TP 5750
TP 5750
TP 5750
Models:
20-2000 kW
Controllers: Decision-Makert 3+, 16-Light Decision-Makert 3+, 7-Light Decision-Makert 3, 16-Light Decision-Makert 3, 6-Light Manual Paralleling Decision-Makert 1 Manual Engine Gauge Box for Paralleling Switchgear
TP-5750 10/03j
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice. Controller Description
Engine Identification
Record the product identification information from the engine nameplate. Manufacturer Model Designation Serial Number
TP-5750 10/03
Table of Contents
Product Identification Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Service Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Section 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 1.2 Specifications, 20--300 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 1.3 Specifications, 350--2000 kW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.4.1 Controller Connection Kit (M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.4.2 Remote Annunciator Kit (M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 1.4.3 Single-Relay Dry Contact Kit (M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 1.4.4 Dry Contact Kits (M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 1.4.5 Audiovisual Alarm (M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1.4.6 Safeguard Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1.4.7 Line Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1.4.8 Run Relay Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1.4.9 Remote Emergency Stop Kit (M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.4.10 FASTCHECK Diagnostic Tester (M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.4.11 Accessory and Prime Power Terminal Strip Connections (M) . . . . . . . . 16 Section 2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.1 Prestart Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.2 Generator Set Exercising . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.3 Microprocessor Controllers Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 2.3.1 Microprocessor Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 2.3.2 Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 2.3.3 Prime Power Mode Operation (Decision-Maker 3+ Controller) . . . . . . . 28 2.3.4 Emergency Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 2.3.5 Fault Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 2.3.6 Controller Resetting After a Fault Shutdown . . . . . . . . . . . . . . . . . . . . . . . 30 2.4 Manual Paralleling Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 2.4.1 Manual Paralleling Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 2.4.2 Single Generator Set Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 2.4.3 Paralleling Setup and Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 2.4.4 Load Disconnection from Paralleled Generator Sets . . . . . . . . . . . . . . . . 34 2.5 Expanded Decision-Maker 1 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 2.5.1 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 2.5.2 Generator Set Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 2.5.3 Generator Set Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 2.5.4 Fault Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 2.5.5 Controller Resetting After a Fault Shutdown . . . . . . . . . . . . . . . . . . . . . . . 36 2.6 Standard Decision-Maker 1 Controller with Engine Gauges . . . . . . . . . . . . . . . . . 37 2.6.1 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 2.6.2 Generator Set Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 2.6.3 Generator Set Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 2.6.4 Fault Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 2.6.5 Controller Resetting After a Fault Shutdown . . . . . . . . . . . . . . . . . . . . . . . 38 2.7 Standard Decision-Maker 1 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 2.7.1 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 2.7.2 Generator Set Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 2.7.3 Generator Set Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 2.7.4 Fault Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 2.7.5 Controller Resetting After a Fault Shutdown . . . . . . . . . . . . . . . . . . . . . . . 40 2.8 Manual Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 2.8.1 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 2.8.2 Generator Set Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 2.8.3 Generator Set Stopping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 2.8.4 Fault Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 2.9 Paralleling Engine Gauge Box Controller (Switchgear) . . . . . . . . . . . . . . . . . . . . . 42
TP-5750 10/03
Table of Contents
Table of Contents
TP-5750 10/03
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS. This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
Accidental Starting
WARNING
WARNING
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well-ventilated area. Isolate the battery charger from explosive fumes. Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid. Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area. Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded
Safety Precautions and Instructions 5
DANGER
Danger indicates the presence of a hazard that will cause severe personal injury, death, or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe personal injury, death, or substantial property damage.
CAUTION
Battery
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
WARNING
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related. Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
TP-5750 10/03
metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases. Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Exhaust System
WARNING
Fuel System
WARNING
nausea,
Explosive fuel vapors. Can cause severe injury or death. Use extreme care when handling, storing, and using fuels. The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels in a well-ventilated area away from spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation. Explosive fuel vapors can cause severe injury or death. Take additional precautions when using the following fuels: Propane (LP)Adequate ventilation is mandatory. Because propane is heavier than air, install propane gas detectors low in a room. Inspect the detectors per the manufacturers instructions. Natural GasAdequate ventilation is mandatory. Because natural gas rises, install natural gas detectors high in a room. Inspect the detectors per the manufacturers instructions.
The exhaust system must be leakproof and routinely inspected. Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building unless the exhaust gas is piped safely outside. Never operate the generator set where exhaust gas could accumulate and seep back inside a potentially occupied building. Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following: D Light-headedness, dizziness D Physical fatigue, weakness in joints and muscles D Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Fire. Can cause severe injury or death. Do not smoke or permit flames or sparks near fuels or the fuel system. Servicing the fuel system. A flash fire can cause severe injury or death. Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor. Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the air cleaner removed.
TP-5750 10/03
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble. LP liquid withdrawal fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an explosion. Check the LP liquid withdrawal gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to at least 90 psi (621 kPa). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load. High voltage test. Hazardous voltage can cause severe injury or death. Follow the instructions of the test equipment manufacturer when performing high-voltage tests on the rotor or stator. An improper test procedure can damage equipment or lead to generator set failure. Installing the battery charger. Hazardous voltage can cause severe injury or death. An ungrounded battery charger may cause electrical shock. Connect the battery charger enclosure to the ground of a permanent wiring system. As an alternative, install an equipment grounding conductor with circuit conductors and connect it to the equipment grounding terminal or the lead on the battery charger. Install the battery charger as prescribed in the equipment manual. Install the battery charger in compliance with local codes and ordinances. Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death. Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies). Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
WARNING
Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.
Hazardous Noise
CAUTION
WARNING
Hazardous noise. Can cause hearing loss. Never operate the generator set without a muffler or with a faulty exhaust system. Engine noise. Hazardous noise can cause hearing loss. Generator sets not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death. If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply. Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
TP-5750 10/03
Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage is present at the voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator. (PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only) Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts. The engine and exhaust system components become extremely hot during operation.
Notice
NOTICE
This generator set has been rewired from its nameplate voltage to
Moving Parts
WARNING
246242
NOTICE
Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
Heavy Equipment
WARNING WARNING
NOTICE
Hardware damage. The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage. Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
Rotating parts. Can cause severe injury or death. Operate the generator set only when all guards, screens, and covers are in place. Tightening the hardware. Flying projectiles can cause severe injury or death. Loose hardware can cause the hardware or pulley to release from the generator set engine and can cause personal injury. Retorque all crankshaft and rotor hardware after servicing. Do not loosen the crankshaft hardware or rotor thrubolt when making adjustments or servicing the generator set. Rotate the crankshaft manually in a clockwise direction only. Turning the crankshaft bolt or rotor thrubolt counterclockwise can loosen the hardware. Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings, and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification.
Hot Parts
WARNING
NOTICE
Canadian installations only. For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Hot engine and exhaust system. Can cause severe injury or death. Do not work on the generator set until it cools. Servicing the alternator. Hot parts can cause severe injury or death. Avoid touching the alternator field or exciter armature. When shorted, the alternator field and exciter armature become hot enough to cause severe burns.
TP-5750 10/03
Introduction
This manual provides operation instructions for 20--2000 kW generator sets equipped with the following controllers:
D Microprocessor Controller, Decision-Maker 3+ D Microprocessor Controller, Decision-Maker 3 D Manual Paralleling Controller D Decision-Maker 1 D Manual Controller D Engine Gauge Box for Paralleling Switchgear
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever. Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference. The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Maintenance work must be performed by appropriately skilled and suitably-trained maintenance personnel familiar with generator set operation and service.
Wiring diagram manuals are available separately. Refer to the engine operation manual for generator set engine scheduled maintenance information. This manual may be used for models not listed on the front cover.
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
GeneratorsElectric
D Visit
China North China Regional Office, Beijing Phone: (86) 10 6518 7950 (86) 10 6518 7951 (86) 10 6518 7952 Fax: (86) 10 6518 7955 East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550 India, Bangladesh, Sri Lanka India Regional Office Bangalore, India Phone: (91) 80 3366208 (91) 80 3366231 Fax: (91) 80 3315972 Japan, Korea North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727 Latin America Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
the Kohler Power Systems website at KohlerPowerSystems.com or review the appropriate literature or documents included with the product
D Call toll free in the US and Canada 1-800-544-2444 D Outside the US and Canada, call the nearest regional
office Headquarters Europe, Middle East, Africa (EMEA) Kohler Power Systems ZI Senia 122 12, rue des Hauts Flouviers 94517 Thiais Cedex France Phone: (33) 1 41 735500 Fax: (33) 1 41 735501 Asia Pacific Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
TP-5750 10/03
Introduction
Notes
10
Service Assistance
TP-5750 10/03
Section 1 Specifications
1.1 Introduction
The specification sheets for each generator set provide specific generator and engine information. Refer to the respective specification sheet for data not supplied in this manual. Consult the generator set service manual, installation manual, engine operation manual, and engine service manual for additional specifications. the main field and the generator sustains up to 300% of rated current. Sustained high current trips correspondingly or rated load circuit fuses/breakers. The safeguard breaker kit collapses the generator sets main field during a sustained heavy overload or short circuit.
1
13
5 6 12 11 10 7
conventionally wound field brushless generator sets because the inductance of the exciter field has no effect.
D Better recovery characteristics than static-excited
generators because the system does not draw excitation power from the generator output voltage.
D The inherent ability to support short-circuit current
9
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Field Main generator SCR assembly Exciter generator Exciter field magnets Exciter armature Optical coupling Starting battery Safegaurd breaker (optional) AC voltage regulator LED board Photo transistor board Stator
TP-5353-1
for
tripping
The PMG exciter system delivers the required level of exciter current to the main field within 0.05 seconds of a load change. For the duration of a short circuit in the load circuit(s), the output voltage drops and the amperage momentarily rises to 600%--1000% of the generator sets rated current. The SCR assembly sends full exciter power to
Figure 1-1
Alternator, 20--300 kW
TP-5750 10/03
Section 1 Specifications
11
1.4.2
A remote annunciator provides convenient monitoring of the generator sets condition from a remote location. See Figure 1-2. The remote annunciator includes an alarm horn, alarm silence switch, lamp test, and the same lamp indicators (except air damper and auxiliary prealarm) as the microprocessor controller, plus the following lamps:
1.4 Accessories
The manufacturer offers several accessories to finalize installation, to add convenience to operation and service, and to comply with state and local codes. Accessories vary with each generator set model and controller. Accessories are available factory-installed or shipped loose. Obtain the most current information by contacting your local authorized service distributor/dealer. The accessories described in Sections 1.4.1 through 1.4.11 were available at the time of print. Note: The accessories with the (M) notation are available only on models with microprocessor controllers.
A-258782
Remote Annunciator
42A 2
PCB ASSY A--320639 10A @120VAC RES. LOAD INPUTCONTACT RATINGS: .01A @28VDC MIN.
10A @28VDC MAX.
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10K11K12K13K14
LOT NO.
NO C NO C NO C NO C NO C NO C NO C NO C K1 K2 K3 K4 K5 K6 K7 K8
A-293983
1.4.1
The controller connection kit allows easy connection of controller accessories without accessing the controller terminal strip. The kit uses a 165-cm (65-in.) wiring harness to link the controller terminal strip(s) with a remote terminal strip. With the exception of a few terminals the remote terminal strip is identical to that of the controller. Connect all accessories except the emergency stop kit to the connection kit terminal strip.
A-256472
Figure 1-2
Line Power lamp illuminates to indicate that the commercial utility is the power source. Generator Power lamp illuminates to indicate that the generator set is the power source. Early models used a 10-relay dry contact box.
12 Section 1 Specifications TP-5750 10/03
1.4.3
D Auxiliary fault D Air damper (if equipped) D Anticipatory high engine temperature D Anticipatory low oil pressure D Emergency stop
The single-relay dry contact kit uses one set of contacts to trigger customer-provided warning devices if a fault condition occurs. Connect any controller fault output connection from the TB1 terminal strip to the singlerelay kit. Use the single-relay dry contact kit as a common fault relay for signaling any of the following common fault conditions:
D Emergency Stop D Auxiliary D Overspeed D Low Oil Pressure D High Engine Temperature
Connect a maximum of three dry contact kits to a single controller output. See Figure 1-3.
Additional connections available with the 20-relay kits include: D Battery charger fault D Low battery voltage D Low fuel level D Engine trouble D Not in AUTO D System ready D Common fault D Overcrank D Crank terminate D Cooldown
1
K1 K2 K3
A-273945
K4 K5 K6
Figure 1-3
K7
K8 K9 K10
1.4.4
Dry contact kits allow monitoring of the standby system and provide the ability to activate warning devices and other customer-provided accessories. Available kits include 10 or 20 sets of relay contacts for connecting customer-provided devices to desired generator set functions. Twenty-relay kits can be used on 450 kW and larger generator sets. Warning devices (lamp and/or audible alarms) and other accessories typically connect to the controller output connections listed below. A total of three dry contact kits may connect to a specific output connection on the controller. Figure 1-4 shows some typical dry contact kits mounted on an assembly panel for 450 kW and larger generator sets. Typical 10-relay contact kit output connections include:
D Overspeed D Overcrank D High engine temperature D Low oil pressure D Low water temperature
1. Ten-relay kit 2. Twenty-relay kit
C0C1C2C3707N
1 2 3 4 5 6
F1 F2 F3
1 2 3 4 5 6
2
K1 K2 K3 K4 K5 K6 K7 K1 K2 K3 K4 K5 K6 K7
K8 K9 K10
K8 K9 K10
C0C1C2C3707N
C0C1C2C3707N
M
1 2 3 4 5 6
N
1 2 3 4 5 6 7 8 9 10 111213141516 17 18 19 20
F1 F2 F3
1 2 3 4 5 6
365569A-C
Figure 1-4
Dry Contact Kits (shown mounted on an assembly panel for 450 kW and larger generator sets)
TP-5750 10/03
Section 1 Specifications
13
1.4.5
1.4.7
An audiovisual alarm warns the operator of fault shutdowns and prealarm conditions (except battery charger fault and low battery voltage) from a remote location. Audiovisual alarms include an alarm horn, an alarm silence switch, and a common fault lamp. See Figure 1-5. Note: Use the audiovisual alarm with a dry contact kit.
Front View Side View
The line circuit breaker interrupts generator output if an overload or short circuit occurs. Use the line circuit breaker to manually disconnect the generator set from the load during generator set service. See Figure 1-7.
