History of Technologies
more efficient , more sophisticated
KX2
KX4
(8~12HP)
KX6
Line Up
Contents
Introduction Outdoor units Indoor units Control systems Corrosion Protection Treatment series High Head series Refresh KX outdoor units Further information 4~17 18~33 34~69 70~77 78 . 79 80~83 84 . 85 86~89
R410A
Product Line Up
<Outdoor units>
from 11.2kW up to 136.0kW(24models)
Single use (1 Outdoor unit)
Capacity Model Code : kW BTU / h kcal / h
10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 28 33.5 40.0 45.0 50.4 56.0 61.5 68.0 95,500 114,300 136,500 153,600 172,000 191,100 209,900 232,000 24,080 28,810 34,400 38,700 43,340 48,160 52,890 58,480
26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP 73.5 80.0 85.0 90.0 96.0 101.0 106.5 113.0 118.0 123.5 130.0 136.0 250,800 273,000 290,100 307,100 327,600 344,700 363,400 385,600 402,700 421,400 443,600 464,100 63,210 68,800 73,100 77,400 82,560 86,860 91,590 97,180 101,480 106,210 111,800 116,960
8HP FDC224KXE6G
10HP FDC280KXE6G
12HP FDC335KXE6G
26HP 12+14
28HP 14+14
30HP 14+16
32HP 16+16
34HP 16+18
36HP 18+18
FDC735KXE6 FDC800KXE6 FDC850KXE6 FDC900KXE6 FDC960KXE6 FDC1010KXE6 FDC335KXE6-K FDC400KXE6 FDC400KXE6 FDC450KXE6 FDC450KXE6 FDC504KXE6 FDC400KXE6 FDC400KXE6 FDC450KXE6 FDC450KXE6 FDC504KXE6 FDC504KXE6 38HP 18+20 40HP 20+20 42HP 20+22 44HP 22+22 46HP 22+24 48HP 24+24
FDC1065KXE6 FDC1130KXE6 FDC1180KXE6 FDC1235KXE6 FDC1300KXE6 FDC1360KXE6 FDC504KXE6 FDC560KXE6 FDC560KXE6-K FDC615KXE6 FDC615KXE6 FDC680KXE6 FDC560KXE6 FDC560KXE6 FDC615KXE6 FDC615KXE6 FDC680KXE6 FDC680KXE6
FDC335KXE6-K & FDC560KXE6-K are only used for combining with other models.
<Indoor units>
Wide variety of 17 types 89 models
A range of 17 types of exposed or concealed indoor units, in wide capacities, 89 indoor models. The best selection of indoor units for many kinds of rooms and preference can be available from our full lineup.
FDTC
FDTW
1way Compact
FDTQ
1way High Static Pressure Low/Middle Static Pressure Low Static Pressure (thin) Compact & Flexible Wall Mounted
FDTS
FDU
FDUM
Duct Connected
FDUT
FDUH
FDK
Ceiling Suspended
FDE
FDFW
with casing
FDFL
without casing
FDFU
OA Processing unit Type Fresh Air Ventilation and Heat Exchange unit Fresh Air DX Assembly
FDU-F Air flow M3/h SAF 250 350 500 800 850 1000 1300 1800
SAF-DX
R410A
User friendly LCD panel with light tap operation introduced as the industry's first Simple interface with only three buttons
High level of visibility Big LCD with 3.8 inch full dot display Back light function Multi language display (9 languages)
NEW
RC-EX1A
Energy-saving operation
Changes set temperature. At 28C in cooling mode and 22C in heating mode, 25C in auto mode. Operation correction by outdoor temperature
1. Basic operation
All settings done by tapping touch screen panel
Operation mode
Cooling Fan Heating
Dry Auto
The desired operation mode can be selected by simply tapping this button.
2. Main functions
Saving energy
Sleep timer Peak cut timer Automatic temerature set back Weekly timer Set ON/OFF timer by hour Set ON/OFF timer by clock
Comfort
Individual flap control High power operation External ventilation ON/OFF Warming up operation Automatic fan speed Temperature increment setting by 0.5C
Convenience
Service
LCD contrast setting Error code display Back light setting Operation data display Filter sign Next service date display Control sound Contact company display Outdoor silent mode USB connection (mini-B) Summer time setting Home leave mode Indoor & outdoor temperature display Heating standby display Defrosting operation display Auto cooling/heating display C/F display Administrator settings Room name setting
Outdoor unit
Indoor unit
eco touch Remote Control USB eco touch Remote Control RC-EX1A Utility Software
R410A
EER in Cooling
COP 4.5 4.0 3.5 3.0 2.5 4 5 6
CLASS
COP in Heating
CLASS
4.00
3.2
3.46 3.41 3.55 3.47 3.42 3.34
4.15
3.6
3.84 3.71 3.84 3.82 3.74 3.75
10
12
14
16
18
20
HP
10
12
14
(ISO-T1 conditions)
16
18
20
HP
= Capacity[kW] / Power Consumption[kW] *COP COP across the KX6 range ensures reduced running costs and reduced environmental impact. *
2. Compact Design
4~6HP(KX6)
Volume
35% less
Weight
1FAN
32% less
KX4
H1300 x W970 x D370mm 125kg / 0.47m3
Transportation Becomes much easier Easier to hide behind the fence
KX6
H845 x W970 x D370mm 85kg / 0.30m3
(Harmonic Appearance)
(FDC112/140/155KXEN6)
8~12HP(KX6)
Volume
2FAN
47% less
Weight
10% less
KX4
H1690 x W1350 x D720mm 245kg / 0.97m3
Transportation Becomes much easier
KX6
H1675 x W1080 x D480mm 221kg / 0.52m3 (FDC224KXE6G)
High efficiency and compact design are realized applying the various advanced functions 4~6HP(KX6)
Compact High Efficient Heat Exchanger New Inverter Control
Vector Inverter Control system
DC Fan Motor
Compact & High efficiency
KX6
8~12HP(KX6)
New DC Fan motor
Downsized accumulator
14~48HP(KX6)
DC Fan Motor Expansion of Heat Exchanger
Double tube
R410A
3D Scroll Compressor
Unit start up speed in heating mode drastically improved for lower outdoor temperature operation.
Present scroll
Same height Fixed scroll
3D scroll
Lower at the inside Higher at the outside
Orbital scroll
2-Dimension compression
3-Dimension compression
3D scroll compressor has the different height scroll at the outside and the inside. A high compression ratio is improved by compressing the refrigerant both radially and axially. 3-Dimension Compression has been realized with a much higher efficiency even if compression ratio is high.
The strength of the scroll is improved by reducing the height of the inner wrap, which receives a heavy load.
DC Fan Motor
Employment of DC fan motor has enabled to realize an excellent efficiency of approximate 60% higher than previous models.
Rotor(Squirrel Cage made of conductor) Stator (coil) Rotor(made of permanent magnet) Stator (coil)
10
3. Design Flexibility
Increased indoor unit connection capacity
KX6 series(4~34HP) can connect indoor unit capacity up to 150~200% from 130% of previous models. If the connection capacity of indoor units is more than 100%, capacity of each indoor unit may be affected by connection capacity ratio.
Capacity connection
HP 5~12 14,16 18~34 36~48 KX4 130% 130% 130% 130% HP KX6 4~12 150% 14,16 200% 18~34 160% 36~48 130%
KX6 14,16HP
FDFL,FDFU and/or FDFW series are connected to the system, the total connecting capacity of indoor units should not exceed 130%.
KX6
KX4
4 5 6
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48 HP
Control Systems
KX6 series offer wide variation of control system and provide the best solution. [KX6 Control system units with "New" SUPERLINK- ]
Classification Type Model
Individual controller Wired Wireless Push buttons Touch screen Center Console PC windows interface units BMS interface BACnet units Lonworks
RC-E5 RC-EX1A RCN-T-36W-E etc. SC-SL1N-E SC-SL2NA-E SC-SL3NA-AE SC-SL3NA-BE SC-WGWNA-A SC-WGWNA-B SC-BGWNA-A SC-BGWNA-B SC-LGWNA-A
11
R410A
8~12HP(KX6)
Total length: 510m
Outdoor unit To the first branch: max 130m
Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 4m 18m
14~48HP(KX6)
Max: 10m
Outdoor unit
Max: 0.4m
Indoor unit
Max: 5m
Indoor unit
Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m 18m
Indoor unit
Indoor unit
From the first branch to the furthest indoor unit: 40m 90m*
Indoor unit
From the first branch to the furthest * indoor unit: 40m 90m
Indoor unit
(1)Divide up the refrigerant system into independent refrigeration circuit systems in case required additional refrigerant on site is 50kg or more for 14~24HP and 100kg or more for 26~48HP. (2)In case indoor unit connection capacity is 130% or more or total piping length is 510m or more, additional charge of refrigerant and oil on site is required. Refer to our Installation Manual for details.
8~12HP (KX6)
850
Easy transportation
800
KX6(14~48HP) is portable and the uniform reduced footprint allows neat, continuous installation.
1350mm
1350mm
1350mm
12
-20C
-15C
Heating KX6
KX4
+15.5C
-15C
-5C
Cooling KX6
KX4
+43C
-20 -10 0 10 20 30 40 For the capacities under low temperature conditions, refer to technical manual.
50
KX4
KX6
3-core
2-core
KX4
KX6
1000m
1500m
4. Serviceability
Easy Service
Quick and easy access to service parts by separation of compartments.
Mechanical compartment
13
R410A
Monitoring Function
KX6 series includes new feature to assist with servicing and trouble shooting. Various data can be monitored through 3-digit or 6-digit display on the outdoor unit PCB. Detailed fault diagnosis and operation history memory via 7-segment display. Equipped with RS232C for connection directly to your PC monitoring and service tasks made simple with our service software (Mente PC). all KX6 series
4~6HP
8~48HP
Keeping operation
Compressor failed
Inverter
Outdoor unit
HP
KX6 R410A
9.52 22.22
Liquid piping
Gas piping
ex.10HP
4 15.88 5 6 9.52 19.05 8 22.22 10 12 25.4[28.58] 14 16 12.7 18 28.58 20 22 24 26 28 31.8[34.92] 30 15.88 32 34 36 38 40 38.1[34.92] 42 19.05 44 46 48 [ ]: Pipe sizes applicable to European installations are shown in parentheses.
1" 11/8" 11/4" 13/8" 11/2" 13/4" 2"
Blue Fin
Due to application of blue coated fins for the heat exchanger of new outdoor unit, corrosion resistance has been improved compared to current models.
mm 9.52 12.7 15.88 19.05 22.22 25.4 28.58 31.8 34.92 38.1 44.5 50.8 inch 3/8" 1/2" 5/8" 3/4" 7/8"
14
Fixed Cooling mode/fixed heating mode (summer/winter switch): It is possible to fix the operational mode of the system (either cooling or heating) using a switch (SW3-7) on the outdoor unit PC board - this enables the building user to decide the operation of the system (e.g. cooling only in summer/heating only in winter), to avoid unnecessary energy wastage. It is also possible to wire the control switch to a remote location (inside the building) to a control room, or even linked to an ambient thermostat.
15
R410A
FDUM
NEW
Duct
New FDUM
Duct Ceiling
Longer Duct
case1
case2
No.1 10Pa
No.2 20Pa
No.3 30Pa
No.4 40Pa
No.5 50Pa
No.6 60Pa
No.7 70Pa
No.8 80Pa
E.S.P. button
RC-E5
FDTW
NEW
Wireless remote control
For wireless remote control simply insert the infrared receiver kit on a corner of the panel.
3
RCN-TW-E
* Wireless remote control and RCH-E3 is not applicable to the lndvidual flap
16
FDUT
Height: 220 200mm
NEW
1dB(A) Down
Current New
2dB(A) Down
30
1m 1m 2m
Depth: 520 500mm
Unit
1.5m 1m
20
29
28 24 22
10
Hi
Fan speed
Lo
Current Model
New Model
[dB(A)]
Serviceability
Access to control
40 30 20 10 0
5dB(A) Down
Current New
4dB(A) Down
37 32 30 26
Hi
Access to control
Fan speed
Lo
Current Model
New Model
FDTS
NEW
RCN-TS-E
17
R410A
The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas. Connect up to 8 indoor units/up to 150% capacity. High efficiency with COP (in cooling) up to 4.0. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 100m and a maximum pipe run of 70m.
Range of operation
50
+43C
40 30 20 10 0
Indoor unit
Max height
difference between indoor units: 15m
Cooling
+15.5C
Indoor unit
Heating
-10
-15C
-20
-20C
Specifications
Item Nominal horse power Power source Nominal capacity Model
FDC112KXEN6
4HP 11.2 12.5 2.80 2.89 13.5-12.4 14.1-12.9
FDC140KXEN6
5HP 1 Phase 220-240V, 50Hz 14.0 16.0 4.17 4.31 20.6-18.9 21.5-19.7 85
FDC155KXEN6
6HP 15.5 16.3 5 4.71 4.38 23.3-21.3 21.9-20.1
FDC112KXES6
4HP 11.2 12.5 2.80 2.89 4.5-4.1 4.7-4.3
FDC140KXES6
5HP 3 Phase 380-415V, 50Hz 14.0 16.0 4.17 4.31 6.9-6.3 7.2-6.6 87
FDC155KXES6
6HP 15.5 16.3 4.71 4.38 7.8-7.1 7.3-6.7
Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating mm Exterior dimensions HxWxD kg Net weight kg Refrigerant charge R410A dB(A) Cooling/Heating Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units
845x970x370 5.0 52/54 53/55 53/56 9.52(3/8") 15.88(5/8") 80~150 6 8 8 6 8 8 52/54 53/55 53/56
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
18
Refrigerant piping
Outdoor unit (HP) Gas pipe Liquid pipe Furthest indoor unit =<70m 4 5 15.88 9.52 6 Branch pipes Header pipe
DIS-22-1G/DIS-180-1G
HEAD6-180-1G
Dimensions
All measurements in mm.
