SERVICE INSTRUCTIONS
Concepcion
Carrier
Air conditioning
Company
38ASB/CCARS240~600 (036~060)
AIR-COOLED CONDENSING UNIT
Philippines
CONTENTS
Safety Considerations
Dimensional Drawing
Start-up
Model Identification
Refrigerant Charging
Specifications
Wiring Diagram
Installation
Refrigerant Piping
Piping Connections
Trouble-Shooting Guide
5
5
5-6
6-7
7 - 13
14
FIG. 1
38ASB/CCARS240~600
(036~060) Export
SAFETY CONSIDERATIONS
INSPECTION
RECEIVING
38ASB/CCARS240~600 condensing units (Fig. 1) are
shipped individually packed in carton boxes. When cartons
are individually off loaded from truck, do not roll, nor throw,
or drop the carton, to avoid damages to the content. Store
boxes upright as the symbols or the boxes indicate. Do not
stack units more than 2 high.
PROTECTION
Protect unit from damage caused by job site debris. Do
not allow dust, debris and water get into the unit.
These will damage units component and units
performance will be affected.
WARNING
Before installing or servicing system always turn off main
power supply. There may be more than one disconnect
switch. Electrical shock can cause personal injury.
2TR
3TR
STD
5TR
(EXPORT)
38ASB
38ASB240BA
38ASB360BA
38ASB036BA
CCAR
CCARS024EA
CCARS036EA
REMARKS
STD
38ASB600DB *
38ASB600DC **
CCARS060KA
(EXPORT)
38ASB060BA
Single phase supply
volatge
Legend:
* - Model used for 40KMC/GKX, 42GX/AR, 40LX
** - Model used for SlimPack ASBFE600BA
TABLE 2 SPECIFICATIONS
38ASB / CCARS
MODEL
240BA
360BA
OPERATING WEIGHT
(kg)
67
80.5
80.5
GROSS WEIGHT
(kg)
69.5
83
83
REFRIGERANT
Type
1.5
2.52
2.52
Type
0.90
1.30
1.30
87.5
87.5
2.55
2.27
2.50
1.66
1.95
1.95
91
91
175
139
135
16.8
26.8
16.7
15.0
230V-1Ph-60Hz
Type
230V-3Ph-60Hz
Propeller
1
550
Speed (rpm)
950
Drive
Direct Drive
Type
Power Supply
230V-1Ph-60Hz
Face Area (m )
1.7
2R - 15
2.5 - 15
0.379
0.536
3.5R - 15
Type
Flare
(9.5) 3/8
(15.88) 5/8
(19.05) 3/4
426 ? 20
SETTINGS
3R - 15
0.654
97.5
16.8
CONNECTIONS
85
66
Number
CONDENSER COIL
85
12.6
Power Supply
FAN MOTOR
95
Hermetic
CONDENSER FAN
600DC
R-22
600DA/DB
320 ? 10
Cut In (psi)
27 ? 4
67 ? 7
Cut In (psi)
NOMINAL POWER SOURCE
V-Ph-Hz
(V)
230V-1Ph-60Hz
230V-3Ph-60Hz
197 - 253
180 - 253
INSTALLATION
SELECTION OF MOUNTING POSITION
1)
2)
3)
4)
5)
6)
7)
UNIT MOUNTING
1)
2)
3)
38ASB /
CCAR
240
360 / 036
600 / 060
5m
10m
15m
20m
25m
30m
0%
1.2%
2.0%
2.8%
3.5%
4.5%
0%
1.6%
2.6%
3.6%
4.6%
5.6%
0%
2.8%
4.8%
6.7%
8.7%
10.2%
(20)15
360 / 036
(20)15
25
25
600 / 060
(25)15
30
151
Note: 1) Values shown are for units operating at 7.2 C saturated suction
0
and 35 C entering air.
2) Values in ( ) indicate a case when the outdoor unit is located at
a lower height than the indoor unit.
PIPING CONNECTIONS
Complete all installation and piping work required for indoor and
outdoor units. If brazing is required pass nitrogen or other inert gas
through piping to prevent formation of cooper oxide. Unit contains R22 charge, do not open Schreader valve at this time. Leak test field
piping by pressure method.
START-UP
PRELIMINARY CHECKS:
1)
Check that all internal wiring connections are tight and all
barriers, covers and panels are in place.
Field electrical power source must agree with unit name
plate rating.
All service valves must be opened.
PIPING INSULATION
No refrigerant control device is shipped with the unit except 024
model. It is already installed in matching Fan coil units, check
carefully the indoor unit. Insulate suction line adequately (Fig. 8)
2)
3)
START SYTEM
NOTE: Model 240 need
to insulate both Suction
and liquid pipes
1.
2.
3.
REFRIGERANT CHARGING
CAUTION
TO PREVENT PERSONAL INJURY, WEAR SAFETY
GLASSES AND GLOVES WHEN HANDLING
REFRIGERANT. DO NOT OVERCHARGED SYSTEM.
