Deep Sea Electronics: DSEA106 Configuration Suite PC Software Manual
Deep Sea Electronics: DSEA106 Configuration Suite PC Software Manual
Deep Sea Electronics: DSEA106 Configuration Suite PC Software Manual
DSEA106
Configuration Suite PC Software Manual
Document Number: 057-242
Author: Fady Atallah
057-242 ISSUE: 1
Comments
Minimum
Module
Version
Required
V1.0
Initial release
Minimum
Configuration
Suite Version
Required
2015.36 V1.261.5
Typeface: The typeface used in this document is Arial. Care must be taken not to mistake the upper case letter I with the numeral 1. The numeral
1 has a top serif to avoid this confusion.
057-242 ISSUE: 1
Page 2 of 20
TABLE OF CONTENTS
1
INTRODUCTION .............................................................................................. 4
1.1
BIBLIOGRAPHY .......................................................................................................................... 4
1.1.1
INSTALLATION INSTRUCTIONS .......................................................................................... 4
1.1.2
MANUALS ............................................................................................................................ 4
1.1.3
OTHER ................................................................................................................................. 4
1.2
INSTALLATION AND USING THE DSE CONFIGURATION SUITE SOFTWARE .......................... 4
SCADA........................................................................................................... 14
3.1
3.2
3.3
3.4
Page 3 of 20
057-242 ISSUE: 1
Introduction
1 INTRODUCTION
DANGER OF DEATH: LIVE PARTS exist within the AVR. To avoid damage to persons and/or
property, only qualified personnel having full understanding of the application must install and configure
the product.
The DSE Configuration Suite PC Software allows the DSEA106 Automatic Voltage Regulator to be connected
to a PC via the DSE814 USB Configuration Interface. Once connected the various operating parameters within
the module are viewed or edited as required by the engineer. This software allows easy controlled access to
these values.
This manual details the configuration of the DSEA106 Automatic Voltage Regulator.
The DSE Configuration Suite PC Software must only be used by competent, qualified personnel, as changes to
the configuration of the module may have safety implications on the panel / generating set to which it is fitted.
The information contained in this manual must be read in conjunction with the information contained in the
appropriate module documentation. This manual only details which settings are available and how they may be
used. A separate manual deals with the operation of the individual module (See section entitled Bibliography
elsewhere in this document).
1.1
BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which is obtained from the DSE
website www.deepseaplc.com
1.1.1
INSTALLATION INSTRUCTIONS
DSE Part
053-177
1.1.2
MANUALS
DSE Part
057-151
057-241
1.1.3
Description
DSEA106 Installation Instructions Sheet
Description
DSE Configuration Suite PC Software Installation & Operation Manual
DSEA106 Operator Manual
OTHER
1.2
Description
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device Function Numbers and
Contact Designations. Published by Institute of Electrical and Electronics Engineers Inc
For information in regards to instating and using the DSE Configuration Suite Software please refer to DSE
publication: 057-151 DSE Configuration Suite PC Software Installation & Operation Manual which is found
on our website: www.deepseaplc.com
057-242 ISSUE: 1
Page 4 of 20
2.1
SCREEN LAYOUT
Move to the
Previous or Next
configuration page
The type of
configuration
file being edited
The coloured
shading shows
the currently
selected page.
Close this
configuration file
Click + or to
show or hide the
sub settings within
each section.
Step forward or
backward through
previously viewed pages
Click to select
the subsection
to view / edit
Page 5 of 20
057-242 ISSUE: 1
2.2
MODULE OPTIONS
Free entry boxes to allow the user
to give the configuration file a
description. Typically this is used to
enter the job number, customer
name, engineers name etc.
2.3
VOLTAGE
NOTE: The voltage range is selected by the DIP switches on the AVR. For further details, refer to
DSE Publication: 057-241 DSEA106 Operators Manual.
The Voltage section is subdivided into smaller sections.
Select the required section with the mouse.