36
51
40
100
L2
Intake
L3
Intake
L4 L1
outlet Service space
Terminal block
B
845
A
L1 L2 L3 L4
52 27 50
I
Open 300 150 5
II
Open 5 300 5
II
500 Open 150 5
242
279
110
10
195
195
C
970
55 50 15
50
50
110
E
60 20 40
190 60
580
200 60 15 15
55
103
410
370
38
150
C
20 40 262 388
50
70
40 15 50
VIEW A
Mark A B C D E F
Item Service valve connection (gas side) Service valve connection (liquid line) Pipe/cable draw-out port Drain discharge port Anchor bolt hole Cable draw-out port 15.88 (5/8") (flare) 9.52 (3/8") (flare) 4 places 20 x 3 places M10 x 4 places 30 x 3 places
Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave a 1m or larger space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The unit name plate is attached on the lower right corner of the front panel.
19
R410A
The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.
Connect up to 22 indoor units/up to 150% capacity. High efficiency with COP (in cooling) up to 4.0. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 510m and a maximum pipe
run of 160m.
Outdoor unit Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 18m
Range of operation
50
+43C
40 30 20 10 0
Indoor unit
Cooling
+15.5C
Indoor unit From the first branch to the furthest indoor unit: 90m*
Indoor unit
Heating
-10
-15C
-20
-20C
* The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m.
Specifications
Item Nominal horse power Power source Nominal capacity Model
FDC224KXE6G
8HP 22.4 25.0 5.60 6.03 9.25-8.47 9.85-9.02 221 58/58 9.52(3/8") 19.05(3/4") 15
FDC280KXE6G
10HP 3 Phase 380-415V, 50Hz 28.0 31.5 5 8.09 8.21 13.22-12.10 13.41-12.28 1675x1080x480 11.5 59/60 22.22(7/8") 50~150 19
FDC335KXE6G
12HP 33.5 37.5 9.82 10.12 15.87-14.53 16.36-14.98 224 61/61 12.7(1/2") 25.4(1") [28.58(1 1/8")] 22
Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
20
Refrigerant piping
Outdoor unit (HP) Gas pipe Liquid pipe Gas pipe Liquid pipe Furthest indoor unit =<90m Furthest indoor unit =<90m 8 19.05 22.22 9.52 12.7 10 22.22 12 28.58 12.7 28.58 DIS-22-1G/DIS-180-1G DIS-371-1G HEAD6-180-1G Branch pipes Header pipe
Dimensions
All measurements in mm.
69
B A G
69 51
L2
Intake
L3
Intake
II
Open 5 300 5
II
1500 Open 300 5
L4
L1
Service space
Outlet
43 60 120
L1 L2 L3 L4
Terminal block
1675
A
553 640(8.10HP) 634(12HP)
20
159 194
174 84
84
F
1080 195 690
51
54 14
159 84
35
35
67 42 989
50
14
54 51
55
55
E
19 39
195 50
E
30 30
701
520 480
105
80
19 39
Mark A B C D E F G
Item Service valve connection of the attached connecting pipe (gas side) Service valve connection (liquid side) Pipe/cable draw-out hole Drain discharge hole Anchor bolt hole Cable draw-out hole Connecting position of the local pipe. (gas side)
FDC224KXE6G 19.05 (3/4") (Flare) 9.52 (3/8") (Flare) 4places 20 x 4places M10 x 4places 30 x 2places (front) 45 (side) 30 x 2places (back) 19.05 (3/4")(Brazing)
FDC280KXE6G 19.05 (3/4") (Flare) 9.52 (3/8") (Flare) 4places 20 x 4places M10 x 4places 30 x 2places (front) 45 (side) 30 x 2places (back) 22.22 (7/8")(Brazing)
FDC335KXE6G 19.05 (3/4") (Flare) 12.7 (1/2") (Flare) 4places 20 x 4places M10 x 4places 30 x 2places (front) 45 (side) 30 x 2places (back) 25.4 (1")(Brazing)
Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave a 1m or larger space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The model name label is attached on the lower right corner of the front. (7) Connect the Service valve with local pipe by using the pipe of the attachment.(Gas side only) (8) Mark shows the connecting position of the local pipe.(Gas side only)
55
21
R410A
The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.
Connect up to 40 indoor units/up to 200% capacity. High efficiency with COP (in cooling) up to 3.6. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.
Outdoor unit Range of operation Height difference 50m(outdoor unit above) 40m(outdoor unit below)
*2
50
+43C
40 30 20 10 0
Indoor unit
Indoor unit
Indoor unit
Cooling
+15.5C
Heating
Furthest indoor unit: 160m
-10
-15C
-20
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. *2 Height difference up to 100m is possible with High Head series. Please refer to page 80.
-20C
Specifications
Item Nominal horse power Power source Nominal capacity Model
FDC400KXE6
14HP 3 Phase 380-415V, 50Hz 40.0 45.0 8 11.27 11.73 18.4-16.9 19.6-17.9 1690x1350x720 334 11.5 59.5/60 12.7(1/2") 25.4(1") [28.58(1 1/8")] 50~200 53
FDC450KXE6
16HP 45.0 50.0 12.97 13.10 21.1-19.3 21.7-19.9
Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
22
Dimensions
All measurements in mm.
250 175 850 1000 250 175
85 101
594 232
726
85
95 140.5
141
234
75 142.5
58.5
1690 797.8
126.2
720
19
Air intake
148 410
140
342 235
1350
7-segment display inspection port Signal wire terminal block Terminal block for power cable connection 682
K B A C (front)
166 169 211 259 291.6
22
240 295
647
57
174 720
296.7
58.5
Rear
19
F I
I F
120
22
74.5
80.5 71
C (right)
C (rear)
L
44.7
84
D (left)
104.9
90
86.5
D (front)
220 180
550
180 214
Mark A B C D F G H K* L
Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.
Installation example
Dimensions
L2
L3
Intake
Wall height H3 L4
Intake
Wall height H2
Intake
Wall height H4 Wall height H1
L1 L2 L3 L4 H1 H2 H3 H4
Service space
Intake
Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination. (For 14,16Hp only)
Installation example
Dimensions
L1
20
Instruction plate
6 86.1
172
95
D (right)
172
80
L3
Wall height H2 Wall height H4
L1
L6 L4
L2
L5
L2 L3 L4 L5 L6 H1 H2 H3 H4
No restrictions No restrictions
23
R410A
Outdoor units Heat pump systems 18, 20, 22, 24hp (50.4kW~68.0kW)
Model No. FDC504KXE6 FDC560KXE6 FDC615KXE6 FDC680KXE6 Nominal Cooling Capacity 50.4kW 56.0kW 61.5kW 68.0kW
The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.
Connect up to 49 indoor units/up to 160% capacity. High efficiency with COP (in cooling) up to 3.4. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.
Uniform footprint of all models (from 8hp~24hp) allows continuous sideby-side installation Outdoor unit Height difference 50m(outdoor unit above) 40m(outdoor unit below)
*2
Range of operation
50
Indoor unit
+43C
40 30 20 10 0
Indoor unit
Indoor unit
Cooling
+15.5C
Heating
-10
-15C
-20
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. *2 Height difference up to 100m is possible with High Head series. Please refer to page 80.
-20C
Specifications
Item Nominal horse power Power source Nominal capacity Model
FDC504KXE6
18HP 50.4 56.5 14.73 15.12 24.1-22.0 25.2-23.1 356
FDC560KXE6
20HP
FDC615KXE6
22HP
FDC680KXE6
24HP 68.0 73.0 24.98 19.08 40.3-36.9 31.6-29.0 375
3 Phase 380-415V, 50Hz 56.0 63.0 8 16.79 16.79 27.4-25.1 28.0-25.7 2048x1350x720 11.5 61.5/62.0 63.0/63.5 12.7(1/2") 28.58(1 1/8") 50~160 53 59 65 72 64.5/64.0 65.0/65.0 20.37 18.48 33.1-30.3 30.7-28.1 61.5 69.0
Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
24
Dimensions
All measurements in mm.
250 175 850 1000 250 175 74.5 85 101 232 D(lower) 185 Rear Dimensions of refrigerant pipe connection (plan)
594 232
726
85
95 140.5
141
234 720
75 142.5
2048
1155.8
126.2
58.5
19
Air intake
148 410
140
342 235
1350
Drain pipe
7-segment display inspection port Signal wire terminal block 175 80 Terminal block for power cable connection 682
K B A C (front)
166 169 211 259 291.6
22
240 295
647
57
174 720
296.7
58.5
F I
I F
19
120
22
80.5 71
C (right)
C (rear)
L
44.7
84
D (left)
104.9
90
86.5
D (front)
220 180
550
180 214
Mark A B C D F G H K L
Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.
Installation example
Dimensions
L2
L3
Intake
Wall height H3 L4
Intake
Wall height H2
Intake
Wall height H4 Wall height H1
L1 L2 L3 L4 H1 H2 H3 H4
Service space
Intake
Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination.
L1
20
Instruction plate
6 86.1
172
95
D (right)
172
25
R410A
Outdoor units Heat pump combination systems 26, 28, 30, 32hp (73.5kW~90.0kW)
Model No. FDC735KXE6 (FDC335-K+FDC400) FDC800KXE6 (FDC400x2) FDC850KXE6 (FDC400+FDC450) FDC900KXE6 (FDC450x2) Nominal Cooling Capacity 73.5kW 80.0kW 85.0kW 90.0kW
The KX6 heat pump 2-pipe systems offer high performance VRF for
applications that require either cooling only or heating only, ideal for open plan areas.
Connect up to 65 indoor units/up to 160% capacity. High efficiency with COP (in cooling) up to 3.6. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum
pipe run of 160m.
Uniform footprint of all models (from 8hp~24hp) allows continuous side-byside installation
Outdoor unit Height difference 50m(outdoor unit above) 40m(outdoor unit below)
*2
Range of operation
50
+43C
40 30 20 10 0
Indoor unit
Indoor unit
Indoor unit
Cooling
+15.5C
Heating
Furthest indoor unit: 160m
-15C
-20
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m. *2 Height difference up to 100m is possible with High Head series. Please refer to page 80.
-20C
Specifications
Item Combination (FDC) Nominal horse power Power source Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units Nominal capacity Model
FDC735KXE6
335KXE6-K 400KXE6 26HP 73.5 82.5 20.21 20.66 32.9-30.2 34.4-31.4
FDC800KXE6
FDC850KXE6
FDC900KXE6
450KXE6 450KXE6 32HP 90.0 100.0 25.94 26.20 42.2-38.6 43.4-39.8
78
400KXE6 400KXE6 400KXE6 450KXE6 28HP 30HP 3 Phase 380-415V, 50Hz 80.0 85.0 90.0 95.0 16 22.54 24.24 23.46 24.83 36.8-33.8 39.5-36.2 39.2-35.8 41.3-37.8 1690x2700x720 334x2 11.5x2 15.88(5/8") 31.8(1 1/4") [34.92(1 3/8")] 50~160 80 80
80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
26
Dimensions
All measurements in mm.
250 175 850 1000 250 175
85 101
594 232
726
85
95 140.5
141
234
75 142.5
58.5
1690 797.8
126.2
720
19
Air intake
148 410
140
342 235
1350
7-segment display inspection port Signal wire terminal block Terminal block for power cable connection 682
K B A C (front)
166 169 211 259 291.6
22
240 295
647
57
174 720
296.7
58.5
Rear
19
F I
I F
120
22
74.5
80.5 71
C (right)
C (rear)
L
44.7
84
D (left)
104.9
90
86.5
D (front)
220 180
550
180 214
Mark A B C D F G H K L
Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.
Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination.
20
Instruction plate
6 86.1
172
95
D (right)
172
80
27
R410A
Outdoor units Heat pump combination systems 34, 36, 38, 40, 42, 44, 46, 48hp (96.0kW~136.0kW)
Model No. FDC960KXE6 (FDC450+FDC504) FDC1010KXE6 (FDC504x2) FDC1065KXE6 (FDC504+FDC560) FDC1130KXE6 (FDC560x2) FDC1180KXE6 (FDC560-K+FDC615) FDC1235KXE6 (FDC615x2) FDC1300KXE6 (FDC615+FDC680) FDC1360KXE6 (FDC680x2) Nominal Cooling Capacity 96.0kW 101.0kW 106.5kW 113.0kW 118.0kW 123.5kW 130.0kW 136.0kW
The KX6 heat pump 2-pipe systems offer high performance VRF for applications that
require either cooling only or heating only, ideal for open plan areas. Connect up to 80 indoor units/up to 130% (960KXE6:160%) capacity. High efficiency with COP (in cooling) up to 3.5. KX6 employs DC inverter compressors ONLY. Industry leading total piping length up to 1000m and a maximum pipe run of 160m.
Outdoor unit Height difference 50m(outdoor unit above) 40m(outdoor unit below)
*2
Range of operation
50
+43C
40 30 20 10 0
Indoor unit
Indoor unit
Indoor unit
Cooling
+15.5C
Heating
Furthest indoor unit: 160m
-15C
-20
-20C
*1 The difference between the longest and the shortest indoor unit piping
from the first branch must be within 40m.
