Tide Load 10 V 1
Tide Load 10 V 1
Tide Load 10 V 1
Input values in Yellow Cells. Values in blue cells are calculated. Building description data input and heating/cooling load output
results are in "Zones" Worksheets. Supplemental data can be found in other worksheets and can be cut and pasted into Zone
Worksheets. - References: ASHRAE Handbook of Fundamentals (1997), HVAC Simplified (2006), and ACCA Manual N, 4th Ed.
1988.
School Addition in Tuscaloosa 10 Classroom Zones with 2 Restrooms (Zone 11) No heat recovery units (HRUs). Loads done at Max. dry
bulb condition - check for loads at Max. wet bulb and Max. humidity ratio conditions (See Plan Below)
Data can be copied & pasted from Weather Tab below. Outdoor Temps. Heating (F) Outdoor Temps Max Dry Bulb Cooling (F)
Temps at Max Wet Bulb
Temps at Max Hum Ratio
Location
Latitude ElevationFeet
TodbHeat
DRangeHtg
TodbCool TowbCool
DailyRange DBatMaxWB Max WB DailyRange DBatMaxHR WBatMax DailyRange
20
Tuscaloosa, AL
33
171
20
96
76
20
90
80
16
84
79
12
Indoor Temperatures
Daytime
TidbHeat
DelTHeat
TidbCool
TiwbCool
DelTCool
Tmean
CLTDcor
Windoor InGrains
70
50
75
63
21
86
4
#VALUE! #VALUE!
TidbHeatUnocDelTHeatUnoc TidbCoolUnoc TiwbCoolUnoc DelTCoolUnoc TmeanUnoc CLTDcorUnoc WindoorUnoc
Evening and Night
60
40
80
67
16
86
-1
#VALUE! #VALUE!
Woutdoor
#VALUE!
OutGrains
DelW
#VALUE! #VALUE!
DelWUnoc
#VALUE!
Input Cells
Output Cells - Do Not Type in these
Floor Plan of Example Building
Classroom
Click on Weather worksheet here for data
for 25 cities. See ASHRAE Fundamentals
Handbook (Climatic Data Chapter) for
additional sites.
Note 2: If Macro security level is set at high, this program will result in errors in the cells
[NAME?]. To reset the security level,
1. Close the program.
2. Click on "Tools" on the main tool bar, select "Macro", select "Security.
3. Reset security level to Medium (recommended) or Low
4. Exit Excel
5. Re-Open Excel
6. Run program
175'
10
Restroom
60'
11
Zone
1
to
1
Zone
2
to
5
Zone
6
to
6
Zone
7
to
10
Zone
11
to
11
Zone
to
Zone
to
Zone
to
Area
Area
Area
Area
Area
Morning Afternoon Morning Area
Morning Afternoon Morning Area
Morning
Afternoon Morning
Morning
Afternoon Morning
Morning
Afternoon Morning
Morning
Afternoon Morning
Morning
Afternoon Morning
Morning Afternoon Morning
960 Cooling Cooling Heating
960 Cooling Cooling Heating
960 Cooling Cooling Heating
960 Cooling Cooling Heating
900 Cooling Cooling Heating
Cooling Cooling Heating
Cooling Cooling Heating
Cooling Cooling Heating
Area-ft2 qc (am) qc(pm)
Area-ft2 qc (am) qc(pm)
Area-ft2 qc (am) qc(pm)
Area-ft2 qc (am) qc(pm)
Area-ft2 qc (am) qc(pm)
Area-ft2 qc (am) qc(pm)
Area-ft2 qc (am) qc(pm)
Area-ft2 qc (am) qc(pm)
qh
qh
qh
qh
qh
qh
qh
qh
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
90
7.03
2.38
90
7.03
2.38
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
90
1.58
6.93
90
1.58
6.93
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Solar
Windows (N)
Windows (E)
Windows (S)
Windows (W)
Other
Enter CLTDs directly from Tables. Program will correct for temperatures.
Conduction
Windows (N)
Windows (E)
Windows (S)
Windows (W)
Other
Other
Conduction
Walls (N)
Walls (E)
Walls (S)
Walls (W)
Other
Other
Conduction
Doors (N)
Doors (E)
Doors (S)
Doors (W)
Other
Other
Roof/Ceiling
Type A
Type B
Floor
U(Btu/hr-ft2-F)
Slab/Basemt
Latent
Lighting
Net Sen.w/o duct
Ductwork
Sensible
Latent
50
50
50
50
50
50
50
50
50
50
Area-ft2
280
230
Area-ft2
20
Area-ft2
960
0.00
0.81
0.00
0.00
0.00
0.00
0.00
2.25
0.00
0.00
0.00
0.00
0.14
0.22
0.00
0.00
0.00
0.00
0.24
0.44
0.00
0.00
0.00
0.00
0.70
0.58
0.00
0.00
0.00
0.00
0.11
0.00
0.00
0.00
0.00
0.00
0.23
0.00
0.00
0.00
0.00
0.00
0.40
0.00
0.00
0.00
0.00
0.00
0.35
0.00
2.27
0.00
1.60
0.00
UP
#VALUE!
T(pm)
21
W
#VALUE!