TP-5352-1
Figure 1-7
A-292887
1.4.8
Figure 1-5
Audiovisual Alarm
1.4.6
Safeguard Breaker
The run relay kit includes three sets of contacts that energize only during generator set operation. The run relay kit can control air intake louvers, radiator louvers, alarms, and other signaling. See Figure 1-8.
The safeguard breaker senses output current on each generator phase and shuts off the AC voltage regulator if a sustained overload or short circuit occurs. It is not a line circuit breaker and does not disconnect the generator set from the load. See Figure 1-6.
273705 X-796
Figure 1-8
Figure 1-6
Safeguard Breaker
14
Section 1 Specifications
TP-5750 10/03
1.4.9
The emergency stop kit shuts down the generator set from a remote location in an emergency. See Figure 1-9. Activating the emergency stop switch lights the EMERGENCY STOP lamp and shuts down the unit. Before restarting the generator set, reset the emergency stop switch by replacing the glass piece and reset the generator set by placing the master switch in the OFF/RESET position. The switch holds a single replacement glass piece, which is available as a service part.
A-222654
Figure 1-9
TP-5750 10/03
Section 1 Specifications
15
Terminal Purpose 1P 2P 3 3P 4 4P Prime power operation. Prime power operation. Remote start ground. Connect transfer switch or remote start switch to TB2-3 and TB2-4. Prime power operation. Remote start. Connect transfer switch or remote start switch to TB2-3 and TB2-4. Prime power operation. Crank mode selection (open: cyclic crank, ground: continuous crank). Connect TB2-9 to TB2-9A for continuous cranking; leave TB2-9 open cyclic cranking; see starting instructions in Section 2, Operation. Crank mode ground.
9A
Figure 1-13 Decision-Makert 3+ Controller TB2 Terminal Strip Lower the controller circuit board panel until it is lying flat when connecting the dry contact kits to the controller TB1 terminal strip. Route dry contact relay leads through the controller grommet and guide loops to the circuit board terminal strip. Place the controller circuit board panel flat to ensure adequate slack in the dry contact relay leads. For specific information on accessory connections refer to the accessory wiring diagrams in the Wiring Diagram Manual and the instruction sheet accompanying the kit. Note: Not all terminals are used for all generator sets (see appropriate wiring diagrams for specific generator set models). Note: To use the prime power mode, use jumpers to connect TB2-1P to TB2-2P, TB2-3P to TB2-4P, and TB2-3 to TB2-4. To deactivate the prime power mode, remove these jumpers.
R41 LED4
P2
P1 A-336415-A
Figure 1-11 TB1 and TB2 Terminal Strips on the Decision-Makert 3+ Controller
1
P2
P1 G-292806
Terminal Purpose 1 Ground. Emergency stop relay (K4). Connect emergency stop across terminals TB1-1 and 1A. * Emergency stop relay (K4) coil; negative side. Connect emergency stop across terminals TB1-1 and 1A. * Ground terminal. Overcrank (OC) signal. [ Auxiliary (AUX) signal. [ Common fault/prealarm line 1. audiovisual alarm or common fault relay activated by OC, 12; AUX, 26; LWT, 35; HET, 36; LOP, 38; OS, 39; AHET, 40; ALOP, 41; and LF, 63 faults. Common fault/prealarm line 2. audiovisual alarm or common fault relay activated by AUX, 26; HET, 36; LOP, 38; OS, 39; and ES, 48 faults. Low water temperature (LWT) signal. High engine temperature (HET) signal. [ Low oil pressure (LOP) signal. [ Overspeed (OS) signal. [ Anticipatory high engine temperature (AHET) signal. [ Anticipatory low oil pressure (ALOP) signal. [ Battery voltage (fuse #1 protected). Accessory power supply; Customer may also provide separate accessory power source. Emergency stop (ES) signal. [ Air damper (AD) switch (if equipped). Standard on all 200--2000 kW Detroit Diesel powered models. System ready signal. [ Battery charger fault. Connect battery charger alarm contact to TB1-61 to activate fault lamp (active low) (if used). Low battery volts. Connect battery charger alarm contact to TB1-62 to activate fault lamp (active low) (if used). Low fuel (LF) fault. Connect fuel level sensor to TB1-63 to activate fault lamp (active low) (if used). Generator in cool down mode signal. Generator in running mode signal. Not in auto signal. [
Terminal Purpose 1 Ground. Emergency stop relay (K4). Connect emergency stop across terminals TB1-1 and 1A. * Emergency stop relay (K4) coil, negative side. Connect emergency stop across terminals TB1-1 and 1A. * Ground terminal. Remote start ground. Connect transfer switch or remote start switch to TB1-3 and TB1-4. Remote start. Connect transfer switch or remote start switch to TB1-3 and TB1-4. Crank mode selection (open: cyclic crank, ground: continuous crank). Connect TB1-9 to TB1-9A for continuous cranking; leave TB1-9 open for cyclic cranking; see Section 2.3.2, Starting. Overcrank (OC) signal. [ Auxiliary (AUX) signal. [ Common fault/prealarm line 1. audiovisual alarm or common fault relay activated by OC, 12; AUX, 26; LWT, 35; HET, 36; LOP, 38; OS, 39; AHET, 40; ALOP, 41; and LF, 63 faults. Low water temperature (LWT) signal. High engine temperature (HET) signal. [ Low oil pressure (LOP) signal. [ Overspeed (OS) signal. [ Anticipatory high engine temperature (AHET) signal. [ Anticipatory low oil pressure (ALOP) signal. [ Battery voltage (fuse #1 protected). Accessory power supply. Customer may also provide separate accessory power source. Emergency stop (ES) signal. [ Air damper switch (if equipped). Standard on 200--2000 kW Detroit Diesel-powered models. System ready signal. [ Battery charger fault. Connect battery charger alarm contact to TB1-61 to activate fault lamp (active low) (if used). Low battery volts. Connect battery charger alarm contact to TB1-62 to activate fault lamp (active low) (if used). Low fuel (LF) fault. Connect fuel level sensor to TB1-63 to activate fault lamp (active low) (if used). Not in auto signal. [
1A 2 12 26 32
1A 2 3 4
32A 35 36 38 39 40 41 42A 48 56 60 61
12 26
32
35 36 38 39 40 41 42A 48 56 60 61
62
63 70C 70R 80
62
* Connect jumper across terminals 1 and 1A if emergency stop switch is not used. [ Use a remote annunciator and/or audiovisual alarm kit as an indicator with a dry contact kit connected to controller terminal strip TB1.
63 80
* Connect jumper across terminals 1 and 1A if emergency stop switch is not used. [ Use a remote annunciator and/or audiovisual alarm kit as an indicator with a dry contact kit connected to controller terminal strip TB1.
Notes
18
Section 1 Specifications
TP-5750 10/03
Section 2 Operation
2.1 Prestart Checklist
To ensure continued satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts. Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine. Battery. Check for tight battery connections. Consult the battery manufacturers instructions regarding battery care and maintenance. Coolant Level. Check the coolant level according to the cooling system maintenance information. Note: On 20--40 kW generator sets with Deutz oil-cooled engines, the low water temperature and low coolant level fault lamps are not used because these engines do not have water-cooled systems. Note: Block heater damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm, and refill the radiator to purge the air from the system before energizing the block heater. Drive Belts. Check the belt condition and tension of the radiator fan, water pump, and battery charging alternator belt(s). Exhaust System. Check for exhaust leaks and blockages. Check the silencer and piping condition and check for tight exhaust system connections. Inspect the exhaust system components (exhaust manifold, exhaust line, flexible exhaust, clamps, silencer, and outlet pipe) for cracks, leaks, and corrosion.
D Check for corroded or broken metal parts and replace D Check that the exhaust outlet is unobstructed. D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal leaks as needed. Fuel Level. Check the fuel level and fill the tank(s) regularly to ensure adequate fuel supply. Lamp Test. Press the lamp test button, if equipped, to verify that all controller LEDs illuminate. Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick. Keep the oil level in the mechanical governor, if equipped, at or near the full level. Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
them as needed.
D Check for loose, corroded, or missing clamps and
TP-5750 10/03
Section 2 Operation
19
2.3.1
Microprocessor controller features include annunciator panel lamps, analog meters, switches and controls, and fuses and terminal strips. The following paragraphs describe the features.
20
Section 2 Operation
TP-5750 10/03
Standard Model 1 2 3 4 5 6 7
18 8
17
16
15
14
13
12
11
10
ADV-5849A
19
Oversize Meterbox
21
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Fuses (inside controller) Frequency meter AC voltmeter Controller TB1 and TB2 terminal strips (on circuit board) AC ammeter Scale lamps (upper/lower) Selector switch Annunciator panel lamps Alarm silence switch Lamp test Generator set master switch
20
12. 13. 14. 15. 16. 17. 18. 19. 20. 21. Alarm horn Emergency stop switch (if equipped) DC voltmeter Water temperature gauge Voltage adjustment (if equipped) Oil pressure gauge Hourmeter Wattmeter (if equipped) Tachometer (if equipped) Engine oil temperature gauge (if equipped)
ADV-5849B
Figure 2-1
TP-5750 10/03
Section 2 Operation
21
Standard Controller 1 2 3 4 5 6 7
18
8 9 10
TP-5849B
17
16
15
14
13
12
11
19
Oversize Meterbox
21
20
TP-5849B
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
Fuses (inside controller) Frequency meter AC Voltmeter Controller TB1 and TB2 terminal strips (on circuit board) AC ammeter Scale lamps (upper/lower) Selector switch Annunciator panel lamps Alarm silence switch Lamp test Generator set master switch
12. 13. 14. 15. 16. 17. 18. 19. 20. 21.
Alarm horn Emergency stop switch (if equipped) DC voltmeter Water temperature gauge Voltage adjustment (if equipped) Oil pressure gauge Hourmeter Wattmeter (if equipped) Tachometer (if equipped) Engine oil temperature gauge (if equipped)
Figure 2-2
7-Light Microprocessor Controller (Standard and Oversize Meterbox Models) Note: 6-Light Microprocessor Controller is similar except where noted.
22
Section 2 Operation
TP-5750 10/03
Description Lights after an emergency stop, overspeed fault, or overvoltage fault to indicate that the engine air damper is closed. The lamp remains lit until the air damper is manually reset. See Section 2.3.4, Emergency Stopping. Flashes or lights upon fault detection. The 16-light and 7-light controllers have an auxiliary fault lamp and the 6-light controller has a low engine temperature/auxiliary fault lamp. Figure 2-4 describes auxiliary fault conditions. Lights if the engine has shut down because of high engine temperature. The shutdown occurs 5 seconds after the engine reaches temperature shutdown range. Lamp lights if the generator set shuts down because of insufficient oil pressure. Lamp lights if the generator set shuts down because the governed frequency on 50 and 60 Hz models exceeds 70 Hz (2100 rpm). Cranking stops and the lamp lights if the engine does not start after 45 seconds of continuous cranking or 75 seconds of cyclic cranking. See Section 2.3.2, Normal Operation. Note: The engine ECM may limit the crank cycle even if the controller is set to a longer time period. Cranking stops and the overcrank lamp lights after 15 seconds if the starter or engine does not turn (locked rotor). The overcrank lamp flashes if the speed sensor signal is absent for longer than one second.
16-Light 7-Light X X
6-Light X
Auxiliary fault
X X X
X X X
X X X
Low water temperature Auxiliary prealarm Battery charger fault Emergency stop
Lights if water temperature approaches the shutdown range. This lamp requires an optional prealarm sender kit in order to function. The lamp does not light on 20--40 kW engines that have oil-cooled systems. Activated by customer-provided sensing devices. This lamp was replaced by a high battery voltage lamp in later models. Lights if the battery charger malfunctions. This lamp requires an optional battery charger. Lights and the generator set shuts down if the optional emergency stop switch is energized either locally or from a remote location. This lamp requires an optional emergency stop switch in order to function. The local emergency stop switch is standard on 200--2000 kW models with Detroit Diesel Engines. Lights when the generator set master switch is in the RUN or OFF/RESET position. Lights if the battery voltage rises above preset level. An optional battery charger is required for the lamp to function. The high battery voltage lamp replaced the auxiliary prealarm lamp on later models.
X X X
X X X
Low battery voltage Lights if the battery voltage drops below a preset level. This lamp requires an optional battery charger in order for the lamp to function. Low fuel warning Lights if the fuel level in tank approaches empty. This lamp requires a low fuel sensor in the fuel tank in order to function. On gas-fueled systems, this lamp lights if the gas line pressure drops below a preset level.
Prealarm high Lights if the engine temperature approaches the shutdown range. This engine temperature lamp requires an optional prealarm sender kit. Prealarm low oil pressure System ready Lights if the engine oil pressure approaches the shutdown range. This lamp requires an optional prealarm sender kit in order to function. Lights when the generator set master switch is in the AUTO position and the system senses no faults. Indicates that the generator set is ready for operation.
X X X
Figure 2-3
TP-5750 10/03
Section 2 Operation
23
Figure 2-4
24
Section 2 Operation
TP-5750 10/03
Name
Description
Alarm horn Horn sounds if any fault or prealarm condition exists (except emergency stop, battery charger fault, or low battery voltage). Place the generator set master switch in the AUTO position before silencing the alarm horn. See controller resetting procedure in Section 2.3.6, Controller Resetting After a Fault Shutdown. Alarm silence switch Switch disconnects the alarm during service. Place the generator set master switch in the AUTO position before silencing the alarm horn. To avoid reactivating the alarm horn, restore all alarm horn switches (controller, remote annunciator, and audiovisual alarm) to their normal positions after correcting the fault. See controller resetting procedure in Section 2.3.6, Controller Resetting After a Fault Shutdown.
Fuses
The fuses listed in Figure 2-7 protect the generator set circuitry.
Name AC voltmeter Description Meter displays the AC output voltage. Use the selector switch to choose the output lead circuits. Meter displays the AC output amperage. Use the selector switch to choose the phase currents. Meter displays the voltage of the starting battery(ies). Meter displays the engine oil temperature.
