Neta BKM PDF
Neta BKM PDF
Neta BKM PDF
for
Electric Power Distribution
Equipment and Systems
Copyright 1997
InterNational Electrical Testing Association
P.O. Box 687, 106 Stone Street
Morrison, CO 80465
303-697-8441 FAX: 303-697-8431
E-mail: neta@compuserve.com
Roderic Hageman
Vern Hegg
Bob Hettchen
Jeffrey J. Hopper
Fredi Jakob
Thomas G. Kunz
Mark Lautenschlager
Richard R. Lussier, Jr.
Al Marden
Charles Potter
Keith Robertson
Richard Sobhraj
Sandy Svatos
John Snell
David Volz
Mark Lautenschlager
Mary R. Jordan
NOTICE
In no event shall the InterNational Electrical Testing Association be liable to anyone for special, collateral,
incidental, or consequential damages in connection with or arising out of the use of these materials. This document should
not be confused with federal, state, or municipal specifications or regulations, insurance requirements, or national safety
codes. While the Association recommends reference to or use of this document by government agencies and others, use
of this document is purely voluntary and not binding.
This document is subject to periodic review, and users are cautioned to obtain the latest edition. Comments and
suggestions are invited from all users for consideration. All questions or other communications relating to this document
should be sent only to NETA headquarters, addressed to the attention of the appropriate section.
For information on the procedures for requesting Formal Interpretations, proposing Tentative Interim
Amendments, proposing amendments for consideration, and appeals on matters relating to the content of the document,
write to Secretariat, Standards Review Council, InterNational Electrical Testing Association. A statement, written or oral,
that is not processed in accordance with NETA Operating Procedures for Standards Accreditation shall not be considered
the official position of NETA or any of its Section Panels and shall not be considered to be, nor relied upon as, a Formal
Interpretation.
PREFACE
It is recognized by the Association that the needs of commercial and industrial power system
owners vary widely. Many criteria are used in determining what equipment is to be tested, at what
intervals, and to what extent. Ambient conditions, availability of down time, and maintenance budgets
are but a few of the considerations that go into the planning of a maintenance schedule. The owner,
with the assistance of a reputable electrical testing firm, must make many decisions each time
maintenance is considered.
It is the intent of this document to list a majority of the field tests available for assessing the
suitability for continued service and reliability of the power distribution system. Certain tests have
been assigned an "optional" classification. The following considerations were used in determining the
use of the "optional" classification:
1.
2.
How did the cost of the test compare to the cost of other tests providing similar
information?
3.
4.
Did the down time required for the particular test greatly increase that required for the
remainder of the maintenance?
While acknowledging the above, it is still necessary to make an informed judgment for each
particular system regarding how extensive a procedure is justified. The approach taken in these
specifications is to present a comprehensive series of tests that are applicable to most industrial and
larger commercial systems. Even in those cases it is necessary to decide how far "down" into the
system the testing should be taken. In smaller systems some of the tests can be deleted. In other
cases a number of the tests indicated as optional should be performed. The guidance of an
experienced testing professional should be sought when making such decisions.
As a further note, it is important to follow the recommendations contained in the
manufacturer's instruction manuals. Many of the details of a complete and effective maintenance
testing procedure can only be obtained from that source.
The Association encourages comment from users of this document. Please contact the NETA
office or your local NETA member firm.
Alan D. Peterson
NETA Technical Committee Chair
CONTENTS
ELECTRICAL MAINTENANCE TESTS
1.
2.
3.
4.
5.
6.
7.
7.6
7.7
7.8
7.9
7.10
7.11
7.12
7.13
7.14
7.15
7.16
7.17
7.18
7.19
7.20
8.
9.
10.
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
10.10
10.11
10.12
10.13
10.14
10.15
10.16
10.17
10.18
10.19
TABLES
Insulation-Resistance Tests on Electrical Apparatus & Systems ................................ 153
Switchgear Low-Frequency Withstand Test Voltages ................................................. 154
Recommended Dissipation Factor/Power Factor of Liquid-Filled Transformers ......... 155
Suggested Limits for Service-Aged Liquids ................................................................. 156
Transformer Insulation-Resistance.............................................................................. 157
Medium-Voltage Cables,Maximum Field Maintenance Test Voltages (kV, dc) ........... 158
Molded-Case Circuit Breakers, Values for Inverse Time Trip Test.............................. 160
Instantaneous Trip Setting Tolerances
for Field Testing of Marked Adjustable Trip Circuit Breakers ...................................... 161
Instrument Transformer Dielectric Tests, Field Maintenance ...................................... 162
Maximum Allowable Vibration Amplitude .................................................................... 163
Periodic Electrical Test Values for Insulating Aerial Devices
Insulating Aerial Devices with a Lower Test Electrode System (A,B) ............... 164
Insulating Aerial Devices without Lower Test Electrode System (C) ................ 164
Insulating Aerial Ladders and Insulating Vertical Aerial Towers ....................... 164
Chassis Insulating Systems Lower Insulated Booms ....................................... 165
Bolt Torques for Bus Connections
Heat-Treated Steel - Cadmium or Zinc Plated.................................................. 166
Silicon Bronze Fasteners.................................................................................. 166
Aluminum Alloy Fasteners ................................................................................ 167
Stainless Steel Fasteners ................................................................................. 167
SF6 Gas Tests ............................................................................................................. 168
Insulation Resistance Conversion Factors
For Conversion of Test Temperature to 20C ............................................................. 169
High-Potential Test Voltage for Automatic Circuit Reclosers....................................... 170
High-Potential Test Voltage for Periodic Test of Line Sectionalizers........................... 171
Metal-Enclosed Bus Dielectric Withstand Test Voltages............................................. 172
Thermographic Survey Suggested Actions Based on Temperature Rise ................... 173
Overpotential Test Voltages for Electrical Apparatus
Other than Inductive Equipment .................................................................................. 174
1.
GENERAL SCOPE
1.1
The owner shall engage the services of a recognized independent testing firm or
independent electrical consulting firm to perform short-circuit and coordination studies
as herein specified in Section 6.
1.2
The owner shall engage the services of a recognized independent testing firm for the
purpose of performing inspections and tests as herein specified.
1.3
The testing firm shall provide all material, equipment, labor, and technical supervision to
perform such tests and inspections.
1.4
It is the purpose of these specifications to assure that all tested electrical equipment
and systems are operational and within industry and manufacturer's tolerances.
MTS-1997 1
2.
APPLICABLE REFERENCES
2.1
All inspections and field tests shall be in accordance with the latest edition of the
following codes, standards, and specifications except as provided otherwise herein.
1.
2.
2 MTS-1997
2.
APPLICABLE REFERENCES
ASTM D 2029-92. Test Methods for Water Vapor Content of Electrical Insulating
Cases by Measurement of Dew Point
ASTM D 2129-90. Test Method for Color of Chlorinated Aromatic Hydrocarbons
(Askarels)
ASTM D 2284-95. Test Method of Acidity of Sulfur Hexafluoride
ASTM D 2285-85 (R1990). Test Method for Interfacial Tension of Electrical
Insulating Oils of Petroleum Origin Against Water by the Drop-Weight Method
ASTM D 2477-84 (R1990). Test Method for Dielectric Breakdown Voltage and
Dielectric Strength of Insulating Gases at Commercial Power Frequencies
ASTM D 2685-95. Test Method for Air and Carbon Tetrafluoride in Sulfur
Hexafluoride by Gas Chromatography
ASTM D 2759-94. Method for Sampling Gas from a Transformer under Positive
Pressure
ASTM D 3284-90a (R1994). Test Method for combustible Gases in Electrical
apparatus in the Field
ASTM D 3612-95. Test Method of Analysis of Gases Dissolved in Electrical
Insulating Oil by Gas Chromatography
ASTM D 3613-92. Methods of Sampling Electrical Insulating Oils for Gas
Analysis and Determination of Water Content
3.
4.
5.
MTS-1997 3
2.
APPLICABLE REFERENCES
ANSI/IEEE Std. 43-1974 (R1991). IEEE Recommended Practice for Testing
Insulation Resistance of Rotating Machinery
IEEE Std. 48-1996. Standard Test Procedures and Requirements for HighVoltage AC Cable Terminations 2.5kV through 276kV
IEEE Std. 81-1983. IEEE Guide for Measuring Earth Resistivity, Ground
Impedance, and Earth Surface Potentials of a Ground System (Part I)
ANSI/IEEE Std. 81.2-1991. IEEE Guide for Measurement of Impedance and
Safety Characteristics of Large, Extended, or Interconnected Grounding Systems
(Part 2)
ANSI/IEEE Std. 95-1977 (R1991). IEEE Recommended Practice for Insulation
Testing of Large AC Rotating Machinery with High Direct Voltage
IEEE Std. 100-1996. The IEEE Standard Dictionary of Electrical and Electronics
Terms
ANSI/IEEE Std. 141-1993. IEEE Recommended Practice for Electrical Power
Distribution for Industrial Plants (IEEE Red Book.)