THIS CAN CAUSE COMPRESSOR FLOODING.
CAUTION
THE CONTROL VOLTAGE FROM THE FAN COIL UNIT
MUST BE OF 230V. DO NOT CONNECT THE POWER
SUPPLY TO THE SIGNAL
POWER Unit is factory wired for voltage shown on name plate.
Provide adequate fused disconnect switch within sign of unit, readily
accessible, but out of reach children.
Provide for locking switch open (OFF) is advisable to prevent power
from being turned on w hile unit is being serviced.
Route power wires through opening in unit side panel and connect in
unit control box (fig. 9). Unit must be grounded.
IMPORTANT
For accurate system performance, charge by superheat method
as shown in table 5 and 6.
To check and adjust charge, follow the following procedures:1)
2)
3)
4)
5)
6)
7)
CAUTION
BEFORE PERFORMING RECOMMENDED MAINTENANCE
AND SERVICE, BE SURE UNIT MAIN POWER SWITCH IS
TURNED OFF. FAILURE TO DO SO MAY RESULT IN
ELECTRIC SHOCK OR INJURY FROM ROTATING FAN
BLADE.
PE720113
PE740132
PE740133
TABLE 5
Superheat Charging Table
(Superheat Entering Suction Service Valve)
OUTDOOR
OUTDOOR
TEMP ( F)
50
52
54
56
58
60
62
64
66
68
70
72
74
76
TEMP ( C)
10
11.1 12.2
13.3
14.4
15.6
16.7
17.8
18.9
21.1
22.2
23.3
55
12
14
17
20
23
26
29
32
35
37
40
42
45
12.8
6.7
7.8
9.4
11.1
12.8
14.4
16.1
17.8 19.4
20.6
22.2
23.3
25
60
10
12
15
18
21
24
27
30
33
35
38
40
43
15.5
3.9
5.6
6.7
8.3
10
11.7
13.3
15
16.7 18.3
19.4
21.1
22.2
23.9
65
--
10
13
16
19
21
24
27
30
33
36
38
41
18.3
--
3.3
5.8
7.2
8.9
10.6
11.7
13.3
15
16.7
18.3
20
21.1
22.8
70
--
--
10
13
16
19
21
24
27
30
33
36
39
21.1
--
--
3.9
5.6
7.2
8.9
10.6
11.7
13.3
15
16.7
18.3
20
21.7
75
--
--
--
12
15
18
21
24
28
31
34
37
23.9
--
--
--
3.3
6.7
8.3
10
15.6
17.2
18.9
20.6
80
--
--
--
--
12
15
18
21
25
28
31
35
26.7
--
--
--
--
2.8
4.4
6.7
8.3
10
11.7
13.9
15.6
17.2
19.4
85
--
--
--
--
--
--
11
15
19
22
26
30
33
29.4
--
--
--
--
--
--
4.4
6.1
8.3
10.6
12.2
14.4
16.7
18.3
90
--
--
--
--
--
--
13
16
20
24
27
31
32.2
--
--
--
--
--
--
2.8
7.2
8.9
11.1
13.3
15
17.2
95
--
--
--
--
--
--
--
10
14
18
22
25
29
36.0
--
--
--
--
--
--
--
4.4
5.6
7.8
10
12.2
13.9
16.1
100
--
--
--
--
--
--
--
--
12
15
20
23
27
37.8
--
--
--
--
--
--
--
--
3.3
6.7
8.3
11.1
12.8
105
--
--
--
--
--
--
--
--
13
17
22
26
40.6
--
--
--
--
--
--
--
--
2.8
7.2
9.40 12.2
14.4
110
--
--
--
--
--
--
--
--
--
11
15
20
25
43.3
--
--
--
--
--
--
--
--
--
3.3
6.1
8.3
11.1
13.9
115
--
--
--
--
--
--
--
--
--
--
14
18
23
46.1
--
--
--
--
--
--
--
--
--
--
4.4
7.8
10
12.8
20
11.7 13.3
24.4
15
TABLE 6
Required Suction Tube Temperature (0C)
(Entering Suction Service Valve)
SUPERHEAT
64.2
67.1
70.0
73.0
76.0
79.2
82.4
85.7
35
37
39
41
43
45
47
49
51
37
39
41
43
45
47
49
51
53
39
41
43
45
47
49
51
53
55
41
43
45
47
49
51
53
55
57
43
45
47
49
51
53
55
57
59
10
45
47
49
51
53
55
57
59
61
12
47
49
51
53
55
57
59
61
63
14
49
51
53