AC ammeter
Emergency Switch (if equipped) immediately shuts down stop switch the generator set in emergency situations. Reset the emergency stop switch after shutdown by rotating the switch clockwise. Use the emergency stop switch for emergency shutdowns only. Use the generator set master switch for normal shutdowns. The local emergency stop switch is standard on Detroit Diesel-equipped 200--2000 kW generator sets. Generator set master switch Switch functions as the controller reset and generator set operation switch. Refer to Section 2.3.2, Normal Operation, Section 2.3.3, Prime Power Mode Operation, and Section 2.3.6, Controller Resetting After a Fault Shutdown. Switch displays the controller indicator lamps. Switch selects the generator set output circuits to measure. When switched to a position with three circuit labels, the meters display the amperage on the lead shown in the upper label and the voltage between the two leads shown in the lower label. The AC ammeter and voltmeter function only with the switch in the ON position. Potentiometer fine tunes (5%) the generator set output voltage. Used with 20--300 kW models only. The voltage adjustment on 350--2000 kW models is located in the generator junction box.
Meter displays the frequency (Hz) of the generator set output. Hourmeter records the generator set total operating hours for reference in maintenance scheduling. Gauge measures the engine oil pressure. Lamps indicate which AC voltmeter and/or ammeter scales to read. Meter displays the engine speed (rpm). Gauge displays the engine coolant temperature. Note: The 20--40 kW models with Deutz oil-cooled engines substitute an engine oil temperature gauge for the water temperature gauge. Meter displays the generator output in kilowatts. Use the selector switch to choose output lead circuits. Note: Manual paralleling controllers use the wattmeter. See Section 2.4, Manual Paralleling Controller, for additional information.
Oil pressure gauge Scale lamps (upper/lower) Tachometer, if equipped Water temperature gauge, if equipped
Figure 2-6
Wattmeter, if equipped
Fuse Description F1 F2 F3 3-amp remote annunciator fuse protects the dry contact kit (if equipped). 3-amp controller fuse protects the controller circuit board, speed sensor, and lamp circuit board. 15-amp engine and accessories fuse protects engine/starting circuitry and accessories.
Figure 2-5
Figure 2-7
Controller Fuses
TP-5750 10/03
Section 2 Operation
25
Terminal Strips
Decision-Makert3+ Controller with DIP Switches. Two terminal strips are mounted on the DecisionMakert3+ controller circuit board. See Figure 2-8 and Figure 2-9. Refer to Section 2.3.3, Prime Power Mode Operation, for information on enabling prime power mode. Decision-Makert3+ Controller. Two terminal strips are mounted on the Decision-Makert3+ controller circuit board. See Figure 2-10 and Figure 2-11. Refer to Section 2.3.3, Prime Power Mode Operation, for information on enabling the prime power mode.
Terminal Strip Description TB1/TB3 Terminal strip for connecting generator set accessories such as an emergency stop switch, a remote start/stop switch, audiovisual alarms, etc. Refer to the wiring diagrams for information on connecting accessories to the TB1 terminal strip. TB2 Terminal strip for selecting the crank mode (cyclic or continuous), remote start/stop switch inputs, and prime power mode. Terminal strip for CAN communication connection. Terminal strip for Modbusr RS-485 communication connection.
Terminal Strip Description TB1 Terminal strip for connecting generator set accessories such as an emergency stop switch, a remote start/stop switch, audiovisual alarms, etc. Refer to the wiring diagrams for information on connecting accessories to the TB1 terminal strip. Terminal strip for selecting the crank mode (cyclic or continuous), remote start/stop switch inputs, and prime power mode.
TB2
1P 2P 3P 4P 9 9A 4 3
P2
P1 A-336415-A
TB4 TB5
Figure 2-8
Figure 2-11 Decision-Makert3+ Controller Circuit Board Decision-Makert3 Controller. One terminal strip is mounted on the Decision-Makert3 controller circuit board. See Figure 2-12 and Figure 2-13.
Terminal Strip Description TB1 Terminal strip for selecting the crank mode and connecting generator set accessories such as an emergency stop switch, a remote start/stop switch, audiovisual alarms, etc. Refer to the wiring diagrams for information on connecting accessories to the TB1 terminal strip.
7
1. 2. 3. 4. 5. 6. 7.
TB1 (TB1A) terminal strip TB3 (TB1B) terminal strip TB2 terminal strip P21 for Modbusr RS-485 communication connection P22 for CAN (engine) communication connection DIP Switches (8 Positions) Fuses
P2
P1
Figure 2-9
G-292806
Engine Cranking
The controller is factory-set for cyclic cranking. To change to the continuous cranking mode on the Decision-Makert3+ controller, install a jumper between circuit board terminals TB2-9 and TB2-9A. On the Decision-Makert3 controller, install a jumper between TB1-2 and TB1-9. To return to cyclic cranking, remove the jumpers. Note: Circuit boards equipped with DIP switches allow cranking selection using a DIP switch.
Note: After setting DIP switches to the generator set application, be sure to power down and then power up the controller (disconnect the battery and then reconnect the battery of the generator set) or use the prime power switch, if equipped. The controller will NOT acknowledge the DIP switch change until after generator set controller is powered up. Push down the end of the DIP switch near the OPEN label to open the switch, or push down the other end to close it. See Figure 2-15.
2 3 4 5 6 7 8
Description Overspeed Selection Temperature Cooldown Enable Crank Mode Selection Engine Comm. Setting Engine Comm. Setting Modbusr Address Bit 0 Modbusr Address Bit 1 Modbusr Address Bit 2 N ECM No MDEC Comm. Isochronous J1939 Communication MDEC Comm. Governor (VSG)
OPEN
1. Push this side down to open circuit.
1 6126
Figure 2-15 DIP Switch Open Position Typically, the factory default settings have all the DIP switches in the closed position except the crank mode selection switch SW3 which is open for cyclic cranking. The overspeed selection switch SW1 is open on 50 Hz. units. Be sure to select the correct DIP switch configuration for each generator set application. Overspeed Frequency (DIP Switch 1). The generator set overspeed frequency is set using DIP switch 1. Select 70 Hz for 60 Hz voltages and 60 Hz for 50 Hz voltages. Temperature Cooldown (DIP Switch 2). The generator set will continue to run during a five-minute cooldown cycle or shut down immediately. The choice is made using DIP switch 2. Engine Cranking (DIP Switch 3). The controller is factory-set for cyclic cranking. To change to the continuous cranking mode, use DIP switch 3. Engine Configuration (DIP Switches 4 and 5). See Figure 2-14 for the DIP switch positions based on engine configurations regarding non-ECM, MDEC, and J1939 engine communication selections.
See selections for DIP switch 4 and DIP switch 5 below Value = 0 Value = 0 Value = 0 Open Open Closed Open Open Closed Closed Closed Value = 2 Value = 4 Value = 8
TP-5750 10/03
Section 2 Operation
27
Modbusr Address
Each Modbusr device requires a unique address. Address numbers are created using a binary number system with DIP switches 6--8. Figure 2-16 shows the DIP switch position for each address number.
DIP Switches Modbusr Address 1 3 5 7 9 11 13 15 6 Value = 2 Open Closed Open Closed Open Closed Open Closed 7 Value = 4 Open Open Closed Closed Open Open Closed Closed 8 Value = 8 Open Open Open Open Closed Closed Closed Closed
Note: Circuit boards equipped with DIP switches allow cranking selection using a DIP switch. Stopping. Run the generator set without load for 5 minutes to ensure adequate engine cooldown. To stop the generator set, place the generator set master switch in the OFF/RESET position and wait until the generator set stops completely. Note: The generator set continues to run during a 5-minute cooldown cycle if a remote switch or automatic transfer switch signals the engine to stop. Note: Circuit boards equipped with DIP switches allow disabling the engine cooldown function.
2.3.3
2.3.2
Normal Operation
Local Starting. Move the generator set master switch to the RUN position to start the generator set at the controller. Note: The alarm horn sounds and the Not in Auto lamp lights when the generator set master switch is not in the AUTO position. Note: The transient start/stop function of the microprocessor controller prevents accidental cranking of the rotating engine. If the generator set master switch is momentarily placed in the OFF/RESET position and then is returned to the RUN position, the generator set slows to 750 rpm (25 Hz) and recranks before returning to rated speed. Automatic Starting. Move the generator set master switch to the AUTO position to allow startup by an automatic transfer switch or a remote start/stop switch. Refer to the wiring diagrams for remote switch connection information. The engine cranks up to 45 seconds continuously or 75 seconds cyclically (crank 15 seconds, rest 15 seconds, crank 15 seconds, etc.) before shutting down on an overcrank fault. Note: The engine ECM may limit the crank cycle even if the controller is set to a longer time period. Select the cyclic or continuous cranking mode on the controller circuit board terminal strip using the instructions in Section 2.3.1, Microprocessor Controller Features.
Modbusr is a registered trademark of Schneider Electric. 28 Section 2 Operation
The Decision-Makert3+ controller can operate in either the normal mode or the prime power mode. In prime power mode, the controller draws less current when the generator set master switch is in the OFF/RESET position, minimizing the battery drain. Use the prime power mode for installations that do not have a battery charger to help prevent discharging the battery when the generator set is not operating. Moving the generator set master switch to the OFF/RESET position disables all controller functions. Moving the generator set master switch to the AUTO position restores controller functions. Enabling and Disabling the Prime Power Mode. Enable the prime power mode by connecting jumpers across the following terminals on terminal strip TB2 on the controller circuit board:
D TB2-1P and TB2-2P D TB2-3P and TB2-4P D TB2-3 and TB2-4
See Figure 2-11. Remove the jumpers listed above to disable the prime power mode. Prime Power Starting. The prime power mode provides local starting only at the controller. The AUTO position no longer functions as a remote start. When the generator set master switch is in the OFF/RESET position, the controller functions are inoperative. Move the generator set master switch to the AUTO position to start the generator set. Do not start the generator set with the master switch in the RUN position because the alarm horn will sound.
TP-5750 10/03
Note: Move the generator set master switch to the AUTO position to return controller functions to normal. Prime Power Stopping. Move the generator set master switch to the OFF/RESET position to stop the generator set and power down the controller. Note: The controller functions are inoperative when the generator set master switch is in the OFF/RESET position.
Emergency Stop Switch Resetting Procedure 1. Investigate the cause of the emergency stop and correct the circuit or wiring problem(s). 2. If the remote emergency stop switch was activated, reset the switch by replacing the glass piece. If the controller-mounted emergency stop switch (if equipped) was activated, reset the controller emergency stop switch by rotating the switch clockwise until it springs back to its original position. Note: The controller auxiliary fault lamp lights if the generator set master switch is in the RUN or AUTO position during the resetting procedure. 3. If the controller air damper lamp is lit, reset the engine air damper by rotating the air damper lever until the air damper light goes out. See Figure 2-18.
2.3.4
Emergency Stopping
Activate the controller emergency stop switch, if equipped, or the optional remote emergency stop switch for immediate shutdown. Use the emergency stop switch(es) for emergency shutdowns only. Use the generator set master switch for normal shutdowns. The unit shuts down and the controller emergency stop lamp lights if an operator activates either the local or remote emergency stop switch. The 6- and 7-light controllers do not have separate emergency stop lamps. The auxiliary or low water temperature lamp illuminates to indicate an emergency stop on these models. See Figure 2-17. On some 200--2000 kW generator sets equipped with Detroit Diesel Series 71, 92, and 149 engines, both the air damper and emergency stop lamps light when an operator activates the emergency stop switch.
Lamp Emergency Stop Auxiliary Low Water Temperature/ Auxiliary 16-Light X X X 7-Light 6-Light
TP-5633-2
Figure 2-18 Air Damper Lever (Detroit Diesel) Note: The air damper lamp functions only on air damper-equipped engines. The engine air damper (air box) is available on some 200--2000 kW generator sets using Detroit Diesel Series 71, 92, and 149 engines. Generator sets with serial numbers above 376029 do not offer the air damper as standard equipment. 4. Toggle the generator set master switch to the OFF/RESET position and then to the RUN or AUTO position to restart the generator set. The generator set does not crank until the resetting procedure is completed.
Figure 2-17 Controller Lamp Indicating an Emergency Stop Condition Use the following procedure to restart the generator set after shutdown by an emergency stop switch. Refer to Section 2.3.6, Controller Resetting After a Fault Shutdown, to restart the generator set following a fault shutdown.
TP-5750 10/03
Section 2 Operation
29
2.3.5
Fault Shutdowns
2.3.6
The generator set shuts down automatically under the fault conditions listed in Figure 2-19.
Fault High engine temperature Description The high engine temperature shutdown shuts down the unit 5 seconds after a fault. The shutdown does not function during the first 30 seconds following startup. Note: Water-cooled engines only. The high temperature shutdown functions only when the coolant level is in the operating range. The low coolant level shutdown shuts down the unit 5 seconds after the fault. The shutdown does not function during the first 30 seconds following startup. The lamp does not function on 20--40 kW models with Deutz oil-cooled engines. The low oil pressure shutdown shuts down the unit 5 seconds after fault detection. The shutdown does not function during the first 30 seconds following startup. Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Overcrank shuts down the unit after 45 seconds of continuous cranking. Shutdown occurs after 75 seconds of cyclic cranking (crank 15 seconds, reset 15 seconds, crank 15 seconds, etc., for a total of 75 seconds). Shutdown occurs after 15 seconds if the engine or starter does not turn (locked rotor). Note: The controller has an automatic restart function. The generator set attempts to restart if the engine speed drops below 390 rpm (output frequency of 13 Hz). Continued low engine speed causes an overcrank fault condition. Overspeed shuts down the unit immediately when governed frequency on 50 and 60 Hz models exceeds 70 Hz (2100 rpm). Note: Circuit boards with DIP switches allow 50 Hz (60 Hz shutdown) or 60 Hz (70 Hz shutdown) selection.
Use the following procedure to restart the generator set after a fault shutdown. Refer to Section 2.3.4, Emergency Stopping, to reset the generator set after an emergency stop. 1. Move the controller alarm horn switch to the SILENCE position. If equipped, the audiovisual annunciator alarm horn and lamp are activated. Move the audiovisual annunciator alarm switch to SILENCE to stop the alarm horn. The audiovisual annunciator lamp stays lit. 2. Disconnect the generator set from the load by using the line circuit breaker or the automatic transfer switch. 3. Correct the cause of fault shutdown. See the Safety Precautions section of this manual before proceeding. 4. Start the generator set by moving the generator set master switch to the OFF/RESET position and then to the RUN position. If equipped, the audiovisual annunciator alarm horn sounds and lamp goes out. 5. Verify that the cause of the shutdown was corrected by test operating the generator set. 6. Reconnect the generator set to the load by using the line circuit breaker or the automatic transfer switch. Note: Place the generator set master switch in the AUTO position before silencing the alarm horn. 7. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch. If equipped, move the audiovisual annunciator alarm switch to NORMAL. 8. Move the controller alarm horn switch to the NORMAL position.
