TS6 - Electrical Services
TS6 - Electrical Services
TS6 - Electrical Services
Document Control
Document owner:
Principal Engineer
Date
Author
Descripton of amendments
30/04/2009
T. Tyler
20/07/2009
T. Tyler
Previously TS 19
12/01/2010
T. Tyler
30/04/2010
T. Tyler
Re-branding
04/05/2010
T. Tyler
08/06/2010
T. TYLER
11/11/2010
John Howard
24/03/2011
28/03/2011
John Howard
31/08/2011
John Howard
5/01/2012
John Howard
10
10/01/2012
John Howard
Jason Zuglian
11
19/01/2012
Jason Zuglian
12
12/02/2012
John Howard
13
13/02/2012
John Howard
14
27/02/2012
John Howard
15
28/03/2012
John Howard
16
11/04/2012
John Howard
17
07/05/2012
John Howard
DOCS 826980v30
General
Page 2 of 50
24/05/2012
John Howard
19
13/07/2012
Jason Zuglian
20
16/07/2012
Jason Zuglian
21
17/10/2012
John Howard
22
26/11/2012
John Howard
23
20/12/2012
John Howard
24
22/01/2013
John Howard
03/04/2013
Runi Sugiharti
25
23/8/2013
John Howard
26
15/01/2014
John Howard
27
06/02/2014
John Howard
28
28/03/2014
John Howard
29
3/06/2014
John Howard
30
13/11/2014
J. McMiles
DOCS 826980v30
Page 3 of 50
Contents
1.
Scope
2.
Definitions
3.
Standards
4.
General requirements
5.
Technical requirements
12
6.
28
7.
28
8.
28
9.
28
DOCS 826980v30
Page 4 of 50
2. Definitions
2.1 Hazardous areas
A hazardous area is defined as an area in which an explosive atmosphere is present, or may
be expected to be present, in sufficient quantities to require the installation of specialised
equipment to reduce the risk of fire or explosion.
The areas within and in proximity of grain storage facilities, including elevator towers and
workhouses, boot pits, road and rail discharge grids, conveyor galleries etc, shall be regarded
as HAZARDOUS AREAS. These areas shall be zoned as 20, 21 or 22 in accordance with
AS/NZS 61241.10 : 2005
Switch-rooms shall not be built within these Hazardous Areas unless they are pressurized
and comply with AS/NZS 61241.4 : 2002
DOCS 826980v30
Page 5 of 50
3. Standards
The principal codes and specifications applicable to this work shall include but not be limited to
the current editions, including all amendments and applicable cross references, of all relevant
Australian Standards as follows:
AS/NZS 4761
AS/NZS 3000:2007
AS/NZS 61241
AS 1939
AS 3947
AS 3008
AS 5000.1
AS 3439
AS 2053
AS 1554.1
AS 1795
AS 1755
DOCS 826980v30
Page 6 of 50
ACA TS 009
AS/NZS 3080
CBHE TS20
CBHE TS21
Where no Australian Standards exist, the relevant IEC Standards shall apply.
The installation shall also conform to the requirements of the Office of Energy WA and the
Supply Authority.
4. General requirements
4.1 Enclosures
Enclosures and equipment installed in Hazardous Areas shall comply with the applicable
requirements of AS/NZS 61241.1
For areas not covered by the requirements of AS/NZS 61241.1 the minimum enclosure ratings
shall be IP 52 for internal locations and IP 65 for external positions, as defined in AS 1939.
All enclosures shall be of the type detailed in the equipment schedule or accepted equal. DIP
standards have been specified for some non- hazardous areas, this is done for standardisation
and alternative standards shall not be accepted.
All glands and packing used for sealing enclosures shall be non-deteriorating neoprene
rubber.
4.3 Standardisation
All similar equipment, brackets, accessories, etc, shall be of the same make and pattern, and
all similar parts shall be jig drilled and interchangeable. Preference shall be given to items of
Australian manufacture, particularly in respect of ready availability of replacement parts and
maintenance.
DOCS 826980v30
Page 7 of 50
4.6 Welding
All welding shall conform to the applicable section of AS 1554.
The Contractor shall not carry out any welding without the Principals approval.
DOCS 826980v30
Page 8 of 50
4.9 Finishes
All ferrous metalwork and equipment installed shall be anti-corrosive treated and finished in
accordance with the enclosed Technical Specification No. TS8.
