Damper Performance
Testing Criteria
Substitution
Wall
Air from
Air Chamber
Ambient
Thermocouple
Chamber
Thermocouple
Heat
Source
Test
Damper
Insulation
Static
Pressure in
Chamber
Damper Performance
Testing Criteria - Pressure Drop
As mentioned, the Thermal Efficiency Ratio (E)
compares the energy lost through the damper being
evaluated with the energy lost through the reference
damper. The formula is:
E = (qref / qd 1) x 100
Where:
qref is the energy lost through the reference damper
qd is the energy lost through the damper being
evaluated.
Using this formula, a damper with the same
performance as the reference damper is 0% efficient.
A damper that loses half as much energy as the
reference damper is 100% efficient.
Pressure Drop
Pressure drop testing was conducted in accordance
with AMCA Standard 500-D using the three
congurations shown. All data has been corrected to
3
represent standard air at a density of .075 lb./ft
(1.201 kg/m3).
Actual pressure drop found in any HVAC system
is a combination of many factors. This pressure
drop information along with an analysis of other
system inuences should be used to estimate actual
pressure losses for a damper installed in a given
HVAC system.
%
'JHVSF
%
'JHVSF
%
D=Duct length
W=Damper width
H=Damper height
'JHVSF
8
)
12 x 12
(305 x 305)
Velocity - fpm
(m/s)
24 x 24
(610 x 610)
36 x 36
(914 x 914)
12 x 48
(305 x 1219)
48 x 12
(1219 x 305)
500 (2.5)
.03 (7.5)
.02 (5)
.01 (2.5)
.01 (2.5)
.03 (7.5)
1000 (5.1)
.11 (27.4)
.08 (19.9)
.05 (12.5)
.06 (14.9)
.14 (34.8)
1500 (7.6)
.25 (62.3)
.19 (47.3)
.11 (27.4)
.14 (34.8)
.32 (79.7)
2000 (10.2)
.45 (112)
.34 (84.7)
.21 (52.3)
.25 (62.3)
.57 (142)
2500 (12.7)
.71 (176.9)
.53 (132)
.33 (82.2)
.40 (99.6)
.89 (221.7)
3000 (15.2)
1.03 (256.6)
.77 (191.8)
.47 (117.1)
.57 (142)
1.29 (321.3)
3500 (17.8)
1.40 (348.7)
1.05 (261.5)
.64 (159.4)
.78 (194.3)
1.76 (438.4)
4000 (20.3)
1.83 (455.8)
1.37 (341.3)
.84 (209.2)
1.02 (254.1)
2.30 (572.9)
12 x 12
(305 x 305)
Velocity - fpm
(m/s)
24 x 24
(610 x 610)
36 x 36
(914 x 914)
12 x 48
(305 x 1219)
48 x 12
(1219 x 305)
500 (2.5)
.01 (2.5)
.01 (2.5)
.01 (2.5)
.01 (2.5)
.04 (10)
1000 (5.1)
.04 (10)
.03 (7.5)
.02 (5)
.02 (5)
.06 (14.9)
1500 (7.6)
.09 (22.4)
.08 (19.9)
.04 (10)
.06 (14.9)
.14 (34.8)
2000 (10.2)
.17 (42.3)
.14 (34.8)
.08 (19.9)
.10 (24.9)
.25 (62.3)
2500 (12.7)
.26 (64.7)
.22 (54.8)
.12 (29.9)
.17 (42.3)
.40 (99.6)
3000 (15.2)
.38 (94.6)
.32 (79.7)
.18 (44.8)
.24 (59.8)
.58 (144.5)
3500 (17.8)
.52 (129.5)
.43 (107.1)
.24 (59.8)
.33 (82.2)
.79 (196.7)
4000 (20.3)
.67 (166.9)
.57 (142)
.32 (79.7)
.43 (107.1)
1.03 (256.6)
12 x 12
(305 x 305)
Velocity - fpm
(m/s)
24 x 24
(610 x 610)
36 x 36
(914 x 914)
12 x 48
(305 x 1219)
48 x 12
(1219 x 3050
500 (2.5)
.05 (12.5)
.05 (12.5)
.03 (7.5)
.04 (10)
.05 (12.5)
1000 (5.1)
.23 (57.3)
.21 (52.3)
.14 (34.8)
.18 (44.8)
.22 (54.8)
1500 (7.6)
.52 (129.5)
.47 (117.1)
.33 (82.2)
.42 (104.6)
.51 (127)
2000 (10.2)
.93 (231.7)
.84 (209.2)
.58 (144.5)
.74 (184.3)
.90 (224.2)
2500 (12.7)
1.44 (358.7)
1.32 (328.8)
.91 (226.7)
1.16 (288.9)
1.41 (351.2)
3000 (15.2)
2.08 (518.1)
1.9 (473.3)
1.31 (326.3)
1.68 (418.5)
2.04 (508.1)
3500 (17.8)
2.83 (704.9)
2.59 (645.1)
1.79 (445.9)
2.28 (567.9)
2.78 (692.5)
4000 (20.3)
3.70 (921.6)
3.39 (844.4)
2.34 (582.9)
2.98 (742.3)
3.70 (921.6)
Greenheck Fan Corporation certifies that the model ICD-44 and ICD-45
shown herein is licensed to bear the AMCA Seal. The ratings shown are
based on tests and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements of the AMCA Certified
Ratings Programs. The AMCA Certified Ratings Seal applies to Air Leakage,
Air Performance and Energy Efficiency ratings.