Overcrank
Overspeed
Overvoltage, Overvoltage shuts down the unit and lights if equipped the auxiliary lamp when voltage is at least 15% over the nominal voltage for longer than 2 seconds. The overvoltage shutdown is standard on Decision-Makert3+ controllers. Note: Overvoltage can damage sensitive equipment in less than 1 second. Provide separate overvoltage protection for online equipment requiring faster shutdowns.
30
Section 2 Operation
TP-5750 10/03
Before using the manual paralleling controller, have a qualified technician perform the reactive droop compensation adjustment and test, load sharing module setup, and reverse power relay test procedures in Section 2.4.3, Paralleling Setup and Test. The manual paralleling controller operates either a single generator set or multiple generator sets in parallel. See the operation procedures for details. Parallel two or more generator sets if the load is expected to be greater than the full-load rating of one generator set. Use the procedures in Section 2.4.3, Paralleling Setup and Test, to parallel two or more generator sets. Note: To avoid a reverse-power condition, do not parallel two or more generator sets without load. Reverse power can shut down one of the generator sets. If the load is less than 10% of the full-load rating of the first generator set, shut down the additional generator sets.
voltage regulator
D Include an electronic governor, reactive droop
TP-5750 10/03
Section 2 Operation
31
2.4.1
Name Microprocessor controller features Reverse power shutdown lamp Sync lights Wattmeter
Description Controller contains all the features of the microprocessor controller described in Section 2.3, Microprocessor Controllers. Lamp lights when a reverse power shutdown occurs. Lights are used for the manual paralleling operation. Wattmeter measures output in kilowatts from the output leads selected with the selector switch. Pushbutton resets the reverse power shutdown circuit. Potentiometer adjusts the generator set frequency. Switch controls the operation of the synchroscope (sync) lights. Potentiometer adjusts the generator set output voltage.
The manual paralleling controller has all the features of the 16-light microprocessor controller described in Section 2.3, Microprocessor Controllers Features, plus additional features used for manual paralleling. For generator controller features and operation procedures, see Section 2.3, Microprocessor Controllers. For identification of the features unique to the manual paralleling controller and an explanation of their functions, refer to Figure 2-20 and Figure 2-21.
Reverse power reset pushbutton Speed adjustment potentiometer Synchroscope switch (OFF/ON) Voltage adjustment potentiometer
7
1. 2. 3. 4.
4
5. Synchroscope switch off/on 6. Speed adjustment potentiometer 7. Voltage adjustment potentiometer
A-328388
Reverse power shutdown lamp Reverse power reset pushbutton Wattmeter Sync lights
32
Section 2 Operation
TP-5750 10/03
2.4.2
Start the first generator set as described in Section 2.3.2, Normal Operation. When the generator set reaches rated voltage and frequency, close the circuit breaker to the load. The first generator set can operate from no-load to full-load rating.
7. Shut down the generator set by placing the generator set master switch in the OFF/RESET position. 8. Move the voltage-sensing lead inside the controller from terminal V9 to terminal V7. Repeat steps 1--7 for additional generator sets.
2.4.3
The manual paralleling controller setup and test procedures include the reactive droop compensation adjustment setup, paralleling the generator sets, the load-sharing module setup, and the reverse-power relay test. Perform the reactive droop compensation adjustment setup on all of the generator sets before attempting the paralleling procedure. After these setup and test procedures, the system requires no further adjustment unless components have been altered or replaced. Reactive Droop Compensation Adjustment Procedure To adjust the reactive droop compensation on 350--1600 kW generator sets, refer to TP-5579, Digital Voltage Regulator manual. Perform the following procedure to test and adjust the reactive droop compensator for 20--300 kW generator sets. Read the entire procedure before beginning. 1. Set the generator set master switch to the OFF/RESET position. 2. Set the reactive droop rheostat at minimum (full counterclockwise position). 3. Move the voltage-sensing lead inside the controller from terminal V7 to terminal V9. 4. Start the generator set and adjust the voltage to the rated system voltage using the voltage-adjusting potentiometer. 5. Check the droop compensation on each generator set as follows: a. With the first generator set operating at the rated speed and voltage, apply a resistive load (1.0 power factor) until rated current is obtained. b. Adjust the reactive droop rheostat to achieve a 6%--8% droop in voltage. 6. Remove the load from the generator set.
After completing the reactive droop compensation adjustment on all of the generator sets, use the following procedure to parallel the generator sets. Note: To avoid a reverse-power condition, do not parallel two or more generator sets without load. Reverse power can shut down one of the generator sets. If the load is less than 10% of the full-load rating of the first generator set, shut down the additional generator sets. Paralleling Procedure 1. Start the first generator set as described in Local Starting in Section 2.3.2, Normal Operation. 2. When the generator set reaches rated voltage and frequency, close the circuit breaker to the load. 3. When the load is approximately 80% of the maximum rated load for the first generator set, start an additional generator set. 4. When the incoming generator set reaches rated voltage and frequency, place the sync-light switch in the ON position. 5. Use the speed potentiometer to adjust the frequency of the incoming generator set until the sync-lights darken from brightest to fully dark in a minimum of 20 seconds. 6. After the sync-lights are dark for a minimum of 2 seconds, close the incoming generator set circuit breaker. 7. Observe the wattmeters of the paralleled generator sets. Adjust the speed potentiometer of the second generator set to share the load proportionally with the first generator set. Repeat the above procedure to parallel additional generator sets.
TP-5750 10/03
Section 2 Operation
33
Reactive Droop Compensation Test After paralleling the generator sets, use the following procedure to ensure that the generator sets are sharing the reactive load. 1. Check the wattmeters to verify that each generator set is carrying equal kW load or a load proportional to its capacity. If the loads are incorrect, adjust and recheck the governor throttle control to balance loading. The engine speed determines the load-sharing ability. 2. With the load balanced, check the ammeters to verify that the current is proportional to the generator set capacities. If the currents are incorrect, adjust the reactive droop rheostat to reduce the highest reading. Load-Sharing Module Setup Procedure Use the following procedure to load-sharing module for a 3% droop. calibrate the
8. If the governors are unstable when the generator sets are paralleled, repeat steps 4--7 and gradually increase the percentage of droop until stable. Note: If there is unequal loading of the phases, the droop is not linear but the units share the load proportionally. Reverse-Power Relay Test Procedure Perform the following steps to test the reverse-power relay. Read the entire procedure before beginning. 1. Start the generator set and adjust the voltage to the rated system voltage using the voltage-adjustment potentiometer. 2. Close the generator sets circuit breaker. 3. Press the PUSH TO TEST switch on the reversepower relay module. The generator sets circuit breaker opens and the reverse-power relay shutdown lamp lights. 4. Press the reverse-power reset button to reset the relay. Repeat steps 1--4 for any additional generator sets.
1. With the droop adjustment potentiometer in the fully counterclockwise position, calibrate the 8000 governor as described in TP-5739, DYNA 8000 Technical Manual. 2. Set the no-load speed to the rated frequency. 3. Adjust the AC line voltage for rated value. 4. Start the first generator set and apply 100% load. 5. While monitoring the frequency, adjust the droop set potentiometer clockwise to achieve 3% droop. 6. Unload the generator set and repeat steps 1--4 on the remaining generator sets. 7. After adjusting the generator sets for equal droop, parallel the generator sets. See the procedure for paralleling generator sets.
2.4.4
Disconnect a generator set when the total system load drops to less than 50% of the lowest single generator set rating. Open the circuit breaker of the desired generator set to remove it from the load. Allow the generator set to run unloaded for a minimum 5-minute cooldown period, then place the engine control switch in the OFF/RESET position to shut down the generator set.
34
Section 2 Operation
TP-5750 10/03
2.5.1
Figure 2-23 and Figure 2-24 describe the controls and indicators located on the controller.
13
1. 2. 3. 4. 5. 6. 7. Frequency meter AC voltmeter AC ammeter Scale lamps (upper/lower) Selector switch Hourmeter Generator set master switch
12
11
10
8. 9. 10. 11. 12. 13.
ADV-5849E-B
Voltage adjustment potentiometer Fault lamp 10-amp controller fuse DC voltmeter Water temperature gauge Oil pressure gauge
Item AC ammeter
Description Meter displays the AC output amperage. Use the selector switch to choose the phase currents. Meter displays the AC output voltage. Use the selector switch to choose the output lead circuits. Meter displays the voltage of the starting battery(ies). Lamp illuminates during engine shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, overcrank, or overspeed. See Section 2.5.4, Fault Shutdowns, for additional shutdown information. Meter displays the frequency (Hz) of the generator set output. Switch functions as the controller reset and generator set operation switch.
Item Hourmeter
Description Hourmeter records the generator set total operating hours for reference in maintenance scheduling. Gauge displays the engine oil pressure. Lamps indicate which AC voltmeter and/or ammeter scales to read. Switch selects the generator set output circuits to measure. When switched to a position with three circuit labels, the meters display the amperage on the lead shown in the upper label and the voltage between the two leads shown in the lower label. The AC ammeter and voltmeter function only with the switch in the ON position. Potentiometer fine tunes (5%) the generator set output voltage. Gauge displays the engine coolant temperature. Fuse protects the controller circuitry from short circuits and overloads.
AC voltmeter
2.5.2
The fault lamp does not stay lit after the generator set shuts down on a fault condition.
Fault High engine temperature Description Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup. Note: The high temperature shutdown functions only when the coolant level is in the operating range. Shutdown occurs 5 seconds after the fault. The low coolant level shutdown does not function during the first 5 seconds after startup. Shutdown occurs 5 seconds after the fault. The low oil pressure shutdown does not function during the first 5 seconds after startup. Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Shutdown occurs after 30 seconds of continuous cranking. Shutdown occurs 30 seconds after startup if there is no AC output. Shutdown occurs immediately when the governed frequency on the 50 and 60 Hz models exceeds 70 Hz.
Local Starting. Move the generator set to the RUN position to immediately start the generator set. Automatic Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or the remote start/stop switch connected to controller terminals TB1-3 and TB1-4. Note: The controller allows up to 30 seconds of continuous cranking before overcrank shutdown occurs.
2.5.3
Local Stopping 1. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown. 2. Move the generator set master switch to the OFF/RESET position. The engine stops. Automatic Stopping
Overcrank
Overspeed
1. The automatic transfer switch (ATS) or other device disconnects the load from the generator set. 2. The generator set continues to run for a preset time if the ATS is equipped with an engine cooldown time delay. 3. The ATS opens the connection between controller terminals TB1-3 and TB1-4. The generator set shuts down if the generator set master switch is in the AUTO position.
2.5.5
Use the following procedure to restart the generator set after a fault shutdown. 1. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch. See the Safety Precautions at the beginning of this section before proceeding. 2. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding. 3. Start the generator set by moving the generator set master switch to RESET/OFF and then to RUN. 4. Verify that the cause of the shutdown has been corrected by test operating the generator set. 5. Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch. 6. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
2.5.4
Fault Shutdowns
The generator set shuts down automatically under the fault conditions shown in Figure 2-25 and cannot be restarted until the fault condition is corrected. The generator set shutdown switches automatically reset when the problem is corrected. Reset the controller after a fault shutdown.
36
Section 2 Operation
TP-5750 10/03
Description Meter displays the voltage of the starting battery(ies). Lamp illuminates during engine shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, overcrank, or overspeed. See Section 2.6.4, Fault Shutdowns, for additional shutdown information. Switch functions as the controller reset and generator set operation switch. Hourmeter records the generator set total operating hours for reference in maintenance scheduling.
Oil pressure gauge Gauge displays the engine oil pressure. Voltage adjustment Potentiometer fine tunes (5%) the potentiometer generator set output voltage. 8 7 6 5 4
ADV-5849F-B
Gauge displays the engine coolant temperature. Fuse protects the controller circuitry from short circuits and overloads.
1. 2. 3. 4. 5. 6. 7. 8.
Hourmeter DC voltmeter Water temperature gauge Oil pressure gauge Voltage adjustment potentiometers Fault lamp 10-amp controller fuse Generator set master switch
2.6.3
Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown. Local Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops. Automatic Stopping. The automatic transfer switch or other device disconnects the load from the generator set and opens the connection between controller terminals TB1-3 and TB1-4. The generator set shuts down if the generator set master switch is in the AUTO position.
2.6.1
Figure 2-27 describes the controls and indicators located on the controller.
2.6.2
Local Starting (Nonautomatic). Move the generator set master switch to the RUN position to start the generator set. Automatic Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or remote start/stop switch (connected to controller terminals TB1-3 and TB1-4). Note: The controller allows up to 30 seconds of continuous cranking before the overcrank shutdown occurs.
TP-5750 10/03
Section 2 Operation
37
2.6.4
Fault Shutdowns
The generator set shuts down automatically under the fault conditions shown in Figure 2-28 and cannot be restarted until the fault condition is corrected. The generator set shutdown switches automatically reset when the problem is corrected. Reset the controller after a fault shutdown.
Fault Description
2. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding. 3. Start the generator set by moving the generator set master switch to RESET/OFF and then to RUN. 4. Verify that the cause of the shutdown has been corrected by test operating the generator set. 5. Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch. 6. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
High engine Shutdown occurs 5 seconds after the fault. temperature The high engine temperature shutdown does not function during the first 5 seconds after startup. Note: The high temperature shutdown functions only when the coolant level is in the operating range. Low coolant Shutdown occurs 5 seconds after the fault. level The low coolant level shutdown does not function during the first 5 seconds after startup. Low oil pressure Shutdown occurs 5 seconds after the fault. The low oil pressure shutdown does not function during the first 5 seconds after startup. Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Shutdown occurs after 30 seconds of continuous cranking. Shutdown occurs 30 seconds after startup if there is no AC output. Shutdown occurs immediately when the governed frequency on 50 and 60 Hz models exceeds 70 Hz.
Overcrank
Overspeed
2.6.5
5
1. 2. 3. 4. 5.
A-227600
Use the following procedure to restart the generator set after a fault shutdown. 1. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch. See the Safety Precautions at the beginning of this section before proceeding.