All brackets, racks and stays shall be finished in a colour to match surrounding steelwork
unless specified otherwise.
Any damage to anti-corrosive finishes on structural steelwork or paintwork on equipment
resulting from application of fastenings, brackets, etc, shall be made good to the satisfaction of
the Principal.
DOCS 826980v30
Page 9 of 50
EQUIPMENT
TYPE OF LABEL
Relays/Pushbuttons/
Switches
Wire Numbering
Control Panels
Breakers
rating
Instruments
Cable Tags
Colors shall be permanent and free from fading. Unless otherwise accepted by the Principal,
all designation labels shall be engraved with black lettering on a white background.
Labels shall be securely fixed to the equipment using not less than two fastenings. Label
fixings shall be such as to allow ready replacement without damage to the label or equipment.
Danger or similar warning labels shall have red lettering on a white background.
Individual items of electrical apparatus installed within hazardous areas shall also be marked
in accordance with AS/NZS 61241. 0.
4.11 Documentation
Prior to the time of commissioning of the installation, the Contractor shall complete the
following requirements...
The site hazardous area verification dossier shall be completed by the responsible designer
and /or installer:
4.11.1
4.11.2
Confirming cable and wiring routes and cable and wiring details.
4.11.3
4.11.4
4.11.5
DOCS 826980v30
Page 10 of 50
This document shall be verified and signed off by the appropriate competent and
accredited responsible person by or on behalf of the designer and / or contractor.
For Supply and Construct contracts the Contractor shall neatly mark up, to the Principals
approval, two sets of prints in red for any alteration made during the contract period.
One set of prints shall be returned to the Principal so that the original contract drawings may
be altered to the As Installed state. The other shall be left on site for maintenance purposes.
For Design and Construct contracts the Contractor shall neatly mark up, to the Principals
approval, one (1) set of prints in red for any alteration made during the contract period which
shall be left on site for maintenance purposes.
The Contractor shall provide the Principal with an electronic copy, on compact disc, of the As
Constructed drawings within 14 days of practical completion of the works. These drawings
shall be in AutoCAD (.dwg).
The drawings are intended to be a final record of the installation and shall contain at least the
following information:
a)
Site layout showing all underground cable routes not included in the dossier
complete with dimensioned locations.
b)
Final location of all equipment supplied under this Contract not included in the
dossier.
c)
d)
Size of all fuses, circuit breakers, conductors, cables, etc, for every circuit installed.
e)
f)
g)
h)
Page 11 of 50
4.14. Co-ordination.
Equipment to be supplied under this Contract that forms part of a composite scheme the
Contractor will be required to co-operate fully with the supplier of associated equipment to
ensure correct operation of the installation. This shall include close liaison between Civil and
Mechanical sub-contractors, the Supply Authority and local CBH Engineering District
Managers as required ensuring timely completion of the works.
5. Technical requirements
5.1. Electricity supply
5.1.1. General
The supply shall be 415/240 volts, 3 phase, 4 wire, 50 hertz and derived as shown on the
drawings.
Page 12 of 50
DOCS 826980v30
Page 13 of 50
5.3.5. Control & indication circuits - extra low voltage (24v & below)
Panel wiring 0.75 mm or 1 mm unless nominated.
Positive - Orange.
Negative Purple (Violet).
DOCS 826980v30
Page 14 of 50
Page 15 of 50
In general the methods employed shall be as specified in AS 3000 covering the installation of
underground cables.
The contractor shall take the utmost care to prevent any damage to existing underground
services.
All necessary information in regard to existing underground services shall be obtained by the
contractor from the appropriate sources, e.g. Telstra, Water Authority, Local Shire etc, before
the commencement of any site works. Electronic cable locators or similar shall be employed to
locate existing underground cables. It shall be the responsibility of the contractor to ensure
that any damage to underground services are immediately being repaired and the appropriate
CBH Engineering District Superintendent and the CBH Engineering Project Supervisor are
informed about the extent of the damage and the progress of the repairs.
All costs relating to the repair or replacement of damaged underground services shall be to the
expense of the contractor, unless the contractor can provide sufficient proof to the satisfaction
of the Principal that all reasonable steps were taken to avoid such damage.
Cables being installed in trenches and or ducts shall be protected from excessive temperature
rise due to solar radiation and vandalism, when stored on site prior to installation.