Specifications
Item Combination (FDC) Nominal horse power Power source Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units Nominal capacity Model
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
28
Dimensions
All measurements in mm.
250 175 850 1000 250 175 74.5 85 101 232 D(lower) 185 Rear Dimensions of refrigerant pipe connection (plan)
594 232
726
85
95 140.5
141
234 720
75 142.5
58.5
19
Air intake
148 410
140
342 235
2048
1155.8
126.2
1350
Drain pipe
7-segment display inspection port Signal wire terminal block 175 80 Terminal block for power cable connection 682
K B A C (front)
166 169 211 259 291.6
22
240 295
647
57
174 720
296.7
58.5
F I
I F
19
120
22
80.5 71
C (right)
C (rear)
L
44.7
84
D (left)
104.9
90
86.5
D (front)
220 180
550
180 214
Mark A B C D F G H K L
Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.
Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination.
20
Instruction plate
6 86.1
172
95
D (right)
172
29
R410A
refrigerant piping
Installation of Interconnecting Pipework Mitsubishi KX6 equipment is manufactured to the highest standards of quality and reliability. It is imperative the method of installation and the materials used are also to high standards, to ensure trouble free operation and long term reliability. The interconnecting pipework must be installed by a competent and trained engineer. Refrigeration quality copper tube must be used, soft copper coils or half-hard straight lengths. The refrigeration quality tube must be soft drawn seamless high grade copper pipe. The copper tube must be selected taking into account the higher operating pressures of R410A refrigerant, and that high pressures will occur throughout the system because of the reverse cycle operation. All pipework material used should be EN12735 European standard. The supplied branch pipe kits, must be used to make connections to indoor units, and the supplied manifold kits must be used to make connections between outdoor units (where applicable); it is not permitted to use standard fittings such as elbows, tees etc. The branch pipes shall be installed in accordance with the manufacturers instructions, allowing unrestricted flow of refrigerant, and in accordance with European standard E378:2000. All brazed joints shall be made with dry nitrogen purge to ensure the prevention of oxidisation to the internal surface of the copper pipes. The ingress of moisture, dirt and any other contaminants to the interior of the copper pipes, and air conditioning units, must be prevented during the installation procedure. After the installation of pipework, prior to the connection of the outdoor units, and sealing of insulation joints, the pipework must be pressure tested for leakage, using dry nitrogen. Additional Refrigerant Additional R410A refrigerant only shall be used, and must be charged by weight only, using electronic scales. The amount of additional refrigerant must be accurately calculated from the manufacturers data, based on the length and diameter of each section of the liquid refrigerant pipework of the system.
HEAD8-371-1G
Liquid pipe
90
90
56
56
36
36
36
36
Gas pipe
56
56
36
36
36
112
112
112
30
refrigerant piping
Outdoor unit (HP) Liquid pipe Gas pipe Liquid pipe Gas pipe Branch pipes Furthest indoor unit =<90m Furthest indoor unit =>90m 8 10 12 14 16 18 12.7 28.58 12.7 22.22 28.58 Header pipe 15.88 20 22 24 9.52 19.05 22.22
19.05 22.22
Floor
Good
DIS-22-1G/DIS-180-1G
HEAD6-180-1G
No Good
Vertically
No
Floor
Floor
DIS-371-1G/DIS-540-2G
DOS-2A-1G
112
112
90
90
90
140
140
140
Outdoor unit's branching piping Outdoor unit 2 units (for 735~1360) Branch piping set DOS-2A-1G
HEAD8-540-2G
Indoor unit's first branching piping Total capacity of indoor units ~179 180~370 371~539 540~ Branch piping set DIS-22-1G DIS-180-1G DIS-371-1G DIS-540-2G Header set Model HEAD4-22-1G HEAD6-180-1G HEAD8-371-1G HEAD8-540-2G Branches Max 4 branches Max 6 branches Max 8 branches Max 8 branches
112
112
90
90
90
140
140
140
31
R410A
Earth leakage breaker (Impulse withstanding type) Circuit breaker for cabling Grounding wire
Outdoor unit
A Power cable (Main Power cable)[4 cores] B Signal wire (Super Link wire)[2 cores] C Power cable (Indoor unit power cable)
[2 cores] [2 cores]
C
Circuit breaker for cabling Earth leakage breaker
Indoor unit
D R R R R R R
Remote control unit
CAUTION
If the earth leakage breaker is exclusively for ground fault protection, then you will need to install a circuit breaker for wiring work.
32
A1
B1
Indoor and outdoor signal line do not have a polarity. Any of the connections in the following illustration can be made.
A1
Indoor signal line terminal block
A B
A1 B1
A B
B1
3. We recommend the both ends of the shield of the cable are connected to ground (earth) at all the indoor units and outdoor units. 4. When plural outdoor units are used, .Connect the signal cable between indoor and outdoor units and the signal cable between outdoor units belonging to the same refrigerant line to A1 and B1. .Connect the signal line between outdoor units on different refrigerant lines to A2 and B2. 5. For current specification of 2-core (AB) wiring, please consult your MHI dealer.
(2) When plural outdoor units are used Outdoor unit Outdoor unit Outdoor unit Outdoor unit
Network connector
A1B1 A2B2
Indoor unit
A1B1 A2B2
A1B1 A2B2
Indoor unit
A1B1 A2B2
A B
Indoor unit
A B
Indoor unit
Refrigerant pipe
A B
Signal line
A B
(a) The maximum number of indoor units that can be connected in a system is 128 and it is possible to configure outdoor units and/or indoor units as an outdoor or indoor unit group connected with each other with two wires. (b) The signal wires can also be connected using the method shown below.
(3) The signal lines can also be connected using the method shown below.
Important
Outdoor unit Outdoor unit Outdoor unit Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
The signal lines cannot form a loop, so the wirings shown as in the diagram are prohibited.
Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
Indoor unit
Indoor unit
A
Indoor unit
A
Indoor unit
A
Indoor unit
A
Indoor unit
Wire size 0.5mm2 x 2 core 0.75mm2 x 2 core 1.25mm2 x 2 core 2.0mm2 x 2 core
Remote control
Wires can be connected across different refrigerant systems when wired within 1 Superlink system
33
R410A
RC-EX1A
RC-E5
RCH-E3
Wireless
RCN-T-36W-E
According to room temperature conditions, four directions of air flow can be controlled by individual flap as preferred. As individual flap control is available even after installation, installation area became wider than before.
Thanks to new design of heat exchanger changed from 2 parts to 1 part, the height of indoor unit is reduced drastically. Furthermore applying DC fan motors to FDT models, the highest energy efficiency level, reduction of weight and significant compact design are realized.
270mm
Due to optimization of outlet design of air flow with our new advanced technology, sufficient air flow is secured and long reach of air flow is realized.
KX4 KX6
365mm
246
mm
FDT28~71
298
mm
FDT112~160
reduction!!
9%
reduction!!
18%
Selection of flap position is possible. Individual flaps can be set at different angles. is not applicable to the *RCH-E3 Individual flap control system
and the Flap control system.
Specifications
Item Model FDT28KXE6F Nominal cooling capacity kW 2.8 Nominal heating capacity kW 3.2 Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow CMM Outside air intake Panel Air filter, Qty Remote control(option) Liquid line:6.35(1/4") Installation data Refrigerant piping size mm(in) Gas line:9.52(3/8")
FDT36KXE6F
3.6 4.0 0.03-0.03 0.03-0.03
FDT45KXE6F
4.5 5.0
FDT56KXE6F
5.6 6.3
FDT71KXE6F
Hi:33 Me:31 Lo:30 Unit:246x840x840 Panel:35x950x950 Unit:22 Panel:5.5 Hi:18 Me:16 Lo:14 Unit:24 Panel:5.5
Unit:298x840x840 Panel:35x950x950 Unit:27 Panel:5.5 Hi:27 Me:24 Lo:20 Hi:30 Me:27 Lo:23
Possible T-PSA-3BW-E Pocket Plastic net x1 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-T-36W-E Liquid line:6.35(1/4") Gas line:12.7(1/2") Liquid line:9.52(3/8") Gas line:15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDT28/36/45 37dB(A), FDT56 39dB(A), FDT71 46dB(A), FDT90/112/140/160 51dB(A). Air flow: FDT28/36/45/56 20CMM, FDT71 28CMM, FDT90/112/140/160 37CMM.
34
Dimensions
All measurements in mm.
35
R410A
RC-EX1A
(dB) 36
Utilizing OA spacer which comes as optional equipment, outside air can be taken into inside. Using 1 joint duct: OA comes up to 1.3m3/min. Using 2 joint ducts: OA comes from 1.3 to 2.6m3/min.
OA Spacer Ceiling OA surface Panel OA Joint Duct
2dB Down
32 dB
30 dB
32 dB
35 34 33 32 31 30 29 28 27 26 25
34 dB
3dB Down
34 dB
31 dB
KX4 (Cooling/Heating)
KX6 (Cooling)
KX6 (Heating)
KX4 (Cooling/Heating)
KX6 (Cooling)
KX6 (Heating)
FDTC22KX, 28KX
(dB) 40
FDTC36KX
39 38 37 36 35 34 33 32 31 30 29 28 27 26 25
5dB Down
36 dB
2dB Down
39 dB
300mm
34 dB 31 dB
34 dB
31 dB
KX4 (Cooling/Heating)
KX6 (Cooling)
KX6 (Heating)
KX4 (Cooling/Heating)
KX6 (Cooling)
KX6 (Heating)
FDTC45KX
FDTC56KX
According to room temperature conditions, four directions of air flow can be controlled by individual flap as preferred. As individual flap control is available even after installation, installation area became wider than before.
Selection of flap position is possible. Individual flaps can be set at different angles.
is not applicable to the Individual flap * RCH-E3 control system and the Flap control system.
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure Cooling dB(A) level Heating Exterior dimensions mm HxWxD kg Cooling Air flow CMM Heating Outside air intake Panel Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in) Net weight Unit:14 Panel:3.5 Hi:9.5 Me:8.5 Lo:7 Hi:9.5 Me:8.5 Lo:8
FDTC22KXE6F
2.2 2.5
FDTC28KXE6F
2.8 3.2 0.03-0.03 0.03-0.03
FDTC36KXE6F
3.6 4.0 1 Phase 220-240V, 50Hz
FDTC45KXE6F
4.5 5.0 0.05-0.05 0.05-0.05
FDTC56KXE6F
5.6 6.3
Unit:15 Panel:3.5 Hi:10 Me:9 Lo:7 Hi:11 Me:9 Lo:7 Hi:10 Me:9 Lo:8 Hi:11 Me:9 Lo:8 Not possible TC-PSA-25W-E Pocket Plastic net x1 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TC-24W-ER Liquid line:6.35(1/4") Gas line:12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDTC22/28 44dB(A), FDTC36 46dB(A), FDTC45 48dB(A), FDTC56 49dB(A). Air flow: FDTC22/28 12CMM, FDTC36 13CMM, FDTC45 15CMM. FDTC56 16CMM.
36
Dimensions
All measurements in mm.
37
R410A
FDTW28~71
RCN-TW-E
FDTW90~140 750mm Drain Pump
Drain can be discharged upward by 750mm from the ceiling surface close to the indoor unit. It allows a piping layout with a high degree of freedom depending on the installation location.
Installation workability
Drainage spout
Drainage flow test can be done easily by use of this drainage spout.
Cleaning
not required
Cleaning
required
Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow CMM Outside air intake Panel Air filter, Qty Remote control(option)
invisible
FDTW28KXE6F
2.8 3.2 0.09-0.09 0.09-0.09
FDTW45KXE6F
4.5 5.0
FDTW56KXE6F
5.6 6.3
FDTW71KXE6F
7.1 8.0 1 Phase 220-240V, 50Hz 0.14-0.14 0.14-0.14
FDTW90KXE6F
9.0 10.0
FDTW112KXE6F
11.2 12.5 0.19-0.19 0.19-0.19 Hi:45 Me:41 Lo:37
FDTW140KXE6F
14.0 16.0
Unit:325x1535x620 Panel:20x1835x680 Unit:23 Panel:8.5 Unit:35 Panel:13 Hi:27 Me:23 Lo:20 TW-PSA-46W-E Pocket Plastic net x3 (Washable)
Unit:20 Panel:8.5
Possible TW-PSA-26W-E Pocket Plastic net x2 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TW-E Liquid line:6.35(1/4") Gas line:12.7(1/2")
Liquid line:6.35(1/4") Installation data Refrigerant piping size mm(in) Gas line:9.52(3/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDTW28/45/56/71 42dB(A), FDTW90/112/140 48dB(A). Air flow: FDTW28/45/56/71 14.5CMM, FDTW90/112/140 31CMM.
38
Dimensions
All measurements in mm.
39
R410A
RCN-TS-E
Compact design
Drain can be discharged upward by 600mm from the ceiling surface close to the indoor unit. It allows a piping layout with a high degree of freedom depending on the installation location.
Flexible hose 600mm
Indoor unit size (W:1,150 x D:565) brings easy installation for 1,200 x 600 ceiling and Panel size (1,250 x 650) is suitable for 1,200 x 600 ceiling. Height is the industry's lowest height level 220mm and weight is 27/28kg only.