350
74
1
1
CLF(am)
CLF(pm) F(ballast)
3.412
0.87
0.95
Insulation Leakage
R8
Sealed
People
25
25
Watts
700
Btu/h
Location
S-Ext
0.00
2.25
0.00
0.00
0.00
0.00
0.00
0.22
0.00
0.00
0.00
0.00
0.00
0.44
0.00
0.00
0.00
0.00
0.00
0.58
0.00
0.00
0.00
0.00
230
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
960
0.35
0.00
2.27
0.00
1.60
0.00
Area-ft2
8.09
5.01
###
###
350
0.25
0.25
74
5.57
3.88
1.62
2.17
3.70
###
People
25
25
Watts
700
Btu/h
0.00
4.05
###
###
###
###
###
Entire Building Totals
No. of Zones like this =
3600 cfm
#VALUE!
350 cfm
#VALUE! #VALUE!
Sens.
###
###
#VALUE! #VALUE!
Lat.
###
###
#VALUE! #VALUE!
TotGain
###
###
#VALUE! #VALUE!
SHR
###
###
#VALUE! NetLoss
#VALUE! TotLoss
### NetLoss
10500.0
Area-ft2
280
230
Area-ft2
20
Area-ft2
960
0.00
0.00
0.00
0.81
0.00
0.00
0.00
0.00
0.00
2.25
0.00
0.00
0.14
0.22
0.00
0.00
0.00
0.00
0.24
0.44
0.00
0.00
0.00
0.00
0.70
0.58
0.00
0.00
0.00
0.00
0.11
0.00
0.00
0.00
0.00
0.00
0.23
0.00
0.00
0.00
0.00
0.00
0.40
0.00
0.00
0.00
0.00
0.00
0.35
0.00
2.27
0.00
1.60
0.00
###
###
350
0.25
0.25
74
2.17
0.00
Watts
1248
###
Location
### S-Ext
3.70
###
People
25
25
Watts
700
Btu/h
0.00
4.05
###
###
###
###
###
1 No. of Zones like this =
###
350 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
0.00
0.22
0.00
0.00
0.00
0.00
0.00
0.44
0.00
0.00
0.00
0.00
0.00
0.58
0.00
0.00
0.00
0.00
230
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
960
0.35
0.00
2.27
0.00
1.60
0.00
###
Location
### S-Ext
###
###
350
0.25
0.25
74
4.17
3.88
5.57
3.88
People
25
25
1.62
2.17
700
Btu/h
0.00
###
###
###
###
4 No. of Zones like this =
###
350 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
0.00
0.14
0.00
0.09
0.00
0.00
0.00
0.29
0.00
0.14
0.00
0.00
0.00
0.38
0.00
0.38
0.00
0.00
150
150
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
900
0.33
0.00
2.13
0.00
1.50
0.00
###
Location
### S-Ext
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
###
###
100
###
###
0.25
0.25
21
0.07
0.07
4.17
3.88
5.57
3.88
People
8
8
Watts
1.62
2.17
0.00
0.00
###
Location
### S-Ext
2.14
###
###
###
###
###
4 No. of Zones like this =
###
100 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
###
###
0.00
0.00
0
Watts
0.00
0.00
0.00
0.00
###
Location
### S-Ext
0.00
###
###
###
###
###
1 No. of Zones like this =
###
0 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
0.00
Perim.-ft
###
###
cfm
0.00
0.00
0.00
###
###
0.00
0.00
0
Watts
0.00
0.00
###
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
###
Location
### S-Ext
0.00
###
###
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
###
0.00
###
0.00
0
Watts
Btu/h
0.00
Watts
0
0.00
People
Btu/h
0.00
Watts
0
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
People
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
cfm
5.50
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
###
0.00
2.33
###
0.00
0.00
0.00
0.00
0.00
0.00
Perim.-ft
Btu/h
0.00
Watts
720
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
People
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
cfm
Btu/h
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
###
1.78
1.24
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
Perim.-ft
1.33
1.24
Area-ft2
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
Area-ft2
2.31
###
###
###
###
1 No. of Zones like this =
###
350 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.43
4.05
###
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
8.09
3.70
###
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
Perim.-ft
###
30
cfm
19.25
100
0.00
Watts
1248
Area-ft2
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
Area-ft2
5.01
4.05
###
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8.09
3.70
###
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
Perim.-ft
###
32
cfm
19.25
350
0.00
Watts
1248
Area-ft2
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
Area-ft2
5.01
1.62
0.00
0.00
0.00
2.25
0.00
0.00
0.00
8.09
5.57
3.88
0.00
0.00
0.00
0.81
0.00
0.00
Area-ft2
Perim.-ft
###
62
cfm
19.25
350
4.17
3.88
90
Area-ft2
0.00
0.00
0.00
0.36
0.00
0.00
Area-ft2
0.00
Perim.-ft
###
32
cfm
19.25
350
4.17
3.88
90
Area-ft2
0.00
0.00
0.00
0.36
0.00
0.00
Area-ft2
0.00
0.00
Watts
1
1248
0.00
0.81
0.00
0.00
0.00
0.00
Area-ft2
5.01
in. wtr.