The Contractor shall allow for all excavation, backfilling and reinstatement (not including
bitumen works) costs for this part of the installation to the Principals acceptance.
Page 16 of 50
DOCS 826980v30
Page 17 of 50
DOCS 826980v30
Page 18 of 50
Equipment
Hand Tamper
Min No.
Passes
Cohesionless
Cohesionless
Cohesive
Materials (1)
Materials (2)
Materials
150mm
100mm
100mm
300mm
250mm
200mm
150mm
Not Suitable
Not Suitable
200mm
100mm
Not Suitable
Min 15 kg
Mechanical
Tamper
Min 50 kg (3)
Vibrating Plate
Min 50 kg
Vibrating Plate
Min 100 kg
Notes:
1. Free draining materials.
2. Non free draining materials.
3. Wacker Packer or similar compactor.
Page 19 of 50
DOCS 826980v30
Page 20 of 50
DOCS 826980v30
Page 21 of 50
5.11. Glands
All cable glands and associated fittings shall be supplied and fitted by the contractor.
All cable glands shall be DIP certified for installation within Zone 20 and Zone 21 classified
areas as required.
All cables shall be terminated using the cable manufacturers recommended cable glands
sizes.
The cable gland and locking nuts and rings shall be metal construction and shall be
compatible with the termination gland plate or terminating box material.
All glands shall be securely fixed to the gland plate and where locknuts are used as a method
of fixing, then a locking ring shall be installed in addition to the normal locknut.
Cable glands shall be terminated at a position such that the conductors can easily be worked
into their final termination position without damaging the conductor insulation.
Cable glands not meeting these requirements shall be replaced at the contractors expense.
DOCS 826980v30
Page 22 of 50
All conductors shall be fitted with the appropriate crimped cable lugs.
5.12.2. Motors.
All motors regardless of location in any area of grain handling equipment shall be a minimum
IP65 DIP.
All motors shall be site tested with a 1000 volt Insulation Resistance tester and the results
including all Motor Nameplate data submitted in writing to the Principal refer Appendix C.
Unless otherwise specified all electric motors will be supplied and fitted by others. Provide
electrical connection to these motors.
Before commissioning each motor liaise with the Mechanical Contractor to verify the required
motor rotation and verify that the overload settings are correct.
Page 23 of 50
DOCS 826980v30
Page 24 of 50
DOCS 826980v30
Page 25 of 50
DOCS 826980v30
Page 26 of 50
DOCS 826980v30
Page 27 of 50
DOCS 826980v30
Page 28 of 50
Circuit
breakerControl &
General
Cable
Ladder
Cable
Ladder
Cable Tray
Cable Cat 6
Socket
Cable-Cat 6
Cable Pits
CableOptic Fibre
CableCommunic
ation
(REPOL)
CablePower &
Control
Cable Ladder (External and installed two metres above the ground).
Kounis Metal Industries. Type 3/50 (NEMA 16A), complete with covers.
DOCS 826980v30
of 50
Page 29
17-25amp
22-32amp
28-40amp
35-50amp
44-63amp
56-80amp
NSX100N
NSX100N
NSX100N
NSX100N
NSX100N
NSX100N
70-100amp
87-125amp
112-160amp
175-250 amp
NSX100N
NSX160N
NSX160N
NSX250N
TM25D
TM32D
TM40D
TM50D
TM63D
TM80D
TM100D (Suit Stacker Loader 90amp outlets,
Set on 85 amps).
TM125D
TM160D
TM250D
Circuit
breakerMain
Switch
Circuit
breakerMain
Switch
Note. If the final sub-circuit supplied via an outlet a 100ma RCD (ELCB) is required.