Hourmeter Voltage adjust potentiometer 10-amp controller fuse Fault lamp Generator set master switch
38
Section 2 Operation
TP-5750 10/03
2.7.1
2.7.3
Figure 2-30 describes the controls and indicators located on the controller.
Item Fault lamp Description Lamp illuminates during engine shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, overcrank, or overspeed. See Section 2.7.4, Fault Shutdowns, for additional shutdown information. Switch functions as the controller reset and generator operation switch. Hourmeter records the generator set total operating hours for reference in maintenance scheduling. Potentiometer fine tunes (5%) generator output voltage. Fuse protects the controller circuitry from short circuits and overloads.
Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown. Local Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops. Automatic Stopping. The automatic transfer switch or other device disconnects the load from the generator set and opens the connection between controller terminals TB1-3 and TB1-4. The generator set shuts down if the generator set master switch is in the AUTO position.
2.7.4
Fault Shutdowns
The generator set shuts down automatically under the fault conditions shown in Figure 2-31 and cannot be restarted until the fault condition is corrected. The generator set shutdown switches automatically reset when the problem is corrected. Reset the controller after a fault shutdown.
Fault High engine temperature Description Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup. Note: The high temperature shutdown functions only when the coolant level is in the operating range.
2.7.2
Local Starting. Move the generator set master switch to the RUN position to immediately start the generator set. Automatic Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or the remote start/stop switch (connected to controller terminals TB1-3 and TB1-4). Note: The controller allows up to 30 seconds of continuous cranking before the overcrank shutdown occurs.
Overcrank
Low coolant level Shutdown occurs 5 seconds after the fault. Low coolant level shutdown does not function during the first 5 seconds after startup. Low oil pressure Shutdown occurs 5 seconds after the fault. Low oil pressure shutdown does not function during the first 5 seconds after startup. Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine. Shutdown occurs after 30 seconds of continuous cranking. Shutdown occurs 30 seconds after startup if there is no AC output. Shutdown occurs immediately when the governed frequency on 50 and 60 Hz models exceeds 70 Hz.
Overspeed
TP-5750 10/03
Section 2 Operation
39
2.7.5
4. Verify that the cause of the shutdown has been corrected by test operating the generator set. 5. Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch. 6. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
Use the following procedure to restart the generator set after a fault shutdown. 1. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch. See the Safety Precautions at the beginning of this section before proceeding. 2. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding. 3. Start the generator set by moving the generator set master switch to RESET/OFF and then to RUN.
1 2
OFF
3%%129 L3 L3--L1
HERTZ
A--C VOLTS
A--C AMPERES
L2 L1--L2
L1 L1--L2
L1 L1--L2
AMPS VOLTS
L2 L2--L3
VOLTAGE
1/16
00000
TOTAL HOURS
ADJUST
OIL PRESS
WATER TEMP
BATTERY
STOP
ADV-5849C-F
13
12
11
10
1. 2. 3. 4. 5. 6. 7.
Frequency meter AC voltmeter AC ammeter Scale lamps (upper/lower) Selector switch Generator set master switch 10-amp fuse
Fault lamp DC voltmeter Water temperature gauge (if equipped) Voltage adjustment (if equipped) Oil pressure gauge Hourmeter
40
Section 2 Operation
TP-5750 10/03
2.8.1
2.8.2
Figure 2-33 describes the controls and indicators located on the controller.
Item AC voltmeter Description Meter displays the AC output voltage. Use the selector switch to choose the output lead circuits. Meter displays the AC output current in amps. Use the selector switch to choose the phase currents. Meter displays the voltage of the starting battery(ies). Lamp illuminates during engine shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, or overspeed. See Section 2.8.4, Fault Shutdowns, for additional shutdown information. Meter displays the frequency (Hz) of the generator set output. Meter displays the engine oil temperature. Note: The 20--40 kW models substitute an engine oil temperature gauge for the water temperature gauge.
Place and hold the controller or remote start/stop switch in the START position until the engine is running, then release. If the engine fails to start after cranking for 5--10 seconds, release the switch. Wait 60 seconds to allow the engine to stop cranking completely and cool down before the next start attempt. Note: Do not crank the engine continuously for longer than 10 seconds. If engine does not start, allow a 60-second cooldown period between cranking attempts. If unit fails to start after three attempts, contact an authorized service distributor/dealer for repair. Failure to follow these guidelines may result in starter-motor burnout.
AC ammeter
2.8.3
Run the generator set at no load for 5 minutes to ensure adequate engine cooldown. To stop the generator set, place the controller start/stop switch or remote start/stop switch in the STOP position and wait until the generator set stops completely.
Generator set Switch functions as the controller reset master switch and generator set operation switch. Hourmeter Hourmeter records the generator set total operating hours for reference in maintenance scheduling. Gauge displays the engine oil pressure. Lamps indicate which AC voltmeter and/or ammeter scales to read. Switch selects the generator set output circuits to measure. When switched to a position with three circuit labels, the ammeter measures current on the upper lead and the voltmeter measures voltage between the lower two leads. The AC ammeter and voltmeter do not register with the switch in the OFF position. The labels 1 and 3 indicate single-phase and three-phase voltage/current respectively.
2.8.4
Fault Shutdowns
The generator set shuts down automatically under the fault conditions shown in Figure 2-34 and cannot be restarted until the fault condition is corrected. The generator set shutdown switches automatically reset when the problem is corrected or the generator set cools (if overheating was the problem).
Fault Description
High engine Shutdown occurs 5 seconds after the fault. temperature The high engine temperature shutdown does not function during the first 5 seconds after startup. Note: Water-cooled engines only. The high temperature shutdown functions only when the coolant level is in the operating range. Low coolant level Low oil pressure Shutdown occurs 5 seconds after the fault. Low coolant level shutdown does not function during the first 5 seconds after startup. Shutdown occurs 5 seconds after the fault. Low oil pressure shutdown does not function during the first 5 seconds after startup. Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.
Voltage Potentiometer fine tunes (5%) the adjustment generator set output voltage. potentiometer Note: Used with 20--300 kW models only; 300--2000 kW models have the voltage adjustment located in the generator junction box. Water temperature gauge Gauge displays the engine coolant temperature.
10-amp Fuse protects the controller circuitry from controller fuse short circuits and overloads.
Overspeed Shutdown occurs immediately when the governed frequency on 50 and 60 Hz models exceeds 70 Hz. AC interlock Shutdown occurs when the start/stop switch is released if there is no AC output.
TP-5750 10/03
Section 2 Operation
41
Note: The fault lamp does not stay lit after the unit shuts down on a fault condition.
Description Use the plug to connect the wiring harness from the generator set governor control, crank relays, safety shutdown switches, and gauge senders to the gauge box terminal strips. Meter displays the voltage of the starting battery(ies).
The paralleling engine gauge box provides the connectors and terminal strips needed to connect the generator set to switchgear-mounted controls. Each generator set in the paralleling system requires an engine gauge box. Some engine gauge box models include an emergency stop switch; the engine gauge box contains no other operating controls. The switchgear contains the generator set operating controls. A connection plug connects the generator set governor, crank relays, safety shutdown switches (high water temperature, low oil pressure, and low coolant level), and gauge senders to gauge box terminal strips. The appropriate terminals on the terminal strips are then hard-wired to the switchgear controls.
Gauge box Use the terminal strips to connect the terminal strips switchgear control wiring to the generator set governor control, crank relays, safety shutdown switches, gauge senders, etc. Hourmeter Hourmeter records the generator set total operating hours for reference in maintenance scheduling. Gauge displays the engine oil pressure. Switch signals the switchgear engine control logic to disconnect the starter motor after startup or to shut down the system if an overspeed fault occurs. The speed switch settings for crank and overspeed are adjustable. Switch Immediately shuts down the generator set in emergency situations. Reset the emergency stop switch after shutdown by rotating the switch clockwise. Use the emergency stop switch for emergency shutdowns only. Use the generator set master switch for normal shutdowns. The local emergency stop switch is standard on Detroit Diesel engine-powered 200--2000 kW generator sets. Gauge displays the engine coolant temperature.
Controller Features
The gauge box also includes an electronic speed switch with overspeed and crank outputs. For identification and explanation of paralleling meter box components, refer to Figure 2-35 and Figure 2-36.
1 2
TP-5633-2
5
1. 2. 3. 4. 5.
Hourmeter Emergency stop switch (if equipped) DC voltmeter Water temperature gauge (if equipped) Oil pressure gauge
42
Section 2 Operation
TP-5750 10/03
WARNING
WARNING
WARNING
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
TP-5750 10/03
43
D Follow procedures and frequencies indicated in the engine manufacturers maintenance manual. If not indicated, follow this service schedule. Some items may not apply to all generator sets. R Replace as necessary. X Action * Service more frequently if operated in dusty areas.
44
TP-5750 10/03
D Follow procedures and frequencies indicated in the engine manufacturers maintenance manual. If not indicated, follow this service schedule. Some items may not apply to all generator sets. R Replace as necessary. X Action. * Service more frequently if operated in dusty areas. [ Do not break manufacturers seals or internally inspect these devices.
TP-5750 10/03
45
1. Place the fuel valves in the fuel system prime position. Close the fuel valve located between the pipe tee and the engine. Open the fuel valves on each side of the fuel prime pump. See Figure 3-1.
3.4.1
20-300 kW Models
Replace the end bracket bearing every 10,000 hours of operation in standby and prime power applications. Service the bearing more frequently if the annual inspection indicates excessive rotor end play or bearing damage. Replace the tolerance ring, if equipped, following end bracket removal. The sealed end bracket bearing requires no additional lubrication.
3.4.2
The alternator bearing requires lubrication at intervals specified in the generator technical manual. Use Chevron SRI or equivalent antifriction, high-quality grease with a lubrication temperature range of --30 to 175C (--22 to 350F).
Valve Open
Valve Closed
3.4.3
PK-272000-H
Figure 3-1
Refer to the generator set service manual for bearing maintenance information.
Hand Prime Pump with Valve Positions for Fuel Priming (Generator Set Without a Fuel/Water Separator Shown)
Note: The illustration shows a generator set without a fuel/water separator. The valve location and position for a generator set equipped with a fuel/water separator is similar. 2. Loosen the bleed screw at the engine. Refer to the engine operation manual for location of the bleed screw(s). The bleed screw allows air to be expelled from the fuel system when the hand prime pump is operated. 3. Rotate the hand prime pump handle counterclockwise until fuel flows from the bleed screw. Stop pumping. 4. Tighten the bleed screw. Wipe up any fuel leakage. 5. Place the fuel valves in the normal operation position. Open the fuel valve located between the pipe tee and the engine. Close the fuel valves on each side of the fuel prime pump.
Bleed air from the fuel system after fuel system maintenance, such as replacing the fuel filter(s) using the hand prime pump kit, when equipped. The hand prime fuel pump eliminates the need for cranking the engine to bleed air from the fuel system. Note: Bleed air from the fuel system according to the engine manufacturers instructions. Trapped air in the fuel system causes difficult starting and/or erratic engine operation. Note: Correct any fuel leaks encountered during the priming procedure.
46
TP-5750 10/03
3.5.2
Level Sensor
An electronic analog float gauge located below the ECM on the mounting bracket determines the day tank fuel level. Nine LEDs on the ECM indicate the day tank fuel level from full to empty.
With an electronic control module (ECM), the optional subbase diesel fuel tank functions as a day tank. Following are operating information and features of the ECM. See Figure 3-2 for the ECM front panel layout.
ECM Mode
The ECM has three pushbutton switches for normal operation and one internal test button. See Figure 3-4.
Pushbutton Off On Description Pushbutton disables the ECM for routine maintenance to the tank system. Pushbutton activates the ECM after the OFF pushbutton is depressed. On powerup after a power outage, the ECM automatically turns on. Pushbutton lights front panel LEDs for 3 seconds and activates the pump/motor for as long as the pushbutton is depressed. The alarm relays maintain their original positions. Pushbutton (located inside the ECM) tests each alarm LED and remote annunciation relay in sequential order (high fuel to ECM functional).
Test
224825
Internal test
Figure 3-2
Servicing the day tank. Hazardous voltage can cause severe injury or death. Service the day tank electrical control module (ECM) as prescribed in the equipment manual. Disconnect the power to the day tank before servicing. Press the day tank ECM OFF pushbutton to disconnect the power. Notice that line voltage is still present within the ECM when the POWER ON light is lit. Ensure that the generator set and day tank are electrically grounded. Do not operate the day tank when standing in water or on wet ground because these conditions increase the risk of electrocution.
Figure 3-4
ECM Pushbuttons
ECM Alarms
The ECM has five standard alarm conditions indicated locally by LEDs and remotely by relays. Figure 3-5 describes the five alarm conditions. Make customer connections to the normally open and normally closed relay contacts provided.
Alarm High fuel Low fuel Description Alarm activates at 106% of normal fuel level. Alarm activates at 62% of normal fuel level. The alarm provides time to respond to a potential problem before a low fuel shutdown occurs. Alarm activates at 6% of normal fuel level to warn the operator to shut down the generator set before fuel runs out.
Fuel in rupture Alarm activates when the ECM basin, if equipped detects fuel in the rupture basin. ECM functional Alarm activates to indicate a problem with the ECM operation. Note: The ECM functional alarm relay activates a customer-installed alarm when the relay deenergizes.
Figure 3-3
TP-5750 10/03
3.5.3
This kit provides for both audible and visual alarm from a location remote from the generator set if a leak is detected in the inner fuel tank of the double-wall subbase fuel tanks. See Figure 3-6. If the inner tank is leaking, a sensor installed in the outer tank sends an electrical signal to the alarm plate when the sensor becomes immersed in the fuel collecting in the outer tank. If a leak is detected, the alarm horn will sound and the fault lamp will light. The alarm horn is quieted by moving the alarm switch to the SILENCE position; the alarm lamp remains lit until the fault is corrected. See Figure 3-7 for troubleshooting information.
Alarm Float Switch Switch Position Position Observation Normal Normal Open Closed The alarm horn and the lamp are not energized. The alarm horn and lamp activate when a fuel leak occurs. If the alarm switch is moved to the silence position the lamp stays on until the fuel leak fault is corrected. The alarm horn sounds to alert the user that the alarm horn switch is not in the normal position and that the alarm horn will not sound should a fuel leak occur.
Silence
Open
Figure 3-7
Inner Tank Fuel Leak Alarm
Resetting Procedure
Use the following procedure to reset the alarm after a fault alarm. 1. Move alarm switch to the SILENCE position to stop alarm horn. Lamp will remain lit.