ANSI/IEEE Std. 142-1991. IEEE Recommended Practice for Grounding of
Industrial and Commercial Power Systems (IEEE Green Book)
ANSI/IEEE Std. 241-1990. IEEE Recommended Practice for Electric Power
Systems in Commercial Buildings (Gray Book)
ANSI/IEEE Std. 242-1986 (R1991). IEEE Recommended Practice for Protection
and Coordination of Industrial and Commercial Power Systems (Buff Book)
ANSI/IEEE Std. 399-1990. IEEE Recommended Practice for Power Systems
Analysis (Brown Book)
ANSI/IEEE Std. 400-1991. IEEE Guide for Making High-Direct-Voltage Tests on
Power Cable Systems in the Field
ANSI/IEEE Std. 421B-1979. IEEE Standard for High-Potential-Test
Requirements for Excitation Systems for Synchronous Machines
ANSI/IEEE Std. 446-1995. IEEE Recommended Practice for Emergency and
Standby Power Systems for Industrial and Commercial Applications (Orange
Book)
4 MTS-1997
2.
APPLICABLE REFERENCES
ANSI/IEEE Std. 450-1994. IEEE Recommended Practice for Maintenance,
Testing, and Replacement of Large Lead Storage Batteries for Generating
Stations and Substations
ANSI/IEEE Std. 493-1990. IEEE Recommended Practice for the Design of
Reliable Industrial and Commercial Power Systems (Gold Book)
ANSI/IEEE Std. 602-1996. IEEE Recommended Practice for Electric Systems in
Health Care Facilities (White Book)
ANSI/IEEE Std. 637-1985 (R1992). IEEE Guide for the Reclamation of Insulating
Oil and Criteria for Its Use
ANSI/IEEE Std. 739-1995. IEEE Recommended Practice for Energy
Conservation and Cost-Effective Planning in Industrial Facilities (Bronze Book)
ANSI/IEEE Std. 1100-1992. IEEE Recommended Practice for Powering and
Grounding Sensitive Electronic Equipment (Emerald Book)
ANSI/IEEE Std. 1106-1995. IEEE Recommended Practice for Maintenance,
Testing, and Replacement of Nickel-Cadmium Storage Batteries for Generating
Stations and Substations
6.
7.
8.
9.
MTS-1997 5
2.
APPLICABLE REFERENCES
ANSI/NFPA 70E-1995. Electrical Safety Requirements for Employee Workplaces
ANSI/NFPA 99-1993. Standard for Healthcare Facilities
ANSI/NFPA 101-1994. Life Safety Code
ANSI/NFPA 110-1993. Emergency and Standby Power Systems
ANSI/NFPA 780-1995. Installation of Lightning Protection Systems
10.
11.
12.
13.
6 MTS-1997
The testing firm shall be an independent testing organization which can function as an
unbiased testing authority, professionally independent of the manufacturers, suppliers,
and installers of equipment or systems evaluated by the testing firm.
3.2
The testing firm shall be regularly engaged in the testing of electrical equipment
devices, installations, and systems.
3.3
The testing firm shall meet the criteria for Full Membership or be a Full Member
company of the InterNational Electrical Testing Association.
3.4
The lead, on site, technical person shall hold a current certification in one of the
following:
1.
2.
3.5
The testing firm shall utilize technicians who are regularly employed by the firm for
testing services.
3.6
The testing firm shall submit proof of the above qualifications with bid documents when
requested.
MTS-1997 7
4.
DIVISION OF RESPONSIBILITY
4.1
The owner shall supply a suitable and stable source of electrical power to each test site.
The testing firm shall specify the specific power requirements.
4.2
The owner shall notify the testing firm when equipment becomes available for
maintenance tests. Work shall be coordinated to expedite project scheduling.
4.3
The owner shall supply a short-circuit analysis and coordination study, a protective
device setting sheet, a complete set of electrical plans, specifications, and any pertinent
change orders to the testing firm prior to commencement of testing.
4.4
The testing firm shall notify the owner prior to commencement of any testing.
4.5
4.6
The testing firm shall maintain a written record of all tests and shall assemble and
certify a final test report.
4.7
8 MTS-1997
Safety practices should include, but are not limited to, the following
requirements:
1.
2.
3.
4.
5.
6.
2.
All tests shall be performed with apparatus de-energized except where otherwise
specifically required.
3.
5.
GENERAL
5.1
5.2
2.
2.
3.
4.
3.
4.
Field test metering used to check power system meter calibration must have an
accuracy higher than that of the instrument being checked.
5.
Accuracy of metering in test equipment shall be appropriate for the test being
performed but not in excess of two percent of the scale used.
6.
The testing firm shall have a calibration program which assures that all
applicable test instruments are maintained within rated accuracy.
2.
MTS-1997 9
5.
GENERAL
3.
5.3
2.
3.
4.
5.
Records, which show date and results of instruments calibrated or tested, must
be kept up-to-date.
6.
7.
Test Report
1.
2.
10 MTS-1997
Summary of project
2.
3.
Description of test
4.
Test results
5.
Furnish a copy or copies of the complete report to the owner as required in the
maintenance contract.
6.
Scope of Services
1.
2.
Short-Circuit Study
1.
2.
The study input data shall include the short-circuit single- and three-phase
contributions from all sources, with the X/R ratio, the resistance and
reactance components of each branch impedance, motor and generator
contributions, base quantities selected, and all other applicable circuit
parameters.
3.
2.
MTS-1997 11
6.
4.
5.
12 MTS-1997
2.
The coordination study shall include all voltage classes of equipment from
the source's incoming line protective device down to and including each
motor control center and/or panelboard. The phase and ground
overcurrent protection shall be included as well as settings for all other
adjustable protective devices.
3.
Study Report
1.
2.
3.
Description, purpose, basis, and scope of the study and a singleline diagram of the portion of the power system which is included
within the scope of study.
2.
6.
6.
3.
4.
5.
Implementation
1.
The owner shall engage an independent testing firm for the purpose of
inspecting, setting, testing, and calibrating the protective relays, circuit
breakers, fuses, and other applicable devices as recommended in the
power-system study report.
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
MTS-1997 13
7.
2.
3.
4.
Verify that fuse and/or circuit breaker sizes and types correspond to
drawings and coordination study as well as to the circuit breaker's address
for microprocessor-communication packages.
5.
6.
Inspect all bus connections for high resistance using one of the following
methods:
7.
8.
14 MTS-1997
1.
2.
3.
2.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
7.
2.
10.
11.
Lubrication
1.
2.
12.
13.
14.
15.
16.
2.
3.
Electrical Tests
1.
2.
MTS-1997 15
7.
Perform resistance measurements through all bus joints with a lowresistance ohmmeter, if applicable, in accordance with Section 7.1.1.6
(Visual and Mechanical Inspection).
4.
*5.
*6.
7.
8.
9.
10.
* Optional
16 MTS-1997
1.
2.
2.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar bus by more than 25 percent of the lowest value.
4.
5.
MTS-1997 17
7.
Transformers
1.
Dry Type
1.
Air-Cooled, 600 Volt and Below - Small
(167 kVA Single-Phase, 500 kVA 3-Phase, and Smaller)
1.
2.
* Optional
18 MTS-1997
2.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
Electrical Tests
1.
2.
*3.
*4.
7.
Transformers
1.
Dry Type
1.
Air-Cooled, 600 Volt and Below - Small
(167 kVA Single-Phase, 500 kVA 3-Phase, and Smaller) (cont.)
3.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
Turns-ratio test results should not deviate more than one-half percent
from either the adjacent coils or the calculated ratio.
MTS-1997 19
7.
Transformers (cont.)
1.
Dry-Type (cont.)
2.
Air-Cooled, All Above 600 Volt and
600 Volt and Below - Large
(Greater than 167 Single-Phase and 500 kVA 3-Phase)
1.
20 MTS-1997
3.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
5.
6.
Verify that resilient mounts are free and that any shipping brackets have
been removed.
7.
8.
9.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
10.
* Optional
7.
Transformers (cont.)
1.
Dry Type (cont.)
2.
Air-Cooled, All Above 600 Volt and
600 Volt and Below - Large
(Greater than 167 kVA Single-Phase and 500 kVA 3-Phase) (cont.)