2.3.1
057-242 ISSUE: 1
Page 6 of 20
Parameter
Preset Enable
Description
= The Voltage Set Point potentiometer is disabled and the voltage output of
the alternator is determined by the Set Point parameter in the configuration.
= The Voltage Set Point potentiometer is enabled and the voltage output of
the alternator is determined by the Voltage Set Point potentiometer on the AVR.
Set the minimum voltage adjustment allowed by the Voltage Set Point
potentiometer
Set the maximum voltage adjustment allowed by the Voltage Set Point
potentiometer
When the Preset Enable option is disabled, this determines the voltage output of
the alternator.
2.3.1.2 DROOP
NOTE: For further details and examples on how to set the droop function, refer to DSE Publication:
057-241 DSEA106 Operators Manual.
Parameter
Preset Enable
Description
= The Droop potentiometer is disabled. The droop percentage is determined
by the Droop parameter in the configuration.
= The Droop potentiometer is enabled. The droop is determined by the Droop
potentiometer on the AVR.
Set the maximum droop adjustment allowed by the Droop potentiometer
Set the droop amount as a percentage of the Voltage Set Point
Set the phase angle between the voltage sensing and droop CT reading
Set the full load current of the Droop CT secondary
Page 7 of 20
057-242 ISSUE: 1
Parameter
Enable
Description
= The Remote Potentiometer input is disabled
= The Remote Potentiometer input is enabled, allowing the voltage biasing via
a 5 k potentiometer
Set the range of voltage bias via the Remote Potentiometer as a percentage of
the Voltage Set Point
Example:
When this is set to 5.0%, the maximum voltage adjustment via the potentiometer
for a nominal voltage 230 V, has a range between 218.5 V and 241.5 V
Parameter
Enable
Description
= The DC Voltage input is disabled
= The DC Voltage input is enabled, allowing the voltage biasing via a 0 V to
10 V DC Voltage signal
Set the range of voltage bias via the DC Voltage Input as a percentage of the
Voltage Set Point
Example:
When this is set to 10.0%, the maximum voltage adjustment via the DC Voltage
Input for a nominal voltage 230 V, has a range between 207 V and 253 V
057-242 ISSUE: 1
Page 8 of 20
2.4
FREQUENCY
NOTE: The operating frequency is selected by the DIP Switches on the AVR. For further details,
refer to DSE Publication: 057-241 DSEA106 Operators Manual.
The Frequency section is subdivided into smaller sections.
Select the required section with the mouse.
2.4.1
50 HZ / 60 HZ FREQUENCY
NOTE: For further details of module operation, refer to DSE Publication: 057-241 DSEA106
Operators Manual.
Parameter
Preset Enable
Dwell Time
Ramp Up Rate After Dwell
(%/s)
Under Frequency Trip Point
Description
= The UFRO Potentiometer is disabled; the Knee Point setting in the
configuration is enabled
= The UFRO Potentiometer is enabled; the Knee Point setting in the
configuration is disabled
Set the low limit for the UFRO potentiometer on the module.
Set the Knee Point for the UFRO protection. This the frequency setpoint at which
the UFRO protection starts.
Set the Ramp Rate for the UFRO protection, this is the percentage of Set Point
Voltage decreased with every 1 Hz drop when the frequency drops below the
configured Knee Point or the setpoint determined by the UFRO potentiometer
Set the time delay before the AVR excitation starts to ramp up when a UFRO
protection has occurred.
Set the rate of voltage ramp up after the Dwell Time expires. This is the
percentage of Set Point Voltage increased every 1 s.
Set the frequency setpoint at which the AVR excitation is disabled.
Page 9 of 20
057-242 ISSUE: 1
2.5
STABILITY
NOTE: The stability range is selected by the DIP switches on the AVR. For further details, refer to
DSE Publication: 057-241 DSEA106 Operators Manual.
The Stability section is subdivided into smaller sections.
Select the required section with the mouse.
This allows the configuration of different stability settings for different sizes of alternators.