55
57
59
61
63
65
16
51
53
55
57
59
61
63
65
67
18
53
55
57
59
61
63
65
67
69
20
55
57
59
61
63
65
67
69
71
22
57
59
61
63
65
67
69
71
73
24
59
61
63
65
67
69
71
73
75
26
61
63
65
67
69
71
73
75
77
28
63
65
67
69
71
73
75
77
79
30
65
67
69
71
73
75
77
79
81
32
67
69
71
73
75
77
79
81
83
34
69
71
73
75
77
79
81
83
85
36
71
73
75
77
79
81
83
85
87
38
73
75
77
79
81
83
85
87
89
40
75
77
79
81
83
85
87
89
TEMP ( F)
91
TEMP ( K)
424
443
463
483
503
524
546
568
591
1.7
2.8
3.9
6.1
7.2
8.3
9.4
10.6
1.1
2.8
3.9
6.1
7.2
8.3
9.4
10.6
11.7
2.2
3.9
6.1
7.2
8.3
9.4
10.6
11.7
12.8
3.3
6.1
7.2
8.3
9.4
10.6
11.7
12.8
13.9
4.4
6.1
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15
5.6
7.2
8.3
9.4
10.6
11.7
12.8
13.9
15
16.1
6.7
8.3
9.4
10.6
11.7
12.8
13.9
15
16.1
17.2
7.8
9.4
10.6
11.7
12.8
13.9
15
16.1
17.2
18.3
8.9
10.6
11.7
12.8
13.9
15
16.1
17.2
18.3
19.4
10.0
11.7
12.8
13.9
15
16.1
17.2
18.3
19.4
20.6
11.1
12.8
13.9
15
16.1
17.2
18.3
19.4
20.6
21.7
12.2
13.9
15
16.1
17.2
18.3
19.4
20.6
21.7
22.8
13.3
15
16.1
17.2
18.3
19.4
20.6
21.7
22.8
23.9
14.4
16.1
17.2
18.3
19.4
20.6
21.7
22.8
23.9
25
15.6
17.2
18.3
19.4
20.6
21.7
22.8
23.9
25
26.1
16.7
18.3
19.4
20.6
21.7
22.8
23.9
25
26.1
27.2
17.8
19.4
20.6
21.7
22.8
23.9
25
26.1
27.2
28.3
18.9
20.6
21.7
22.8
23.9
25
26.1
27.2
28.3
29.4
20.0
21.7
22.8
23.9
25
26.1
27.2
28.3
29.4
30.6
21.2
22.8
23.9
25
26.1
27.2
28.3
29.4
30.6
31.7
22.2
23.9
25
26.1
27.2
28.3
29.4
30.6
31.7
32.8
10
12
13
NO COOLING OR
IN-SUFFICIENT
COOLING
COMPRESSOR RUNS
BUT CYCLES ON
INTERNAL OVERLOAD
COMPRESSOR
WILL NOT RUN
CONTACTOR OPEN
FAULTY POWER
SUPPLY
CONTACTOR
CLOSED
OUTDOOR FAN
STOPPED OR CYLING
COOLING
LOOSE LEAD AT
FAN MOTOR
COMPRESSOR
POWER
SUPPLY OPEN
OUTDOOR AIR
RESTRICTED OR
RECIRCULATING
MOTOR DEFECTIVE
RESTRICTED
DISCHARGE LINE
OPEN CONTROL
CIRCUIT
OPEN SHORTED OR
GROUNDED
COMPRESSOR
MOTOR WINDINGS
OVERCHARGE OR
NONCONDENSABLES
IN SYSTEM
COMPRESSOR
STUCK
LOW REFRIGERANT
CHARGE
HIGH SUCTION
LOW HEAD
PRESSURE
DEFECTIVE
COMPRESSOR
VALVE
HIGH SUCTION
LOW SUPERHEAT
UNIT OVERCHARGED
INCORRECT
OUTDOORFANMOTOR
CAPACITOR
DUCT RESTRICTED
INTERNAL
PRESSURE
RELIEF OPEN
INCORRECT
METERING DEVICE
DAMPERS PARTY
CLOSED
CONTACTOR OR
COIL DEFECTIVE
LOOSE ELECTRICAL
CONNECTION
LOW SUCTION
PRESSURE
DEFECTIVE TIME
DELAY
COMPRESSOR RUNS
BUT INSUFFICIENT
COOLING
INDOOR COIL
FROSTED
COMPRESSOR
INTERNAL
PROTECTION OPEN
LINE VOLTAGE
TO HIGH OR LOW
SLIGHTLY LOW OR
REFRIGERANT
COMPRESSOR
BEARINGS
INTERNAL
OVERLOAD OPEN
OPEN DISCHARGE
LINE
PRESSURE SWITCH
METERING DEVICE
RESTRICTED
INCORRECT
METERING DEVICE
INDOOR COIL
STRAINER
RESTRICTED
14
Concepcion
Carrier
Air conditioning
Company
Philippines
Manufacturer reserve the right to discontinue, or charge at any time, specifications or designs without notice and without incurring obligations
Form 38ASB/CCARS024~060-1IOM