90
Area-ft2
0.00
0.36
0.00
0.00
0.00
0.00
Area-ft2
Area-ft2
50
T(slab) Perim.-ft
50
62
T
cfm
50
350
Btu/person CLF(am)
CLF(pm)
245
0.68
0.91
155
1
1
CLF(am)
CLF(pm)
3.412
0.68
0.91
90
Area-ft2
0.00
0.36
0.00
0.00
0.00
0.00
T(flr)
Area-ft2
50
50
50
50
0.00
Watts
0.00
###
0.00
###
###
###
###
###
0 No. of Zones like this =
###
0 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
###
Location
### S-Ext
###
###
###
###
0 No. of Zones like this =
###
0 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
###
###
0
###
###
Solar
Windows (N)
Windows (E)
Windows (S)
Windows (W)
Other
Zone
1
to
1
Zone
Area
Night
Evening
Evening Area
960 Cooling Cooling Heating
960
2
Area-ft qc(nite) qc(eve) qh(eve) Area-ft2
0
0.00
0.00
0
90
0.00
0.79
90
0
0.00
0.00
0
0
0.00
0.00
0
0
0.00
0.00
0
Enter CLTDs directly from Tables. Program will correct for temperatures.
Conduction
Windows (N)
Windows (E)
Windows (S)
Windows (W)
Other
Other
Conduction
Walls (N)
Walls (E)
Walls (S)
Walls (W)
Other
Other
Conduction
Doors (N)
Doors (E)
Doors (S)
Doors (W)
Other
Other
Roof/Ceiling
Type A
Type B
U (Btu/hr-ft2-F)
0.5
0.5
0.5
0.5
0
0
2
U(Btu/hr-ft -F)
0.05
0.05
0.05
0.05
0
0
2
U(Btu/hr-ft -F)
0.4
0.4
0.4
0.4
0
0
U(Btu/hr-ft2-F)
0.03333333
0
Floor
U(Btu/hr-ft2-F)
People
Sensible
Latent
0.00
-0.05
0.00
0.00
0.00
0.00
0.00
0.50
0.00
0.00
0.00
0.00
0.00
1.26
0.00
0.00
0.00
0.00
0.15
0.15
0.00
0.00
0.00
0.00
0.27
0.38
0.00
0.00
0.00
0.00
0.39
0.32
0.00
0.00
0.00
0.00
0.02
0.00
0.00
0.00
0.00
0.00
0.22
0.00
0.00
0.00
0.00
0.00
0.22
0.00
0.00
0.00
0.00
0.00
0.32
0.00
2.50
0.00
0.90
0.00
0.58
0.19
Area-ft2
0.00
0
Perim.-ft
###
32
cfm
1.08
350
###
###
350
74
0.25
0.25
74
People
25
25
0.00
0.00
0.00
0.00
People
25
25
T(flr)
Area-ft2
28
0
T(slab) Perim.-ft
UP
#VALUE!
28
62
T(ngt)
28 cfm
5
28
350
W
#VALUE!
350
0
Ins. Position Insulation
Vertical
R5 x 48 in
T(eve)
Ventilation
Sensible
1.1
15
W
HRU Eff. (sen.) =
0
Latent
4840 #VALUE!
HRU Eff. (lat.) =
0
Infil (% of Vent)
0%
Vent Air Fan
TSP =
1 in. wtr.
Slab/Basemt
Area-ft2
0
90
0
0
0
0
Area-ft2
0
230
0
0
0
0
Area-ft2
0
0
0
0
0
0
Area-ft2
960
0
Internal
Sensible
Latent
Lighting
Net Sen.w/o duct
Ductwork
Sensible
Latent
1
1
CLF(am) CLF(pm) F(ballast)
3.412
0.02
0.12
Watts
700
Btu/h
0
Watts
1
1000
Insulation Leakage
R3
NoWrap-Unsealed
Location
S-Ext
3.412
CLF(am) CLF(pm)
0.04
0.31
0.10
0.74
0.00
0.00
0.07
###
0.41
###
###
###
###
###
Entire Building Totals
No. of Zones like this =
Night Vent Air
360 cfm
#VALUE!
35 cfm
Total Sensible
(MBtu/h)
#VALUE! #VALUE!
Sens.
###
###
Total Latent
(MBtu/h)
#VALUE! #VALUE!
Lat.
###
###
Total Gain
(MBtu/h)
#VALUE! #VALUE!
TotGain
###
###
SHR
#VALUE! #VALUE!
SHR
###
###
Total Loss
(MBtu/h)
#VALUE! NetLoss
#VALUE! TotLoss
### NetLoss
Total Area
10500.0
sqft/ClgTon
ft2/Ton
#VALUE!
ft2/ton
###
2
2
Btu/hrft
Btu/hrft
ClLoad/sqft
#VALUE!
###
HtLoad/sqft
Btu/hrft2
#VALUE!
