D2 FloPro Control Valve
D2 FloPro Control Valve
D2 FloPro Control Valve
D2 FloPro Valve
51.2:D2
June 2012
D102816X012
Features
www.Fisher.com
W9235-1
Product Bulletin
D2 FloPro Valve
51.2:D2
June 2012
D102816X012
Specifications
Valve Assembly Pressure Class(1)
ASME B16.34 CL900
Maximum Travel
Temperature Range(1)
13 mm (0.5 inch)
See figure 2
Approximate Weight
7.7 kg (17 lb)
Dimensions
See figure 3
Material Temperature Capabilities
Valve Body Assembly: -46 to 149C
(-50 to 300F)
Actuator Assembly: -46 to 93C (-50 to 200F)
Bonnet/Body Connection
Screwed with leakoff bleed
Standard Actuator Configuration
The D2 FloPro actuator is an on-off
spring-and-diaphragm.
Globe Valve Body: Supplied as either Air-to-Open or
Air-to-Close.
Maximum Actuator Casing Pressure
2.8 bar (40 psig)
Minimum Required Actuator Casing Pressure
2.1 to 2.4 bar (30 to 35 psig)
Actuator Diaphragm Effective Area
194 cm2 (30 square inches)
Actuator Pressure Connections
1/4 NPT internal; see figure 3 for locations
1. The pressure or temperature limits in the referenced tables and any applicable ASME code limitations should not be exceeded.
2. Standard flow direction.
Product Bulletin
D2 FloPro Valve
51.2:D2
June 2012
D102816X012
GE15452
FloPro TRAVEL
INDICATOR
SAFETY
VENT
FLOW ADJUSTOR
GE15452
Product Bulletin
D2 FloPro Valve
51.2:D2
June 2012
D102816X012
76
(3.00)
194
(7.65)
1/4 NPT
SUPPLY CONNECTION
51
(2.00)
DIAMETER
1 NPT
43
(1.69)
mm
(INCH)
60
(2.35)
19B8490-B
E0783
120
(4.70)
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and ENVIRO-SEAL are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson
Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
E
4 2001, 2012 Fisher Controls International LLC. All rights reserved.