Data Sheet Compact Controller
Data Sheet Compact Controller
Data Sheet Compact Controller
(Based on CFA)
Compatible memory card
: 5 V flash memory card
Capacity 4, 20 and 32 MB
Application : Process data logging (3 points)
Saving period : 1s min.
Data storage capacity
Memory card
capacity
Data storge
4MB about 180 thousand data
20MB about 900 thousand data
32MB about 1.35 million data
[Remark] Values of 4 points are recorded si-
multaneously by one data.
[Note] The data of max. 16 points (4
screens) can be storaged at stor-
age time as 1 s.
Format method
: Dependent on this controller
Data readout : Readout by PC using PCMCIA card slot
Recommended memory card
: Made by Sandisk corporation
Sandisk compact Flash memory card is
standardized and on the market.
Models ; SDCFB-4-101-00 (4MB)
SDCFB-20-101-00 (20MB)
SDCFB-32-101-00 (32MB)
15. Standards under Conformity
(1) General safety
: IEC 1010-1 (1990)
EN 61010-1 (1993)
(2) EMC : Emission EN 50081-2 (1994)
Immunity EN 50082-2 (1995)
PDA1
6
Table 1
List of Thermocouple and Resistance Bulb Measurable
range
Thermocouple J 01 00 0.0~400.0
J 01 0.0~800.0
K 02 0.0~400.0
K 03 0.0~800.0
K 04 0.0~1200.0
R 05 0.0~1600.0
B 06 0.0~1800.0
T 07 -200.0~200.0
T 08 -150.0~400.0
E 09 0.0~800.0
E 10 -200.0~800.0
S 11 0.0~1600.0
N 12 0.0~1300.0
U 13 -200.0~400.0
WRe5-26 14 0.0~2300.0
PL2 15 0.0~1300.0
Resistance bulb Pt100 00 00 0.0~150.0
01 0.0~300.0
02 0.0~500.0
03 0.0~600.0
04 -50.0~100.0
05 -100.0~200.0
06 -200.0~600.0
07 -200.0~850.0
Resistance bulb JPt100 00 08 0.0~150.0
09 0.0~300.0
10 0.0~500.0
11 0.0~600.0
12 -50.0~100.0
13 -100.0~200.0
14 -200.0~600.0
Input type code Input range code Measurable rangeC Input signal
SCOPE OF DELIVERY
Controller, panel mounting bracket, instruction manual
(depend on code symbols)
Optional Items
Type Specification
Available
unit
Item
(Note 1) Screw terminal type. Required when using digital input/output.
(Note 2) Cable for T-link/Modbus communication.
(Note 3) The instruction manual in Japanese and English are included.
(Note 4) This is the improved mounting bracket adopted from PDA-2.
Refer to the outline diagram for shape and dimensions.
Terminator
for communication (100 )
34-pin multiple connector
Shunt resistor (250 )
Communication cable (Note2)
For screw terminal, from
PDA to PDA
For screw terminal, from
PDA to PLC
For screw terminal, from
PDA to PC
For compression terminal,
from PDA to PDA
For compression terminal,
from PDA to PLC
For compression terminal,
from PDA to PC
Replacing case
Compact Controller M
(PDA1) Instruction Manual
in book form (in Japanese)
Compact Controller M
(PDA1) Instruction Manual
in book form (in English)
Instruction Manual on
CD-ROM (in Japanese and
English) (Note3)
Mounting bracket (Note4)
PDZR1001 For screw terminal 1
PDZR2001 For compression terminal 1
PDZC1001 Solder type straight terminal 1
PDZC2001 Solder type right angle terminal 1
PDZC3001 Solderless type straight terminal 1
PDZC4001 Solderless type right angle terminal 1
PDZS1001 For screw terminal 1
PDZS2001 For compression terminal 1
PDZK1xx1 M3.5 solderless terminals 1
at both ends
PDZK2xx1 M3.5 solderless terminals 1
at both ends
PDZK3xx1 9-pin connector at 1
PC side end
PDZK4xx1 With compression 1
terminal at both ends
PDZK5xx1 With M3.5 solderless 1
terminal on PLC side
PDZK6xx1 9-pin connector on PC side 1
PDZE1002 For replasing CC-F 1
PDZX1101 Instruction manual in 1
book form
PDZX2101 Instruction manual in 1
book form
PDZQ1001 Instruction manual on 1
CD-ROM
PDZA1001 Improved mounting 1
bracket
(Note1)
Block diagram of electrical isolation
(Note) The communication unit is not isolated from
the AI/AO unit when using T-link.
(Note)
Power
supply
Ground
PV1
Modbus
DI1 to DI10
Solid line shows
isolation from the
other units or circuits.
