Nothing Special   »   [go: up one dir, main page]

Sub: Multipurpose Hall - Lusail Sports Club - Package 2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12
At a glance
Powered by AI
The document is a quotation for diesel generator sets and related equipment for a sports club project in Qatar.

The equipment being quoted includes CAT model 3512BTA 1600 KVA diesel generator sets, batteries, fuel tanks and other accessories.

Payment terms include 25% advance payment with order confirmation and balance before delivery.

OurRef:PSD/215/2012/HB

Date:05092012

M/s.ETAStarEngineering&ContractingWLL
Tel:+97444666768
Attn:Mr.SirajKafoor
EMail:sirajkafoor.eta@gmail.com
Sub:MultipurposeHallLusailSportsClubPackage2

DearSir,

Wethankyouforyourvalued enquiryandarepleasedtosubmitourquotationas
follows:
1. 1 x New CAT Model 3512BTA 1600 KVA/ 1280 eKW ,
415/240volts,3Phase,1500RPM,50Hertz,at0.8p.f.Stanby
Diesel Generator set with NO 10% overload for 1 Hr in 12
HrsofOperation,asperattachedspecifications.

Price,Each(ExourFacility)QRS.
Pricefor4gensetsQRS.
(QatariRiyalsFiveMillionTwoHundredandTen
ThousandOnly)
2. 1xSetOfSAFTmakeNicadBatteries,SPH130,24VD.C,
130Ah,tobeusedwithaboveofferedItem#1

Price,Each(ExourFacility)QRS.
Pricefor4SetofbatteriesQRS.
(Qatari Riyals One Hundred and Sixty Eight Thousand
only)
3. 1x3000ltr,Singlewall,CylindricalTypeDieselDaytank
for8hrFullLoadOperationofaboveofferedgensets.

Price,Each(ExourFacility)QRS.
Pricefor4TanksQRS.
(QatariRiyalsSixtyThousandonly)

1,302,500.00
5,210,000.00

42,000.00
168,000.00

15,000.00
60,000.00

4. Delivery:

TobediscussedatthetimeofOrderFinalization.

5. ScopeofWork:

Supply&Commissioningofgeneratoronly.
Loadingofgensetatourfacility.
Transportationtosite,offloadingatsite.
Installationandinstallationrelatedmaterials.
FloorMountedGCP
30days

6. Exclusions:

7. Validity:

1of2

P.O.BOXNO.2171,TELEPHONENO.097444600222,FAXNO.44600225,DOHAQATAR
(IFTHISFAXMESSAGEISILLEGIBLEORINCOMPLETE,PLEASECONTACTUSIMMEDIATELY)

OurRef:PSD/215/2012/HB
8. PaymentTerms:

9. Countryof
Origin:

10. Warranty:

11. ForceMajeure:
12. TaxesAnd
Duties:
13. SpecialNote:

Date:05092012

25% as advance along with your confirmed order and


balancebeforedelivery,againstreadinessofmaterialsat
ourfacility.
USA

The equipment would carry warranty of 12 months


from the date of commissioning or 18 months from the
date of supply, whichever is earlier, against
manufacturingdefects,onlyinQatar,asperCaterpillar
standardwarrantytermsandconditions.
Above delivery is subject to standard force majeure
conditions.
Any additional cost resulting from increase in customs
duties,taxesetc.orasaresultofchangesintheexisting
lawsofthestateshallbebornebyyou.
Caterpillar has a continuous program for product
improvement and product renewal. Due to this we reserve
our rights to deliver modified/new product, which meets or
exceedscommittedspecifications/performance

Incaseyourequireanyadditionalinformation/clarification,pleasedonothesitate
tocontactus.

BestRegards
ForMohamedAbdulrahmanAlBahar

HussanButt

AnilRaina
ApplicationEngineer

BranchSalesManager
(Power Systems Dept)
(Power Systems)

Encl:Specification

2of2

P.O.BOXNO.2171,TELEPHONENO.097444600222,FAXNO.44600225,DOHAQATAR
(IFTHISFAXMESSAGEISILLEGIBLEORINCOMPLETE,PLEASECONTACTUSIMMEDIATELY)

DIESEL GENERATOR SET

STANDBY
1280 ekW 1600 kVA
50 Hz 1500 rpm 415 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.