220mm
Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow CMM Outside air intake Panel Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in)
FDTS45KXE6F
4.5 5.0 1 Phase 220-240V, 50Hz 0.04 0.04 Hi:40 Me:38 Lo:35 Unit:220x1150x565 Panel:35x1250x650 Unit:27 Panel:5 Hi:12 Me:11 Lo:9.5 Possible TS-PSA-3AW-E Pocket Plastic net x2 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-TS-E Liquid line:6.35(1/4") Gas line:12.7(1/2")
FDTS71KXE6F
7.1 8.0 0.09 0.09 Hi:46 Me:41 Lo:36
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDTS45 42dB(A), FDTS71 49dB(A). Air flow: FDTS45 13CMM, FDTS71 17CMM.
40
Dimensions
All measurements in mm.
41
R410A
RCN-KIT3-E
Compact design
63
600 or less
210
Specifications
Model Item FDTQ22KXE6F FDTQ28KXE6F FDTQ36KXE6F Direct blow panel Duct panel Direct blow panel Duct panel Direct blow panel Duct panel Panel Name Panel mode (Option) TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER TQ-PSA-15W-E TQ-PSB-15W-E QR-PNA-14W-ER QR-PNB-14W-ER Nominal cooling capacity kW 2.2 2.8 3.6 Nominal heating capacity kW 2.5 3.2 4.0 Power source 1 Phase 220-240V, 50Hz Cooling 0.05-0.07 0.05-0.07 0.05-0.07 Power consumption Heating kW 0.05-0.07 0.05-0.07 0.05-0.07 Sound pressure level dB(A) Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 Hi:41 Me:38 Lo:33 250x570x570 250x570x570 250x570x570 Exterior dimensions Unit mm HxWxD 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 35x625x650 35x780x650 Panel Net weight kg Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Unit:23 Panel:2.5 Unit:23 Panel:3 Air flow Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 Hi:7 Me:6 Lo:5 CMM Outside air intake Possible Air filter, Qty Pocket Plastic net x1 (Washable) Remote control(option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Installation data Refrigerant piping size mm(in) Liquid line:6.35(1/4") Gas line:9.52(3/8") Liquid line:6.35(1/4") Gas line:12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDTQ22/38/36 45dB(A). Air flow: FDTQ22/38/36 8CMM.
42
285
295~325
Dimensions
All measurements in mm.
Direct blow panel (TQ-PSA-15W-E) Direct blow panel (TQ-PSB-15W-E)
Dimension Table
model TQ-PSA-15W-E TQ-PSB-15W-E a 625 780 b 514 514 c 650 650
Unit:mm
Dimension Table
model QR-PNA-14W-ER QR-PNB-14W-ER a 625 780 b 650 650
Unit:mm
d 580 580
c 580 580
43
R410A
RC-EX1A Wireless
RC-E5
RCH-E3
RCN-KIT3-E
You can set External Static Pressure (E.S.P.) by method of manual setting on remote control. Indoor unit will control fan-speed to keep rated air flow volume at each fan speed setting. You can set required E.S.P. by wired remote control that calculated with the set air flow rate and RC-E5 pressure loss of the duct connected. E.S.P. button External Static Pressure (E.S.P.) can be set by E.S.P. button.
Duct
Current
New
FDU71KXE6F FDU112/140KXE6F
Reduction of weight
297 350
280 280
New FDU
Duct Ceiling
Longer Duct
Current
New
case1
Setting No. E.S.P. No.8 80Pa No.9 No.10 No.11 No.12 No.13 No.14 No.15 90Pa 100Pa 110Pa 120Pa 130Pa 140Pa 150Pa
case2
40 63 63
34 34 54
*Range of 80~150 Pa is set at ex-factory default. Range of 10~200 Pa is available by setting SW8-4 switch on at site.
12dB(A) less!!
35 40 dB(A) Lo mode
10~130Pa
10~200Pa
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM External Static pressure Pa Outside air intake Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in)
37 38 39
25 30 29
FDU45KXE6F
4.5 5.0
FDU56KXE6F
5.6 6.3
FDU71KXE6F
7.1 8.0
FDU90KXE6F
FDU112KXE6F
FDU140KXE6F
14.0 16.0 0.35-0.36/0.35 0.35-0.36/0.35 Hi:40 Me:34 Lo:29 280x1370x740 54 Hi:32 Me:26 Lo:20 200 (at 39CMM)
FDU160KXE6F
16.0 18.0 0.42-0.43/0.42 0.42-0.43/0.42 Hi:40 Me:35 Lo:30
0.10-0.10/0.10 0.10-0.10/0.10 Hi:32 Me:29 Lo:26 280x750x635 29 Hi:10 Me:9 Lo:8 200 (at 13CMM)
9.0 11.2 10.0 12.5 1 Phase 220-240V, 50Hz 0.24-0.25/0.24 0.31-0.32/0.31 0.24-0.25/0.24 0.31-0.32/0.32 Hi:33 Me:29 Lo:25 Hi:38 Me:36 Lo:30 280x950x635
34 Hi:19 Me:15 Lo:10 Hi:28 Me:25 Lo:19 200 (at 24CMM) 200 (at 36CMM) Possible Procure locally wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Liquid line:9.52(3/8") Gas line:15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of indoor unit is 60Pa. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. Powerful-Hi can be selected. Sound pressure level: FDU45/56 37dB(A), FDU71/90 38dB(A), FDU112 44dB(A), FDU140 45dB(A),FDU160 47dB(A). Air flow: FDU45/56 13CMM, FDU71/90 24CMM, FDU112 36CMM, FDU140 39CMM, FDU160 48CMM.
44
Dimensions
All measurements in mm.
FDU45KXE6F, 56KXE6F
FDU71KXE6F, 90KXE6F
45
R410A
RC-EX1A Wireless
RC-E5
RCH-E3
RCN-KIT3-E
Fan motor
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM External Static pressure Pa Outside air intake Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in)
FDU224KXE6F
22.4 25.0 1 Phase 220-240V, 50Hz 0.94-1.03 0.86-0.90 Hi:51 360x1570x830 92 Hi:51 200 Possible(on Return duct) Procure locally wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Liquid line:9.52(3/8") Gas line:19.05(3/4")
FDU280KXE6F
28.0 31.5 0.96-1.05 0.88-0.96 Hi:52
Hi:68
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of indoor unit is 100Pa. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. Values of sound pressure level become increased 5dB(A), when external static pressure is 200Pa (factory setting). 4. Values of air flow volume are those at external static pressure 200Pa (factory setting).
46
Dimensions
All measurements in mm.
VIEW
VIEW
47
R410A
NE
RC-EX1A
Thin design
RC-E5
RCH-E3
RCN-KIT3-E
Air flow sound was reduced by new fan and casing design. Refrigerant flow sound was decreased by advanced refrigerant distributor design.
Indoor model name NEW Current FDUM Improvement dB(A) 22/28/36 26 28 2 45/56 26 29 3 71 25 29 4 90 25 30 5 112 30 32 2 140 29 33 4
Fan unit (impeller and motor) can be pulled out from the right side or the bottom side of the unit. Maintenance can be available from the right side or the bottom side.
H 299
H 280 FDUM22~90KXE6F
Specifications
Model FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F FDUM45KXE6F FDUM56KXE6F FDUM71KXE6F FDUM90KXE6F FDUM112KXE6F FDUM140KXE6F FDUM160KXE6F Item Nominal cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0 Nominal heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 18.0 Power source 1 Phase 220-240V, 50Hz Cooling 0.29-0.29 0.45-0.45 0.10-0.10 0.20-0.20 0.33-0.33 Power consumption Heating kW 0.29-0.29 0.45-0.45 0.10-0.10 0.20-0.20 0.33-0.33 Hi:32 Me:29 Lo:26 Hi:38 Me:36 Lo:30 Hi:40 Me:34 Lo:29 Hi:40 Me:35 Lo:30 Sound pressure level dB(A) Hi:33 Me:29 Lo:25 Exterior dimensions mm HxWxD Net weight Air flow External Static pressure Outside air intake Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in) Liquid line:6.35(1/4") Gas line:9.52(3/8") kg CMM Pa 280 x 750 x 635 29 Hi:10 Me:9 Lo:8 100(at 13CMM) 280 x 950 x 635 34 Hi:19 Me:15 Lo:10 100 (at 24CMM) Possible Procure locally wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:12.7(1/2") Liquid line:9.52(3/8") Gas line:15.88(5/8") 280 x 1370 x 740 54 Hi:28 Me:25 Lo:19 Hi:32 Me:26 Lo:20 Hi:35 Me:28 Lo:22 100 (at 36CMM) 100 (at 39CMM) 100 (at 48CMM)
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of indoor unit is 35Pa(22/28/36/45/56/71/90), 60Pa(112/140/160). 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDUM22/28/36/45/56 37dB(A), FDUM71/90 38dB(A), FDUM112 44dB(A), FDUM140 45dB(A), FDUM160 47dB(A). Air flow: FDUM22/28/36/45/56 13CMM, FDUM71/90 24CMM, FDUM112 36CMM, FDUM140 39CMM, FDUM160 48CMM.
48
Dimensions
All measurements in mm.
FDUM71KXE6F, 90KXE6F
49
R410A
RC-EX1A Wireless
RC-E5
RCH-E3
RCN-KIT3-E
(2) Regarding pipe length (150m or more is required) and temperature condition (the lowest is 10C) in the cooling operation etc. , please refer to our technical manual.
Contents 1 2+3
Specifications
Item Model FDUT15KXE6F-E Nominal cooling capacity kW 1.5 Nominal heating capacity kW 1.7 Power source Cooling 0.06-0.06/0.06 Power consumption Heating kW 0.06-0.06/0.06 Sound pressure level 1 dB(A) Hi:28 Me:26 Lo:22 Sound pressure level 2 dB(A) Hi:32 Me:29 Lo:25 Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM External Static pressure Pa Outside air intake Suction guard(Air filter) Remote control(option) Installation data Refrigerant piping size mm(in) Hi:6 Me:5 Lo:4
3 Filter
FDUT22KXE6F-E
2.2 2.5
FDUT28KXE6F-E
2.8 3.2
FDUT36KXE6F-E
3.6 4.0 1 Phase 220-240V, 50Hz
FDUT45KXE6F-E
4.5 5.0
FDUT56KXE6F-E
5.6 6.0
FDUT71KXE6F-E
7.1 8.0 0.08-0.08 0.07-0.07 Hi:35 Me:31 Lo:28 Hi:41 Me:37 Lo:32 220x1150x565 31 Hi:16 Me:13 Lo:9.5
0.07-0.07 0.07-0.07 Hi:28 Me:26 Lo:22 Hi:32 Me:29 Lo:26 200x750x500 21 Hi:7.5 Me:6 Lo:5 Standard:10, Max:35
0.08-0.08 0.08-0.08 Hi:34 Me:32 Lo:28 Hi:35 Me:33 Lo:30 Hi:36 Me:33 Lo:27 Hi:38 Me:33 Lo:29 200x950x500
Not possible Procure locally wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:9.52(3/8") Liquid line:6.35(1/4") Gas line:12.7(1/2") Liquid line:9.52(3/8") Gas line:15.88(5/8")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. External static pressure of indoor unit is 10Pa. 2. The data of nominal cooling and heating capacity and sound pressure level are measured with 10Pa of external static pressure. 3. The sound level indicates the value of rear-intake type with duct in anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 4. Sound pressure levels are values when 2m supply duct and 1m return duct are connected. 1 : Mike position is 1.5m below unit, 2 : Mike position is 1m in front and 1m below the air supply duct.
50
Dimensions
All measurements in mm.
FDUT45KXE6F-E, 56KXE6F-E
FDUT71KXE6F-E
51
R410A
RC-EX1A Wireless
RC-E5 RCH-E3
UH-DU-E RCN-KIT3-E
Our leading high technology has realized the best solution for air conditioning in hotels with compact and thin size units and high energy efficiency. In addition, weight is only 20kg.
The lowest sound level in the industry can ensure comfortable stay and rest in hotels.
257 mm
530m
Installation Flexibility
Control box and drain piping can be installed on both side of the unit and air intake to the unit is available from bottom or back side. Our highest technology can satisfy diverse installation requirements.
Control box
RCH-E3
(option)
Drain piping
Specifications
Item Model Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions HxWxD mm Net weight kg Air flow CMM External static pressure Pa Outside air intake Air filter, Q'ty Remote control(option) Installation data mm(in) Refrigerant piping size
FDUH22KXE6F
2.2 2.5
FDUH28KXE6F
2.8 3.2 1 Phase 220-240V, 50Hz 0.05-0.07 0.05-0.07 HI: 33 Me: 30 Lo: 27 257x570x530 22 HI: 7 Me: 6.5 Lo: 6 30 Not possible Procure locally wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:9.52(3/8")
FDUH36KXE6F
3.6 4.0
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDUH22/28/36 39dB(A). Air flow: FDUH22/28/36 8.5CMM.
52
Dimensions
All measurements in mm.
30.8 32.5 83.3 53
Symbol A B C1,C2 D E F Model Gas piping Liquid piping Drain piping Hole for wiring Suspension bolts Inspection hole Content FDUH22KXE6F,28KXE6F 9.52 (3/8") (Flare) 6.35 (1/4") (Flare) VP20(I.D.20, O.D.26) Note (2) 30 (M10) (635X890) Note (3) FDUH36KXE6F 12.7 (1/2") (Flare) (Duct dimension)
12-4
Holes for tapping screws
32 27.6
150
150 494
(Duct dimension)
150
32 27.6
30.8
145.6
Air outlet
32.5
100 145
255.8 21 40
66 95.3
C1 A B
30.8 66
F
610
156.8
488
530
62.1
C2
(D)
68
549.2
12-4
Holes for tapping screws
21
188.5 148.5
38.2
Air inlet
32 27.5
150
150
32 27.5
G
Bottom plate (Able to be located on the back side)
View G
In case of Bottom air intake
50.5
12-4
Holes for tapping screws
30 28.3
37.6
160 200
30
30
28.5
Air inlet
198.2
160
View G
(After bottom plate is replaced to back side)
30
Air inlet
E
Notes ( 1 ) The model name label is attached on the fan case inside the air return grille. ( 2 ) Prepare the connecting socket (VP20) on site. (As for drain piping, it is possible to choose C1 or C2) ( 3 ) When control box is located on the reverse side, Installation space should be modified to new location. ( 4 ) Contorl box and Drain hose piece are able to be relocated on the reverse side.
