1. SUMMARY
EA07 is a self excited Analogue type Automatic
Voltage Regulator. The sensing and power inputs
are independent and accept power input from the
auxiliary winding. The wide voltage adjustment
range fulfills any voltage adjustment requirements.
2. SPECIFICATION
Sensing Input
Voltage
Power Input
Voltage
4, 5C
Range 90~350VAC
3A, 5
80 ~ 270V
1 phase 50/60Hz
1 phase 50/60Hz
Output F+, F
Voltage
Max. 63 VDC @ 220VAC
Current
Continuous 6A
Max. Intermittent 7A for 10 sec
Exciter Field DC Resistance
10 ~ 100 Ohm
Voltage Regulation
< 1% (with 4% engine governing)
Storage temperature
-40 ~ 80 C
Voltage Build-up
Residual voltage at AVR terminal > 5 VAC, 25Hz
External VR
100K ohm 1/2 watt 7%
Dimensions
97mm L * 92mm W * 39mm H
Weight
275g 2%
ATTENTION
1. AVR can be mounted directly on the
engine, genset, switchgear, control panel,
or any position that will not affects
operation. For dimension reference,
please see Figure 1.
2. All voltage readings are to be taken with an
average-reading voltmeter Meggers and
high-potential test equipment must not be
used. Use of such equipment could
damage the AVR.
High Temperature
EA07
3. WIRING / ADJUSTMENTS
3.1 Field Excitation Wiring
3 F+, 1 F
Connect AVR terminal 3 to field +, connect
AVR terminal 1 to the field .
NOTE
The Exciter field resistance is between 10~
100 Ohm.
If field resistance is less than 10 Ohm when
generator is under full load and the field voltage is
under the maximum output, please series a
suitable wattage (W) resistor to have the overall
field resistance to equal to 10~ 100 Ohm.
4. OPERATION PROCEDURE
4.1 Please confirm the follow condition
before starting the generator :
Starting Setting
1. Confirm if the AVR specification conforms to the
system requirements ?
voltage
protection
4.4 Maintenance
Regular maintenance to make sure the AVR surface
is clean and free from oil or moisture. All connection
terminals and wirings must be firmly tightened and
no signs of visible oxidation or erosion.
EA07
F+
F-
O/E U/F
EXCITER
EA07
10
9
12
OUT
IN
STATOR
11
Figure 2
Diagram
Use only original supplied spare protection fuse for fuse replacement.
Please accept our sincere apology if any modification in performance, specification or appearance is
made without prior notice.