FEATURES
FUEL/EMISSIONS STRATEGY
Low Fuel consumption
DESIGN CRITERIA
The generator set accepts 100% rated load in one
step per NFPA 110 and meets ISO 8528-5 transient
response.
FULL RANGE OF ATTACHMENTS
Wide range of bolt-on system expansion
attachments, factory designed and tested
Flexible packaging options for easy and cost
effective installation
SINGLE-SOURCE SUPPLIER
Fully prototype tested with certified torsional
vibration analysis available
WORLDWIDE PRODUCT SUPPORT
Cat dealers provide extensive post sale support
including maintenance and repair agreements
Cat dealers have over 1,800 dealer branch stores
operating in 200 countries
The Cat SOSSM program cost effectively detects
internal engine component condition, even the
presence of unwanted fluids and combustion
by-products

CAT 3512B TA DIESEL ENGINE


Reliable, rugged, durable design
Field-proven in thousands of applications
worldwide
Four-stroke-cycle diesel engine combines
consistent performance and excellent fuel
economy with minimum weight
CAT SR5 GENERATOR
Matched to the performance and output
characteristics of Cat engines
Industry leading mechanical and electrical design
Industry leading motor starting capabilities
High Efficiency
CAT EMCP 3 SERIES CONTROL PANELS
Simple user friendly interface and navigation
Scalable system to meet a wide range of
customer needs
Integrated Control System and Communications
Gateway

STANDBY 1280 ekW 1600 kVA


50 Hz 1500 rpm 415 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT


System
Air Inlet

Standard
Single element canister type air cleaner
Service indicator
Radiator with guard
Coolant drain line with valve
Fan and belt guards
Cat Extended Life Coolant*

Optional
[ ] Dual element & heavy duty air cleaners
[ ] Air inlet adapters & shutoff
[ ] Radiator duct flange
[ ] Jacket water heater

Exhaust

Dry exhaust manifold


Flanged faced outlets

Fuel

Secondary fuel filters


Fuel priming pump
Flexible fuel lines
Fuel cooler*
Class H insulation
Cat digital voltage regulator (CDVR) with kVAR/PF
control, 3-phase sensing
Reactive droop
Bus bar (NEMA or IEC mechanical lug holes)
Top cable entry

[ ] Mufflers and Silencers


[ ] Stainless steel exhaust flex fittings
[ ] Elbows, flanges, expanders & Y adapters
[ ] Water separator
[ ] Duplex fuel filter

Cooling

Generator

Power Termination

[ ] Oversize & premium generators


[ ] Winding temperature detectors
[ ] Bearing temperature detectors
[ ] Anti-condensation heaters
[ ] Circuit breakers, UL listed, 3 pole with shunt
trip,100% rated, manual or electrically operated [ ]
Circuit breakers, IEC compliant, 3 or 4 pole with shunt
trip, manual or electrically operated
[ ] Bottom cable entry
[ ] Power terminations can be located on the right, left
and/or rear as an option.
[ ] Load share module

Governor

ADEM 3

Control Panels

EMCP 3.1 EMCP 4.2


User Interface panel (UIP) - wall mounted
AC & DC customer wiring area (right side)
Emergency stop pushbutton

[ ] EMCP 3.2 ... [ ] EMCP 3.3


[ ] Option for right or left mount UIP
[ ] Local & remote annunciator modules
[ ] Digital I/O Module
[ ] Generator temperature monitoring & protection
[ ] Remote monitoring software

Lube

Lubricating oil and filter


Oil drain line with valves
Fumes disposal
Gear type lube oil pump

Mounting

Rails - Engine / generator / radiator mounting


Rubber anti-vibration mounts (shipped loose)

Starting/Charging

24 volt starting motor(s)