150
150
150
18.2
537.6
70
15
53
R410A
RC-EX1A Wireless
RC-E5
RCH-E3
Innovative Design
Installation Workability
New FDK models adopt the air flow design that's proven to minimise resistance in a CFD analysis to achieve uniform air conditioning to the furthest corners of the room.
259
The new slimmer design allows easy & neat installation even in tight spaces.
Fast
Slow
Improved Maintainability
Selection of flap position is possible. A flap can be set at different angles. *RCH-E3 is not applicable to the Flap control system.
Also included is a new easy clean mechanism where the front panel is opened/closed simply from the bottom to easily access the detachable filters.
Upper position Movable range Lower position
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure Cooling dB(A) level Heating Exterior dimensions mm HxWxD Net weight kg Air flow CMM Outside air intake Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in) 12 Hi:8 Me:7 Lo:6
FDK22KXE6F
2.2 2.5
FDK28KXE6F
2.8 3.2 0.05 0.04
FDK36KXE6F
FDK45KXE6F
FDK56KXE6F
5.6 6.3 0.05 0.05
FDK71KXE6F
7.1 8.0 0.09 0.09 Hi:47 Me:43 Lo:39 Hi:47 Me:43 Lo:39 318 x 1098 x 248 15.5 Hi:21 Me:18 Lo:15
12.5 13 Hi:10 Me:9 Lo:7 Hi:11 Me:9 Lo:7 Hi:14 Me:12 Lo:10 Not possible Polypropylene net x2 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-K-E (for FDK22~56), RCN-K71-E (for FDK71) Liquid line:6.35(1/4") Gas line:12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDK22/28 38dB(A), FDK36 48dB(A)(Cooling)&42dB(A)(Heating), FDK45 48dB(A)(Cooling)&43dB(A)(Heating), FDK56 48dB(A)(Cooling)&47dB(A)(Heating), FDK71 48dB(A). Air flow: FDK22/28 11CMM, FDK36/45 15CMM, FDK56 16CMM, FDK71 24CMM.
54
Dimensions
All measurements in mm.
FDK71KXE6F
55
R410A
RCH-E3
RCN-E-E
Upper position
210mm
Movable range Lower position
Slim and sleek design starting at just 28kgs in weight means quick, easy & neat installation.
Installation Workability
Up
Rear Right
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow CMM Outside air intake Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in)
Refrigerant piping can be routed in three directions (rear, up, right) & drain piping in left or right directions, allowing free layout to meet installation conditions.
FDE36KXE6F
3.6 4.0
FDE45KXE6F
4.5 5.0 0.05-0.06 0.05-0.06 Hi:39 Me:38 Lo:36 210 x 1070 x 690 28 Hi:10 Me:9 Lo:7
FDE56KXE6F
FDE71KXE6F
FDE112KXE6F
11.2 12.5 0.14-0.16 0.13-0.15 Hi:44 Me:41 Lo:39
FDE140KXE6F
14.0 16.0 0.16-0.18 0.15-0.17 Hi:46 Me:44 Lo:43
5.6 7.1 6.3 8.0 1 Phase 220-240V, 50Hz 0.10-0.11 0.09-0.10 Hi:41 Me:39 Lo:37 210 x 1320 x 690 37 Hi:16 Me:14 Lo:12 Not possible Pocket Plastic net x2 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-E-E
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. Powerful-Hi can be selected. Sound pressure level: FDE36/45/56 46dB(A), FDE71 50dB(A), FDE112 46dB(A), FDE140 50dB(A). Air flow: FDE36/45/56 11CMM, FDE71 18CMM, FDE112 28CMM, FDE140 32CMM.
56
Dimensions
All measurements in mm.
C1,C2
290 (Suspension bolts pitch) 135 68 5 410
D
145
52
10
40
B A
108
Note) The slope of drain piping inside the unit must take decline of 10mm.
Symbol A B C 1,2 D E F G Content Gas piping Liquid piping Drain piping Hole for suspension bolt Back cutout Top cutout Hole for drain piping (for left back)
53
40
990 1070
40
15 20 100
60
C1,C2
Air supply
12.7 (1/2") (Flare) 6.35 (1/4") (Flare) VP20 (I.D.20) (M10 or M8) PE cover Plate cover (Knock out)
173
210
215
53 109
27
27
31
20
12
175
19
308
100 or more
300 or more
F
150 or more 5 or more
Right side cutout
G E
Note(1)The model name label is attached on the fan casing inside the air return grille.
C2
76
A C1
75 110 135
Obstacle Make a space of 4000 or more between the units when installing more than one.
C1,C2
FDE71KXE6F
24 1272 (Suspension bolts pitch) 24
D
145 52
40
B A
108
Note)The slope of drain piping inside the unit must take decline of 10mm.
Symbol A B C 1,2 D E F G Content Gas piping Liquid piping Drain piping Hole for suspension bolt Back cutout Top cutout Hole for drain piping(for left back) 15.88 (5/8") (Flare) 9.52 (3/8") (Flare) VP20 (I.D.20) (M10 or M8) PE cover Plate cover (Knock out)
10
53 7
Position of top cutout and back cutout
173
210
215
53 109
27
40
1240 1320
40
15 20 100
60
Air supply
C ,C
27
31
20
12
175
19
308
100 or more
300 or more
F
150 or more 5 or more
Right side cutout
G E
Note(1)The model name label is attached on the fan casing inside the air return grille.
C2
76
A C1
75 110 135
Obstacle
Make a space of 4500 or more between the units when installing more than one.
FDE112KXE6F, 140KXE6F
24 1572 (Suspension bolts pitch) 24
C1,C2
290 (Suspension bolts pitch) 135 68 5 410
D
145 52
250
255
40
B A
108
Note) The slope of drain piping inside the unit must take decline of 10mm.
10
53
40
1540 1620
40
15 20 100
60
Air supply
C ,C
Symbol A B C1,2 D E F G
Content Gas piping Liquid piping Drain piping Hole for suspension bolt Back cutout Top cutout Hole for drain piping (for left back)
15.88 (5/8") (Flare) 9.52 (3/8") (Flare) VP20 (I.D.20) (M10 or M8) PE cover Plate cover (Knock out)
173
53 109
27
27
31
20
300 or more 308 100 or more
0 12
175
19
F
150 or more 5 or more Right side cutout
G E
Note(1)The model name label is attached on the fan casing inside the air return grille.
C2
76
A C1
75 110 135
Obstacle
Make a space of 5000 or more between the units when installing more than one.
57
R410A
RC-EX1A
Sophisticated Design
Quiet Operation
With classy semi flat front panel in chic white, the new series fit in various kinds of rooms and create relaxing atmosphere. Choice of wall hanging, floor standing or behind gallery installation is available.
Flap control system
Thanks to optimum balance of air outlet direction and sufficient air flow volume, the sound level has been minimized. The level of FDFW28KXE6F in the cooling lo mode is 30dB(A) only.
Convenient to use operation
Simultaneous lower and upper air outlets or upper outlet can be selected by air flow direction button. Further control can be arranged by a remote control.
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in) 19 Hi:9 Me:8 Lo:7 Polypropylene net x1 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-FW-E Liquid line:6.35(1/4") Gas line:9.52(3/8") Liquid line:6.35(1/4") Gas line:12.7(1/2")
FDFW28KXE6F
2.8 3.2 0.02-0.02 0.02-0.02 Hi:36 Me:34 Lo:30
FDFW45KXE6F
4.5 5.0 1 Phase 220-240V, 50Hz 0.02-0.02 0.02-0.02 Hi:38 Me:36 Lo:33 600x860x238 20
FDFW56KXE6F
5.6 6.3 0.03-0.03 0.03-0.03 Hi:44 Me:37 Lo:33
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
58
Dimensions
All measurements in mm.
59
R410A
Floor Standing (with casing) FDFL Floor Standing (without casing) FDFU
Model No. FDFL71KXE6F FDFU28KXE6F FDFU45KXE6F FDFU56KXE6F FDFU71KXE6F
FDFL
RC-EX1A
RC-E5 RCH-E3
RCN-KIT3-E
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMM Air filter, Qty Remote control(option) Installation data Refrigerant piping size mm(in)
FDFL71KXE6F
7.1 8.0 0.09-0.10 0.09-0.10 Hi:43 Me:41 Lo:40 630x1481x225 40 Hi:18 Me:15 Lo:12
FDFU28KXE6F
2.8 3.2
FDFU45KXE6F
4.5 5.0 1 Phase 220-240V, 50Hz 0.09-0.10 0.09-0.10 630x1077x225 25
FDFU56KXE6F
5.6 6.3
FDFU71KXE6F
7.1 8.0
Hi:14 Me:12 Lo:10 Polypropylene net x1 (Washable) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Liquid line:6.35(1/4") Gas line:12.7(1/2")
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
60
Dimensions
All measurements in mm.
FDFL
FDFU
Dimension Table
model FDFU28KXE6F, 45KXE6F, 56KXE6F FDFU71KXE6F a 786 1071 b 810 1095 c 722 1007 d 750 1035
Unit:mm
e 806 1091
61
R410A
RC-EX1A
RC-E5 RCH-E3
Wireless
RCN-KIT3-E
Outdoor Air processing unit can be connected in a KX6 system as one of indoor unit series and can create fresh and comfortable air supply together from our high advanced technology.
indoor unit office outside air supply corridor refresh room, rest room
Compact design
Compact design at just 360mm in height, high static pressure of 200Pa and the industry's lowest noise level can meet various kind of installation location for office, refresh room, restroom and kitchen of restaurant etc.
exhaust air
outdoor air
(1) This unit is the specific unit for processing the outdoor air temperature closer to the room temperature. For conditioning the room temperature a dedicated air-conditioner is required additionally. (2) This unit monitors the outdoor air temperature and controls thermostat ON/OFF at the setting temperature by the remote controller, which indicates the outdoor air temperature for controlling thermostat ON/OFF. When thermostat is turned OFF, the operation is changed to the fan mode so that unprocessed outdoor air will be blown into the room directly. Therefore place the air outlet port or orient the air outlet direction not to blow air directly to persons in the room, especially in the small room such as a restroom and/or sanitary hot water supplying room. (3) It is strictly prohibited to monitor the room temperature by switching to the thermistor at remote controller side and/or the optional remote thermistor. Otherwise dew formation at air outlet port and/or dew dripping may occur during cooling operation due to the lower outdoor air temperature. Therefore keep the remote controller of this unit in place closer to the administrator so as not to be touched it freely by the end user. (4) Dehumidifying operation with this unit is prohibited. (5) When handing over this unit to the end user, make sure to explain sufficiently about the foregoing cautions, the installation place and usage of remote control for this unit and the location of the air outlet.
62
Combination
The total capacity of FDU-F is 50~100% of outdoor capacity
The total capacity of FDU-F and dedicated air-conditioners is 50~100% of outdoor capacity and max quantity of FDU-F should be below 30% of outdoor unit capacity.
[A]
10HP FDU850FKXE6F FDU850FKXE6F (5HP) (5HP)
[B]
18HP
FDU850FKXE6F (5HP)
6HP
6HP
Outside
Air Supply
Exhaust Air
SAF
Outside
63
R410A
Specifications
Model Item Nominal cooling capacity kW Nominal heating capacity kW Power source Cooling Power consumption Heating kW Sound pressure level dB(A) Exterior dimension mm HxWxD Net weight kg CMM CMH External static pressure Pa Air filter, Q'ty Remote control(option) Air flow (Standard) Installation data mm Refrigerating piping size (in)
FDU500FKXE6F
9.0 4.2 0.11 0.11 38 360x820x830 48 8.5 510
FDU850FKXE6F
14.0 7.0
FDU1300FKXE6F
22.4 10.9
FDU1800FKXE6F
28.0 14.8 0.31 0.31 46 360x1570x830
1 Phase 220-240V, 50Hz 0.16 0.16 41 360x1200x830 62 14 840 82 22 1320 0.27 0.27 43
84 30 1800
200 Procure locally wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E Liquid line:9.52(3/8") Gas line:19.05(3/4")
1. The data are measured at 33CDB 28CWB (68%RH) during cooling and 0CDB-2.9CWB (50%RH) during heating (no frost). External static pressure of indoor unit with optional fan controlling kit "U-FCRB" is 100Pa. 2. Temperature range of outdoor air must be 20~40CDB (32CWB) during cooling and -10~24CDB during heating. 3. Operation sound is measured in an anechoic room based on JIS standard. In case of actual room installation, it usually becomes higher than the displayed value due to the surrounding noise and echo. 4. The total connection capacity of the other standard air conditioning units and the outdoor air processing units must be from 50% to 100% (the total includes the outdoor air processing unit). The connection capacity of the outdoor air processing unit must not exceed 30% of the capacity of the outdoor unit. 5. Single outdoor air processing unit can be used alone. The connection capacity of the outdoor air processing unit must be from 50% to 100% of the total capacity of the outdoor unit. 6. Single outdoor air processing unit can be used alone. Maximum number of outdoor air processing units that can be connected to the outdoor unit is 2units. 7. Values of sound pressure level become increased 5dB(A), when external static pressure is 200Pa (factory setting). 8. Values of air flow volume are those at external static pressure 200Pa (factory setting).