2. Disconnect generator set from load with line circuit breaker or automatic transfer switch. 3. Repair or replace the inner fuel tank. 4. Move generator master switch to the OFF/RESET position and then to the RUN position for startup. Alarm horn sounds and lamp goes out. 5. Reconnect generator to load via line circuit breaker or automatic transfer switch. 6. Move generator master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch. Move alarm switch to the NORMAL position.
FF-273000-D
Figure 3-6
48
TP-5750 10/03
3.6.3
3.6.1
Most models operate on either LP gas or natural gas fuel by performing the fuel conversion procedure. Some models require a different fuel kit when changing gas fuels. Consult your local generator distributor/dealer for additional information. Fuel conversion may decrease generator set output and affect exhaust emissions. Consult your local generator distributor/dealer for additional information. Fuel Conversion Procedure When converting the generator set to operate with LP gas, remove the internal spring from the secondary regulator. Install the spring to operate the generator set on natural gas. Note: Not all fuel regulators require spring and retainer removal for fuel conversion. A hang tag on the fuel regulator identifies the conversion procedure. LP Fuel Conversion Procedure Use the following steps to remove the internal spring from the fuel regulator: 1. Remove the fuel regulator cover plug. Figure 3-9. See
The gaseous fuel system uses a fuel valve with a solenoid to control the fuel flow to the fuel regulator. The generator-mounted regulator reduces the fuel pressure as fuel passes to the carburetor. See Figure 3-8. The carburetor/mixer controls the ratio of fuel to air under varying load and speed conditions. Because the carburetor receives fuel in a gaseous state, it does not have to vaporize the fuel. When switching from natural gas to LP gas or LP gas to natural gas, verify that the electronic governor maintains the rated engine speed (1800 rpm at 60 Hz or 1500 rpm at 50 Hz). If the engine speed is incorrect, refer to the generator service manual for the governor adjustment procedure.
1
TP-5750-3
1. 2. 3. 4. 5.
Primary regulator (supplied by gas supplier or customer) Pressure gauge Solenoid valve Secondary regulator Carburetor
Figure 3-8
3.6.2
With the LP liquid withdrawal fuel system, pressurized liquid LP fuel passes from the tank to a vaporizer. The vaporizer converts the liquid fuel to gas before sending it to the carburetor. The system also includes a fuel valve that shuts off the fuel flow when the engine stops. Contact an authorized service distributor/dealer for availability.
1. 2. 3. 4.
Figure 3-9
2. Remove the adjustment screw and spring from the fuel regulator. Save the adjustment screw and spring for possible conversion back to natural gas. 3. Reinstall the cover plug.
TP-5750 10/03
49
Natural Gas Fuel Conversion Procedure Use the following steps to convert the generator set to natural gas: 1. Remove the fuel regulator cover plug. Figure 3-9. 2. Replace the spring and adjustment screw. 3. Connect a manometer to check the fuel supply pressure on the carburetor side of the regulator downstream of any fuel system equipment accessories. The recommended fuel supply pressures are shown on the generator set spec sheet. 4. Adjust the fuel supply pressure with the generator set running at full load. Rotate the adjustment screw on the fuel regulator until the pressure indicated by the manometer matches the specified pressure. Use the lower pressure value if the generator set still provides good response and full power. Lower-than-specified pressures may result in poor response to load changes or lack of power. 5. Reinstall the cover plug. See
3.6.4
Automatic Changeover
A changeover fuel system kit provides automatic changeover from natural gas to LP gas vapor or from LP gas vapor to natural gas. The primary and backup fuels each have a secondary fuel regulator and a fuel valve. Typically, the primary fuel is natural gas; the backup fuel is LP gas vapor. When the generator set starts, the primary fuel valve opens and the backup fuel valve closes. The primary fuel line has a vacuum switch in series with a relay connected to the start/run circuit. When the primary fuel pressure drops below 0.6 kPa (1.4 oz./in.2) or 6.4 cm (2.5 in.) water column , a relay opens the backup fuel valve and closes the primary fuel valve. When the primary fuel pressure rises above 0.6 kPa (1.4 oz./in.2) or 6.4 cm (2.5 in.) water column, the generator set uses the primary fuel. Contact an authorized service distributor/dealer for kit availability.
Manual Changeover
A manual changeover fuel system allows manual changeover from gasoline to natural gas or LP gas, or from natural gas or LP gas to gasoline. Typically, the combination system uses gas as the primary, preferred fuel and gasoline in emergencies. If the primary fuel is unavailable (an empty fuel tank or fuel supply disruption), the system uses gasoline. A toggle switch on the generator set controls the fuel choice and energizes either a fuel solenoid and electric fuel pump for gasoline or a fuel valve for gas. Pull out the control cable for gasoline and push in the control cable for gas.
50
TP-5750 10/03
3.6.5
Carburetor Adjustment
3.6.6
Before adjusting the carburetor, verify that the engine compression and the ignition system meet specifications. Do not adjust the carburetor to compensate for other engine disorders. If the engine speed is incorrect, adjust the electronic governor to achieve 1800 rpm (at 60 Hz) or 1500 rpm (at 50 Hz). Adjust the carburetor if governor adjustment alone does not result in the desired engine speed. Adjusting the carburetor affects the engine fuel mixture. Routine carburetor adjustment is not necessary. However, if the carburetor is removed or tampered with, the carburetor may require adjustment to achieve optimum engine performance. Some engines have sealed carburetors that are not adjustable.
Gasoline Models
Clean or replace the fuel filter at the specified interval. Service the filters more frequently if the engine runs roughly, as a clogged fuel filter can cause rough engine operation. Some models use a disposable inline fuel filter, which must be replaced. Other models have a fuel pump with an integral fuel filter that requires cleaning at the specified interval.
Gaseous Models
This fuel system requires no regular maintenance.
3.7.1
The engine and generator manufacturers engine oil viscosity recommendations for engines used in generator applications differ from the recommendations for engines used in other applications. Use oil that has a minimum rating of (API) classification SH/CD, SG/CD, SH/CC, or SG/CC to ensure long life and minimal engine wear. See Figure 3-11 for oil viscosity selection for the Ford-powered models listed above.
For Air Temperatures Consistently Above 0C (32F) --23C (--10F)
TP-5750-3
Figure 3-10 Fuel Mixture Adjustment, Typical 3. Apply varying loads and readjust the carburetor as necessary to achieve smooth engine performance at all load levels. 4. Stop the generator set.
TP-5750 10/03
51
3.7.2
3.7.3
Turbocharger Maintenance
After changing the engine lube oil, use the following procedure to prime the turbocharger bearing to prevent premature turbocharger bearing wear. 1. Place the generator set master switch in the OFF/RESET position. 2. Disconnect the wire between the ignition coil and the distributor at the distributor terminal. Connect a jumper wire from the ignition coil lead to the engine block. Note: Electronic Ignition Damage. Ground the ignition coil to the engine block to prevent electronic ignition system damage. 3. Place an oil-collection container under the oil drain line. Disconnect the turbocharger oil drain line at the engine connection. 4. Place the generator set master switch in the RUN position to crank the engine until fresh oil flows from the turbocharger oil drain line. Note: Starter Damage. Do not crank the engine continuously for longer than 10 seconds. Allow a 60-second cooldown period between cranking cycles to prevent starter motor and/or starter solenoid failure caused by overheating. 5. Place the generator set master switch in the OFF/RESET position. 6. Reconnect the turbocharger oil drain line at the engine connection. 7. Remove the jumper wire and reconnect the ignition coil wire to the distributor. 8. Place the generator set master switch in the RUN position, run the generator set for a few minutes, and check for oil leaks at the turbocharger drain line connection. Stop the generator set. 9. Check the oil level. Add oil to bring the level up to the full mark. Consult the engine operation manual for oil capacity. 10. Wipe up spilled oil and dispose of rags in a fireproof container.
Service Check for abnormal turbo rotor noise during operation (e.g., high frequency pitch) and check for oil leakage at the turbocharger. Check turbo rotor shaft for wear (end play and radial tolerances). Overhaul turbocharger.* Change lube oil. Change lube oil filter. Change air filter.
WARNING
Hot coolant and steam. Can cause severe injury or death. Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
52
TP-5750 10/03
Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool. Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.
deteriorated cap. Remove dirt and other debris from the pressure cap and filler neck. The pressure cap raises the boiling point of the coolant, enabling higher operating temperatures. Replace a leaking pressure cap with one rated for the same pressure. The pressure cap rating usually appears on the pressure cap.
Note: Engine damage. Bleed the air from the cooling system to prevent overheating and subsequent engine damage. Note: Block heater damage. The block heater will fail if the energized heater element is not immersed in coolant. Fill the cooling system before turning on the block heater. Run the engine until it is warm, and refill the radiator to purge the air from the system before energizing the block heater.
3.8.3
For optimum protection, drain, flush, and refill the cooling system at the intervals listed in the service schedule. Note: Dispose of all waste materials (oil, fuel, coolant, filters, and gaskets) in an environmentally safe manner. 1. Deenergize the block heater, if equipped.
3.8.1
Check the coolant level in the coolant recovery tank, if equipped. Maintain the coolant level between the high and low marks. Note: Periodically check the coolant level by removing the pressure cap. Do not rely solely on the level in the coolant recovery tank. Add fresh coolant until the level is just below the overflow tube opening of the filler neck.
3.8.2
3.8.4
Remove dirt and foreign material using a soft brush or cloth to avoid damaging the radiator fins.
D Check the hoses and connections for leaks. Replace
Use the instructions in the engine operation manual when available to flush and clean the cooling system. Otherwise, use the following procedure and the cooling system cleaner manufacturers instructions. 1. Flush the cooling system with clean water. 2. If the inside of the radiator still has mineral deposits, use a radiator cleaner to remove the remaining deposits following the manufacturers instructions. 3. Drain, clean, and flush the coolant recovery tank.
and water pump belt(s). Follow the belt tension procedure in this manual and/or the engine operation manual.
TP-5750 10/03
53
3.8.5
10. Remove the pressure cap. 11. Add coolant to bring the coolant level to just below the overflow tube opening of the filler neck. 12. Replace the pressure cap. 13. Maintain the coolant level in the coolant recovery tank between the high and low marks. Note: Air pockets often form in the engine water jacket when the coolant system is refilled. Check the coolant level in the coolant recovery tank after each generator set operation and add coolant as necessary until the coolant level stabilizes. Then check the coolant at the interval specified in the service schedule. 14. Reenergize the block heater, if equipped.
See the generator set spec sheet for coolant capacity. Note: Do not add coolant to a hot engine. Adding coolant to a hot engine can cause the cylinder block or cylinder head to crack. Wait until the engine has cooled. 1. Remove the pressure cap. 2. Close the radiator and/or engine block coolant drain valve(s) and tighten the cooling system hose clamps. 3. Open the air-bleed petcocks, if equipped. Close the air-bleed petcocks when coolant begins to flow from them. 4. Add coolant additives or water pump lubricants according to the engine manufacturers recommendations in the engine operation manual. 5. Fill the cooling system with the recommended coolant/antifreeze mixture of 50% ethylene glycol and 50% clean, softened water to inhibit rust/corrosion and prevent freezing. Note: A coolant solution of 50% ethylene glycol provides freezing protection to --37C (--34F) and overheating protection to 129C (265F). A coolant solution containing less than 50% ethylene glycol may not provide adequate freezing and overheating protection. A coolant solution containing more than 50% ethylene glycol can cause engine or component damage. Do not use alcohol or methanol antifreeze or mix them with the specified coolant. Refer to the engine operation manual for recommendations regarding the coolant mixture to use in extreme temperatures. 6. Replace the pressure cap. 7. Fill the coolant recovery tank to the low mark. 8. Operate the generator set until the thermostat opens when the upper cooling system hose warms. 9. Stop the engine and allow it to cool.
TP-5353-3
1. 2. 3. 4.
Air flow Expansion joint nuts for rear tank, left side Expansion joint nuts for front tank, left side Top front of radiator
Figure 3-13 Expansion Joint Nuts, Top Left Side of Radiator, Typical
54
TP-5750 10/03
7. Reinstall the belt guards using the original hardware. 8. Reconnect the generator set engine starting battery(ies), negative (--) lead last. 9. Test run the generator set for a few minutes and listen for belt noise (squeal) indicating a slipping belt. Stop the generator set. If the belt slips after the belt tension procedure, clean the pulley surfaces and repeat the belt tension procedure. If slippage continues, replace the fan belt.
1
5 2
4 2 3
TP-5353-3
1
1. 2. 3. 4. 5. Grease fittings Pressure relief port Radiator assembly Idler shaft grease fittings Fan shaft grease fittings
Figure 3-15 Radiator Fan Bearings and Pressure Relief Ports, Typical
TP-5750 10/03
55
3.11 Battery
WARNING
Battery acid cleanup. Battery acid can cause severe injury or death. Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery gases. Explosion can cause severe injury or death. Battery gases can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases. Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together. Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Refer to this section for general battery information and maintenance. All generator set models use a negative ground with a 12-volt or 24-volt engine electrical system. Consult the generator set nameplate for the engine electrical system voltage. Consult the generator spec sheet for battery capacity recommendations for replacement purposes. The wiring diagrams provide battery connection information. See Figure 3-16, Figure 3-17, and Figure 3-18 for typical battery connections, including multiple battery configurations.
2 1 2
EZ-273000-J
1. To positive (+) terminal on starter solenoid. 2. To ground (--) terminal on or near starter motor.
Figure 3-16 12-Volt Engine Electrical System Single Starter Motor Typical Battery Connection
56
TP-5750 10/03
3.11.1 Cleaning
Clean the battery and cables and tighten the battery terminals according to the service schedule recommendations. Clean the battery by wiping it with a damp cloth. Keep the electrical connections dry and tight. If corrosion exists, disconnect the cables from the battery and remove the corrosion with a wire brush. Clean the battery and cables with a solution of baking soda and water. Do not allow the cleaning solution to enter battery cells. Flush the battery and cables with clean water and wipe the battery with a dry cloth.
2 1
1 2
After reconnecting the battery cables, coat the terminals with petroleum jelly, silicon grease, or other nonconductive grease.