Batteries with rack and cables
Battery disconnect switch

[ ] Oil level regulator


[ ] Deep sump oil pan
[ ] Electric & air prelube pumps
[ ] Manual prelube with sump pump
[ ] Duplex oil filter
[ ] Isolator removal
[ ] Spring-type vibration isolator (shipped loose)
[ ] IBC Isolator
[ ] Battery chargers (5 or 10 amp)
[ ] 45 amp charging alternator
[ ] Oversize batteries
[ ] Ether starting aids
[ ] Heavy duty starting motors
[ ] Barring device (manual)

February 21 2011 03:18 AM

STANDBY 1280 ekW 1600 kVA


50 Hz 1500 rpm 415 Volts

SPECIFICATIONS
CAT GENERATOR

CAT EMCP SERIES CONTROLS

Cat Generator
Frame size....................................................................... 1468
Excitation............................................................................. IE
Pitch.............................................................................. 0.6667
Number of poles...................................................................4
Number of bearings............................................................. 1
Number of Leads.............................................................. 006
Insulation....................... UL 1446 Recognized Class H with
tropicalization and antiabrasion
IP Rating........................................................................... IP23
Alignment.............................................................. Pilot Shaft
Overspeed capability - % of rated................................... 150
Wave form....................................................................002.00
Paralleling kit/Droop transformer.......................... Standard
Voltage regulator.3 Phase sensing with selectible volts/Hz
Voltage regulation............Less than +/- 1/2% (steady state)
Less than +/- 1% (no load to full load)
Telephone Influence Factor.............................. Less than 50
Harmonic distortion......................................... Less than 5%

EMCP 3.1 (Standard)


EMCP 3.2 / EMCP 3.3 (Option)
Single location customer connection point
True RMS AC metering, 3-phase
Controls:
- Run / Auto / Stop control
- Speed Adjust
- Voltage Adjust
- Emergency Stop Pushbutton
- Engine cycle crank
Digital Indication for:
- RPM
- Operating hours
- Oil pressure
- Coolant temperature
- System DC Volts
- L-L volts, L-N volts, phase amps, Hz
- ekW, kVA, kVAR, kW-hr, %kW, PF (EMCP 3.2 / 3.3)
Shutdowns with common indicating light for:
- Low oil pressure
- High coolant temperature
- Low coolant level
- Overspeed
- Emergency stop
- Failure to start (over crank)
Programmable protective relaying functions: (EMCP 3.2
& 3.3)
- Under and over voltage
- Under and over frequency
- Overcurrent (time and inverse time)
- Overcurrent
Reverse power (3.3)
MODBUS isolated data link, RS-485 half-duplex (EMCP
3.2 & 3.3)
Options

CAT DIESEL ENGINE


3512B TA, 4-stroke-cycle watercooled diesel
Bore - mm.............................................. 170.00 mm (6.69 in)
Stroke - mm........................................... 190.00 mm (7.48 in)
Displacement - L................................... 51.80 L (3161.03 in3)
Compression ratio........................................................ 14.0:1
Aspiration........................................................................... TA
Fuel system..................................... Electronic unit injection
Governor type............................................................ ADEM3

February 21 2011 03:18 AM

STANDBY 1280 ekW 1600 kVA


50 Hz 1500 rpm 415 Volts

TECHNICAL DATA
Open Generator Set - - 1500 rpm/50 Hz/415 Volts
Low Fuel Consumption

DM8045

Generator Set Package Performance


Genset Power rating @ 0.8 pf
Genset Power rating with fan
Coolant to aftercooler
Coolant to aftercooler temp max

1600 kVA
1280 ekW

Fuel Consumption
100% load with fan
75% load with fan
50% load with fan
Cooling System1
Air flow restriction (system)
Engine Coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity
Inlet Air
Combustion air inlet flow rate
Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)
Heat Rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
Alternator2
Motor starting capability @ 30% voltage dip
Frame
Temperature Rise
Lube System
Sump refill with filter