Leakage Class*
Maximum
Damper Width
1 in. wg
(0.25 kPa)
4 in. wg
(1 kPa)
8 in. wg
(2 kPa)
10 in. wg
(2.5 kPa)
48 in. (1219mm)
1A
Construction Features
There are four frame types available:
Quick Connect for easy connection to duct
Channel
Single Flange
Reverse Flange
The ICD-44 features an extruded aluminum frame.
The ICD-45 features an aluminum frame with two
polyurethane resin thermal breaks and insulated on
four sides with polystyrene.
Quick
Connect
Channel
Single
Flange
Reverse
Flange
Construction Features
Figure 1
Airow works
against
actuator
Airow works
against
actuator
Actuator
Torque
Actuator
Torque
Airow
works with
actuator
Unbalanced Blade
Balanced Blade
Figure 2
Blades
The ICD series damper blades feature thermally broken airfoil shaped blade
with polyurethane foam.
Bearings
Dual bearing with acetal inner sleeve and flanged outer bearing features no
metal-to-metal or metal-to-plastic contact.
Bearing
Linkage
Greenhecks ICD series dampers have blade linkage concealed
in the insulated frame. This prevents any transfer point for cold
or heat, unlike some of our competitors products. The linkage is
engineered to accurately control each and every blade without
need for adjustment.
Tag Label
Greenheck labels include the tag information for your order. This label provides
the damper model, size, actuator model, and purchase order number. This
label will help save time in the field when you have multiple locations for the
dampers on the jobsite. On ICD series dampers, you will see a QR code on
the label too. When you scan the QR code with your smartphone, you will be
directed to www.greenheck.com for model specific information.
6
ICD-44
ICD-45
593%
941%
4000
(20.3)
4000
(20.3)
8 (2)
8 (2)
-70 to 200
(-56 to 93)
-70 to 200
(-56 to 93)
Aluminum
.125 in.
(3.2mm)
.125 in.
(3.2mm)
Channel
Quick Connect
Reverse Flange
Single Flange
Parallel
Opposed
Blade Type
Blade Material
Blade Seal
Silicone
304SS
Silicone
Plated Steel
304SS
Plated Steel
304SS
Anodize
Baked Enamel
Epoxy
Hi Pro Polyester
Industrial Epoxy
Frame Type
Blade Action
Jamb Seal
Axle Bearings
Axle Material
Linkage
Paint Finishes*
Kynar/Hylar (70%)
Minimum Size
Sizing
Inches (mm)
Channel, Single or
Reverse Flange
12 x 7
(305 x 178)
12 x 7
(305 x 178)
Quick Connect
12 x 6
(305 x 152)
12 x 6
(305 x 152)
48 x 74
(1219 x 1880)
48 x 74
(1219 x 1880)
Channel, Single or
Reverse Flange
144 x 148
(3658 x 3759)
144 x 120
(3658 x 3048)
Quick Connect
96 x 148
(2438 x 3759)
96 x 120
(2438 x 3048)
Maximum Multi
Section Size
In-House Testing
State-of-the-art laboratory and testing facilities have
always been important to Greenheck continuing
business success. A laboratory facility devoted
exclusively to development and testing of damper
related products for testing to the latest versions
of AMCA, ANSI, ASHRAE, UL, and other industry
standards of performance.
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties.
Prepared to Support
Green Building Efforts
00.DMP.1005 R3 3-2015 RG