Btu/hrft2
###
2
2
People/sqft
Occupancy/1000ft =
10.3
P/Mft =
26.0
Watts
700
Btu/h
0
Watts
1248
###
Location
### S-Ext
to
Night
Evening
Zone
Evening Area
0.00
0.18
0.00
0.00
0.00
0.00
0.00
0.72
0.00
0.00
0.00
0.00
0.00
1.26
0.00
0.00
0.00
0.00
0.00
0.21
0.00
0.00
0.00
0.00
0.00
0.44
0.00
0.00
0.00
0.00
0.00
0.32
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.48
0.00
2.66
0.00
0.90
0.00
0.58
0.19
Area-ft2
0.00
0
Perim.-ft
###
62
cfm
1.08
350
###
###
0.25
0.00
0.00
to
Night
Evening
Evening
Zone
7
to
10
Zone
Area
Night
Evening
Evening Area
Cooling Cooling Heating
960 Cooling Cooling Heating
900
2
qc(nite) qc(eve) qh(eve) Area-ft qc(nite) qc(eve) qh(eve) Area-ft2
0.00
0.00
0
0.00
0.00
0
0.00
0.00
0
0.00
0.00
0
0.00
0.00
0
0.00
0.00
0
0.00
7.03
90
0.00
7.03
0
0.00
0.00
0
0.00
0.00
0
Area-ft2
0
0
0
90
0
0
Area-ft2
0
230
0
0
0
0
Area-ft2
0
0
0
0
0
0
Area-ft2
960
0
0.00
0.00
0.00
0.18
0.00
0.00
0.00
0.00
0.00
0.72
0.00
0.00
0.00
0.00
0.00
1.26
0.00
0.00
0.22
0.21
0.00
0.00
0.00
0.00
0.34
0.44
0.00
0.00
0.00
0.00
0.39
0.32
0.00
0.00
0.00
0.00
0.06
0.00
0.00
0.00
0.00
0.00
0.26
0.00
0.00
0.00
0.00
0.00
0.22
0.00
0.00
0.00
0.00
0.00
0.48
0.00
2.66
0.00
0.90
0.00
0.58
0.19
Area-ft2
0.00
0
Perim.-ft
###
32
cfm
1.08
350
350
###
###
0.25
74
0.25
0.00
0.00
People
25
25
0.00
0.00
Perim.-ft
Area-ft2
0
0
0
0
0
0
Area-ft2
0
150
0
150
0
0
Area-ft2
0
0
0
0
0
0
Area-ft2
900
0
0.00
0.00
0.00
0.18
0.00
0.00
0.00
0.00
0.00
0.72
0.00
0.00
0.00
0.00
0.00
1.26
0.00
0.00
0.00
0.21
0.00
0.00
0.00
0.00
0.00
0.44
0.00
0.00
0.00
0.00
0.00
0.32
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.48
0.00
2.66
0.00
0.90
0.00
0.58
0.19
Area-ft2
0.00
0
Perim.-ft
###
30
cfm
1.08
100
350
###
###
100
0.25
74
0.25
0.25
21
0.00
0.00
People
25
25
0.00
0.00
0.00
0.00
People
8
8
0.10
0.74
0.00
0.00
0.09
###
0.51
###
Location
###
###
###
###
No. of Zones like this =
35 cfm
###
###
###
###
###
###
###
###
### NetLoss
###
###
###
26.0
Watts
700
Btu/h
0
Watts
1248
###
0.10
0.74
0.00
0.00
0.09
###
0.51
###
Location
### S-Ext
###
###
###
###
4 No. of Zones like this =
###
35 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
ft2/ton
Btu/hrft2
Btu/hrft2
P/Mft2=
###
###
###
26.0
700
Btu/h
0
Watts
1248
###
0.10
0.74
0.00
0.00
0.09
###
0.51
###
Location
### S-Ext
###
###
###
###
1 No. of Zones like this =
###
35 cfm
Sens.
###
###
Lat.
###
###
TotGain
###
###
SHR
###
###
### TotLoss
### NetLoss
ft2/ton
Btu/hrft2
Btu/hrft2
P/Mft2=
###
###
###
26.0
Watts
0
Btu/h
0
Watts
720
###
Location
### S-Ext
4 No. of Zones like this =
###
Sens.
Lat.
TotGain
SHR
### TotLoss
ft2/ton
Btu/hrft2
Btu/hrft2
P/Mft2=
11
to
Night
Evening
11
Zone
to
Evening Area
Night
Evening
Evening
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.14
0.00
0.37
0.00
0.00
0.00
0.29
0.00
0.33
0.00
0.00
0.00
0.21
0.00
0.21
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.45
0.00
2.49
0.00
0.84
0.00
0.17
Area-ft2
0
0
0
0
0
0
Area-ft2
0
0
0
0
0
0
Area-ft2
0
0
0
0
0
0
Area-ft2
0
0
Zone
Area
to
Night
Zone
Evening Area
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.06
Area-ft2
0.00
0
Perim.-ft
###
0
cfm
0.31
0
0.00
Area-ft2
0.00
0
Perim.-ft
#VALUE!
0
cfm
0.00
0.00
0
###
###
###
###
0.07
0.07
0.00
0.00
0.00
0.00
0.00
People
0
0
0.00
0.00
Perim.-ft
Evening
Area-ft2
0
0
0
0
0
0
Area-ft2
0
0
0
0
0
0
Area-ft2
0
0
0
0
0
0
Area-ft2
0
0
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Area-ft2
0.00
0
Perim.-ft
###
0
cfm
0.00
0
###
###
0.00
0.00
0.00
0.00
0.00
People
0
0
0.00
0.00
0.00
0.00
People
0
0
0.00
0.00
0.00
0.00
0.05
###
0.29
###
Location
###
###
###
###
No. of Zones like this =
10 cfm
###
###
###
###
###
###
###
###
### NetLoss
###
###
###
8.9
Watts
0
Btu/h
0
Watts
0
###
0.00
0.00
0.00
0.00
0.00
###
0.00
### #VALUE!
Watts
0
Btu/h
0
Watts
0
0.00
0.00
0.00
0.00
0.00
###
0.00
###
Location
### S-Ext
Location
###
### #VALUE! S-Ext
###
###
###
###
###
###
1 No. of Zones like this =
0 No. of Zones like this =
###
0 cfm
#VALUE!