30 C

86 F

323.3 L/hr
246.4 L/hr
170.7 L/hr

85.4 Gal/hr
65.1 Gal/hr
45.1 Gal/hr

0.12 kPa
286.8 L
156.8 L
130.0 L

0.48 in. water


75.8 gal
41.4 gal
34.3 gal

110.9 m/min

3916.4 cfm

393.7 C
260.0 m/min
203.2 mm
6.7 kPa

740.7 F
9181.8 cfm
8.0 in
26.9 in. water

502 kW
1092 kW
363 kW
114 kW
56.1 kW

28549 Btu/min
62102 Btu/min
20644 Btu/min
6483 Btu/min
3190.4 Btu/min

4592 skVA
1468
150 C

270 F

310.4 L

82.0 gal

Emissions (Nominal)3
NOx mg/nm3
3223.1 mg/nm
CO mg/nm3
682.4 mg/nm
HC mg/nm3
68.0 mg/nm
PM mg/nm3
30.2 mg/nm
1
For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.
2
UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator
temperature rise is based on a 40 degree C ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77F, 28.42 in HG and number 2 diesel fuel
with 35 API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.

February 21 2011 03:18 AM

STANDBY 1280 ekW 1600 kVA


50 Hz 1500 rpm 415 Volts

RATING DEFINITIONS AND CONDITIONS


Meets or Exceeds International Specifications: AS1359,
CSA, IEC60034-1, ISO3046, ISO8528, NEMA MG 1-22,
NEMA MG 1-33, UL508A, 72/23/EEC, 98/37/EC,
2004/108/EC
Standby - Output available with varying load for the
duration of the interruption of the normal source power.
Average power output is 70% of the standby power
rating. Typical operation is 200 hours per year, with
maximum expected usage of 500 hours per year.
Standby power in accordance with ISO8528. Fuel stop
power in accordance with ISO3046. Standby ambients
shown indicate ambient temperature at 100% load which
results in a coolant top tank temperature just below the
shutdown temperature.

Ratings are based on SAE J1349 standard conditions.


These ratings also apply at ISO3046 standard conditions.
Fuel rates are based on fuel oil of 35 API [16 C (60 F)]
gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
when used at 29 C (85 F) and weighing 838.9 g/liter
(7.001 lbs/U.S. gal.). Additional ratings may be available
for specific customer requirements, contact your Cat
representative for details. For information regarding Low
Sulfur fuel and Biodiesel capability, please consult your
Cat dealer.

February 21 2011 03:18 AM

STANDBY 1280 ekW 1600 kVA


50 Hz 1500 rpm 415 Volts

DIMENSIONS

Package Dimensions
Length
Width
Height
Weight

5137.1 mm
1974.9 mm
2342.0 mm
12 896 kg

NOTE: For reference only - do not use for


installation design. Please contact
your local dealer for exact weight
and dimensions. (General
Dimension Drawing #2882684).

202.25 in
77.75 in
92.2 in
28,431 lb

www.Cat-ElectricPower.com

Performance No.: DM8045

2011 Caterpillar
All rights reserved.

Feature Code: 512DE6X

Materials and specifications are subject to change without notice.


The International System of Units (SI) is used in this publication.

Gen. Arr. Number: 2523822

CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the


"Power Edge" trade dress, as well as corporate and product identity used
herein, are trademarks of Caterpillar and may not be used without
permission.

Source: U.S. Sourced


February 21 2011

17515702
6

MOHAMED ABDULRAHMAN AL-BAHAR

SPECIFICATIONANDCONSIST
3512BTA,1600KVA/1280KW,415V,1500RPM,50Hz,STANDBYRATED

MODEL&RATING

CaterpillarModel3512BTA1600KVA/1200KW,0.8powerfactor,415/240volts,3
phase,1500rpm,standbypowerdieselgeneratingsetforstandbyapplication.

AIRINLETSYSTEM

Aircleanerdualelement
Serviceindicator.