2.
Electrical Tests
1.
2.
3.
4.
*5.
*6.
7.
*8.
9.
* Optional
MTS-1997 21
7.
Transformers (cont.)
1.
Dry Type (cont.)
2.
Air-Cooled, All Above 600 Volt and
600 Volt and Below - Large
(Greater than 167 kVA Single-Phase and 500 kVA 3-Phase) (cont.)
3.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
Turns-ratio test results should not deviate more than one-half percent
from either the adjacent coils or the calculated ratio.
7.
22 MTS-1997
8.
9.
7.
Transformers (cont.)
1.
Dry Type (cont.)
2.
Air-Cooled, All Above 600 Volt and
600 Volt and Below - Large
(Greater than 167 kVA Single-Phase and 500 kVA 3-Phase) (cont.)
10.
11.
MTS-1997 23
7.
Transformers (cont.)
2.
Liquid-Filled
1.
* Optional
24 MTS-1997
*4.
Verify operation of all alarm, control, and trip circuits from temperature
and level indicators, pressure relief device, and fault pressure relay.
5.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
6.
7.
8.
9.
10.
11.
7.
Transformers (cont.)
2.
Liquid-Filled (cont.)
2.
Electrical Tests
1.
2.
3.
4.
5.
*6.
7.
*8.
*9.
* Optional
MTS-1997 25
7.
Transformers (cont.)
2.
Liquid-Filled (cont.)
10.
2.
*3.
11.
3.
* Optional
26 MTS-1997
4.
5.
6.
*7.
*8.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
7.
Transformers (cont.)
2.
Liquid-Filled (cont.)
3.
4.
5.
6.
Turns-ratio test results shall not deviate more than one-half percent from
either the adjacent coils or the calculated ratio.
7.
8.
9.
10.
11.
12.
13.
14.
Gas/Vapor - Reserved
MTS-1997 27
7.
Cables
1.
Low-Voltage, 600 Volt Maximum
1.
2.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
3.
2.
28 MTS-1997
1.
2.
3.
Electrical Tests
1.
2.
7.
Cables (cont.)
1.
Low-Voltage, 600 Volt Maximum (cont.)
3.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
MTS-1997 29
7.
Cables (cont.)
2.
Medium-Voltage, 69 kV Maximum
1.
2.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
Use of low-resistance ohmmeter in accordance with Section
7.3.2.2.3 (Electrical Tests).
2.
3.
4.
5.
6.
7.
8.
Electrical Tests
1.
30 MTS-1997
1.
7.
Cables (cont.)
2.
Medium-Voltage, 69 kV Maximum (cont.)
2.
3.
4.
2.
3.
4.
5.
6.
7.
Insure that the maximum test voltage does not exceed the limits for
terminators specified in ANSI/IEEE Standard 48 or manufacturer's
specifications.
MTS-1997 31
7.
Cables (cont.)
2.
Medium-Voltage, 69 kV Maximum (cont.)
3.
32 MTS-1997
9.
10.
11.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
*5.
* Optional
8.
6.
7.
8.
7.
Cables (cont.)
3.
High-Voltage
1.
2.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
4.
5.
6.
7.
8.
Electrical Tests
1.
MTS-1997 33
7.
Cables (cont.)
3.
High-Voltage (cont.)
34 MTS-1997
2.
3.
4.
2.
3.
4.
5.
6.
7.
Insure that the maximum test voltage does not exceed the limits for
terminators specified in ANSI/IEEE Standard 48 or manufacturer's
specifications.
7.
Cables (cont.)
3.
High-Voltage (cont.)
3.
8.
9.
10.
11.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
*5.
6.
7.
8.
* Optional
MTS-1997 35
7.
Metal-Enclosed Busways
1.
2.
36 MTS-1997
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
4.
5.
6.
Electrical Tests
1.
2.
3.
4.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar bus joints and connections by more than 25 percent of the
lowest value.
4.
Length of Run
1000
MTS-1997 37
7.
Switches
1.
Air Switches
1.
Low-Voltage
1.
38 MTS-1997
2.
3.
4.
5.
Verify that fuse sizes and types are in accordance with drawings and
short-circuit and coordination studies.
6.
7.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
8.
9.
10.
11.
12.
13.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
7.
Switches (cont.)
1.
Air Switches (cont.)
1.
Low-Voltage (cont.)
14.
2.
1.
2.
Electrical Tests
1.
3.
Lubrication
2.
3.
4.
5.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar switches by more than 25 percent of the
lowest value.
4.
5.
MTS-1997 39
7.
Switches (cont.)
1.
Air Switches (cont.)
2.
Medium-Voltage, Metal-Enclosed
1.
40 MTS-1997
2.
3.
4.
5.
Verify that fuse sizes and types are in accordance with drawings and
short-circuit and coordination studies.
6.
7.
8.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
9.
10.
11.
12.
7.
Switches (cont.)
1.
Air Switches (cont.)
2.
Medium-Voltage, Metal-Enclosed (cont.)
2.
3.
13.
14.
15.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
16.
Lubrication
1.
2.
Electrical Tests
1.
2.
Perform an overpotential test on each pole with switch closed. Test each
pole-to-ground with all other poles grounded. Test voltage shall be in
accordance with manufacturer's published data or Table 10.2.
3.
4.
5.
Test Values
1.
2.
MTS-1997 41
7.
Switches (cont.)
1.
Air Switches (cont.)
2.
Medium-Voltage, Metal-Enclosed (cont.)
42 MTS-1997
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar switches by more than 25 percent of the
lowest value.
4.
5.
6.
Investigate fuse resistance values that deviate from each other by more
than 15 percent.
7.
Switches (cont.)
1.
Air Switches (cont.)
3.
High- and Medium-Voltage, Open
1.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
4.
5.
6.
7.
8.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
9.
Lubrication
1.
2.
MTS-1997 43
7.
Switches (cont.)
1.
Air Switches (cont.)
3.
High- and Medium-Voltage, Open (cont.)
2.
3.
* Optional
44 MTS-1997
Electrical Tests
1.
*2.
3.
Perform an overpotential test on each pole with switch closed. Test each
pole-to-ground with all other poles grounded. Test voltage shall be in
accordance with manufacturer's published data or Table 10.19.
4.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar switches by more than 25 percent of the
lowest value.
4.
5.
7.
Switches (cont.)
2.
Oil Switches: Medium-Voltage
1.
2.
3.
4.
5.
6.
7.
8.
9.
Test all electrical and mechanical interlock systems for correct operation
and sequencing.
10.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
11.
1.
2.
3.
MTS-1997 45
7.
Switches (cont.)
2.
Oil Switches: Medium-Voltage (cont.)
2.
12.
13.
Lubrication
2.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
15.
Electrical Tests
1.
2.
3.
*5.
46 MTS-1997
14.
4.
* Optional
1.
1.
2.
3.
7.
Switches (cont.)
2.
Oil Switches: Medium-Voltage (cont.)
*6.
3.
Perform an overpotential test on each pole with switch closed. Test each
pole-to-ground with all other poles grounded. Test voltage shall be in
accordance with manufacturer's published data or Table 10.19.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar switches by more than 25 percent of the
lowest value.
4.
5.
6.
* Optional
MTS-1997 47
7.
Switches (cont.)
3.
Vacuum Switches: Medium-Voltage
1.
48 MTS-1997
2.
3.
4.
5.
6.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
7.
8.
9.
10.
Test all electrical and mechanical interlock systems for correct operation
and sequencing.
11.
7.
Switches (cont.)
3.
Vacuum Switches: Medium-Voltage (cont.)
12.
2.
Lubrication
1.
2.
13.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
14.
Electrical Tests
1.
Perform resistance measurements through all bus joints with a lowresistance ohmmeter, if applicable. See Section 7.5.3.1.7 (Visual and
Mechanical Inspection).
2.
3.
4.
5.
MTS-1997 49
7.
Switches (cont.)
3.
Vacuum Switches: Medium-Voltage (cont.)
6.
3.
* Optional
50 MTS-1997
2.
3.
*7.
*8.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar switches by more than 25 percent of the
lowest value.
4.
5.
6.
7.
8.
7.
5.
Cutouts - Reserved
MTS-1997 51
7.
Circuit Breakers
1.
Low-Voltage
1.
Insulated Case/Molded Case
1.
2.
3.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
5.
2.
* Optional
52 MTS-1997
1.
2.
3.
Electrical Tests
1.
2.
3.
*4.
7.
6.
7.
8.
9.
Verify correct operation of any auxiliary features such as trip and pickup
indicators, zone interlocking, electrical close and trip operation, trip-free,
and antipump function.