0 cfm
Sens.
###
###
Sens.
###
###
Lat.
###
###
Lat.
###
###
TotGain
###
###
TotGain
###
###
SHR
###
###
SHR
###
###
### TotLoss
### NetLoss #VALUE! TotLoss
### NetLoss
ft2/ton
###
2
Btu/hrft
###
Btu/hrft2
###
2
P/Mft = #DIV/0!
ft2/ton
###
2
Btu/hrft
###
Btu/hrft2
###
2
P/Mft = #DIV/0!
Watts
0
Btu/h
0
Watts
0
###
Location
### S-Ext
0 No. of Zones like this =
###
Sens.
Lat.
TotGain
SHR
### TotLoss
ft2/ton
Btu/hrft2
Btu/hrft2
P/Mft2=
to
Night
Evening
Evening
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Perim.-ft
###
0.00
0.00
###
###
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
###
0.00
###
###
Location
###
###
###
###
No. of Zones like this =
0 cfm
###
###
###
###
###
###
###
###
### NetLoss
###
###
###
#DIV/0!
###
0
###
###
The Table below provides only a few of the sites listed in electronic format in the 2005 ASHRAE Fundamentals Handbook.
data for over 1200 locations in the USA and Canada and 1700 international locations.
A
Location
Lat.
Elev.
Heating
Cooling
-99.60%
City/State
Ft.
Albuquerque, NM
Atlanta, GA
Baltimore, MD
Birmingham, AL
Boise, ID
Boston, MA
Brownsville, TX
Chicago, IL
Cleveland, OH
Dallas, TX
Denver, CO
Lake Charles, LA
Los Angeles, CA
Madison, WI
Miami, FL
Minneapolis, MN
Nashville, TN
Omaha, NE
Oklahoma City
Phoenix, AZ
Raleigh, NC
Sacramento, CA
St. Louis, MO
Salt Lake, UT
Seattle, WA
Tallahassee, FL
Tuscaloosa, AL
35
34
39
34
44
42
26
42
41
33
40
30
34
43
26
45
36
41
35
34
36
39
39
41
47
30
33
5320
1033
154
630
2870
30
20
673
804
597
5330
33
105
860
13
837
590
1332
1300
1089
440
23
564
4230
450
69
171
13
18
11
18
2
7
36
-6
1
17
-3
29
43
-10
46
-16
10
-8
9
34
16
31
2
6
23
25
20
D.Range
F
22
17
15
19
13
13
18
14
13
18
24
17
15
16
15
16
17
18
19
22
19
15
15
14
9
23
20
Evaporation2
DB
F
-0.40%
MWB
F
-0.40%
D.Range
F
MDB
F
96
93
93
94
96
91
95
91
89
100
93
93
85
90
91
91
94
95
99
110
93
100
95
96
85
95
96
60
75
75
75
63
73
78
74
73
74
60
78
64
74
77
73
76
75
74
70
76
69
76
62
65
77
76
25
17
19
19
30
15
17
20
19
20
27
16
11
21
11
19
19
20
21
23
19
33
18
28
18
19
20
83
88
88
89
90
87
89
88
85
92
81
88
78
86
87
88
89
90
91
97
88
96
90
85
83
89
90
1This design conditions typically result in the highest sensible cooling load and highest total load when ventilation requirem
2These design conditions will result in higher total cooling loads when the ventilation air requirements and infiltration are h
3These design conditions typically result cooling loads with the lowest sensible heat ratio (SHRLoad).
4 Gr = Grains of moisture (7000 Grains = 1 lb)
E Fundamentals Handbook. The 2001 version of the Handbook (Chapter 27) contains tablular climatic
F
Evaporation
Dehumidification3
-0.40%
WB
F
D.Range
F
DB
F
65
77
78
78
66
75
80
77
76
78
65
80
70
77
80
76
78
78
77
76
78
72
79
66
66
80
80
12
14
15
14
24
14
16
17
19
13
15
12
8
17
9
16
14
15
14
17
14
29
15
18
16
15
16
68
82
83
83
72
80
83
84
82
82
69
84
75
83
83
83
83
85
83
82
82
82
85
73
71
83
84
WB
F
-0.40%
D.Range
F
DP
F
HR
Gr4
63
76
77
77
63
74
79
77
75
77
63
80
70
76
79
76
77
77
76
74
77
69
78
64
64
79
79
5
10
10
10
5
8
10
20
10
8
5
10
6
12
8
11
10
11
11
13
10
12
13
5
5
11
12
61
74
75
75
58
72
78
74
73
75
60
78
67
74
78
73
75
75
73
71
75
62
76
60
60
77
77
98
133
132
135
79
119
146
130
125
132
96
148
99
129
144
124
134
136
129
118
134
84
138
92
78
142
142
hr-F-ft2
Btu
0.25
0.17
0.68
0.8-1.6
0.9-1.5
0.8-1.7
0.8-2.2
0.45
0
0.06
0.21
0.93
0.62
0.85
0.5
1.32
0.1/in.