CONTROLPANELSEMCP4.2
CONTROLS

Run/Auto/Stop
EngineCoolDownTimer
EmergencyStop
EngineCycleCranking
Speed&Voltageadjust

DIGITAL(LCD)INDICATION
GeneratorACVoltage3phase(LLandLN)
GeneratorACCurrent(perphaseandaverage)
GeneratorFrequency
GeneratorkW,kVAR,kVA(Average,Phase,%)
GeneratorPowerFactor(Average,Phase)
GeneratorkWhr,kVArhr(Total)
GeneratorExcitationvoltageandcurrent(withCDVR)
EngineRPM
BatteryVoltage
EngineHours
EngineOilPressure
EngineCoolantTemperature
Twenty(20)EventFaultLog

WARNING/SHUTDOWNINDICATION
Overcrank
HighCoolantTemperatureWarning/Shutdown
LowOilPressureWarning/Shutdown
1of4

P.O.BOXNO.2171,TELEPHONENO.097440159555,FAXNO.4600225,DOHAQATAR
(IFTHISFAXMESSAGEISILLEGIBLEORINCOMPLETE,PLEASECONTACTUSIMMEDIATELY)

MOHAMED ABDULRAHMAN AL-BAHAR

Overspeed
High/LowBatteryVoltage
EmergencyStopActivated
ControlNOTinAUTO

DIGITALINPUTS(6TOTAL)
Twodedicateddigitalinputs
RemoteStart
4Programmable

RELAYOUTPUTS(6TOTAL)
TwoDigitaloutputs
SixProgrammablefromAdrycontacts
TwoprogrammableformCdrycontacts

COMMUNICATIONS
CANdatalinks
RS485annunciatordatalink
ModbusRTU(RS485Halfduplex)

COOLINGSYSTEM

Radiatorwithguardsizedfor50C
Ductflange
Coolantdrainlinewithvalve,pipedtoedgeofbase
Fanandbeltguards
CaterpillarExtendedLifeCoolant
Coolantlevelshutdown
Jacketwaterheaterwithcirculatingpump.

EXHAUSTSYSTEM

ExhaustManifoldDry
flangedoutlet.
StandardTypeMuffler

FUELSYSTEM

Primaryfuelfilter
2of4

P.O.BOXNO.2171,TELEPHONENO.097440159555,FAXNO.4600225,DOHAQATAR
(IFTHISFAXMESSAGEISILLEGIBLEORINCOMPLETE,PLEASECONTACTUSIMMEDIATELY)

MOHAMED ABDULRAHMAN AL-BAHAR

Waterseparator
Secondaryfuelfilter
Fuelprimingpump
Flexiblefuellinesterminatedonbase
Fuelpressuregauge

GENERATORSANDGENERATORATTACHMENTS

SR5PermanentMagnetExcitation(PMG)
ClassHinsulation
Randomwound
DigitalVoltageRegulator
Segregatedlowvoltage(AC/DC)wiringpanel
AirCircuitBreaker3pole2500Amps,IECcompliantwithGroundFaultProtection
Spaceheater
VoltageRaise/LowerSwitch
AlarmModule
RTDmodule
RemoteMonitoringKit

GOVERNINGSYSTEM

CatElectronicGovernor.

LUBESYSTEM

Lubricatingoil
Oilfilter
Oildrainlinewithvalve,pipedtoedgeofbase
CrankCaseBreather,Fumespipedtofrontofradiator
Deepsumpwithmanualpump

MOUNTINGSYSTEM

Base,formedsteel
AntivibrationmountingLinearSpringIsolators

3of4

P.O.BOXNO.2171,TELEPHONENO.097440159555,FAXNO.4600225,DOHAQATAR
(IFTHISFAXMESSAGEISILLEGIBLEORINCOMPLETE,PLEASECONTACTUSIMMEDIATELY)

MOHAMED ABDULRAHMAN AL-BAHAR

STARTING/CHARGINGSYSTEM

45ampchargingalternator
24voltstartingmotor
Batterywithrack,cables
Batterydisconnectswitch
BatteryCharger10Amps.

4of4

P.O.BOXNO.2171,TELEPHONENO.097440159555,FAXNO.4600225,DOHAQATAR
(IFTHISFAXMESSAGEISILLEGIBLEORINCOMPLETE,PLEASECONTACTUSIMMEDIATELY)

You might also like