Dimensions
All measurements in mm.
FDU500FKXE6F
Control box Duct connection port for outdoor air inlet Above
12-M5 screw
12-M5 screw
Below
Installation space
Installation space
or more
or more
or more
Plan view
or more
Front view
Symbol
Content
Slab Ceiling Service space (Service from side) or more Piping space (Service from below) (Service from side and below)
64
or more
Gas piping Liquid piping Drain piping connection Power supply wiring connection Suspension bolt Inspection Opening Inspection Opening
FDU850FKXE6F
Control box
16-M5 screw
Above
12-M5 screw
Below
or more
or more
or more
FDU1300FKXE6F, FDU1800FKXE6F
or more
Service space
Gas piping Liquid piping Drain piping connection Power supply wiring connection Suspension bolt Inspection Opening Inspection Opening
Control box 20-M5 screw Duct connection port for outdoor air inlet 20-M5 screw Above Port for air outlet
Below
(Inner size of duct flange) Installation space or more or more Plan view or more Installation space Slab
Symbol
Content
Gas piping Liquid piping Drain piping connection Power supply wiring connection Suspension bolt Inspection Opening Inspection Opening
65
R410A
Capturing this waste energy, means the heating/ cooling requirements of the building are reduced, so smaller size plant can be selected, savings can be made in long term energy consumption, and carbon emissions are reduced. The inclusion of the SAF energy recovery ventilation units in the building design, will reduce the total amount of carbon emissions.
EA (Exhaust Air)
RA (Room Air)
OA (Outside Air)
SA (Supply Air)
Specifications
Item Model Power source Exterior dimensions mm Height x Width x Depth Exterior appearance Power input W Running current A Enthalpy Cooling exchange UHi efficiency Heating Temperature exchange efficiency Enthalpy Cooling exchange Hi efficiency Heating % Temperature exchange efficiency Enthalpy Cooling exchange Lo efficiency Heating Temperature exchange efficiency Motor & Qty kW Air handling equipment Fan type & Qty UHi Air flow Hi m3/h Lo UHi Available static pressure Hi Pa Lo Remote control Out take intake air Air filter Exhaust air
SAF250E4
270x882x599 99-114 0.46-0.48 63 70 63 70 66 73 77 0.02x2 250 250 170 90 80 37
SAF350E4
270x882x804 124-137 0.59-0.60 66 69 66 69 69 71 77 0.044x2 350 350 280 95 65 42
SAF500E4
1 Phase 220-240V, 50Hz 270x962x904 Galvanised steel sheet 169-188 0.79-0.81 62 67 75 62 67 75 77 67 75 0.062x2 Sirocco fan x 2 500 500 370 105 70 38 Standard equipment Protection for element (Washable) PS400
SAF800E4
388x1322x884 309-359 1.48-1.50 65 71 65 71 68 74 76 0.117x2 800 800 650 140 110 70
SAF1000E4
388x1322x1135 360-399 1.85-1.93
Capacity
66
Dimensions
All measurements in mm.
SAF250E4,350E4,500E4
SAF800E4
SAF1000E4
Installation reference
Pipe Hood Outside Intake Duct Ceiling Suspension Bolt Supply Air Duct
(Supply Air)
SA
OA
(Room Air)
RA
EA
Dimension table
NO.
1 2 3 4 5 6 7 8 9 10 11
Unit:mm
Name
Frame Adaptor Electrical Equipment Box Inspection Cover Fan Motor Heat Exchange Element Filter Damper Damper Motor Ceiling Suspension Fixture
Quantity
1 4 1 1 2 2 2 2 1 1 4
Material
Zinc-plated steel ABS Resin Zinc-plated steel ABS Resin
Remarks
Model
SAF250E4 SAF350E4 SAF500E4
a
142 162 202
b
810 810 890
c
599 804 904
d
315 480 500
e
655 860 960
Model
SAF250E4 SAF350E4 SAF500E4
f
219 219 246
g
164 164 210
h
144 144 194
i
882 882 962
j
95 95 107
Flame Retardant Paper + Plastic Air to air Heat Exchanger Non-woven Cloth Collection Efficiency Gravimetric Method 82%
Zinc-plated Steel
Note(1) An inspection port is needed for cleaning the heat exchanger and filter 1 or 2 times a year. 67
R410A
DXA-DU-E
RC-E5
RCH-E3
Wireless
RCN-KIT3-E
SAF-DX is a heating or cooling coil incorporating MHI KX6 series controls. It can be used in combination with our SAF series of total heat exchanger. Combination of SAF-DX together with other KX6 indoor units is possible. The capacity code index of each model is shown below and must be used when
making the system selection. Total capacity code index must be within 100% of outdoor unit capacity code index.
Remote control option is the same as with other KX6 indoor units (see above). Connection to all superlink controls is also possible. Optional condensate lift mechanism is also available (600mm height). Return air temp. control or supply air temp. control can be selectable.
RA
(Outside Air)
(Room Air)
OA
SAF-DX
EA
(Exhaust Air)
SA (Supply Air)
Heating or cooling coil
SAF-DX can provide heating or cooling to the fresh air supplied through a 3rd party air handling unit or total heat exchanger such as our SAF series.
Specifications
Model Item Nominal cooling capacity *1 kW Nominal heating capacity *2 kW Capacity code Power source Cooling Power consumption Heating W Cooling Running A current Heating Exterior dimensions mm HxWxD Net weight kg Air flow (Standard) CMH Internal resistance Pa Remote control(option) Installation data Refrigerant piping size mm(in)
(1) The data are measured at the following conditions. Item Operation Cooling*1 Heating*2 Return/fresh air temperature DB WB 27C 19C 20C Outdoor air temperature DB WB 35C 24C 7C 6C Standards
SAF-DX250E6
2.0 1.8 22
SAF-DX350E6
2.8 2.2 28
SAF-DX500E6
3.6 2.8 36 1 Phase 220-240V, 50Hz 7.2 7.2 0.05 0.05 315 x 537 x 422
SAF-DX800E6
5.6 4.5 56
SAF-DX1000E6
6.3 5.6 71
315 x 452 x 422 12.3 250 38 Liquid line:6.35(1/4") Gas line:9.52(3/8") 350
13.6 500 66 wired: RC-E5, RCH-E3 wireless: RCN-KIT3-E Liquid line:6.35(1/4") Gas line:12.7(1/2")
ISO-T1
(2) This air-conditioner is manufactured and tested in conformity with ISO-T1 "UNITARY AIR-CONDITIONERS".
68
Dimensions
All measurements in mm.
SAF-DX250E6,350E6
SAF-DX500E6
SAF-DX800E6
SAF-DX1000E6
69
R410A
Weekly timer function as standard RC-E5 provides (as a standard feature) a weekly timer, which allows one-week operation schedules to be registered. A user can specify up to four times a day to start/stop the air conditioner. (Temperature setting is also possible with the timer). Timer operation
AUTO restart
This function allows starting the air conditioner automatically when power supply is restored after power failure or by turning on the power switch.
*RCH-E3 is not applicable to the Individual flap control system and the Flap control system. *When RCH-E3 is used, the fan speed setting can only be set to 3 speed settings (Hi-Me-Lo).
RCN-T-36W-E, RCN-TC-24W-ER
RCN-TW-E
RCN-TS-E
RCN-K-E, RCN-K71-E
RCN-E-E
RCN-FW-E
RCN-KIT3-E
wireless remote control is not applicable to the Individual flap control system and the Flap control system. *The *When the wireless remote control is used, the fan speed setting can only be set to 3 speed settings (Hi-Me-Lo).
70
<Control System>
SUPERLINKMHI has now combined simplicity of installation with our highly sophisticated Superlink- control system, to offer building owners and occupiers a comprehensive control and management system, while providing complete commissioning and service maintenance assistance for installers and service engineers. The Superlink- network utilises two wire, non-polar cable - for further details of wiring. Superlink- is an advanced high speed data transmission system that can connect up to 128 indoor units and 32 outdoor units as a network. MHI offers a wide range of control options for the Superlink- network to suit any application large or small, as well as connection to new or existing building management systems. Individual MHI split systems can also be integrated on to the Superlink- network using SC-ADNA-E.
Capable of control and monitoring up to 64 indoor units. All operational functions, plus enable/disable connected remote control. KX6 Outdoor units
3-core + earth cable for connecting indoor and outdoor units SRK/SRF-ZJXseries SC-BIKN-E
One-to-one
Wireless
71
R410A
<Central Control>
SC-SL1N-E
Start/stop control of up to 16 indoor units either individually or collectively. Simple centralised control. 1. The SC-SL1N-E is connected to the Superlinknetwork via 2-core, non-polar wires (AB connection). 2. It will monitor and control the start/stop function of up to 16 units, with the sixteen operation button. 3. The unit or group numbers in operation or in need of service are displayed with an LED. 4. Collective start/stop is also available through the simultaneous on/off button. 5. Up to 12 SC-SL1N-E units can be connected to a Superlink- network (consisting of up to 128 indoor units). 6. If a power failure occurs, the SC-SL1N-E will resume the operation of the system according to a stored operation condition, once power is restored.
SL1N-E
SC-SL2NA-E
Central control of up to 64 indoor units including weekly timer function as standard. 1. The SC-SL2NA-E is connected to the Superlink- network via 2-core, non-polar wires (AB connection). 2. It will monitor and control the start/stop function of up to16 units, or 16 groups of units, with the sixteen operation buttons. 3. It also monitors and controls the following functions for individual units, groups of units or the complete network: operation mode, set point temperature, return air temperature, louvre position, error code. Air flow and center lock function. 4. The unit or group numbers in operation or in need of service are displayed with an LCD. 5. Collective start/stop is also available through the simultaneous on/off button. 6. If a power failure occurs, the SC-SL2NA-E will resume the operation of the system according to a stored operation condition, once power is restored. 7. The SC-SL2NA-E can be connected to an external timer to facilitate timed on/off cycles. 8. The number of units connected to one network are detailed on the table below.
More than one unit (up to 16) can be controlled for individual or collective start/stop operation and indication of unit statuses such as in operation or in need of service. Outer dimensions: H120 x W120 x D15+62*mm. 62* is the measurement including the part contained in a recess.
SL1N-E
An SC-SL2NA-E performs the start/stop control, monitoring and mode setting of up to 64 units. It is a high quality air conditioner control system that allows up to 64 indoor units to be freely grouped into 1 to 16 groups. It allows not only the start/stop control but also the monitoring, display of operation statuses such as in operation or in need of service and mode setting such as switching of operation modes of connected units collectively, by group or individually. Outer dimensions: H120 x W215 x D25+35*mm. 35* is the measurement including the part contained in a recess.
( 2) Number of units in combination of SC-WGWNA-A/B, SC-BGWNA-A/B, SC-LGWNA-A, SC-SL3NA-AE/BE, SC-SL2NA-E and SC-SL1N-E
Connectable number of controls in one superlinkSC-WGWNA-A/B or SC-BGWNA-A/B or SC-LGWNA-A 1 SC-SL1N-E 0-4 SC-SL3NA-E-AE/BE 0-1
Regarding previous Superlink, refer to Technical Manual '06 SC-T-111, '08 SC-T-119.
Regarding previous Superlink, refer to Technical Manual '06 SC-T-111, '08 SC-T-119.
72
SC-SL3NA-AE/BE
MHI introduces the full colour touch screen central control SC-SL3NAAE/BE, with 7 inch interactive LCD display. Offers control, monitoring, scheduling and service/maintenance functions for up to 128 indoor units. Indoor units can be controlled, scheduled, monitored and interrogated either individually, as groups or as blocks of groups with the following functions:
Control
Run/Stop Mode (cool/heat/fan) Set temperature Operation permitted/prohibited Fan speeds Air direction Filter reset Filter sign Maintenance (1, 2 or back-up) Breakdown Demand control Emergency stop Power failure recovery control
Monitoring
Operating state Mode Set temperature Room temperature Operation enabled Fan speed Air direction
Scheduling
Yearly schedule Today's schedule Special day schedule
Administration/Service
Block definition Group definition Unit definition Time and date setting Alarm history Energy consumption calculation period Energy consumption cumulative operation time
Collective stop signal input
Applicable products Ventilation fan, Air purifier By using SC-GIFN-E together with central control such as SC-SL1N-E, SC-SL2NA-E and SC-SL3NA-AE/BE, you can start-stop, operate & monitor the operation of applicable products.
Address setting switch Set address number will be the address for SC-SL1N-E, SC-SL2NA-E, SC-SL3NA-AE/BE
NEW
Printed board
Terminal block
51X 52 52R
1 2 3 4 5 6 7 8 A B
Net work communication line AC220-240V To A & B terminal block on SC-SL1N-E, SC-SL2NA-E, SC-SL3NA-AE/BE
40
SLA3R-BX
Model
SC-SL3NA-AE/SC-SL3NA-BE
0 ~ 40oC 1 Phase 100-240V 50/60Hz 18W 162mm x 240mm x 108mm 2.0kg up to 128 units Colour LCD, 7 inches wide 3 systems 8-point pulse width 100ms or more 1 point non-voltage a contact input continuous input (closed, forced stop) 1 point non-voltage a contact input continuous input (closed, demand control) 1 point maximum rated current 40mA, 24 V During full stop; Open. If even one unit is operating; Closed 1 point maximum rated current 40mA, 24 V Normal; closed. If even one unit is abnormal; Open
SC-SL3NA-BE gives outputs as electric power consumption kW data -each indoor unit, each group, each SUPERLINK- system and each power pulse system- and uses USB memory. The data can be edited by using the software that comes with the unit.