2.5.1
NOTE: For further details on stability settings, refer to DSE Publication: 057-241 DSEA106
Operators Manual.
Parameter
Preset Enable
Set Point
Parameter
Preset Enable
Set Point
057-242 ISSUE: 1
Description
= The Proportional Potentiometer on the AVR is disabled; the Set Point setting
in the configuration is enabled
= The Proportional Potentiometer on the AVR is enabled; the Set Point setting
in the configuration is disabled
When the potentiometer is disabled, this paramter fixes the Proportional Gain
setting in the AVR
Description
= The Integral Potentiometer on the AVR is disabled; the Set Point setting in
the configuration is enabled
= The Integral Potentiometer on the AVR is enabled; the Set Point setting in
the configuration is disabled
When the potentiometer is disabled, this paramter fixes the Integral Gain setting
in the AVR
Page 10 of 20
Parameter
Set Point
Description
NOTE: For further details on the gain settings, refer to DSE
Publication: 057-241 DSEA106 Operators Manual.
Set the Derivative Gain parameter in the AVR
Parameter
Output Offset
Output Limit
Parameter
Ramp Start Point (% of Set
Point)
Ramp Rate (%/s)
Description
Set the initial output duty cycle when starting. This is useful to ensure a fast
voltage build-up upon starting.
Set the maximum output duty cycle.
Description
Set the start point for the voltage build-up ramp. This is configured in percentage
of the set point voltage. This is useful to allow a quick voltage build-up when
starting the set.
Set the rate for the voltage build-up ramp in percentage of set point voltage per
second.
Page 11 of 20
057-242 ISSUE: 1
2.6
PROTECTIONS
Parameter
Start-up Fail Delay
Loss of Feedback Delay
Parameter
Over Excite Trip
057-242 ISSUE: 1
Description
Set the time delay for the Start-up Fail alarm when the module does not measure
the auxiliary voltage upon starting.
Set the time delay for the Loss Of Feedback Delay alarm when the module sees a
sudden loss of feedback voltage.
Description
Set the Over Excite Trip level. The Over Excite Trip alarm activates when the
excitation voltage exceeds the configured setting for longer than the Over Excite
Trip delay.
Set the time delay for the Over Excite Trip alarm.
Page 12 of 20
2.7
COMMUNICATIONS
The DSE814 Configuration Interface communication port is provided to give a simple means of connection
between a PC and the controller.
The Communications page is subdivided into smaller sections.
Select the required section with the mouse.
2.7.1
COMMUNICATIONS OPTIONS
2.7.2
For advanced Modbus users of the controller, configurable Gencomm pages are available.
The intention is to allow the user to create personal collections of data in subsequent registers to minimise the
number of modbus reads required by the master, and hence speed up data collection.
All configurable Gencomm registers are 32-bit unsigned format.
Page 13 of 20
057-242 ISSUE: 1
SCADA
3 SCADA
NOTE: The DSE814 USB Configuration Interface and the USB port on the module are designed to be
used for configuration and diagnostics, not for monitoring.
SCADA stands for Supervisory Control And Data Acquisition and is provided both as a service tool and also as a
means of monitoring and control.
As a service tool, the SCADA pages is to check the operation of the module as well as checking the system
parameters.
Click to connect
to the module
When connection is made
Modules firmware
revision number
The SCADA page is subdivided into smaller sections.
Select the required section with the mouse.
057-242 ISSUE: 1
Page 14 of 20
SCADA
3.1
MODULE IDENTITY
Shows the modules current settings for Site Identity and Module Identity.
Page 15 of 20
057-242 ISSUE: 1
SCADA
3.2
057-242 ISSUE: 1
Page 16 of 20
SCADA
3.3
DIAGNOSTICS
NOTE: For further details on Dip Switch Adjustment, refer to DSE Publication: 057-241 DSEA106
Operators Manual.
Page 17 of 20
057-242 ISSUE: 1
SCADA
3.4
STATUS
057-242 ISSUE: 1
Page 18 of 20