~0
0.5
0.45
0.56
1.79
Insulation
3 inch Fiberglass
w/ 20% wood framing
3 inch Fiberglass
w/ 20% wood framing
5 inch Fiberglass
w/ 10% wood framing
w/ 20% wood framing
7 inch Fiberglass
w/ 10% wood framing
9 inch Fiberglass
w/ 10% wood framing
11 inch Fiberglass
w/ 10% wood framing
Cellulose
w/ 10% wood framing
w/ 20% wood framing
Panel-3"beadbrd.+OSB
Panel-3"extr.poly+OSB
1 inch Duct Liner/Wrap
2 inch Duct Liner/Wrap
Expanded Polysty (beads)
Extruded Polystyrene
Polyisocyanurate
Polyurethane foam
hr-F-ft2
Btu
11
9.6
13
10.5
19
17.3
15.2
25
21
30
26
38
32.5
3.7/in.
3.1/in.
2.7/in.
12.8
17
4
8
3.5/in.
5.0/in.
6.0/in.
6.0/in.
ructural Units
R-Value Calculator
hr-F-ft2
Btu
2
5.5
2.4
7.2
1.11
0.14/in.
1.25/in.
0.9/in.
Structural
8 inch LW block
with perlite cores
12 inch LW block
with perlite cores
12 inch HW block
Concrete
Softwood
Hardwood
R-Values in hr-F-ft /Btu
U-Values in Btu/hr-F-ft2
Windows
Sgl. Pane Alum. frame
Dbl. Pane Alum. frame
Dbl. Vinyl/Alum. frame
Dbl. Wood/Vinyl frame
Triple Vinyl/Al. frame
Doors
1- inch Solid Wood
with storm door
1- inch Panel
with storm door
1- inch Insul. Metal
with storm door
2- inch Solid Wood
with storm door
2
R(Total)=
R(Total)=
U (Overall)=
2" extr,poly
10
R-to-U Inverter
R(Total)=
U (Overall)=
13
0.077
hr-ft2-F/Btu
Btu/hr-ft2-F
R/U
0.79/1.27 U (Overall)=
0.061 Btu/hr-ft2-F
1.20/0.83 R(Total)=
16.39 hr-ft2-F/Btu
1.75/0.57
R-per-Inch to R-Value Calculator
1.82/0.55
2.30/0.43 R per Inch
Inches
1.25
3.5
2.50/0.40 R(Total)=
4.375 hr-ft2-F/Btu
3.80/0.26 U (Overall)=
0.229 Btu/hr-ft2-F
1.85/0.54
2.80//0.36
P a ra lle l H e a t F lo w P a th s
2.50/0.40
W o o d (o r S te e l)
F ra m in g P a th
In s u la tio n P a th
3.80/0.26
F ra m e
3.7/0.27
5.0/0.20
In s u la tio n
B e tw e e n W o o d F ra m e
W a ll
E x te rio r F in is h
R oo
A ttic S p a c e
In
Ab
R o o fC e ilin g
I
Be
C e ilin g
other
In. Surf.
0.68
R
12.12
e Walls
hs
n g P a th
In s u la tio n
B e tw e e n W o o d F ra m e
E x te rio r F in is h
R oof
R a fte rs
A ttic S p a c e
In s u la tio n
A b o v e J o is t
In s u la tio n
B e tw e e n J o is t
J o is t
C e ilin g
R-Path Total
18.53
9.905
Hr = 2
0
Wall Type
2
N
E
S
W
Wall Type
10
N
E
S
W
Wall Type
16
N
E
S
W
Roof Type
1
2
3
4
5
8
9
10
13
14
24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. N
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
3
32
3
31
3
30
3
29
3
28
3
30
3
30
3
30
3
30
3
30
3
28
3
31
3
33
3
35
3
37
5
69
5
69
5
69
5
69
5
69
24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. N
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
3
32
6
28
9
25
12
20
15
19
3
30
7
32
10
33
14
34
17
35
3
28
7
28
10
28
14
28
17
28
5
69
11
60
17
50
45
40
30
30
24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. N
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
16
20
16
19
16
18
17
17
17
16
17
34
19
34
20
33
22
33
23
32
14
19
16
20
17
21
19
22
20
23
28
30
30
29
31
27
32
26
33
25
24 Deg. N 24 Deg. N 27 Deg. N 27 Deg. N 30 Deg. N 30 Deg. N 33 Deg. N 33 Deg. N 36 Deg. N 36 Deg. N
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
Hr = 2
Hr = 18
-2
58
-2
59
-2
60
-2
60
-2
60
0
70
0
70
0
70
0
70
0
70
8
68
8
68
8
68
8
68
8
68
11
80
11
80
11
79
11
79
11
79
16
70
16
70
16
70
16
70
16
70
24
58
25
58
25
58
25
58
25
58
25
65
26
65
26
64
26
64
26
64
31
56
32
56
32
56
32
56
32
56
31
49
31