*10.
3.
Verify the calibration of all functions of the trip unit by means of secondary
injection.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
4.
5.
* Optional
MTS-1997 53
7.
54 MTS-1997
6.
7.
For molded-case circuit breakers all trip times shall fall within Table 10.7.
Circuit breakers exceeding specified trip time at 300 percent of pickup
shall be tagged defective.
8.
7.
2.
3.
Verify that all maintenance devices are available for servicing and
operating the breaker.
4.
Verify that primary and secondary contact wipe and other dimensions vital
to satisfactory operation of the breaker are correct.
5.
Perform all mechanical operator and contact alignment tests on both the
breaker and its operating mechanism.
6.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
7.
8.
9.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
MTS-1997 55
7.
2.
56 MTS-1997
1.
2.
Electrical Tests
1.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
*4.
* Optional
Lubrication
1.
2.
3.
5.
6.
7.
7.
9.
10.
3.
*11.
Verify the calibration of all functions of the trip unit by means of secondary
injection.
12.
13.
Verify correct operation of any auxiliary features such as trip and pickup
indicators, zone interlocking, electrical close and trip operation, trip-free,
and antipump function.
14.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
4.
5.
6.
* Optional
MTS-1997 57
7.
2.
3.
Verify that all maintenance devices are available for servicing and
operating the breaker.
4.
Verify that primary and secondary contact wipe and other dimensions vital
to satisfactory operation of the breaker are correct.
5.
Perform all mechanical operator and contact alignment tests on both the
breaker and its operating mechanism.
6.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
Use of low-resistance ohmmeter in accordance with Section
7.6.2.1.2.3 (Electrical Tests).
2.
3.
7.
8.
9.
10.
58 MTS-1997
1.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
7.
12.
2.
Lubrication
1.
2.
Electrical Tests
1.
2.
3.
*4.
5.
2.
3.
*4.
*6.
*7.
8.
* Optional
MTS-1997 59
7.
60 MTS-1997
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
4.
5.
6.
7.
8.
Minimum pickup for trip and close coils shall conform to manufacturer's
published data.
7.
2.
3.
4.
5.
6.
7.
1.
2.
3.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
MTS-1997 61
7.
10.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
11.
Lubrication
12.
2.
1.
2.
Electrical Tests
1.
2.
2.
*3.
*4.
5.
* Optional
62 MTS-1997
3.
4.
7.
3.
5.
*6.
7.
8.
9.
*10.
*11.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
4.
* Optional
MTS-1997 63
7.
64 MTS-1997
5.
6.
7.
8.
9.
10.
11.
Minimum pickup for trip and close coils shall conform to manufacturer's
published data.
7.
2.
3.
Perform all mechanical operational tests on both the circuit breaker and its
operating mechanism.
4.
5.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
6.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
7.
Lubrication
8.
1.
2.
MTS-1997 65
7.
Electrical Tests
1.
*2.
*3.
4.
5.
6.
7.
8.
*9.
* Optional
66 MTS-1997
*10.
*11.
*12.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
4.
5.
6.
7.
8.
9.
10.
11.
MTS-1997 67
7.
2.
3.
4.
5.
6.
7.
Verify correct operation of all air and SF6 gas pressure alarms and
cutouts.
8.
9.
10.
11.
68 MTS-1997
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
7.
13.
2.
Lubrication
1.
2.
Electrical Tests
1.
2.
3.
*4.
*5.
Remove a sample of SF6 gas and test in accordance with Table 10.13.
*6.
*7.
*8.
9.
10.
* Optional
MTS-1997 69
7.
70 MTS-1997
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
4.
5.
6.
7.
8.
9.
10.
11.
Minimum pickup for trip and close coils shall conform to manufacturer's
published data.
7.
2.
3.
4.
5.
6.
2.
3.
4.
7.
8.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
MTS-1997 71
7.
11.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
12.
Lubrication
13.
2.
1.
2.
Electrical Tests
1.
2.
2.
*3.
*4.
5.
* Optional
72 MTS-1997
3.
4.
7.
3.
*6.
*7.
8.
Perform power-factor tests on each pole with breaker open and each
phase with breaker closed. Determine tank loss index.
9.
*10.
*11.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
4.
* Optional
MTS-1997 73
7.
74 MTS-1997
5.
6.
7.
8.
9.
10.
11.
Minimum pickup for trip and close coils shall conform to manufacturer's
published data.
7.
2.
3.
Inspect and service operating mechanism and SF6 gas insulated system
in accordance with manufacturer's published data.
4.
5.
Verify correct operation of all air and SF6 gas pressure alarms and
cutouts.
6.
7.
8.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
9.
10.
11.
1.
2.
3.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
Lubrication
1.
2.
MTS-1997 75
7.
Electrical Tests
1.
2.
3.
*4.
*5.
Remove a sample of SF6 gas and test in accordance with Table 10.13.
*6.
*7.
*8.
9.
10.
3.
* Optional
76 MTS-1997
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar breakers by more than 25 percent of the
lowest value.
7.
4.
4.
5.
6.
7.
8.
9.
10.
11.
Minimum pickup for trip and close coils shall conform to manufacturer's
published data.
MTS-1997 77
7.
Circuit Switchers
1.
2.
Lubrication
1.
2.
3.
4.
Perform all mechanical operational tests on both the circuit switcher and
its operating mechanism.
5.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
Use of low-resistance ohmmeter. See Section 7.7.2.1 (Electrical
Tests).
2.
Verify tightness of accessible bolted electrical connections by
calibrated torque-wrench method in accordance with manufacturer's
published data or Table 10.12.
3.
2.
6.
7.
8.
9.
Electrical Tests
1.
78 MTS-1997
Perform resistance measurements through all connections with a lowresistance ohmmeter, if applicable, in accordance with Section 7.7.1.5
(Visual and Mechanical Inspection).
7.
4.
5.
*6.
*7.
8.
3.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar switchers by more than 25 percent of the
lowest value.
4.
Minimum pickup for trip and close coils shall conform to manufacturer's
published data.
5.
6.
7.
* Optional
MTS-1997 79
7.
80 MTS-1997
Open the protector and rack it out of the enclosure. Note that the network
bus and transformer generally will be energized. Exercise extreme
caution. Observe clearances and check for smoothness of operation when
racking.
2.
3.
Inspect the enclosure door gasket and sight glass for damage.
4.
5.
Check for missing parts on the protector. Check tightness of electrical and
mechanical connections. Tighten as necessary according to
manufacturer's published data.
6.
7.
Inspect network protector fuse covers, fuses, and blown fuse indicators for
damage.
8.
9.
10.
Inspect main and arcing contacts. Clean surfaces and align contacts as
necessary.
11.
12.
Manually open and close the protector and verify that the mechanism
latches correctly in each position. Verify correct operation of the position
indicator.
7.
2.
13.
14.
15.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
16.
Lubrication
1.
2.
17.
18.
Electrical Tests
1.
*2.
*3.
4.
*5.
6.
* Optional
MTS-1997 81
7.
Measure minimum pickup voltage of the trip actuator. Verify that the
actuator resets correctly.
9.
10.
3.
* Optional
82 MTS-1997
Verify that the motor can charge the closing mechanism at the minimum
voltage specified by the manufacturer.
2.
3.
4.
Verify the protector will close with voltage on the transformer side
only.
5.
Verify the protector will open when the source feeder breaker is
opened.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar protectors by more than 25 percent of the
lowest value.
4.
5.
6.
7.
Minimum voltage to operate the trip actuator shall not exceed 7.5 percent
of rated control circuit voltage.
8.
9.
MTS-1997 83
7.
Protective Relays
1.
2.
3.
2.
Tighten case connections. Inspect cover for correct gasket seal. Clean
cover glass. Inspect shorting hardware, connection paddles, and/or knife
switches. Remove any foreign material from the case. Verify target reset.
3.
Inspect relay for foreign material, particularly in disc slots of the damping
and electromagnets. Verify disk clearance. Verify contact clearance and
spring bias. Inspect spiral spring convolutions. Inspect disk and contacts
for freedom of movement and correct travel. Verify tightness of mounting
hardware and connections. Burnish contacts. Inspect bearings and/or
pivots.
4.
Verify that all settings are in accordance with coordination study or setting
sheet supplied by owner.
Electrical Tests
1.
2.
2.
3.
Functional Operation
1.
84 MTS-1997
1.
2.
7.
21 Distance Relay
1.
2.
3.
Determine offset.
*4.
3.
4.
5.
24 Volts/Hertz Relay
1.
2.
3.
2.
3.
Determine live line, live bus, dead line, and dead bus set points.
4.