DO1 to DO10
MI1
AO1 to AO5
PV2
AI1 to AI6
T-link
Power supply
unit
Ground
TC or RTD
input unit
Communication unit
DI / DO
unit
AI / AO
unit
7
CODE SYMBOLS
D A 2 P 0 1 - -
Controller function <4th digit code>
With fixed function 1
1 2 3 4 5 6 7 8 9 10111213 1415
Number of control loops <5th digit code>
1 loop (1 control output) 1
Input signal <7th digit code>
1 to 5 V DC Note 1
Thermocouple Note 2
Resistance bulb Pt100 : 1 Note 2
Resistance bulb JPt100 : 1 Note 2
A
C
D
E
External terminal <6th digit code>
M3.5 screw terminal
Compression terminal
1
2
Backup operation unit <11th digit code>
Without
For 1 control output, 100 to 240 V AC
For 1 control output, 24 V DC
Y
A
D
Communicatioin / Memory card interface <12th digit code>
(Slave communication) (Master communication) (memory card interface) Note3 Note4
Without Without Without
Without Without With
Modbus Without Without
Modbus Without With
T-link Without Without
T-link Without With
Y
M
C
U
A
S
Instruction manual <13th digit code>
Without
Instruction manual on CD-ROM (in Japanese and English) Note 5
Y
C
Power supply voltage <9th digit code>
100V to 240V AC (Usable range 85V to 264V AC) 50 / 60Hz
24V DC (Usable range 20 to 30V DC)
Note 1) For current input, a shunt resistor is used for conversion into voltage.
Shunt resistor is optional item.
Note 2) Thermocouple and resistance bulb input are opitons.
Allowable up to 1 point.
Note 3) Communication cable and terminator are optional items.
Note 4) Recommended maker: Sandisk corporation.
Note 5) This instruction manual is recorded in PDF format file. To read this manual,
Adobe
Acrobat
- +
- +
)
)
(+)
(-)
(COM)
24V
23
24
25
26
27
28
29
30
31
32
33
34
DO1
DO2
DO3
DO4
DO5
DO6
VPD
DO7
DO8
DO9
DO10
PCD
1
2
3
4
5
6
7
8
9
10
11
12
MI+3
MI-3
MI+4
MI-4
AO1
AO2
SC
AI1
AI2
AI3
AI4
PCD PCD
13
14
15
16
17
18
19
20
21
22
DI1
DI2
DI3
DI4
DI5
DI10
DI6
DI7
DI8
DI9
- +
Process
value
input
Voltage
input
Voltage
input
Resistance
bulb input
Thermocouple
input
Manipulated
output 1
24V external
supply (+)
Voltage
input
Grounding
Instrument power supply
100 to 240V AC
or
Instrument power supply 24V DC
24V supply for DIO
24V external supply
(-)
External
setting
input
Note) Screw terminal No. 16, 32, 35, 36, 37, 51, 71, 74, 75, 79, 80
Multiple connector terminal No. 1, 2, 3, 4 not usable (connection not allowed)
RS485 communication
(Modbus) or T-link host
communication
(Same as screw No. 32)
(Same as screw No. 33)
(Same as screw No. 51)
(Same as screw No. 52)
(Same as screw No.71)
(Same as screw No. 72)
(Same as screw No. 74)
(Same as screw No. 73)
(Same as screw No. 56,57,76)
(Same as screw No. 62)
(Same as screw No. 34)
(Same as screw No. 62)
(Same as
screw No. 82)
11
EXTERNAL CONNECTION DIAGRAM
COMPRESSION TERMINAL TYPE
Voltage
input
24 V external
supply
24 V
supply
for
DIO
Process
value
input
Voltage
input
Resistance
bulb
input
Thermo-
couple
input
Manipulated
output 1
Instrument power supply 100 to 240VAC
or
Instrument power supply 24VDC
43
44
45
46
47
48
49
50
51
52
53
54
55
56
MI+1
MI-1
AO1
SC
AO2
AO3
SC
AO4
FLT
DO1
DO2
DO3
DO4
57
58
59
60
61
62
63
64
65
66
67
DO5
DI1
DIO-COM
DI2
DI3
DIO-COM
DI4
DI5
I+1
Io1
Rcj1
Rcj
VPD
VPD
PCD
I-1
22
23
24
25
26
27
28
29
30
31
32
33
34
35
MI+2
MI-2
MI+3
MI-3
MI+4
MI-4
DO6
DO7
DO8
DIO-COM
DI6
DI7
DIO-COM
36
37
38
39
40
41
42
DI8
OPT+
OPT-
COM
I+2
Io2
Rcj2
I-2
PCD
)
)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
AI1
SC
AI2
AI3
SC
AI4
AI5
SC
AI6
SC
VP
PC
DI9
15
16
17
18
19
20
21
DI10
DO9
DO10
MOD+
MOD-
COM
VPD
PCD
PCD
(+)
(-)
(+)
(-)
(COM)
L/+ N/- G
+ -
VPD
PCD
A
b
B
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Note)
Grounding
The area enclosed with a dotted
line is the circuit within the main unit.
External
setting
input
RS485
communication
(Modbus) or T-link
host communication
Note) Compression terminal No. 1, 6, 7, 9, 22, 23, 24, 25, 26, 27, 32, 36, 37, 38, 40,
41, 45, 52, 53, 60, 62 not usable (connection not allowed)
PDA1
[Note] Windows
and Acrobat