DOCS 826980v30
of 50
Page 30
Motor Size
Current setting
Breaking
capacity
Type
0.37kw
0.63-1.0 amp
100kA
GV2ME05
0.55kw
1.0-1.6 amp
100kA
GV2ME06
0.75kw
1.6-2.5 amp
100kA
GV2ME07
1.1kw
2.5-4.0 amp
100kA
GV2ME08
2.2kw
4.0-6.3 amp
100kA
GV2ME10
4kw
6-10amp
100kA
GV2ME14
5.5kw
9-14 amp
15kA
GV2ME16
7.5kw
13-16 amp
15kA
GV2ME20
9kw
17-23 amp
15kA
GV2ME21
11kw
20-25 amp
15kA
GV2ME22
15kw
24-32 amp
10kA
GV2ME32
DOCS 826980v30
of 50
Page 31
Motor
size
Set thermal on
Type
Set magnetic
on
35 amp
18.5kw
NSX100N
TM50D, 35-50amp
0.8
38 amp
22kw
NSX100N
TM50D, 35-50amp
0.8
53 amp
30kw
NSX100N
TM63D, 44-63amp
0.9
61 amp
37kw
NSX100N
TM80D, 56-80amp
1
73 amp
45kw
NSX100N
TM100D, 70-100amp
1
81 amp
55kw
NSX160N
TM100D, 70-100amp
1
115 amp
75kw
NSX160N
TM160D, 112-160amp
1
141 amp
Horn
Heat Shrink
EnclosuresNon DIP
Contactor
Conduit
90kw
NSX250N
TM200D, 140-200amp
0.9
DOCS 826980v30
of 50
Page 32
LanyardDIP
J BoxNon DIP
J BoxDIP
Indicator
Horn
LightingHand Rail
Staunching
mounted Non DIP
LightingHand Rail
Staunching
mounted DIP
Lanyard
DIP
nd
DOCS 826980v30
of 50
Page 33
DOCS 826980v30
of 50
Page 34
DOCS 826980v30
of 50
Page 35
LightingFlood
Lighting, Non
DIP
Lighting External Area Flood Lights Non DIP Zone Application Mounted at high
level on structures or as nominated.
Weatherproof IP65 with integral ballast.
Sylvania: 2000w, 415v, MH, BLS2000/2000
Thorn: 2000w, 415v, MH, MUNC2000DEGMDKITWP
Poles Suit E & V Pits
G & S Industries, 6 metres type F6BM.
Cage Bolts to suit above - G & S Industries, 890614, CR16/4/282.
Cross arm for two flood lights to suit above 890213, CA1200T3.
Lighti
ngPhoto
Electr
ic
Cell
Lighting External Area Flood Lights Non DIP Zone Application Under garner bins
& over road / rail grids
Weatherproof IP65 with integral ballast.
Philips: Con TEMPO L 400w HPS, RVP350SON-T400S.
Thorn: 400w HPS, AP2400HST
LightingFlood
Lighting, Non
DIP
LightingFlood
Lighting
Poles
Lighting Internal Storage DIP Zones 21 & 22 Application Flood Lighting / Pendant
Lighting.
PLEASE NOTE:
Ex tD T4 IP65 for use in hazardous areas with a maximum surface temperature 175
degrees Centigrade if not T4.
Flood Light Fitting & Globe:
TBC
DOCS 826980v30
of 50
Page 36
Power
OutletNon DIP
Power
OutletNon DIP
phase
10amp
Overload
Limit Switch
HOLD
Limit
SwitchInductive
Proximity,
DIP
Limit Switch
Limit Switch
LightsTraffic Lights
LightsTraffic Lights
LightsTraffic Lights
24vdc LED, 200mm diameter Traffic Lights - Suit Sample Platforms etc.
RED/GREEN Type STL-200-RG-24, Available from EX Engineering 0408 221 337.
Replacement RED module SRM-200-R-24.
Replacement GREEN module SRM-200-G-24.
240vac LED, 200mm diameter Traffic Lights - Suit Sample Platforms etc.
RED/GREEN Type STL-200-RG-240, Available from EX Engineering 0408 221 337.
Replacement RED module SRM-200-R-240.
Replacement GREEN module SRM-200-G-240.
Limit Switch
Honeywell - SPDT, LS4A1A-DIP and DPDT, LS4A2A-DIP.
Adjustable arm to suit above LSZ52C.
Notehas the same fixings and shaft size as Cutler Hammer E50.
Limit Switch
STAHL. DIP.
8070/1-1-HV. 1NC + 1NO, C/W ADUSTABLE ARM.
Power Outlets & Plug (Non DIP) Three Phase & N 150amp 3P+N+E
Marechal 150amp Socket Outlet c/w self-returning lid DS9 31-98-017R. Plus Wall Box 399A-053. Or equivalent.
Marechal 150amp Inlet (Plug Top) DS9 31-98-017. Plus handle 65-9A-013-D45 (E).