SC-SL3NA-BE
* The receiving side power supply is DC 12V (10mA). The air conditioning charges calculations of this unit are based on OIML, the international standard. * In case embodying in a wall, please be sure to special box SLA3R-BX (option).
73
R410A
Control and monitoring of up to 96 cells (some cells can have two or more indoor units and total number of indoor units can be up to 128 units) centralised to a network PC using the Superlink- web gateway. Simple installation is assured with no special software requirements, operation is via Internet Explorer. A low power embedded CPU and compact flash ROM ensure a large storage capacity with high reliability (no moving parts such as a PC fan, etc). An IP address filter function combined with three-level user authentication check also ensures security.
SUPERLINK- No. 1 system
48 cells HUB Ethernet 10 BASE-T/ 100BASE-TX pulse 48 cells SC-ADNA-E 64 units
Additional engineering service cost etc. is required. Please consult your dealer when using this central control.
Internet Explorer
Cell
PC requirements: Windows XP or Windows Vista or Windows 7. Monitor resolution 1024 x 768. Web browser requirements: Internet Explorer 6.0 or 7.0.
Production by order
48 cells SC-ADNA-E
Cell
Additional engineering service cost etc. is required. In case of SC-BGWNA-B, communication test by qualified person regarding electric cost calculation function is required before commissioning. Please consult your dealer when using this gateway.
Production by order
SC-LGWNA-A is an interface device that converts MHIs Superlink- communication data to LonWorks code. Control and monitoring functions of the a/c system for up to 96 indoor units can be integrated to a central control point via the building management system network.
SUPERLINK- No. 2 system LonWorks network (FTT-10) Network for lighting Emergency sensor network SC-ADNA-E 48 units
Additional engineering service cost etc. is required. Please consult your dealer when using this gateway.
74
Mechanical chamber
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
75
(Max 48 indoor units / Superlink I & II) (Max 128 indoor units / Superlink II)
MH-AC-KNX-128
Alams
INTEGRATED GATEWAY Bidirectional: Supervision and Control Robust and reliable hardware Direct connection to KNX TP-1 BUS Independent management of communications Power supply: 230 VAC 50/60Hz Wall mounting case
MH-AC-MBS-48
MH-AC-MBS-128
MODBUS
INTEGRATED GATEWAY Bidirectional: Supervision and Control Robust and reliable hardware Modbus TCP or Modbus RTU RS-485/RS-232 Independent management of communications Power supply: 230 VAC 50/60Hz Wall mounting case
76
Integration of MHI PAC in your KNX installation by Remote control line MH-RC-KNX-1i
Example : Device as Master Example : Device as Slave
TOUCH SCREEN
TOUCH SCREEN
Windows blinds
Energy management
Windows blinds
Energy management
RC-E5
Alams
Lighting HVAC
Alams
Lighting HVAC
Integration of MHI PAC in your Modbus installation by Remote control line MH-RC-MBS-1
Example : Device as Master
MODBUS
RC-E5
Integration of MHI PAC in your EnOcean installation by Remote control line MH-RC-ENO-1i/1iC
Example : Device as Master Example : Device as Slave
RC-E5
Protocol : EnOcean 1i : 868MHz@EU 1iC : 315MHz@USA, ASIA Dimension : 100 x 70 x 28 mm External Power supply : no need
URL email tel http://www.intesis.com info@intesis.com +34 938047 134
77
R410A
Production by order
Sea breeze
Sea
Model No. FDCS335KXE6-K FDCS400KXE6 FDCS450KXE6 FDCS504KXE6 FDCS560KXE6 FDCS560KXE6-K FDCS615KXE6 FDCS680KXE6
Nominal Cooling Capacity 33.5kW 40.0kW 45.0kW 50.4kW 56.0kW 56.0kW 61.5kW 68.0kW
Combination systems:26~48hp (73.5kW~136.0kW) are the same as that of the standard KX6 series shown on previous pages. Specifications and Dimensions are the same as that of the standard KX6 series shown on previous pages. Non-CE Marking models.
For outside sheet metals, Cation electrodeposition coating is used for undercoat plus polyester powder coating or acrylic backed coating for top coat and corrosion protection is applied for heat exchanger, welded parts, fan guard, fin guard and other major parts. Preventing corrosion by salt damage or sulfurous acid gas has made service life of KX6 series longer while its exterior appearance has been greatly improved. Durability of KX6 series for anticorrosion is about two times that of standard outdoor units under the same conditions.
78
4~12HP
Exterior panel undercoat: Cation electrodeposition coating topcoat: polyester powder coating or acrylic baked coating undercoat: Cation electrodeposition coating topcoat: polyester powder coating or acrylic baked coating
12.20*.14~24HP
undercoat: Cation electrodeposition coating topcoat: acrylic baked coating undercoat: Cation electrodeposition coating topcoat: acrylic baked coating undercoat: Cation electrodeposition coating topcoat: acrylic baked coating
Base plate
Drain pan Fan motor Fan motor base Fin Heat exchanger pipe Side plate Compressor Accumulator Receiver Control box application of anticorrosion compound 4~6HP 8~12HP application of anticorrosion compound
application of anticorrosion compound application of anticorrosion compound Precoated Aluminum Blue Fins in high anticorrosion specification application of anticorrosion compound application of anticorrosion compound application of anticorrosion compound application of anticorrosion compound application of anticorrosion compound galvanized steel sheet + undercoat: Cation electrodeposition coating + topcoat: acrylic baked finish
Precoated Aluminum Blue Fins in high anticorrosion specification application of anticorrosion compound application of anticorrosion compound application of anticorrosion compound application of anticorrosion compound application of anticorrosion compound 4~6HP 8~12HP 4~6HP 8~12HP 4~6HP 8~12HP application of anticorrosion compound zinc coating + chromate treatment + fluorine coating zinc coating + chromate treatment + fluorine coating application of anticorrosion compound application of anticorrosion compound
Baffle plate
Service valve bracket Screw tap for exterior panel Screw tap for inside of exterior panel
galvanized steel sheet + undercoat: Cation electrodeposition coating + topcoat: acrylic baking finish zinc coating + chromate treatment + fluorine coating zinc coating + chromate treatment + fluorine coating
Corrosion protection treatment complies with regulation of The Japan Refrigeration and Air Conditioning Industry Association (JRA9002)
Caution
Even if the outdoor unit is protected with the anti-salt damage treatment, it cannot be perfectly free from rusting. The following points should be kept in mind during installation and maintenance of the outdoor units.
Installation
(1) When installing the outdoor unit close to the coastal area, provide a windbreak to protect it from direct sea breeze and salt water splash. (2) Select a well-drained place to install. (3) If any scratch or damages occurred on the outdoor unit during installation, repair it carefully.
Maintenance
(1) Clean salt grains on the outdoor unit with fresh water periodically. (2) Apply rust preventive at regular intervals for maintenance depending on the conditions at the installation place (consulting with the withstanding capacity). (3) Confirm reset of screw tap after maintenance, if missing it may cause corrosion occurred from the hole of screw tap. (4) During prolonged non operation periods, protect the unit with covering.
79
R410A
Outdoor units High Head series (100m) cooling only 14~48hp (40.0~136.0kW)
Model No. FDCH335CKXE6G-K FDCH400CKXE6G FDCH450CKXE6G FDCH504CKXE6G FDCH560CKXE6G FDCH560CKXE6G-K FDCH615CKXE6G FDCH680CKXE6G Nominal Cooling Capacity 33.5 kW 40.0 kW 45.0 kW 50.4 kW 56.0 kW 56.0 kW 61.5 kW 68.0 kW
Production by order
FDCH335CKXE6G-K & FDCH560CKXE6G-K are only used for combining with other models.
Model No. FDCH735CKXE6G (FDCH335-K+FDCH400) FDCH800CKXE6G (FDCH400x2) FDCH850CKXE6G (FDCH400+FDCH450) FDCH900CKXE6G (FDCH450x2) FDCH960CKXE6G (FDCH450+FDCH504) FDCH1010CKXE6G (FDCH504x2) FDCH1065CKXE6G (FDCH504+FDCH560) FDCH1130CKXE6G (FDCH560x2) FDCH1180CKXE6G (FDCH560-K+FDCH615) FDCH1235CKXE6G (FDCH615x2) FDCH1300CKXE6G (FDCH615+FDCH680) FDCH1360CKXE6G (FDCH680x2)
Nominal Cooling Capacity 73.5 kW 80.0 kW 85.0 kW 90.0 kW 96.0 kW 101.0 kW 106.5 kW 113.0 kW 118.0 kW 123.5 kW 130.0 kW 136.0 kW
FDCH504~680CKXE6G
Max: 10m
Outdoor unit
Range of operation
50
+43C
40
To the first branch: max 130m From the first branch to the furthest indoor unit: 90m *1
Max: 5m
Indoor unit
50~100m
*2
30
Indoor unit
Indoor unit
20
Cooling
10
-5C
-10
*2 In case of less than 50m, the High Head models can not be applied.
80
In case Indoor unit is higher than outdoor unit, the High Head models can not be applied.
Specifications
Model FDCH400CKXE6G FDCH450CKXE6G FDCH504CKXE6G FDCH560CKXE6G FDCH615CKXE6G FDCH680CKXE6G 20HP 22HP 24HP 18HP 14HP 16HP 3 Phase 380-415V, 50Hz kW Cooling 56.0 61.5 68.0 50.4 40.0 45.0 A Starting current 8 kW Electrical characteristics Power consumption Cooling 16.79 20.37 24.98 14.73 11.27 12.97 Running current Cooling A 27.4-25.1 33.1-30.3 40.3-36.9 24.1-22.0 18.4-16.9 21.1-19.3 HxWxD Exterior dimensions mm 1690x1350x720 2048x1350x720 Net weight kg 357 319 343 R410A Refrigerant charge kg 11.5 Cooling dB(A) Sound pressure level 63.0 64.5 65.0 61.5 59.5 62.5 12.7(1/2") Liquid line 15.88(5/8") mm(in) Refrigerant piping size Gas line 28.58(1 1/8") 25.4(1") [28.58(1 1/8")] 28.58(1 1/8") 50~200 % Capacity connection 50~160 Number of connectable indoor units 40 44 49 36 40 36 Item Nominal horse power Power source Nominal capacity Item Combination (FDCH) Nominal horse power Power source Nominal capacity Electrical characteristics Exterior dimensions Net weight Refrigerant charge Refrigerant piping size Model
FDCH735CKXE6G
335CKXE6G-K 400CKXE6G 26HP
FDCH800CKXE6G
FDCH850CKXE6G
FDCH900CKXE6G
450CKXE6G 450CKXE6G 32HP 90.0 25.94 42.2-38.6
Cooling Starting current Power consumption Cooling Running current Cooling HxWxD R410A Liquid line Gas line
kW A kW A mm kg kg mm(in) %
Capacity connection Number of connectable indoor units Item Combination (FDCH) Nominal horse power Power source Nominal capacity Electrical characteristics Exterior dimensions Net weight Refrigerant charge Refrigerant piping size
53 Model
400CKXE6G 400CKXE6G 400CKXE6G 450CKXE6G 28HP 30HP 3 Phase 380-415V, 50Hz 80.0 85.0 16 22.54 24.24 36.8-33.8 39.5-36.2 1690x2700x720 319x2 11.5x2 19.05(3/4") 31.8(1 1/4") [34.92(1 3/8")] 50~160 58 61
65
FDCH960CKXE6G
450CKXE6G 504CKXE6G 34HP
FDCH1010CKXE6G
FDCH1065CKXE6G
FDCH1130CKXE6G
560CKXE6G 560CKXE6G 40HP 113.0 33.58 54.8-50.2
Cooling Starting current Power consumption Cooling Running current Cooling HxWxD R410A Liquid line Gas line
kW A kW A mm kg kg mm(in) %
504CKXE6G 504CKXE6G 504CKXE6G 560CKXE6G 36HP 38HP 3 Phase 380-415V, 50Hz 101.0 106.5 16 29.46 31.52 48.2-44.0 51.5-47.1 2048x2700x720 343x2 11.5x2 22.22(7/8") 38.1(1 1/2") 50~130 62
Capacity connection Number of connectable indoor units Item Combination (FDCH) Nominal horse power Power source Nominal capacity Electrical characteristics Exterior dimensions Net weight Refrigerant charge Refrigerant piping size
66
Model
FDCH1180CKXE6G
560CKXE6G-K 615CKXE6G 42HP
FDCH1235CKXE6G
FDCH1300CKXE6G
FDCH1360CKXE6G
680CKXE6G 680CKXE6G 48HP 136.0 49.96 80.6-73.8
Cooling Starting current Power consumption Cooling Running current Cooling HxWxD R410A Liquid line Gas line
kW A kW A mm kg kg mm(in) %
69
615CKXE6G 615CKXE6G 615CKXE6G 680CKXE6G 44HP 46HP 3 Phase 380-415V, 50Hz 123.5 130.0 16 40.74 45.35 66.2-60.6 73.4-67.2 2048x2700x720 357x2 11.5x2 22.22(7/8") 38.1(1 1/2") 50~130 72 76
80
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Piping length is 7.5m. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions. 3. [ ] : Pipe sizes applicable to European installations are shown in parentheses.