5.
Verify dead bus/live line, dead line/live bus and dead bus/dead line
control functions.
27 Undervoltage Relay
1.
2.
3.
Determine the time delay at a second point on the timing curve for
inverse time relays.
* Optional
MTS-1997 85
7.
2.
3.
4.
5.
Verify the time delay at a second point on the timing curve for
inverse time relays.
*6.
7.
2.
3.
Determine offset.
*4.
8.
9.
* Optional
86 MTS-1997
2.
3.
2.
3.
4.
7.
11.
2.
3.
4.
5.
2.
*3.
12.
13.
2.
Determine pickup.
2.
Determine dropout.
*3.
14.
15.
Determine pickup.
51 Time Overcurrent
1.
2.
2.
* Optional
MTS-1997 87
7.
17.
59 Overvoltage Relay
1.
2.
18.
19.
* Optional
88 MTS-1997
2.
3.
20.
2.
*3.
*4.
5.
6.
7.
79 Reclosing Relay
1.
2.
3.
*4.
5.
22.
23.
24.
81 Frequency Relay
1.
2.
3.
2.
3.
87 Differential
1.
2.
3.
Determine slope.
4.
5.
*6.
* Optional
MTS-1997 89
7.
Control Verification
1.
5.
90 MTS-1997
Verify that each of the relay contacts performs its intended function in the
control scheme including breaker trip tests, close inhibit tests, 86 lockout
tests, and alarm functions.
Test Values
1.
2.
When critical test points are specified, the relay should be calibrated to
those points even though other test points may be out of tolerance.
7.
2.
2.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
4.
5.
Verify correct primary and secondary fuse sizes for voltage (potential)
transformers.
6.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
2.
Perform insulation-resistance test of the current transformer and wiring-toground at 1000 volts dc. For units with solid-state components, follow
manufacturer's recommendations.
3.
MTS-1997 91
7.
3.
* Optional
92 MTS-1997
4.
5.
6.
7.
2.
Perform insulation-resistance tests winding-to-winding and each windingto-ground. Test voltages shall be applied for one minute in accordance
with Table 10.1. Do not perform this test with solid-state devices
connected.
3.
4.
5.
*6.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
7.
8.
MTS-1997 93
7.
2.
2.
3.
4.
5.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
Electrical Tests
1.
2.
*3.
* Optional
94 MTS-1997
7.
2.
3.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
5.
Verify motor and drive train for correct operation and automatic motor cutoff at maximum lower and maximum raise.
6.
7.
8.
9.
MTS-1997 95
7.
1.
Remove oil.
2.
3.
4.
5.
6.
7.
8.
11.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
12.
Lubrication
13.
96 MTS-1997
1.
2.
7.
Electrical Tests
1.
2.
Perform insulation-resistance tests on each winding-to-ground in any offneutral position with the test voltage in accordance with Table 10.5. Test
duration shall be for ten minutes. Calculate polarization index.
3.
4.
5.
6.
*7.
8.
Perform turns ratio test on each voltage step position. Verify that the
indicator correctly identifies all tap positions.
9.
10.
*11.
Verify functioning and accuracy of bandwidth, time delay, voltage and linedrop compensation adjustments.
If regulator has a separate tap-changer compartment, sample insulating
liquid in the main tank in accordance with ASTM D3613 and perform
dissolved-gas analysis in accordance with ANSI/IEEE C57.104 or ASTM
D3612.
* Optional
MTS-1997 97
7.
13.
*14.
Remove a sample of insulating liquid from the main tank or common tank
in accordance with ASTM D923. Sample shall be tested in accordance
with the referenced standard.
1.
2.
3.
4.
5.
6.
*7.
*8.
2.
3.
* Optional
98 MTS-1997
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
7.
Bushing power factors and capacitances should not vary by more than ten
percent of the nameplate values. Investigate any hot collar watts-loss
results that exceed the test equipment manufacturer's published data.
8.
9.
10.
11.
12.
MTS-1997 99
7.
100 MTS-1997
2.
3.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
5.
Check motor and drive train for correct operation and automatic motor cutoff at maximum lower and maximum raise.
6.
7.
8.
9.
10.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
11.
Lubrication
1.
2.
7.
Electrical Tests
1.
2.
Perform insulation-resistance tests winding-to-winding and winding-toground in accordance with Table 10.5. Test duration shall be ten minutes.
Calculate polarization index.
3.
4.
5.
6.
7.
8.
2.
*3.
4.
5.
6.
*7.
*8.
* Optional
MTS-1997 101
7.
3.
* Optional
102 MTS-1997
*9.
*10.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
7.
Bushing power factors and capacitances should not vary by more than ten
percent of nameplate values. Any hot collar watts-loss results that exceed
the test equipment manufacturer's recommendations should be
investigated.
8.
The regulation shall be a linear ratio throughout the range between the
maximum raise and the maximum lower positions.
7.
2.
10.
11.
12.
Current - Reserved
MTS-1997 103
7.
2.
3.
4.
Verify motor and drive train for correct operation and automatic motor
cutoff at maximum lower and maximum raise.
5.
6.
7.
8.
9.
10.
104 MTS-1997
Remove oil.
2.
3.
4.
5.
6.
7.
8.
7.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
12.
Lubrication
13.
2.
1.
2.
Electrical Tests
1.
2.
*3.
4.
5.
6.
2.
3.
* Optional
MTS-1997 105
7.
8.
3.
106 MTS-1997
Test Values
1.
2.
3.
4.
Turns ratio test results shall maintain a normal deviation between each
voltage step and shall not deviate more than one-half percent from the
calculated voltage ratio.
5.
6.
7.
8.
7.
2.
3.
Electrical Tests
1.
2.
Test Values
1.
The resistance between the main grounding electrode and ground should
be no greater than five ohms for commercial or industrial systems and one
ohm or less for generating or transmission station grounds unless
otherwise specified by the owner. (Reference ANSI/IEEE Standard 142)
2.
MTS-1997 107
7.
2.
2.
1.
2.
3.
Verify that all phase conductors and the neutral pass through the
sensor in the same direction for zero sequence systems.
4.
5.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
3.
4.
Electrical Tests
1.
108 MTS-1997
7.
3.
4.
3.
1.
Verify that the relay does not operate at 90 percent of the pickup
setting.
2.
2.
5.
6.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
MTS-1997 109
7.
110 MTS-1997
4.
5.
6.
7.
2.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
4.
2.
3.
*4.
1.
2.
* Optional
MTS-1997 111
7.
7.
8.
9.
10.
11.
Perform a rotation test to insure correct shaft direction if the motor has
been electrically disconnected.
12.
*13.
3.
*2.
112 MTS-1997
2.
* Optional
3.
*4.
7.
7.
8.
Verify that the field application timer and the enable timer for the powerfactor relay have been tested and set to the motor drive manufacturer's
recommended values.
*9.
Record stator current, stator voltage, and field current by strip chart
recorder for the complete acceleration period including stabilization time
for a normally loaded starting condition. From the recording determine the
following information:
1.
2.
3.
4.
Locked-rotor current.
5.
6.
7.
8.
9.
10.
*10.
*11.
* Optional
MTS-1997 113
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
7.
Salient pole voltage drop should be equal for each pole. For direct current
tests each pole (or pair of poles) should not vary more than two percent
from the average.
NOTE: An ac test is more sensitive in determining shorted turns. A pole
with shorted turns will have a substantially lower voltage than sound coils.
Coils adjacent to coils with shorted turns will exhibit slightly lower voltage.
8.
114 MTS-1997
7.
2.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
4.
5.
Perform special tests such as air gap spacing and pedestal alignment, if
applicable.
Electrical Tests
1.
2.
3.
1.
2.
7.
*5.
6.
*7.
8.
3.
2.
Verify that all protective devices are in accordance with Section 7.16.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
2.
* Optional
116 MTS-1997
5.
6.
Generators - Reserved
7.
2.
Inspect contactors.
1.
2.
*3.
4.
Motor-Running Protection
1.
2.
3.
2.
3.
* Optional
MTS-1997 117
7.
2.
5.
6.
Lubrication
1.
2.
Electrical Tests
1.
2.
Measure insulation resistance of each combination starter, phase-tophase and phase-to-ground, with the starter contacts closed and the
protective device open. Test voltage shall be in accordance with Table
10.1. Refer to manufacturer's published data for devices with solid-state
components.
*3.
4.
* Optional
118 MTS-1997
5.
6.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
MTS-1997 119
7.
120 MTS-1997
2.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
3.
Test all electrical and mechanical interlock systems for correct operation
and sequencing.
4.
5.
6.
Inspect contactors.
1.