49
31
49
31
49
31
49
32
45
32
45
32
45
32
45
32
45
Gap
" air
"argon
" air
"argon
" air
"argon
Glass
Only
1
0.93
0.87
0.87
0.7
0.7
0.71
0.71
Alum
Frame
0.86
0.82
0.76
0.76
0.66
0.66
0.68
0.68
Wood
Frame
0.72
0.69
0.63
0.63
0.55
0.55
0.59
0.59
Vinyl
Frame
0.72
0.69
0.63
0.63
0.55
0.55
0.59
0.59
N
E
S
W
N
E
S
W
N
E
S
W
Zone Type
B
Zone Type
C
Zone Type
D
Med. Blind Lt. Blind Med. Blind Lt. Blind Dark RollerWhite Roller
at 45
at 45
Closed
Closed
Closed
Closed
0.74
0.67
0.63
0.58
0.81
0.39
0.62
0.58
0.63
0.58
0.71
0.35
0.39
0.36
0.4
0.22
Drape Color / Weave
Lt./Open Med./Open Dk./Open Lt./Closed Med./CloseDk./Closed
0.69
0.74
0.82
0.69
0.59
0.39
0.63
0.65
0.71
0.63
0.53
0.35
0.36
0.37
0.37
0.36
0.32
0.22
48 Deg. N
Hr = 15
35
38
88
156
48 Deg. N
Hr = 15
34
47
109
137
48 Deg. N
Hr = 15
31
47
76
130
48 Deg. N
Hr = 15
30
53
72
110
48 Deg. N 48 Deg. N
Hr = 2
Hr = 18
0
34
0
19
0
24
0
167
48 Deg. N 48 Deg. N
Hr = 2
Hr = 18
2
34
2
27
2
34
7
156
48 Deg. N 48 Deg. N
Hr = 2
Hr = 18
5
33
9
31
9
32
16
138
48 Deg. N 48 Deg. N
Hr = 2
Hr = 18
7
31
14
38
14
39
24
123
Activity
Seated
Seated
Office work
Standing
Light
Nightclub
Heavy
Sensible
Latent
Total
Level
Heat Gain Heat Gain Heat Gain
at Rest
245
105
350
Light work
245
155
400
Moderate
250
200
450
Walking
250
250
500
Bench work
275
475
750
Dancing
305
545
850
Work
580
870
1450
Heat Gain From Lighting - Watts
(For incandescent fixtures, Bulb Watts = Fixture Watts)
Length
(in.)
18
18
24
24
36
36
48
48
60
60
72
96
96
Dia.
T8
T12
T8
T12
T8
T12
T8
T12
T8
T12
T12
T8
T12
Compact Flour.
Rated Actual
Watts (w/bal)
13
17
18
23
22
24
Electronic Ballast
Ballast
Net
Factor Wattage
.94
16
.96
24
.97
31
.92
31
.90
36
.90
45
1.07
59
.94
55
.92
55
Compact Flour.
Rated Actual
Watts (w/bal)
13
17
18
23
22
24
ng Types
Electronic Ballast
Ballast
Net
Factor Wattage
.94
16
.96
24
.97
31
.92
31
.90
36
.90
45
1.07
59
.94
55
.92
55
g
Metal Halide
Rated Actual
Watts (w/bal)
50
72
100
128
175
215
Computer 15 Monitor
- 17 Monitor
- 19 Monitor
Laser Printer - Desktop
- Small Office
- Large Office
Fax Machine
Other Office Equipment
Continuous
110
125
135
130
320
550
(Watts voltsamps)
1050 +
1540 Btu/h Latent
400
300
350
Microwave Oven 1 ft 3
Refrigerator 15 ft 3
Water Cooler 8 gal/hr
hp Motor
hp Motor
Average
100
160
275
30
25% Nameplate
270
750
g
Metal Halide
Rated Actual
Watts (w/bal)
50
72
100
128
175
215
ment Watts
Btu/hr)
Average
100
160
275
30
25% Nameplate
(Watts voltsamps)
1050 +
1540 Btu/h Latent
400
300
350
Occupancy
Zone Type B
Hr = 10 Hr = 15 Hr = 2 Hr = 18
0.87
0.95
0.02
0.12
0.88
0.96
0.05
0.97
0.9
0.97
0.15
0.98
Zone Type C
Hr = 10 Hr = 15
0.82
0.9
0.84
0.92
0.97
0.93
Occupancy
Zone Type B
Hr = 10 Hr = 15 Hr = 2 Hr = 18
0.78
0.94
0.03
0.22
0.78
0.94
0.08
0.97
0.8
0.94
0.25
0.97
Zone Type C
Hr = 10 Hr = 15
0.72
0.89
0.73
0.89
0.76
0.91
Zone Type B
Hr = 10 Hr = 15 Hr = 2 Hr = 18
0.68
0.91
0.04
0.31
0.69
0.92
0.11
0.96
0.72
0.92
0.36
0.96
Zone Type C
Hr = 10 Hr = 15
0.6
0.82
0.6
0.82
0.66
0.88
Zone Type D
Hr = 10 Hr = 15 Hr = 2 Hr = 18
0.74
0.85
0.08
0.2
0.77
0.87
0.15
0.9
0.81
0.89
0.28
0.92
Occupancy
8 hrs/day
12 hrs/day
16 hrs/day
Zone Type D
Hr = 10 Hr = 15 Hr = 2 Hr = 18 Occupancy
0.71
0.85
0.07
0.24 8 hrs/day
0.73
0.87
0.16
0.91 12 hrs/day
0.78
0.89
0.31
0.93 16 hrs/day
Zone Type D
Hr = 10 Hr = 15 Hr = 2 Hr = 18 Occupancy