DOCS 826980v30
of 50
Page 37
Power Outlets & Plug (Non DIP) Three Phase 30amp 3P+E
Marechal 30amp Socket Outlet c/w self-returning lid DS1 31-14-013R. Plus Wall Box 311A-053. Or equivalent.
Marechal 30amp Inlet (Plug Top) DS1 31-18-013. Plus handle 31-1A-013.
Power Outlets & Plug (Non DIP) Three Phase 50amp 3P+E
Marechal 50amp Socket Outlet c/w self-returning lid DS3 31-34-013R. Plus Wall Box 313A-053. Or equivalent.
Marechal 50amp Inlet (Plug Top) DS3 31-38-013. Plus handle 31-3A-013.
Power Outlets & Plug (Non DIP) Three Phase 90amp 3P+E
Marechal 90amp Socket Outlet c/w self-returning lid DS6 31-64-013R. Plus Wall Box 316A-053. Or equivalent.
Marechal 90amp Inlet (Plug Top) DS6 31-68-013. Plus handle 31-6A-013.
Proximity
SensorCapacitive
Proximity SensorCapacitive
Power Supply24vdc
Power
OutletNon DIP
Power
OutletNon DIP
Power
OutletNon DIP
Power
OutletNon DIP
Power
OutletDIP
Power
OutletDIP
DOCS 826980v30
of 50
Page 38
RelayControl
Relay timers
Schneider.
NHP Sprecher Schuh.
Or as specified.
SwitchEmergency
SwitchEmergency
Soft Starter
RelayControl
RelayPower
RelayTimer
DOCS 826980v30
of 50
Page 39
SwitchLocal
Control
SwitchIsolator
Timer-Ondelay
Timer ON-DELAY
&
INSTA NTANEOUS
TimerDouble on --delay
Terminals
BlockPower
connections
TerminalsControl wiring
SwitchLocal
Control
SwitchLocal Control
SwitchLocal
Control
Terminals
Schneider AB1
DOCS 826980v30
of 50
Page 40
WiringPanel wiring
Ferrules
VSD
TimerOff delay
Timer-Ondelay
1 C/O (8amp),
NOTE:
No changes to the Equipment Schedule shall apply without prior approval by the
Principal.
DOCS 826980v30
of 50
Page 41
Cubicle
Equipment
Initials
Comments
Motor
Interlock
Manual
Cabling
Local Isolators
Protection
Indicator Lights
Elevator running
Ammeter
Motor
Interlock
Manual
Cabling
Limit Switches
Valve Motor
Interlock
Manual
Cabling
Timing
Cabling
Limit Switches
Grain Sensors
Cubicle
Indicator Lights
Head Valve
Motor
Interlock
Manual
Cabling
Limit Switches
Cubicle
Indicator Lights
Labelling
Fitted
Inching Drive
Road Hopper
DOCS 826980v30
of 50
Page 42
Operation
Electrical
Interlock
Manual
Cabling
Cubicle Protection
Indicator Lights
Initials
Comments
GROUND CONVEYORS
Equipment
Drive motor
Cubicle
Isolating Switches
Operation
Electrical
Interlock
Manual
Cabling
Protection
Indicator Lights
Warning sirens
Lanyard switches
Initials
Comments
Set correctly
Manufacturers specification
Operation
Stacker Outlets
Cabling
9m maximum
Spaces between
36m maximum
Accessibility
Cubicle
Labelling
Cabling
Protection
Indicator Lights
Stacker running
Fitted
Cable Ladder
Mounting
Fixing
DOCS 826980v30
of 50
Cable spacing
Cable fixing
Page 43
Cubicle
Operation
Electrical
Interlock
Manual
Cabling
Protection
Indicator Lights
Initials
Comments
Set correctly
Operation
Cabling
Cable Ladder
Mounting
Fixing
Labelling
Cable spacing
Cable fixing
Cable bends
Fitted
DOCS 826980v30
of 50
Page 44
Operation
Initials
Comments
Main switch
Rating
Circuit breakers
Rating
Labelling
Fitted
Control Panel
Indicators
Layout
As per drawings
System
Interlock
Manual
Wiring
Lamps
General
Switches Pushbuttons
Rotary
General
Valve
Sirens
(2) Time
(3) Hysteresis
(4) Current
(5) Contact
Motor overloads
Settings
Cabling / Wiring
Incoming
Internal
Terminations
Protection
Timers
Current Sensors
DOCS 826980v30
of 50
Page 45
Site:
Contractor:
Plant Area:
Equipment:
Make:
Rated RPM:
Type:
Rated kW:
Serial No.:
Rated Voltage:
Frame:
Rated IFL:
Bearing
Types:
Drive End
Insulation
Test:
A to E
Non D E
.. Megohms B to E
C to E
Megohms
Provide actual
Megohms
Amps
Amps
Amps
Seconds
Starts/hour
Amps
Amps
Remarks:
Tested By:
Signed:
DOCS 826980v30
of 50
Date:
..//
Page 46
When all Mod Tap Testing is completed, record your results on the test sheets.