2.
7.
8.
Thoroughly clean unit prior to testing unless as-found and as-left tests are
required.
7.
2.
Lubrication
1.
2.
Electrical Tests
1.
*2.
Perform system function tests at 1000 volts dc on all control wiring. For
units with solid-state components, follow manufacturer's
recommendations.
3.
4.
5.
*6.
7.
8.
9.
* Optional
MTS-1997 121
7.
11.
12.
3.
122 MTS-1997
13.
14.
15.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
7.
7.
8.
MTS-1997 123
7.
2.
2.
1.
2.
3.
4.
2.
3.
4.
124 MTS-1997
7.
2.
2.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
3.
4.
5.
6.
7.
8.
Tests
1.
2.
3.
4.
5.
Measure each cell voltage and total battery voltage with charger
energized and in float mode of operation.
MTS-1997 125
7.
*7.
*8.
3.
* Optional
126 MTS-1997
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
7.
8.
7.
2.
3.
3.
2.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
Electrical Tests
1.
2.
3.
4.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
Rectifiers - Reserved
MTS-1997 127
7.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
4.
2.
128 MTS-1997
1.
2.
3.
Electrical Tests
1.
2.
3.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
Resistance between the arrester ground terminal and the ground system
shall be less than 0.5 ohm.
MTS-1997 129
7.
2.
2.
3.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
2.
3.
5.
Electrical Tests
1.
2.
4.
130 MTS-1997
4.
*3.
* Optional
1.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
Resistance between the arrester ground terminal and the ground system
shall be less than 0.5 ohm.
5.
6.
MTS-1997 131
7.
2.
132 MTS-1997
2.
3.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
Electrical Tests
1.
2.
3.
4.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
Discharge Time
1 minute
5 minutes
2.
3.
Reactors - Reserved
MTS-1997 133
7.
2.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
3.
2.
2.
3.
Clean insulators.
1.
*2.
4.
134 MTS-1997
Electrical Tests
3.
* Optional
1.
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
MTS-1997 135
7.
2.
3.
136 MTS-1997
2.
2.
3.
4.
5.
6.
Test Values
1.
2.
3.
7.
2.
3.
4.
Test all electrical and mechanical interlock systems for correct operation
and sequencing.
5.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
6.
Thoroughly clean unit prior to tests unless as-found and as-left tests are
required.
7.
8.
MTS-1997 137
7.
Electrical Tests
1.
2.
Test static transfer from inverter to bypass and back. Use normal load, if
possible.
3.
4.
5.
6.
7.
8.
9.
10.
138 MTS-1997
7.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from similar connections by more than 25 percent of the lowest value.
4.
5.
6.
7.
MTS-1997 139
7.
140 MTS-1997
2.
Lubrication
1.
2.
3.
4.
5.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
1.
2.
3.
6.
7.
7.
Electrical Tests
1.
2.
3.
4.
5.
Calibrate and set all relays and timers in accordance with Section 7.9.
6.
7.
1.
2.
3.
4.
2.
3.
4.
5.
6.
7.
8.
MTS-1997 141
7.
7.23
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar switches by more than 25 percent of the
lowest value.
4.
142 MTS-1997
7.
2.
3.
Perform all mechanical operation and contact alignment tests on both the
recloser and its operating mechanism in accordance with manufacturer's
published data.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
5.
2.
1.
2.
3.
Electrical Tests
1.
2.
3.
2.
3.
MTS-1997 143
7.
5.
6.
7.
*8.
*9.
*10.
3.
* Optional
144 MTS-1997
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar reclosers by more than 25 percent of the
lowest value.
7.
5.
6.
7.
8.
9.
MTS-1997 145
7.
2.
3.
Perform all mechanical operation and contact alignment tests on both the
sectionalizer and its operating mechanism in accordance with
manufacturer's published data.
4.
Inspect all bolted electrical connections for high resistance using one of
the following methods:
5.
2.
146 MTS-1997
1.
2.
3.
Electrical Tests
1.
2.
3.
2.
3.
7.
6.
7.
8.
*9.
*10.
3.
Test Values
1.
2.
3.
Microhm or millivolt drop values shall not exceed the high levels of the
normal range as indicated in the manufacturer's published data. If
manufacturer's data is not available, investigate any values which deviate
from adjacent poles or similar sectionalizers by more than 25 percent of
the lowest value.
4.
5.
6.
7.
* Optional
MTS-1997 147
7.
2.
3.
148 MTS-1997
Field Test
1.
2.
3.
4.
Test Values
1.
2.
7.
2.
Electrical Tests
1.
2.
3.
3.
Category A: Used for bare-hand work and has lower test electrode
system.
2.
3.
Category C: Used for rubber-glove work and does not have lower
test electrode system. Rated for 46 kV and below.
2.
3.
4.
5.
Test Values: Maximum currents should be less than indicated on Table 10.11.
MTS-1997 149
7.
150 MTS-1997
8.
General
1.
2.
Implementation
1.
2.
Verify the correct operation of all interlock safety devices for fail-safe
functions in addition to design function.
3.
Verify the correct operation of all sensing devices, alarms, and indicating
devices.
MTS-1997 151
9.THERMOGRAPHIC SURVEY
9.1
2.
9.2
9.3
Discrepancies.
2.
Temperature difference between the area of concern and the reference area.
3.
4.
5.
*6.
9.4
9.5
Test Parameters
1.
2.
Equipment shall detect emitted radiation and convert detected radiation to visual
signal.
3.
Test Results
Suggested actions based on temperature rise can be found in Table 10.18.
* Optional
152 MTS-1997
TABLE 10.1
Insulation Resistance Tests
on
Electrical Apparatus and Systems
Maximum Rating of
Equipment in Volts
Recommended Minimum
Insulation Resistance in
Megohms
250
500
25
600
1,000
100
5,000
2,500
1,000
8,000
2,500
2,000
15,000
2,500
5,000
25,000
5,000
20,000
35,000
15,000
100,000
46,000
15,000
100,000
69,000
15,000
100,000
In the absence of consensus standards dealing with insulation-resistance tests, the NETA Technical Committee
suggests the above representative values.
See Table 10.14 for temperature correction factors.
Actual test results are dependent on the length of the conductor being tested, the temperature of the insulating
material, and the humidity of the surrounding environment at the time of the test. In addition, insulation resistance
tests are performed to establish a trending pattern and a deviation from the baseline information obtained during
maintenance testing enabling the evaluation of the insulation for confined use.
MTS-1997 153
TABLE 10.2
Switchgear Low-Frequency Withstand Test Voltages
Type of Switchgear
(kV) (rms)
ac
dc
.254/.508/.635
1.6
2.3
MC
4.76
14.0
20.0
(Metal-Clad Switchgear)
8.25
27.0
37.0
15.0
27.0
37.0
38.0
60.0
SC
15.5
37.0
(Station-Type Cubicle
38.0
60.0
Switchgear)
72.5
120.0
MEI
4.76
14.0
20.0
(Metal-Enclosed
8.25
19.0
27.0
Interrupter Switchgear)
15.0
27.0
37.0
15.5
37.0
52.0
25.8
45.0
38.0
60.0
LV
(Low-Voltage Power
Circuit Breaker
Switchgear)
Derived from ANSI/IEEE C37.20.1-1993, Paragraph 5.5, Standard for Metal-Enclosed Low-Voltage Power Circuit-Breaker
Switchgear, C37.20.2-1993, Paragraph 5.5, Standard for Metal-Clad and Station-Type Cubicle Switchgear and C37.20.31993, Paragraph 5.5, Standard for Metal-Enclosed Interrupter Switchgear, and includes 0.75 multiplier with fraction rounded
down.
The column headed "DC" is given as a reference only for those using dc tests to verify the integrity of connected cable
installations without disconnecting the cables from the switchgear. It represents values believed to be appropriate and
approximately equivalent to the corresponding power frequency withstand test values specified for voltage rating of
switchgear. The presence of this column in no way implies any requirement for a dc withstand test on ac equipment or that a
dc withstand test represents an acceptable alternative to the low-frequency withstand tests specified in this specification,
either for design tests, production tests, conformance tests, or field tests. When making dc tests, the voltage should be
raised to the test value in discrete steps and held for a period of one minute.
Because of the variable voltage distribution encountered when making dc withstand tests, the manufacturer should be
contacted for recommendations before applying dc withstand tests to the switchgear. Voltage transformers above 34.5kV
should be disconnected when testing with dc. Refer to ANSI/IEEE C57-13-1978 (R1987) IEEE Standard Requirements for
Instrument Transformers [10], Section 8 and, in particular 8.8.2, (the last paragraph) which reads "Periodic kenotron tests
should not be applied to transformers of higher than 34.5 kV voltage rating."