Check the electrolyte level and specific gravity of batteries that have filler caps. Maintenance-free batteries do not require electrolyte level checking or specific gravity testing. Check the electrolyte level before each startup. Remove the filler caps and verify that the electrolyte level reaches the bottom of each filler hole. See Figure 3-19. Refill as necessary with distilled water or clean tap water. Do not add fresh electrolyte. Tighten the filler caps. After adding water during freezing temperatures, run the generator set 20--30 minutes to mix the electrolyte and the water to prevent battery damage from freezing.
Figure 3-17 24-Volt Engine Electrical System Single Starter Motor Typical Battery Connection
1 1 2 3 4
KW-272000-B
1. 2. 3. 4.
To positive (+) terminal on starter solenoid. To ground (--) terminal on or near starter motor. To positive (+) terminal on second starter solenoid. To ground (--) terminal on or near second starter motor. 1. Filler caps 2. Electrolyte level
2
1-046
Figure 3-18 24-Volt Engine Electrical System Dual Starter Motors Typical Battery Connections
TP-5750 10/03
57
71.1
160
65.6
150
+ .028 + .026
Example No. 1 Temperature below 26.7C (80F) Hydrometer Reading 1.250 Acid Temperature --6.7C (20F) Subtract .024 Specific Gravity Corrected Specific Gravity is 1.226 1.250 -- .024 = 1.226
60.0
140
+ .024 + .022
54.4
130
+ .020 + .018
48.9
120
+ .016 + .014
43.3
110
+ .012 + .010
37.8
100
+ .008 + .006
Example No. 2 Temperature above 26.7C (80F) Hydrometer Reading 1.235 Acid Temperature 37.8C (100F) Add .008 Specific Gravity Corrected Specific Gravity is 1.243 1.235 + .008 = 1.243
32.2
90
+ .004 + .002
26.7
80
0 - .002
21.1
70
- .004 -. 006
15.6
60
- .008 - .010
10
50
- .012 - .014
4.4
40
- .016 - .018
- 1.1
30
- .020 - .022
- 6.7
20
- .024 - .026
- 12.2
10
- .028
The temperature correction amounts to about .004 (4 points) of specific gravity for each 5.5C (10F) change in temperature.
1-787
58
TP-5750 10/03
3.11.4 Charging
Use a battery charger to maintain a fully charged battery when the generator set is used in a standby application. The engine battery-charging alternator charges the battery only while the generator set is running. Note: If the generator set is in a temporary prime power application in which the generator set has periods of inactivity, the controller circuitry may drain the battery. If there is no power source for a battery charger, place the controller in the prime power mode, if equipped, or disconnect the battery from the generator set.
control box. ECM memory software logs malfunction codes. Consult the engine operation manual or engine service manual to identify the stored failure code. See Figure 3-22 for the DDEC control box features.
Figure 3-22 DDEC Control Box Access the stored codes in one of three ways:
D Place the switch in the DIAGNOSTIC REQUEST
Place the switch in the DIAGNOSTIC DATA READER position. Plug the DDR into the control box. The DDR displays the stored failure codes.
D Use a personal computer software package with a
translator to access stored codes. Follow the instructions provided with the software.
Code Types
Active code. A code flashing on the SEL lamp indicates a fault currently exists. Inactive code. A code flashing on the CEL lamp indicates a previous fault occurrence. The ECM memory stores inactive codes with time/date identification and the following information:
D First occurrence of each diagnostic code in engine
The major components of the DDEC system include the engine control module (ECM), engine sensors, and control box, which is located in the generator set junction box.
operating hours.
operating hours.
D Total time in seconds that the diagnostic code was
active.
TP-5750 10/03
59
2. Stop the generator set. 3. With the engine still warm, drain the oil from the crankcase. 4. Remove and replace the oil filter. 5. Refill the crankcase with oil suited to the climate. 6. Run the generator set for two minutes to distribute the clean oil. 7. Stop the generator set. 8. Check the oil level and adjust, if needed.
Diesel-Fueled Engines
1. Fill the fuel tank with #2 diesel fuel. 2. Condition the fuel system with compatible additives to control microbial growth.
A-364162-B
3. Change the fuel filter/separator and bleed the fuel system. See the engine owners manual.
Gasoline-Fueled Engines
1. Add stabilizer to the fuel system. Follow the manufacturers recommended procedure. 2. Run the generator set for 15 minutes to ensure that the stabilized fuel reaches the carburetor. 3. Place the generator set master switch in the OFF/RESET position. 4. Close the fuel valve.
Gas-Fueled Engines
1. Start the generator set. 2. With the generator set running, shut off the gas supply. 3. Run the generator set until the engine stops. 4. Place the generator set master switch in the OFF/RESET position.
3.14.5 Exterior
1. Clean the exterior surface of the generator set. 2. Seal all engine openings except for the air intake with nonabsorbent adhesive tape. 3. To prevent impurities from entering the air intake and to allow moisture to escape from the engine, secure a cloth over the air intake. 4. Mask electrical connections. 5. Spread a light film of oil over unpainted metallic surfaces to inhibit rust and corrosion.
3.14.6 Battery
Perform battery storage after all other storage procedures. 1. Place the generator set master switch in the OFF/RESET position. 2. Disconnect the battery(ies), negative (--) lead first. 3. Clean the battery. Refer to Section 3.11.1 for the battery cleaning procedure. 4. Place the battery in a cool, dry location. 5. Connect the battery to a float/equalize battery charger or charge it monthly with a trickle battery charger. Refer to the battery charger manufacturers recommendations. Maintain a full charge to extend battery life.
TP-5750 10/03
61
Notes
62
TP-5750 10/03
Section 4 Troubleshooting
This section contains generator set troubleshooting, diagnostic, and repair information. Use the chart on the following page to diagnose and correct common problems. First check for simple causes such as a dead engine starting battery or an open circuit breaker. The chart includes a list of common problems, possible causes of the problem, recommended corrective actions, and references to detailed information or repair procedures. Maintain a record of repairs and adjustments performed on the equipment. If the procedures in this manual do not explain how to correct the problem, contact an authorized distributor/dealer. Use the record to help describe the problem and repairs or adjustments made to the equipment.
TP-5750 10/03
Section 4 Troubleshooting
63
Starts hard
Stops suddenly
Lacks power
Overheats
64
Trouble Symptoms
Probable Causes
Controller circuit board(s) inoperative Controller fault Controller fuse blown Controller master switch inoperative Controller master switch in the OFF/RESET position Engine start circuit open Replace the controller master switch. Troubleshoot the controller.[ Replace the blown controller fuse. If the fuse blows again, troubleshoot the controller.[ Replace the controller circuit board.
Recommended Actions
Controller
Section 4 Troubleshooting x Air openings clogged Coolant level low Cooling water pump inoperative High temperature shutdown Low coolant level shutdown, if equipped x Thermostat inoperative x x x Clean the air openings. Restore the coolant to normal operating level. Tighten or replace the belt. Replace the water pump. Allow the engine to cool down. Then troubleshoot the cooling system. Restore the coolant to normal operating level. Replace the thermostat. Verify that the battery connections are correct, clean, and tight. Recharge or replace the battery. The spec sheet provides recommended battery CCA rating. Replace the starter or starter solenoid. Battery connections loose, corroded, or incorrect Battery weak or dead Starter/starter solenoid inoperative Engine harness connector(s) not locked tight High water temperature switch inoperative Fault shutdown High exhaust temperature switch inoperative Disconnect the engine harness connector(s) then reconnect it to W/D the controller. Replace the inoperative switch. Reset the fault switches and troubleshoot the controller. Replace the inoperative switch.
Move the controller master switch to the RUN or AUTO position. Section 2
Move the controller master switch to the RUN position to test the Section 2, W/D, generator set. Troubleshoot the auto start circuit and time Gen. I/M, S/M delays. ATS O/M, S/M
Cooling System Section 3 Eng. O/M or S/M Sec. 3, Eng. O/M Section 3 Eng. S/M Section 3 Section 3, S/S Eng. S/M
TP-5750 10/03
* Sec./Sectionnumbered section of this manual; ATSAutomatic Transfer Switch; Eng.Engine; Gen.Generator Set; I/MInstallation Manual; O/MOperation Manual; S/MService Manual; S/SSpec Sheet; W/DWiring Diagram Manual [ Have an authorized service distributor/dealer perform this service.
Starts hard
Stops suddenly
Lacks power
Overheats
TP-5750 10/03
Trouble Symptoms
Probable Causes
Air cleaner clogged Clean or replace the filter element. Check the compression.[
Recommended Actions
Engine x x Compression weak Engine overload x Exhaust system leak x TP-5750 10/03 x x Governor inoperative x Valve clearance incorrect Vibration excessive Ignition system inoperative (gas/gasoline only) Air in fuel system (diesel only) Ether canister empty or system inoperative, if equipped (diesel only) Fuel tank empty or fuel valve shut off x x x Fuel filter restriction Fuel solenoid inoperative x x x Fuel pressure insufficient (gas only) Fuel injection timing out of adjustment (diesel only) x Adjust the valves.[ Tighten all loose hardware. Check the ignition system (spark plugs, spark plug wires, etc.). x x Adjust the governor.[ x x Exhaust system not securely installed x x x x x x
Reduce the electrical load. See the generator set spec sheet for S/S wattage specifications. Inspect the exhaust system. Replace the inoperative exhaust system components.[ Inspect the exhaust system. Tighten the loose exhaust system components.[ I/M I/M Gen. S/M Eng. S/M Eng. O/M
Fuel System x Bleed the diesel fuel system. Replace or repair the ether starting system. Add fuel and move the fuel valve to the ON position. Eng. O/M Eng. O/M Eng. S/M Clean, test, and/or replace the inoperative fuel injector.[ Clean or replace the fuel filter. Troubleshoot the fuel solenoid.[ Check the fuel supply and valves.[ Adjust the fuel injection timing.[ Eng. S/M Eng. O/M Eng. S/M S/S, Gen. O/M Eng. S/M
Fuel feed or injection pump inoperative Rebuild or replace the injection pump.[ (diesel only) Fuel or fuel injectors dirty or faulty (diesel only)
Section 4 Troubleshooting
* Sec./Sectionnumbered section of this manual; ATSAutomatic Transfer Switch; Eng.Engine; Gen.Generator Set; I/MInstallation Manual; O/MOperation Manual; S/MService Manual; S/SSpec Sheet; W/DWiring Diagram Manual [ Have an authorized service distributor/dealer perform this service.
65
Starts hard
Stops suddenly
Lacks power
Overheats
66
Trouble Symptoms
Probable Causes
AC output circuit breaker open Transfer switch test switch in the OFF position Transfer switch fails to transfer load Wiring, terminals, or pin in the exciter field open Main field (rotor) inoperative (open or grounded) Stator inoperative (open or grounded) Test and/or replace the rotor.[ Test and/or replace the stator.[ Tighten loose components.[ Adjust the voltage regulator. Replace the voltage regulator fuse, If the fuse blows again, troubleshoot the voltage regulator. Adjust the voltage regulator. Check for continuity. Reset the breaker and check for AC voltage at the generator side of the circuit breaker. Move the transfer switch test switch to the AUTO position.
Recommended Actions
Alternator
Section 4 Troubleshooting Move the ATS test switch to the AUTO position. Troubleshoot the transfer circuit and time delays. x Vibration excessive Voltage regulator digital settings incorrect (digital controller only) Voltage regulator inoperative Voltage regulator out of adjustment x x Oil level low Low oil pressure shutdown x x x Crankcase oil type incorrect for ambient temperature Restore the oil level. Inspect the generator set for oil leaks. Check the oil level.
Lube System Change the oil. Use oil with a viscosity suitable for the operating Eng. O/M climate. Eng. O/M Eng. O/M
* Sec./Sectionnumbered section of this manual; ATSAutomatic Transfer Switch; Eng.Engine; Gen.Generator Set; I/MInstallation Manual; O/MOperation Manual; S/MService Manual; S/SSpec Sheet; W/DWiring Diagram Manual [ Have an authorized service distributor/dealer perform this service.
TP-5750 10/03
WARNING
Hazardous voltage. Moving rotor. Can cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
WARNING
Reconnect the generator set stator leads to change the output phase or voltage. Refer to the following procedure and the connection schematics in Figure 5-5, Figure 5-6, or Figure 5-7. Follow the safety precautions at the front of this manual and in the text and observe National Electrical Code (NEC) guidelines. Voltage Reconnection Procedure 1. Place the generator set master switch in the OFF/RESET position. 2. Disconnect the generator set engine starting battery, negative (--) lead first. Disconnect power to the battery charger (if equipped). 3. Use Figure 5-5, Figure 5-6, or Figure 5-7 to determine the generator set voltage configuration. Note the original voltage and reconnect as needed. Route leads through current transformers (CTs) and connect them according to the diagram for desired phase and voltage. Note: Position current transformers CT1, CT2, and CT3 with the dot or HI side toward the generator set. Note: Only generator sets equipped with AC meter controllers and/or safeguard circuit breakers require CTs.
Accidental starting. Can cause severe injury or death. Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Turn the generator set master switch and switchgear engine control switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by an automatic transfer switch or a remote start/stop switch. Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
TP-5750 10/03
67
4. If the controller has meters, remove the controller cover and reposition the meter scale lamp jumper (see Figure 5-1) to match the position for desired voltage (shown in Figure 5-5, Figure 5-6, or Figure 5-7). Replace the controller cover.
1
Recalibrate the overvoltage shutdown if the reconnection changes the voltage to or from one of these configurations. See Section 5.2, Overvoltage Shutdown Adjustment. Do not recalibrate the overvoltage adjustment for other voltage changes. 6. If the controller has meters, set the phase selector switch to the L1-L2 position (1-phase or 3-phase depending on generator set connection). Connect a voltmeter across leads L1 and L2 if the controller has no meters. 7. Reconnect the starting battery, negative (--) lead last. Place the generator set master switch in the RUN position to start the generator set. Check the voltmeter to verify that the voltage changed to the desired value. a. 20--300 kW Models: Adjust the voltage with the voltage adjustment potentiometer on the generator set controller front panel or switchgear. See Figure 5-2.