81
R410A
Dimensions
All measurements in mm.
594 232
726
85
95 140.5
141
234
75 142.5
58.5
1690 797.8
126.2
720
19
Air intake
148 410
140
342 235
1350
7-segment display inspection port Signal wire terminal block Terminal block for power cable connection 682
K B A C (front)
166 169 211 259 291.6
22
240 295
647
57
174 720
296.7
58.5
F I
I F
19
120
22
250 175
850 1000
250 175
74.5
80.5 71
C (right)
C (rear)
L
44.7
84
D (left)
104.9
90
86.5
D (front)
220 180
550
180 214
Mark A B C D F G H K* L
Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.
Installation example
L1 L2 L3 L4 H1 H2 H3 H4
L2
L3
Dimensions
2
Intake
Wall height H2
Intake
Wall height H3 L4
Intake
Wall height H4 Wall height H1
Service space
Intake
Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination. (For 14,16Hp only)
Installation example
Dimensions
L1
20
Instruction plate
6 86.1
172
95
D (right)
172
80
L3
Wall height H2 Wall height H4
L1
L6 L4
L2
L5
L2 L3 L4 L5 L6 H1 H2 H3 H4
No restrictions No restrictions
82
Dimensions
All measurements in mm.
594 232
726
85
95 140.5
141
234
75 142.5
2048
1155.8
126.2
720
58.5
19
Air intake
148 410
140
342 235
1350
Drain pipe
7-segment display inspection port Signal wire terminal block 175 80 Terminal block for power cable connection 682
K B A C (front)
166 169 211 259 291.6
22
240 295
647
57
174 720
296.7
58.5
F I
I F
19
120
22
250 175
850 1000
250 175
74.5
80.5 71
C (right)
C (rear)
L
44.7
84
D (left)
104.9
90
86.5
D (front)
220 180
550
180 214
Mark A B C D F G H K L
Item Service valve connection (gas side) Service valve connection (liquid line) Refrigerant pipe draw-out port Power cable draw-in port Anchor bolt hole Drain hose hole Drain discharge port Oil-equalising pipe joint Sling holes for haulage or hoisting
For refrigerant piping, please refer to the unit specifications.
Installation example
L1 L2 L3 L4 H1 H2 H3 H4
L2
L3
Dimensions
2
Intake
Wall height H2
Intake
Wall height H3 L4
Intake
Wall height H4 Wall height H1
Service space
Intake
Notes: (1) The unit must be fixed with anchor bolts. (2) Leave a 2m or larger space above the unit. (3) The unit name plate is attached on the lower right corner of the front panel. (4) The ports for refrigerant pipe and power cable penetrations are covered with half-blanks. Please cut off a half-blank with nippers in using these ports. (5) Use a 88 port for refrigerant pipe connection. (6) Anchor holes marked L J (four holes for M10) are for a renewal installation. (7) The oil-equalising pipe K should be used when outdoor units are used in combination.
L1
20
Instruction plate
6 86.1
172
95
D (right)
172
83
R410A
If replacing a used unit with a new one, Refresh KX can reuse existing piping.
Nominal Cooling Capacity 22.4kW 28.0kW
NEW
Applies to a wide range of pipe sizes (R22, R407C, R410A standard size). Meets to a short period of renewal installation. Savings on replacement expenses such as scrapping waste material or procuring new pipe. Possible to replace the existing unit with a new larger capacity unit. Possible to replace plural systems with one system.
For example:Existing 5HP x 2units can be replaced with a new 10HP x 1unit.
5HP x 2
10HP x 1
Outdoor unit Range of operation Height difference 50m(outdoor unit above) 40m(outdoor unit below) Max height difference between indoor units: 15m
-10 30 20 10 0 50
Indoor unit
+43C
40
Indoor unit
Cooling
+15.5C
Indoor unit
Heating
-15C
-20
-20C
Specifications
Item Nominal horse power Power source Nominal capacity Model
FDCR224KXE6
8HP 3 Phase 380-415V, 50Hz 22.4 25.0 5 5.60 6.03 9.25-8.47 9.85-9.02 1675x1080x480 224 11.5 58/58 9.52(3/8")~15.88(5/8") 19.05(3/4")~25.4(1") 50~130 13
FDCR280KXE6
10HP 28.0 31.5 8.09 8.21 13.22-12.10 13.41-12.28
Cooling kW Heating A Starting current Cooling Power kW Electrical characteristics consumption Heating Cooling Running A current Heating HxWxD mm Exterior dimensions kg Net weight R410A kg Refrigerant charge Cooling/Heating dB(A) Sound pressure level Liquid line mm(in) Refrigerant piping size Gas line % Capacity connection Number of connectable indoor units
59/60 22.22(7/8")~28.58(11/8") 16
1. The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB. Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. 2. Sound pressure level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
84
1.Implement cooling operation of all indoor units for more than 30 minutes. 2.Implement pump-down after cooling operation. 3.Recover refrigerant and remove the existing outdoor unit and indoor unit.
7-segment display Pipe refresh kit (FDCR-KIT-E)
Piping system
outdoor unit heat exchanger high efficiency strainer compressor accumlator Pipe refresh kit Service valve kit indoor unit
refrigerant flow
Dimensions
All measurements in mm. Service valve kit
Mark A B C D E F1 F2 F3 F4 G
Item Service valve connection of the attached connecting pipe (gas side) Service valve connection (liquid side) Pipe/cable draw-out hole Drain discharge hole Anchor bolt hole Cable draw-out hole Cable draw-out hole Cable draw-out hole Cable draw-out hole Connecting position of the local pipe. (gas side)
19.05 (3/4") (Flare) 12.7 (1/2) (Flare) 4places 20 x 4places M10 x 4places 30 45 22 34 25.4 (1")(Brazing)
Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave a 1m or larger space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The model name label is attached on the lower right corner of the front. (7) Connect the Service valve with local pipe by using the pipe of the attachment.(Gas side only) (8) Mark shows the connecting position of the local pipe.(Gas side only)
85
R410A
/further information
Mitsubishi Heavy Industries operates a continuous CSR (Corporate Social Responsibility) policy, with a role to realise a sustainable society through its various areas of business.
We strongly believe that the customer comes first and that we are obliged to be an innovative partner to society. We base our activities on honesty, harmony, and a clear distinction between public and private life. We shall strive for innovative management and technological development from an international perspective.
MHIs creed was established based on The Three Corporate Principles shared by the Mitsubishi Group from the companys beginnings. In the spirit of this creed, MHI continues its efforts to fulfil its three corporate social responsibilities (CSRs): corporate governance and compliance, the environment, human rights and labour, and contribution to society through business activities.
MISSION
Supply all areas of the world with highly efficient, clean energy
MISSION
Industries
MISSION
Help people lead fulfilled lives
MISSION
Support manufacturing activities worldwide
86
The KX6 product range has been developed in compliance with the Mitsubishi Heavy Industries Policy on the Environment.
In order to make the sustainable development of society possible, a basic policy on environmental matters has been established.
Pursuant to the express provision of Section 1 of its creed that We strongly believe that customers come first and that we are obligated to be an innovative partner to society, MHI shall, as a matter of primary importance, strive, through its R&D, manufacturing and other business activities, to play a useful role in the development of society. To this end, while remaining aware that a business enterprise is a member of society, MHI shall endeavour, in all aspects of its business activities, to reduce the burden on the environment and shall concentrate and fully utilise its technological capabilities for the development of technologies and products that will protect the environment, thus contributing to the establishment of a society in which sustainable development is possible.
In order to realise its basic policy, MHI has set the following seven conduct guidelines.
1. Recognise that environmental protection is top priority in the companys operations, and encourage the entire company in its endeavours to protect and improve the environment. 2. Define roles and responsibilities regarding environmental protection by developing and maintaining a corporate organisation designated for environmental protection, and create and implement corporate policies and procedures on environmental matters. 3. Endeavour to reduce the burden on the environment by preventing pollution, saving resources, saving energy, reducing waste, reusing materials, and recycling in all aspects of the companys business activities in R&D, designing, procurement of materials, manufacturing, transportation, use, service and disposal. 4. Endeavour to develop and provide advanced, highly reliable, unique technologies and products that contribute to solving environmental and energy problems. 5. Comply with national and local environmental laws and regulations, beyond mere compliance by enacting, implementing and evaluating voluntary standards where necessary, and to endeavour to continuously improve and promote environmental protection activities by establishing environmental goals and targets. 6. Endeavour to protect the environments of foreign countries by carefully examining the consequences of the companys overseas business operations and the exportation of its products, and to become actively involved in technological co-operation overseas in areas of environmental protection. 7. Provide environmental training and other programs to enhance the environmental awareness of all company employees, and take steps to expand public relations activities, such as providing environment-related information to the public and social contribution activities.
as of March, 2011
Europe
Major subsidiaries 12
Africa
Major subsidiary 1
Oceania
Major subsidiaries 2
87
global activity
On the land and sea, in the sky and even in space, MHIs stage of operations is expanding limitlessly. We manufacture more than 700 different products which support various industrial and civil activities in both domestic and international markets. Ships, steel structures, power systems, machinery for both industrial and general use, air-conditioners, pollution reduction and environmental control systems, aerospace systems the MHI product lines which create rich and comfortable living environments, are as harmonious as an orchestra. What creates this harmony is MHIs general technological expertise developed over more than a century of hard work. We are highly esteemed in the world for providing high quality products through untiring technological research and development. From new energy development and environmental concerns to the exploration of space, with the advent of the 21st century MHI is confronting a variety of issues to ensure the realisation of a society in which there is harmony between mankind and technology.
Ultra-High Steel Stacks Refuse Incineration Plants Night Soil Treatment Plants Electrostatic Precipitators Flue Gas Desulfurization System Fluidized Incinerators CFC Collecting Equipment
Crude Oil Storage Barges LNG Tanks Boilers & Turbines Oil Production Plants Contra-Rotating Propellers Thermal Power Plants Combined Cycle Plants Fuel Cells Water Turbines Wind Turbines Geothermal Power Plants PWR Nuclear Power Plants Uranium Enrichment Equipment FBRs Co-Generation Systems
Spillway Radial Gates Steel Bridges Penstocks Desalination Plants Physical Distribution Equipment Engines
URCE RESO
C LO
Unloader & Container Cranes Mechanical Parking Facilities Integrated Automated Storage Systems Rubber & Tyre Machinery Skyrails Monorail Cars New Transportation Systems Passenger Boarding Bridges
Toll Collection Machine Systems Forklift Trucks Helicopters Aircraft Railway Maintenance Equipment LNG Carrier Container Ships
TR
AL DE
SP OR TA TIO N
EN
AN
VIR
S/ENE
PM LO VE
N ME ON T
RGY
EN
88
Chemical Plants Wind Tunnel/Experiment Equipment Casting Machines Strip Mill Cement Plant Stepless Variable Speed Gears Industrial Robots Injection Moulding Machines Pulp & Paper Machinery Corrugation Machines Box Making Machines Machine Tools
Ceiling Recess Packaged Air Conditioners Automotive Air Conditioners Residential Use Split Air Conditioners Refrigeration Units Dry Cleaning Machines Food Machinery Cruise Ships Multi-purpose Dome Stage Machinery Systems
Oceanographic Research Ships Deep Submergence Research Vehicles Communications Satellite Rockets Space Transportation Rockets & Engines
V DE
EL
E PM
NT
N EFE
CE
Submarines Naval Vessels Jet Fighters Helicopters Missiles Tanks & Infantry Fighting Vehicles
89
Refrigerant leakage
The refrigerant (R410A) used for Air conditioner is non-toxic and inflammable in its original state. However, in consideration of a state where the refrigerant leaks into the room, measures against refrigerant leaks must be taken in small rooms where the tolerable level could be exceeded. Take measures by installing ventilation devices, etc.
Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air intake port or enter and freeze in the outdoor unit.
Snow piling
In areas with heavy snow fall, the piled snow could block the air intake port. In this case, a frame that is 50cm or higher than the estimated snow fall must be installed underneath the outdoor unit.
Safety Precautions
Air-conditioner usage target
The air-conditioner described in this catalog is a dedicated cooling/heating device for human use. Do not use it for special applications such as the storage of foodstuffs, animals or plants, precision devices or valuable art, etc. This could cause the quality of the items to drop, etc. Do not use this for cooling vehicles or ships. Water leakage or current leaks could occur. , Always read the "User s Manual" thoroughly before starting use.
Installation
Always commission the installation to a dealer or specialist. Improper installation will lead to water leakage, electric shocks and fires. Make sure that the outdoor unit is stable in installation. Fix the unit to stable base.
Usage place
Do not install in places where combustible gas could leak or where there are sparks. Installation in a place where combustible gas could be generated, flow or accumulate, or places containing carbon fibers could lead to fires.
Before use
Mitsubishi Heavy Industries, Ltd. Air-Conditioning & Refrigeration Systems 16-5, Konan 2-chome, Minato-ku, Tokyo, 108-8215 Japan http://www.mhi.co.jp Our factories are ISO9001 and ISO14001 certified.
Certified ISO 9001 Certified ISO 14001
ISO 14001
Certificate 04104 1998 0813 E5 BIWAJIMA PLANT MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO., LTD. Mitsubishi Heavy Industries-Haier (Quingdao) Air-conditioners Co.,Ltd. BIWAJIMA PLANT MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO.,LTD. Mitsubishi Heavy Industries-Haier (Quingdao) Air-conditioners Co.,Ltd.
HB91-13KX01E
Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.
Printed in Japan