+ Consult Manufacturer
154 MTS-1997
TABLE 10.3
Recommended Dissipation Factor/Power Factor
of Liquid-Filled Transformers
Oil
Maximum
Silicone
Maximum
Tetrachloroethylene
Maximum
Power
Transformers
2.0%
0.5%
3.0%
2.0%
Distribution
Transformers
3.0%
0.5%
3.0%
3.0%
In the absence of consensus standards dealing with transformer dissipation factor/power factor values, the NETA
Technical Committee suggests the above representative values.
MTS-1997 155
TABLE 10.4
Suggested Limits for Service-Aged Insulating Fluids
Mineral Oil*
ASTM Method
69 kV and
Below
Above 69 kV
through 288 kV
345 kV and
Above
Dielectric breakdown, kV
minimum
D877
26
26
26
Dielectric breakdown, kV
minimum @ 0.04 gap
D1816
23
26
26
Dielectric breakdown, kV
minimum @ 0.08 gap
D1816
34
45
45
D971
24
26
30
Neutralization number, mg
KOH/g maximum
D974
0.2
0.2
0.1
D1533
35
25
20
D924
1.0****
1.0****
1.0****
D924
1.0****
1.0****
1.0****
Test
ASTM Method
Silicone**
Less Flammable
Hydrocarbon***
D877
25
24
Visual
D2129
Colorless, clear,
free of particles
N/A
D1533
100
45
D924
0.2
1.0
D445
47.5 - 52.5
N/A
D92
340
300
D974
0.2
N/A
D664
N/A
0.25
D971
N/A
22
Test
*
**
***
****
IEEE C57.106-1991 Guide for Acceptance and Maintenance of Insulating Oil in Equipment, Table 5.
IEEE C57.111-1989 Guide for Acceptance of Silicone Insulating Fluid and Its Maintenance in Transformers, Table
3.
IEEE C57.121-1988 Guide for Acceptance and Maintenance of Less Flammable Hydrocarbon Fluid in
Transformers, Table 3.
IEEE Standard. 637-1985 IEEE Guide for the Reclamation of Insulating Oil and Criteria for Its Use.
156 MTS-1997
TABLE 10.5
Transformer Insulation-Resistance
Recommended Minimum
Insulation Resistance in Megohms
Transformer Coil
Rating Type in Volts
Minimum dc Test
Voltage
Liquid Filled
Dry
0 - 600
1000
100
500
601 - 5000
2500
1000
5000
5001 - 15000
5000
5000
25000
In the absence of consensus standards, the NETA Technical Committee suggests the above representative values.
NOTE: Since insulation resistance depends on insulation rating (kV) and winding capacity (kVA), values obtained should
be compared to manufacturer's published data.
MTS-1997 157
TABLE 10.6
Medium-Voltage Cables
Maximum Maintenance Test Voltages (kV, dc)
Insulation Type
Insulation Level
Elastomeric:
5 kV
100%
19
5 kV
133%
19
15 kV
100%
41
15 kV
133%
49
25 kV
100%
60
Elastomeric:
5 kV
100%
19
EPR
5 kV
133%
19
8 kV
100%
26
8 kV
133%
26
15 kV
100%
41
15 kV
133%
49
25 kV
100%
60
25 kV
133%
75
28 kV
100%
64
35 kV
100%
75
Polyethylene
5 kV
100%
19
(see Note 4)
5 kV
133%
19
8 kV
100%
26
8 kV
133%
26
15 kV
100%
41
15 kV
133%
49
25 kV
100%
60
25 kV
133%
75
35 kV
100%
75
Derived from ANSI/IEEE Standard 141-1993 Table 12-9 and by factoring the applicable ICEA/NEMA Standards by 75% as
recommended in Section 18-9.2.4 of NFPA 70B, 1994 Edition Electrical Equipment Maintenance.
Refer to notes on the following page.
158 MTS-1997
Selection of test voltage for in-service cables depends on many factors. The owner should be consulted
and/or informed of the intended test voltage prior to performing the test. Caution should be used in
selecting the maximum test voltage and performing the test since cable failure during the test will require
repair or replacement prior to re-energizing.
NOTE 2:
AEIC C55 and C56 list test voltages approximately 20 percent higher than the ICEA values for the first five
years of service. These values are based on 65 percent of the factory test voltages. A reduction to 40
percent is recommended for a cable in service longer than five years.
NOTE 3:
ANSI/IEEE 400-1991 specifies much higher voltages than either the ICEA or the AEIC. These voltages
overstress cables and are intended to find marginal cable during shutdown to avoid in-service failures.
These test voltages should not be used without the concurrence of the owner. If the cable is still in
warranty, the cable manufacturer should be consulted for their concurrence. (See the Standard for a
discussion of the pros and cons of high direct-voltage tests.)
NOTE 4:
See Electric Power Research Institute Report, EPRI TR-101245, "Effect of DC Testing on Extruded
Cross-Linked Polyethylene Insulated Cables." DC high potential testing of aged XLPE-insulated cable in
wet locations may reduce remaining life.
MTS-1997 159
TABLE 10.7
Molded-Case Circuit Breakers
Values for Inverse Time Trip Test
(At 300% of Rated Continuous Current of Circuit Breaker)
Range of Rated Continuous
Current Amperes
251 - 600V
0-30
50
70
31-50
80
100
51-100
140
160
101-150
200
250
151-225
230
275
226-400
300
350
401-600
------------
450
601-800
------------
500
801-1000
------------
600
1001-1200
------------
700
1201-1600
------------
775
1601-2000
------------
800
2001-2500
------------
850
2501-5000
------------
900
For integrally-fused circuit breakers, trip times may be substantially longer if tested with the fuses replaced by solid links
(shorting bars).
160 MTS-1997
TABLE 10.8
Instantaneous Trip Setting Tolerances
for Field Testing
of Marked Adjustable Trip Circuit Breakers
Tolerances of High and Low Settings
Ampere Rating
High
Low
250
+40%
-25%
+40%
-30%
>250
25%
30%
MTS-1997 161
TABLE 10.9
Instrument Transformer Dielectric Tests
Field Maintenance
Nominal System (kV)
BIL
(kV)
dc
0.6
10
2.6
1.1
30
6.5
10
2.4
45
9.7
15
4.8
60
12.3
19
8.32
75
16.9
26
13.8
95
22.1
34
13.8
110
22.1
34
25
125
26.0
40
25
150
32.5
50
34.5
150
32.5
50
34.5
200
45.5
70
46
250
61.7
69
350
91.0
115
450
120.0
115
550
149.0
138
550
149.0
138
650
178.0
161
650
178.0
161
750
211.0
230
900
256.0
230
1050
299.0
Table 10.9 is derived from Paragraph 8.8.2 and Tables 2 and 7 of ANSI/IEEE C57.13, "Standard Requirements for
Instrument Transformers."
+ Periodic dc potential tests are not recommended for transformers rated higher than 34.5 kV.
* Under some conditions transformers may be subjected to periodic insulation test using direct voltage from kenotron sets.
In such cases the test direct voltage should not exceed the original factory test rms alternating voltage. Periodic kenotron
tests should not be applied to (instrument) transformers of higher than 34.5 kV voltage rating.
162 MTS-1997
TABLE 10.10
Maximum Allowable Vibration Amplitude
Speed - RPM
0.001
1500 - 2999
0.002
1000 - 1499
0.0025
0.003
Derived from NEMA publication MG 1-1993, Sections 20.53, 21.54, 22.54, 23.52, and 24.50.
MTS-1997 163
TABLE 10.11
Periodic Electrical Test Values for Insulating Aerial Devices
Insulating Aerial Devices with a Lower Test Electrode System
(Category A and Category B)
Unit Rating
Voltage kV
(rms)
Maximum
Allowable
Current
Microamperes
Time
Voltage kV
Maximum
Allowable
Current
Microamperes
Time
46 kV & below
40
40
1 minute
56
28
3 minutes
69 kV
60
60
1 minute
84
42
3 minutes
138 kV
120
120
1 minute
168
84
3 minutes
230 kV
200
200
1 minute
240
120
3 minutes
345 kV
300
300
1 minute
360
180
3 minutes
500 kV
430
430
1 minute
602
301
3 minutes
765 kV
660
660
1 minute
924
462
3 minutes
46 kV & below
Voltage kV
(rms)
Maximum
Allowable Current
Microamperes
Time
Voltage kV
Maximum
Allowable Current
Microamperes
Time
40
400
1 minute
56
56
3 minutes
Voltage kV
(rms)
Maximum
Allowable Current
Microamperes
Time
Voltage kV
Maximum
Allowable Current
Microamperes
Time
46 kV & below
40
400
1 minute
56
56
3
minutes
20 kV & below
20
200
1 minute
28
28
3
minutes
164 MTS-1997
Voltage kV
(rms)
Maximum
Allowable Current
Milliamperes
Time
Voltage kV
Maximum
Allowable Current
Microamperes
Time
35
3.0
3 minutes
50
50
3 minutes
NOTE:
1.