Install RAD Line Drivers on the last point of the installation at the Sampling
Platform, wall sockets Nos 1 to 6, then at the Weighbridge on Infra 1 & 2, Balance
1 & 2 and Term 1 & 2, making sure that all Patch Leads are connected in the
Patch Panel in Sampling Platform in the correct positions.
g) Set all RAD Line Drivers to DCE at all locations and connect one of the RAD LBT
Testers to Infra 1 at the Sampling Platform and the other RAD LBT Tester on Infra
1 at the weighbridge. Do the same procedure for the remaining area Infra 2,
Balance 1 & 2 and Term 1 & 2.
NOTE: If only single Repols installation required, Infra 2, Balance 2 and Term 3 are not
required.
h)
i)
The first test should be run for a minimum of 3 minutes. After 3 minutes you
should have approximately 6,000 blocks received. There should be no block
errors or sync errors with this test.
Test No. 2 should be run for a minimum of 5 minutes, during this time you should
inject no less than 5 error bits into the system. After 5 minutes you should have
received more than 11,000 blocks and not have a block error rate of more than
.0650%. Record all your results on the test sheet.
After all tests are completed, make sure RAD Line Drivers are set back to the
settings as per the information on the Repols drawing. Submit all tabulated results
to Co-operative Bulk Handling Limited with As-Built Drawings.
j)
k)
DOCS 826980v30
of 50
Page 47
BLOCK
ERROR
% RATE
RECEIVE
D
BLOCKS
CONTAINI
NG
BLOCKS
ERRORS
SYNC
LOSS
LINE
DRIVER
SERIAL
No.
WEIGHBR
IDGE
LINE
DRIVER
SERIAL
No.
SAMPLE
HUT
INITIALS
INFRA 1
TERM 1
BALANCE 1
INFRA 2
TERM 2
BALANCE 2
5 minutes
minimum
BLOCK
ERROR
RECEIVED
BLOCKS
CONTAINING
% RATE
BLOCKS
ERRORS
SYNC
LOSS
No. OF
ERRORS
INITIALS
INJECTED
INFRA 1
TERM 1
BALANCE 1
INFRA 2
TERM 2
BALANCE 2
RECIEVAL POINT :
DATE:
CONTRACTOR :
NAME OF TECHNICIAN :
TEST COMPLETED :
DOCS 826980v30
of 50
YES
NO
Page 48
No OF PAIRS
SHOWING ON
TESTER
CORRECT LABELLING
& WIRING OF
STANDARD 568A
TERMINATION
INITIALS
FLY LEAD 1
FLY LEAD 2
FLY LEAD 3
FLY LEAD 4
FLY LEAD 5
FLY LEAD 6
PATCH LEAD 1
PATCH LEAD 2
PATCH LEAD 3
PATCH LEAD 4
PATCH LEAD 5
PATCH LEAD 6
No OF PAIRS
SHOWING ON
TESTER
CORRECT WIRING
OF STANDARD
568A
TERMINATION
CORRECT
LABELLING OF
INSTALLATION
INITIALS
SOCKET 1
SOCKET 2
SOCKET 3
SOCKET 4
SOCKET 5
SOCKET 6
RECIEVAL POINT :
DATE:
CONTRACTOR :
NAME OF TECHNICIAN :
TEST COMPLETED :
DOCS 826980v30
of 50
YES
NO
Page 49
No OF THE PAIRS
SHOWING ON
TESTER
INITIALS
INFRA 1
TERM 1
BALANCE 1
INFRA 2
TERM 2
BALANCE 2
RECIEVAL POINT :
DATE:
CONTRACTOR :
NAME OF TECHNICIAN :
TEST COMPLETED :
DOCS 826980v30
of 50
YES
NO
Page 50