OFF
L3 L3--L1 L1 L1--L2
HERTZ
A--C VOLTS
A--C AMPERES
L2 L1--L2
L1 L1--L2
L2
TP-5353-6
00000
ADJUST
S
O
PREALARM HIGH ENGINE TEMPERATURE PREALARM LOW OIL PRESSURE LOW WATER TEMPERATURE LOW FUEL
HIGH ENGINE TEMPERATURE LOW OIL PRESSURE EMERGENCY STOP OVERSPEED RUN OFF/RESET
AUXILIARY FAULT BATTERY CHARGER FAULT LOW BATTERY VOLTAGE OVERCRANK AUTO
AUXILIARY PREALARM AIR DAMPER SYSTEM READY GENERATOR SWITCH NOT IN AUTO SILENCE NORMAL ALARM LAMP TEST
1. Lamp Jumper
Figure 5-1
OIL PRESS
WATER TEMP
BATTERY
5. The overvoltage shutdown is standard on Decision-Makert 3+ controllers and optional on Decision-Makert 3 controllers. A circuit board mounted to the back of the Decision-Makert 3 controller frequency meter indicates the presence of an overvoltage shutdown kit. a. If the generator set has a Decision-Makert 3 without overvoltage shutdown, go to step 6. b. The 139/240 volt (low wye) and 277/480 volt (high wye), 3-phase, 4-wire, 60 Hz configurations use different overvoltage shutdown settings than all other configurations.
1
1. Output voltage adjustment potentiometer
ADV-5849A-
Figure 5-2
Voltage Adjustment
b. 350--2000 kW Models: Adjust the voltage with the voltage adjustment potentiometer on the voltage regulator or switchgear. Use the applicable technical manual for voltage regulator adjustment. 8. Stop the generator set after completing the voltage adjustment. Replace the controller cover.
68
TP-5750 10/03
5. Connect a digital AC voltmeter (or other highly accurate voltmeter) to terminals V0 and V7 on the controller terminal block. See Figure 5-1. 6. Reconnect the battery, negative (--) lead last. 7. Start the generator set by placing the generator set master switch in the RUN position. 8. Adjust the output voltage to 115% of the nominal output voltage by adjusting the potentiometer described in a or b. If the voltage configuration is 139/240 volts (low wye) or 277/480 volts (high wye), 3-phase, 4-wire, 60 Hz, adjust to produce approximately 160 volts across V0 and V7. For all other voltages, adjust to produce approximately 140 volts across V0 and V7. a. 20--300 kW Models: Adjust the output voltage with the voltage adjustment potentiometer on the generator set controller front panel or switchgear. See Figure 5-2. b. 350--2000 kW Models: Adjust the output voltage with the voltage adjustment potentiometer on the voltage regulator or switchgear. Use the applicable technical manual for voltage regulator adjustment. 9. Use the wrapped screwdriver to slowly rotate the overvoltage adjustment potentiometer (R41 or R42) counterclockwise until red LED4 lights. See Figure 5-3. The generator set should shut down on overvoltage fault in approximately 2 seconds.
1
5.2.1
Decision-Maker 3+ Controller
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load. Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Procedure 1. Disconnect the generator set engine starting battery, negative (--) lead first. Disconnect power to the battery charger (if equipped). 2. With the generator set idle, open the output line circuit breaker to disconnect the load from the generator set. 3. Remove the controller cover.
P2 R41 or R42 LED4
4. Wrap the shaft of an insulated-handle screwdriver with electrical tape. Turn the overvoltage potentiometer (R41 or R42) on the main circuit board fully clockwise. See Figure 5-3. Note: The overvoltage potentiometer is R41 or R42. R41 is found on A-336415 circuit boards. R42 is found on GM28724 circuit boards with the DIP switches and communication ports.
P1 A-336415-A
2
1. Overvoltage adjustment potentiometer (R41 or R42) 2. LED4 (red)
Figure 5-3
TP-5750 10/03
69
10. Turn the voltage adjustment potentiometer counterclockwise to reduce output voltage. Restart the generator set. Slowly increase voltage and verify the shutdown setting by observing the voltmeter and noting when red LED4 lights. The generator set should shut down on overvoltage fault in approximately 2 seconds. If shutdown voltage is not within tolerance, repeat the calibration output procedure; otherwise, continue to step 11. 11. Turn the voltage adjustment potentiometer counterclockwise to reduce output voltage. Restart the generator set. Readjust the generator set output to the nominal voltage. 12. Stop the generator set by placing the generator set master switch in the OFF/RESET position. Seal the overvoltage adjustment potentiometer (R41) with RTV sealant or equivalent. Replace the controller cover.
Procedure 1. With the generator set idle, open the output line circuit breaker to disconnect the load from the generator set. 2. Remove the controller cover. 3. Check for the J1 jumper on the overvoltage circuit board. Install the J1 jumper if the generator set is connected for 139/240 volts (low wye) or 277/480 volts (high wye) 3-phase, 4-wire, 60 Hz. Remove the J1 jumper for all other voltages. See Figure 5-4. 4. Replace the cover.
5.2.2
Decision-Maker 3 Controller
1
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load. Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
G-291739-B
1. J1 Jumper wire
Figure 5-4
70
TP-5750 10/03
Figure 5-5
TP-5750 10/03
Reconnection Notes
Note: Position the current transformers with the dot or HI side CT mark toward the generator set. Some generator sets have no current transformers. Note: Phase Rotation: A = L1, B = L2, and C = L3. Note: All 12-lead generator sets are reconnectable. The 6-lead, 600-volt generator set is not reconnectable. Some specially wound stators made for a single voltage are also not reconnectable. Note: (600-volt models only) Use 1 turn of the output lead through the current transformer on 6-lead, 600-volt stators. Some stators may have two turns of the output lead through the current transformer. Continue using the original factory two-turn current transformer wiring system.
WITH DIGITAL
ADV-5875A-DI
Figure 5-6
72
Note: On 10-lead generators, leads T10, T11, and T12 are all brought out together and labeled TO. Note: Position the current transformers with the dot or HI side toward the generator set. Current transformers are not used on all sets. Note: Phase Rotation: A = L1, B = L2, and C = L3. Note: All 10- and 12-lead generator sets are reconnectable. The 4-lead generator set is not reconnectable. Some specially wound stators are made for a specific voltage configuration and are also not reconnectable. Note A: Use the delta connection shown in this illustration to ensure correct phase sensing. Do not use the configuration shown in the alternator technical manual.
5750-6
Figure 5-7
TP-5750 10/03
Notes
74
TP-5750 10/03
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, amp ABDC AC A/D ADC adj. ADV AHWT AISI ALOP alt. Al ANSI ampere after bottom dead center alternating current analog to digital analog to digital converter adjust, adjustment advertising dimensional drawing anticipatory high water temperature American Iron and Steel Institute anticipatory low oil pressure alternator aluminum American National Standards Institute (formerly American Standards Association, ASA) anticipatory only American Petroleum Institute approximate, approximately as required, as requested as supplied, as stated, as suggested American Society of Engineers American Society of Mechanical Engineers assembly American Society for Testing Materials after top dead center automatic transfer switch automatic auxiliary audiovisual average automatic voltage regulator American Wire Gauge appliance wiring material battery before bottom dead center battery charger, battery charging battery charging alternator Battery Council International before dead center brake horsepower black (paint color), block (engine) block heater brake mean effective pressure bits per second brass before top dead center British thermal unit British thermal units per minute Celsius, centigrade calorie California Air Resources Board circuit breaker cubic centimeter cold cranking amps counterclockwise Canadian Electrical Code certificate, certification, certified cubic feet per hour cfm CG CID CL cm CMOS cubic feet per minute center of gravity cubic inch displacement centerline centimeter complementary metal oxide substrate (semiconductor) cogen. cogeneration com communications (port) coml commercial Coml/Rec Commercial/Recreational conn. connection cont. continued CPVC chlorinated polyvinyl chloride crit. critical CRT cathode ray tube CSA Canadian Standards Association CT current transformer Cu copper cu. in. cubic inch cw. clockwise CWC city water-cooled cyl. cylinder D/A digital to analog DAC digital to analog converter dB decibel dBA decibel (A weighted) DC direct current DCR direct current resistance deg., degree dept. department dia. diameter DI/EO dual inlet/end outlet DIN Deutsches Institut fur Normung e. V. (also Deutsche Industrie Normenausschuss) DIP dual inline package DPDT double-pole, double-throw DPST double-pole, single-throw DS disconnect switch DVR digital voltage regulator E, emer. emergency (power source) EDI electronic data interchange EFR emergency frequency relay e.g. for example (exempli gratia) EG electronic governor EGSA Electrical Generating Systems Association EIA Electronic Industries Association EI/EO end inlet/end outlet EMI electromagnetic interference emiss. emission eng. engine EPA Environmental Protection Agency EPS emergency power system ER emergency relay ES engineering special, engineered special ESD electrostatic discharge est. estimated E-Stop emergency stop etc. et cetera (and so forth) exh. ext. F fglass. FHM fl. oz. flex. freq. FS ft. ft. lb. ft./min. g ga. gal. gen. genset GFI GND, gov. gph gpm gr. GRD gr. wt. HxWxD HC HCHT HD HET hex Hg HH HHC HP hr. HS hsg. HVAC HWT Hz IC ID IEC IEEE IMS in. in. H2O in. Hg in. lb. Inc. ind. int. int./ext. I/O IP ISO J JIS exhaust external Fahrenheit, female fiberglass flat head machine (screw) fluid ounce flexible frequency full scale foot, feet foot pounds (torque) feet per minute gram gauge (meters, wire size) gallon generator generator set ground fault interrupter ground governor gallons per hour gallons per minute grade, gross equipment ground gross weight height by width by depth hex cap high cylinder head temperature heavy duty high exhaust temperature, high engine temperature hexagon mercury (element) hex head hex head cap horsepower hour heat shrink housing heating, ventilation, and air conditioning high water temperature hertz (cycles per second) integrated circuit inside diameter, identification International Electrotechnical Commission Institute of Electrical and Electronics Engineers improved motor starting inch inches of water inches of mercury inch pounds incorporated industrial internal internal/external input/output iron pipe International Organization for Standardization joule Japanese Industry Standard
AO API approx. AR AS ASE ASME assy. ASTM ATDC ATS auto. aux. A/V avg. AVR AWG AWM bat. BBDC BC BCA BCI BDC BHP blk. blk. htr. BMEP bps br. BTDC Btu Btu/min. C cal. CARB CB cc CCA ccw. CEC cert. cfh
TP-5750 10/03
Appendix 75
k K kA KB kg kg/cm2
kilo (1000) kelvin kiloampere kilobyte (210 bytes) kilogram kilograms per square centimeter kgm kilogram-meter kilograms per cubic meter kg/m3 kHz kilohertz kJ kilojoule km kilometer kOhm, k kilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kVA kilovolt ampere kVAR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical L liter LAN local area network L x W x H length by width by height lb. pound, pounds lbm/ft3 pounds mass per cubic feet LCB line circuit breaker LCD liquid crystal display ld. shd. load shed LED light emitting diode Lph liters per hour Lpm liters per minute LOP low oil pressure LP liquefied petroleum LPG liquefied petroleum gas LS left side Lwa sound power level, A weighted LWL low water level LWT low water temperature m meter, milli (1/1000) M mega (106 when used with SI units), male cubic meter m3 m3/min. cubic meters per minute mA milliampere man. manual max. maximum MB megabyte (220 bytes) MCM one thousand circular mils MCCB molded-case circuit breaker meggar megohmmeter MHz megahertz mi. mile mil one one-thousandth of an inch min. minimum, minute misc. miscellaneous MJ megajoule mJ millijoule mm millimeter mOhm, m milliohm MOhm, M megohm MOV metal oxide varistor MPa megapascal mpg miles per gallon mph miles per hour MS military standard m/sec. meters per second
mean time between failure mean time between overhauls mounting megawatt milliwatt microfarad normal (power source) not available, not applicable natural gas National Bureau of Standards normally closed National Electrical Code National Electrical Manufacturers Association NFPA National Fire Protection Association Nm newton meter NO normally open no., nos. number, numbers NPS National Pipe, Straight NPSC National Pipe, Straight-coupling NPT National Standard taper pipe thread per general use NPTF National Pipe, Taper-Fine NR not required, normal relay ns nanosecond OC overcrank OD outside diameter OEM original equipment manufacturer OF overfrequency opt. option, optional OS oversize, overspeed OSHA Occupational Safety and Health Administration OV overvoltage oz. ounce p., pp. page, pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph., phase PHC Phillips head crimptite (screw) PHH Phillips hex head (screw) PHM pan head machine (screw) PLC programmable logic control PMG permanent-magnet generator pot potentiometer, potential ppm parts per million PROM programmable read-only memory psi pounds per square inch pt. pint PTC positive temperature coefficient PTO power takeoff PVC polyvinyl chloride qt. quart, quarts qty. quantity R replacement (emergency) power source rad. radiator, radius RAM random access memory RDO relay driver output ref. reference rem. remote Res/Coml Residential/Commercial RFI radio frequency interference RH round head
round head machine (screw) relay root mean square round read only memory rotate, rotating revolutions per minute right side room temperature vulcanization Society of Automotive Engineers scfm standard cubic feet per minute SCR silicon controlled rectifier s, sec. second SI Systeme international dunites, International System of Units SI/EO side in/end out sil. silencer SN serial number SPDT single-pole, double-throw SPST single-pole, single-throw spec, specs specification(s) sq. square sq. cm square centimeter sq. in. square inch SS stainless steel std. standard stl. steel tach. tachometer TD time delay TDC top dead center TDEC time delay engine cooldown TDEN time delay emergency to normal TDES time delay engine start TDNE time delay normal to emergency TDOE time delay off to emergency TDON time delay off to normal temp. temperature term. terminal TIF telephone influence factor TIR total indicator reading tol. tolerance turbo. turbocharger typ. typical (same in multiple locations) UF underfrequency UHF ultrahigh frequency UL Underwriters Laboratories, Inc. UNC unified coarse thread (was NC) UNF unified fine thread (was NF) univ. universal US undersize, underspeed UV ultraviolet, undervoltage V volt VAC volts alternating current VAR voltampere reactive VDC volts direct current VFD vacuum fluorescent display VGA video graphics adapter VHF very high frequency W watt WCR withstand and closing rating w/ with w/o without wt. weight xfmr transformer
76 Appendix
TP-5750 10/03
Notes
TP-5750 10/03
77
Notes
78
TP-5750 10/03
KOHLER CO. Kohler, Wisconsin 53044 Phone 920-565-3381, Fax 920-459-1646 For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KohlerPowerSystems.com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
TP-5750 10/03j
E 1995, 1999, 2000, 2001, 2002, 2003, 2005 by Kohler Co. All rights reserved.