Derived from ANSI/SIA A92-2-1990.
2.
A method of calculating test voltages for units rated other than those tabulated here is as follows:
1.
The 60 Hz test values are equal to line to ground at the unit rating value time 1.5.
2.
Multiply the 60 Hz test values times 1.4 to arrive at the direct current values.
MTS-1997 165
TABLE 10.12
US Standard
Bolt Torques for Bus Connections
Heat-Treated Steel - Cadmium or Zinc Plated
Grade
SAE 1 & 2
SAE 5
SAE 7
SAE 8
Minimum Tensile
(P.S.I.)
64K
105K
133K
150K
Bolt Diameter
In Inches
1/4
4.0
5.6
8.0
8.4
5/16
7.2
11.2
15.2
17.6
3/8
12.0
20.0
27.2
29.6
7/16
19.2
32.0
44.0
48.0
1/2
29.6
48.0
68.0
73.6
9/16
42.4
70.4
96.0
105.6
5/8
59.2
96.0
133.6
144.0
3/4
96.0
160.0
224.0
236.8
7/8
152.0
241.6
352.0
378.4
1.0
225.6
372.8
528.0
571.2
Nonlubricated
Lubricated
5/16
15
10
3/8
20
14
1/2
40
25
5/8
55
40
3/4
70
60
Bronze alloy bolts shall have a minimum tensile strength of 70,000 pounds per square inch.
166 MTS-1997
Lubricated
5/16
8.0
3/8
11.2
1/2
20.0
5/8
32.0
3/4
48.0
Aluminum alloy bolts shall have a minimum tensile strength of 55,000 pounds per square inch.
Uncoated
5/16
14
3/8
25
1/2
45
5/8
60
3/4
90
Bolts, cap screws, nuts, flat washers, locknuts: 18-8 alloy. Belleville washers: 302 alloy.
MTS-1997 167
Table 10.13
SF6 Gas Tests
Test
Test Limits
Dielectric Breakdown
using hemispherical contacts at 0.10 inch
gap at atmospheric pressure
11.5 - 13.5 kV
(1)
(2)
(3)
(4)
(3)
(4)
168 MTS-1997
TABLE 10.14
Insulation Resistance
Conversion Factors
For Conversion of Test
Temperature to 20C
Temperature
C
Multiplier
F
Apparatus Containing
Immersed Oil Insulations
Apparatus Containing
Solid Insulations
32
0.25
0.40
41
0.36
0.45
10
50
0.50
0.50
15
59
0.75
0.75
20
68
1.00
1.00
25
77
1.40
1.30
30
86
1.98
1.60
35
95
2.80
2.05
40
104
3.95
2.50
45
113
5.60
3.25
50
122
7.85
4.00
55
131
11.20
5.20
60
140
15.85
6.40
65
149
22.40
8.70
70
158
31.75
10.00
75
167
44.70
13.00
80
176
63.50
16.00
MTS-1997 169
TABLE 10.15
High-Potential Test Voltage
for Automatic Circuit Reclosers
Nominal Voltage
Class, kV
Maximum Voltage, kV
Rated Impulse
Withstand Voltage, kV
14.4 (1 and 3)
15.0
95
26.2
14.4 (1 and 3)
15.5
110
37.5
24.9 (1 and 3)
27.0
150
45.0
34.5 (1 and 3)
38.0
150
52.5
46.0 (3)
48.3
250
78.7
69.0 (3)
72.5
350
120.0
Derived from ANSI/IEEE C37.61-1973(R1993) (Standard Guide for the Application, Operation, and Maintenance
of Automatic Circuit Reclosers), C37.60-1981(R1993) (Standard Requirements for Overhead, Pad-Mounted, DryVault, and Submersible Automatic Circuit Reclosers and Fault Interrupters for AC Systems).
170 MTS-1997
TABLE 10.16
High-Potential Test Voltage
for Periodic Test of Line Sectionalizers
Nominal Voltage
Class kV
Maximum
Voltage kV
Rated Impulse
Withstand
Voltage kV
Maximum Field
Test Voltage
kVAC
DC 15 Minute
Withstand (kV)
14.4 (1)
15.0
95
26.2
39
14.4 (1)
15.0
125
31.5
39
14.4 (3)
15.5
110
37.5
39
24.9 (1)
27.0
125
45.0
58
34.5 (3)
38.0
150
52.5
77
Derived from ANSI/IEEE C37.63-1984(R1990) Table 2 (Standard Requirements for Overhead, Pad-Mounted, Dry-Vault,
and Submersible Automatic Line Sectionalizers of AC Systems).
The table includes a 0.75 multiplier with fractions rounded down.
In the absence of consensus standards, the NETA Technical Committee suggests the above representative values.
NOTE: Values of ac voltage given are dry test one minute factory test values.
MTS-1997 171
Table 10.17
Metal-Enclosed Bus Dielectric Withstand Test Voltages
Type of Bus
Rated kV
dc
24.5
29.5
34.5
37.0
45.0
60.0
52.0
---
15.5
25.8
38.0
37.0
45.0
60.0
52.0
---
Nonsegregated Phase
0.635
4.76
15.0
25.8
38.0
1.6
14.2
27.0
45.0
60.0
2.3
20.0
37.0
63.0
--
Segregated Phase
15.5
25.8
38.0
37.0
45.0
60.0
52.0
63.0
--
0.3
0.8
1.2
1.6
3.2
1.6
2.7
3.4
4.0
6.6
2.3
3.9
4.8
5.7
9.3
DC Bus Duct
Derived from ANSI-IEEE C37.23-1987, Tables 3A, 3B, 3C, 3D and paragraph 6.4.2. The table includes a 0.75 multiplier
with fractions rounded down.
Note:
The presence of the column headed "dc" does not imply any requirement for a dc withstand test on ac equipment.
This column is given as a reference only for those using dc tests and represents values believed to be appropriate
and approximately equivalent to the corresponding power frequency withstand test values specified for each class
of bus.
Direct current withstand tests are recommended for flexible bus to avoid the loss of insulation life that may result
from the dielectric heating that occurs with rated frequency withstand testing.
Because of the variable voltage distribution encountered when making dc withstand tests and variances in leakage
currents associated with various insulation systems, the manufacturer should be consulted for recommendations
before applying dc withstand tests to this equipment.
172 MTS-1997
TABLE 10.18
Thermographic Survey
Suggested Actions Based on Temperature Rise
Temperature difference (DT)
based on comparisons
between similar components
under similar loading.
Recommended Action
1C - 3C
0C - 10C
4C - 15C
11C - 20C
-- -- --
> 16C
22C - 40C
> 40C
Temperature specifications vary depending on the exact type of equipment. Even in the same class of
equipment (i.e., cables) there are various temperature ratings. Heating is generally related to the
square of the current; therefore, the load current will have a major impact on T. In the absence of
consensus standards for T, the values in this table will provide reasonable guidelines.
MTS-1997 173
TABLE 10.19
Overpotential Test Voltages for Electrical Apparatus
Other than Inductive Equipment
Nominal
System (Line)
1
Voltage (kV)
Insulation
Class
AC Factory
Test (kV)
Maximum
Field Applied
AC Test (kV)
Maximum
Field Applied
DC Test (kV)
1.2
1.2
10
6.0
8.5
2.4
2.5
15
9.0
12.7
4.8
5.0
19
11.4
16.1
8.3
8.7
26
15.6
22.1
14.4
15.0
34
20.4
28.8
18.0
18.0
40
24.0
33.9
25.0
25.0
50
30.0
42.4
34.5
35.0
70
42.0
59.4
46.0
46.0
95
57.0
80.6
69.0
69.0
140
84.0
118.8
In the absence of consensus standards, the NETA Technical Committee suggests the above representative values.
1
Intermediate voltage ratings are placed in the next higher insulation class.
174 MTS-1997
2 years $125
or Visa
3 years $150
Mastercard
Expiration Date
Acceptance Specification OR
Maintenance Specification
I hereby agree to abide by the ByLaws of the Association and not to use the NETA logo. I understand my Affiliate status
does not entitle me to claim NETA membership in the performance of electrical testing.
Signature
Date