mu has the same value as the factored Mu.
Ae from before = 666in.2
From Figures 11.7c and 11.12, taking the moment of area of the critical plane about
axis AB,
(2 X 18 + 20 + 18)X= 18 +
x = 50~~25
-t )
= 6.84 - 9.0/2 = 2.34 in, where g is the distance from the column face to the centroidal
axis of the section.
To transfer the shear Vu from the face of column to the centroid of the critical section adds
an additional moment to the value of Me = 80,571ft-Ib.Therefore, the total external factored
moment Mue = 80,571 + 60,850(2.34/12) = 92,437 ft-Ib. Total required minimum unbalanced
moment strength is
and g
Iii
fll
Mue
Mn
=~ =
92,437
0.90 = 102,708ft-Ib
R:
,.
= ci + d/2 =18 + 4.5 = 22.5 in. and b2 =c2 + d =20 + 9 = 29 in. It should be noted that
the dimension ci + d for the end column in the above expression becomes CI+ d/2. Hence
where bl
Mnv
= 0.37
Mn. Moment
bh3
II
hb3
= 12 + Ar2 + 12
=[
12
9.0(22.5)3
II
+ (9.0 X 22.5) Z-
- 6.84 +
22.5(9.0)3
12
]2
Therefore,
torsional moment of inertia Ie = 27,696+ 12,211
= 39,907 in.4
467
If Eq. 11.7e is used instead from first principle calculations, as shown above, the same value
Ie = 39,907 in.4 is obtained.
Shearing stress due to perimeter shear, effect of Mn, and weight of wall is
60,850
0.75 X 666
Therefore, accept plate thickness. For the comer panel column, special shear-head provision or
an enlarged column or capital might be needed to resist the high-shear stresses at that location.
Check for shear-moment transfer at the interior column joint:
Vn = 155,691+
9(29)3
= 35,467 ft-Ib
66,933- 60,850
0.75
= 163,802lbat the face of the column
(9? X 29
Ie
=~
= 20/2 = lOin.
9 X 29(29f
= 149,858ID.
35,467X 12
.
0.9
+ 163,802X 10 = 2,110,913ID.-Ib
1
= (1.5 X 10.0)2 +
= AJy(d - ~)
20
= 50.0in.
assumethat ( d - ~) = 0.9d
._. u
._
...
468
1.60 X 60,000
.
a = 0.85 X 4,000 X 50.0 = 0.56m.
Therefore,
0.56
162,692
.d
..
69
= 0.9 = 180,7
96,685
28
= o:g- = 07,4
extenor
<I>
80,571
= o:g- = 89,523
M
I
mtenor co umn negative n
.
exterior
..
54,230
= o:g-= 60,256
IDldspan posItive Mn
64,457
= o:g- = 71,619
column negative Mn
=A.f,(d -~)
or 241,025= A. X 60,000(9.0 - ~)
469
Assume that moment arm d - a/2 "" 0.9d for first trial and d =h
"" 9.0 in. for all practical purposes. Therefore,
_
241,025
_
. 2
As - 60,000X 0.9 X 9.0 - 0.50m.
As!,
0.50 X 60,000
a = 0.85f~ = 0.85 X 4000 X 12
= 0.74 m.
:rature:
, at the.
tal end
tly de-.
0.74
.
spacmgs =
= 0.47
-2
'
.
.
reqUIre dA s per 12-m. strip
Therefore,
s for negative moment = 0.305 = 7 79 . _ (194
)
(No.5 bars)
0.47/12'
m. c c
mm
le face
neces'
or not
_ 143,237
As
minin1um temperature
~~'~~
= 13.11in. c-c (326mm)
,
241,025 X 0.47
28 .
= 0.0018 bh = 0.0018 X 12 X 10
= 0.216in.2/ft < 0.28in.2 OK
reinforcement
0.20
(
)
s = 0.28/12 = 8.57m. c-c 218mm
For an external negative moment, use No.4 bars.
89,523 X 12
.
Moment =
9.0
= 119,364m. -lb
143,237
Use 14 No.5 bars at in. center to center for negative moment at interior column side, 12
No.4 bars at 8! in. center to center for positive moment; and 10 No.4 bars at 10 in. center to
center for the exterior negative moment M. with 8 of these bars to be placed outside the
shear moment transfer band width 50 in., as seen in Figure 11.13b.
4. Design of reinforcement for middle strip
.
urnt -
. M
urnt -
.
54,230'
6
= 0,256acting on a strip width of 18.0 - 9.0 = 9.0ft
. .dth .
60,276X 12
'
12
80 lib
n = 0:9
per
-m.-WI
strip
As
. 2
- 0.17In.
_ 0.17 X 60,000 _
.
a - 0.85X 4000 X 12 - 0.25m.
Second cycle:
0.25
- - --
- - - - -
,34
-m.