0.6
0.77
0.1
0.34 8 hrs/day
0.62
0.82
0.23
0.87 12 hrs/day
0.68
0.85
0.44
0.9 16 hrs/day
Yellow Cells
Input Req'd
Occupancy Category
Education
Day Care
Classroom (age 5-8)
Classroom (age 9+)
Lecture Classroom
Food & Beverage
Restaurant Dining
Cafeteria/fast food
Hotels, Dorms
Bed/Living rooms
Lobbies/pre-function
Assembly
Office Buildings
Office space
Reception area
Telephone/data entry
Public Assembly
Conference
Auditorium
Library
12
0.27
1.00
221
1.00
0.7
316
people
cfm
cfm/ft2
cfm
People Factor
cfm/person
Lps/Person
Rp (IP Units)
Rp (SI Units)
Area factor
cfm/ft2
Lps/m2
Ra (IP Units) Ra (SI Units)
10
10
10
7.5
5
5
5
3.8
0.18
0.12
0.12
0.06
0.9
0.6
0.6
0.3
7.5
7.5
3.8
3.8
0.18
0.18
0.9
0.9
5
5
5
2.5
2.5
2.5
0.06
0.06
0.06
0.3
0.3
0.3
5
5
5
2.5
2.5
2.5
0.06
0.06
0.06
0.3
0.3
0.3
5
5
5
2.5
2.5
2.5
0.06
0.06
0.12
0.3
0.3
0.6
Museum
Retail
Sales
Mall - common area
Supermarket
Sports
Gym, playing areas
Spectator areas
Aerobics room
Dance floor
Game arcade
7.5
3.8
0.06
0.3
7.5
7.5
7.5
3.8
3.8
3.8
0.12
0.06
0.06
0.6
0.3
0.3
3.8
10
10
3.8
0.3
0.06
0.06
0.06
0.18
1.5
0.3
0.3
0.3
0.9
7.5
20
20
7.5
Blue Cells
Output
Green Cells
Input Optional
Ez
1.00
Vo=
Ra
0.06
0.06
0.06
0.06
0.06
0.18
0.06
Peo./1000 ft2
(Peo./100 m2)
346 cfm
A (ft2)
200
300
300
400
250
300
250
Ra*Area
12
18
18
24
15
54
15
2000
156
Default Values
cfm/person
Vbz
17
43
43
124
30
114
25
0
0
0
Vp
200
300
300
400
250
300
250
Vp
Zpmax
Lps/person
25
25
35
65
17
15
13
8
8.6
7.4
6.7
4.3
70
100
10
9
5.1
4.7
10
20
120
11
8
6
5.5
4
2.8
5
30
60
17
7
6
8.5
3.5
3
50
150
10
6
5
17
3.1
2.7
8.5
Zp
0.09
0.14
0.14
0.31
0.12
0.38
0.10
0.00
0.00
0.00
0.38
40
4.6
15
40
8
16
9
15
7.8
4.6
7.6
30 150
40
100
20
8
22
21
17
4
10.8
10.3
8.3
Unheated Slabs
Insulation Depth or Width (in.)
0
12
24
36
0.73
0.72
0.7
0.68
0.73
0.71
0.7
0.66
0.73
0.61
0.58
0.56
0.73
0.58
0.54
0.51
For RIns=5,
For RIns=10,
F=0.46
48
0.67
0.64
0.54
0.48
F=0.36
Heated Slabs
Insulation Depth or Width (in.)
0
12
1.35
1.31
1.3
1.35
1.06
1.35
1
1.35
For RIns=5,
F=0.74
Table 7.6 Crawl Space and Basement Heat Transmission Coefficients (Fcsb) in Btu/hr-ft
Lag
(ft.)
Crawl Space or
Fcsb (Btu/hr-ft-F)
Basement Heights
{qcsb=FcsbPBldg(ft)[ti-to](F)}
Lbg
(ft.)
Lcsb
(ft.)
RIns.= 0
RIns.= 4
RIns.= 8
RIns.= 12
hr-ft2-F/Btu
hr-ft2-F/Btu
hr-ft2-F/Btu
hr-ft2-F/Btu
1
4
7
1
3
5
1
2
3
2
5
8
5
7
9
8
9
10
1.13
4.42
9
2.95
4.96
7.62
4.76
5.66
6.78
0.39
2.08
4.71
0.92
1.91
3.41
1.45
1.87
2.44
0.24
1.41
3.34
0.55
1.22
2.3
0.86
1.14
1.54
0.17
1.07
2.62
0.4
0.9
1.75
0.61
0.82
1.12
r-ft-F
Heated Slabs
Depth or Width (in.)
24
1.28
1.26
0.99
0.9
For RIns=5,
36
48
1.24
1.2
1.2
1.13
0.95
0.91
0.84
0.78
For RIns=10,
F=0.74
H o r iz o n t a l
I n s u la t io n
* F u ll y I n s u l a t e d = V e r t ic a l
a n d H o r i z o n t a l I n s u la t i o n
V e r t ic a l
I n s u la t io n
B lo c k ( o r C o n c r e t e )
S la b - o n - G r a d e
F=0.55
(Fcsb) in Btu/hr-ft-F
W a ll
to
In s * .
ag
F lo o r
ti
L
L
bg
csb
C ra w l S p a c e o r
B a s e m e n t F lo o r
F o o t in g
* I n s u la t io n c a n a ls o b e lo c a t e d o n in t e r io r w a ll.
Filename: TuscTenClass
.zon
Note: Zone data file will be located in My Documents
Zone
Zone
Zone
Zone
Zone
Zone
Zone
Zone
1
2
6
7
11
to 1
to 5
to 6
to 10
to 11
to
to
to
BldgType NineMonthSchool
City
Atlanta
EFLHc =
#VALUE!
EFLHh =
#VALUE!