Chapter 11
470
1"(""
la)
Design
column
strip
I.
...(
9 ft
I:'
5 No.4
I
I
I
I
I
I
I
I
I
I
I
5 No.5
I
I
I
I
I
I
50 in.
I
I'
5No.
4
I
I
I
I
I
I
.I
(b)
i
Figure 11.13 Shear moment transfer zone: (a) effective bandwidth; (b) reinforcing details.
minimum As = 0.216
.
umt + M =
_
As
Hence
use negative
64,457X 12
.
.,
9 X 0.9 = 95,492m.-Ibper 12-m.strip
95,492
60,000 X 8.875
and positive
0.18m.
use minimum
As
ter). Use No.3 bars at 6 in. center to center for both the negative moment and positive moments.
(b) N-S direction (short span): The same procedure has to be followed as for the E-W
direction.
N ;. ~ ~
1It!1~g
O'Ir'
""
.,.
S'
~(1)(1)'"1
.?:iE!. 9.
Strip
Column
Middle
aMinimum
Moment
(lb-inJ12 in.)
Req'd
Bar Size
and
Spacing
241,025
0.47
No.5 at 7!
170,490
0.37
No.4 at 6
119,364
0.23
No.4 at 10
84,434b
0.18
No.3 at 6
143,237
0.28
No.4at8!
101,320
0.22
No.3 at 6
80,341
0.15
No.3 at 6
34,098
0.07
No.3 at 6
0.22
No.3 at 6&
0.22
No.3 at 6
95,492
0.18
No.3 at 6
40,528
0.09
NO.3at6
Moment
(lb-InJ12In.)
Interior
negative
Exterior
negative
Midspan
positive
Interior
negative
Exterior
negative
Midspan
positive
As
"\
steel = O.OO18bh
where it controls.
~
....
Req'd
Bar Size
and Spacing
Moment
Type
temperature
N-S
on page 494).
transfer
negative
reinforcement
As
472
.,
'iF
if
(;"
11.
It
;;
'-k-
..
..,w.
8'aI:..""',.
.1,;.tl
'.
';.,
'l
,
'';
!
K
!:i
'.,
1 ...
.f'
J-
:;
8.5 in. The moment values and the bar size and distribution for the panel in the N-S direction
as well as the E-W directions are listed in Table 11.6. It is recommended for crack-control,
purposes that a minimum of No. 3 bars at 12 in. center to center be used and that bar spacing
not exceed 12 in. center to center. In this case, the minimum reinforcement required by the,
ACI Code for slabs reinforced with fy = 60,000-psisteel = 0.0018bh = No.3 at 6! in. on centers. Space at 6 in. on centers.
The choice of size and spacing of the reinforcement is a matter of engineering judgment. As an example, the designer could have chosen for the positive moment in the middle
strip No.4 bars at 12 in. center to center, instead of No.3 bars at 6 in. center to center, as
long as the maximum permissible spacing is not exceeded and practicable bar sizes are used
for the middle strip.
The placing of the reinforcement is schematically shown in Figure 11.14. The minimum,
cutoff of reinforcement for bond requirements in flat-plate floors is given in Figure 11.15.The
exterior panel negative steel at outer edges, if no edge beams are used, has to be bent into full
hooks in order to ensure sufficient anchorage of the reinforcement. The floor reinforcement
plan gives the E-W steel for panel AB23 and N-S steel for panel BC12 of Figure 11.10.
11.5.3
Slab on Beams
A two-story factory building is three panels by three panels in plan, monolithically supported
on beams. Each panel is 18 ft (5.49 m) center to center in the N-S direction and 24 ft (7.32m)
center to center in the E-W direction, as shown in Figure 11.16. The clear height between the
floors is 16 ft. The dimensions of the supporting beams and columns are also shown in Fig;:
11.16, and the building is subject to gravity loads only. Given:
live load
= 60,000psi (414MPa)
11.5
473
Edge of building
<t.of exterior column
TopNo.5 at 7~ in.
I
N o.4atB2m.
;-
I
I
~
Bottom
---~
~--I
1
I
I
JUL-
4 ft 6 in.1
:1
Top No.3 at 6 in. :
. :1.
14ft 6 in.
Middle
strip=15ft
. I.
:
;pacing'
by the!
)n CeO"1
.i
t column strip
2 columnstrip
}.5I2j =.:
rectioq
control
li1i+--ru
:he 001-'
-9.0=1 .
~O'3.'".,
I No.3 at 6 in.
I
I
,-----
No.3 at 6 in.
I#W N03.~
Bottom
IIII
--f
span
=24/18
= 203 psf
Wi = 135psf <
= 101.5 psf
2Wd
2Wd
= 24 X 12 = 18 X 12 -
2 X8
= 272 in.
2 X8
= 200in.
272
~ = 200 =
1.36
h=
In(0.8 + 20~000)
36 + 9~