Schneider NS MCCB
Schneider NS MCCB
Schneider NS MCCB
12481
DATA SHEET
NS MCCB
Based on Schneider LVPED208012EN Catalogue
General characteristics
12481
DB105167
Standardised characteristics indicated on the rating plate: Ui: rated insulation voltage Uimp: rated impulse withstand voltage Icu: ultimate breaking capacity, for various values of the rated operational voltage Ue cat: utilisation category Icw: rated short-time withstand current Ics: service breaking capacity In: rated current suitable for isolation
Pollution degree
Compact NS circuit breakers are certified for operation in pollution-degree 3 environments as defined by IEC standard 60947 (industrial environments).
Tropicalisation
Compact NS circuit breakers have successfully passed the tests prescribed by the following standards for extreme atmospheric conditions: b IEC 60068-2-1 - dry cold (-55 C) b IEC 60068-2-2 - dry heat (+85 C) b IEC 60068-2-30 - damp heat (95 % relative humidity at 55 C) b IEC 60068-2-52 - salt mist (severity level 2).
Environmental protection
Compact NS circuit breakers take into account important concerns for environmental protection. Most components are recyclable and the parts of Compact NS630b to NS3200 circuit breakers are marked as specified in applicable standards.
Ambient temperature
b Compact NS circuit breakers may be used between -25 C and +70 C. For temperatures higher than 40 C (65 C for circuit breakers used to protect motor feeders), devices must be derated as indicated in the documentation. b circuit-breakers should be put into service under normal ambient operatingtemperature conditions. Exceptionally, the circuit breaker may be put into service when the ambient temperature is between -35 C and -25 C. the permiss ble storage-temperature range for Compact NS circuit breakers in the original packing is -50 C (1) to +85 C.
Discrimination
As standard, the Compact NS range ensures discrimination between two circuit breakers positioned in series in an installation.
E22037
CB1
CB2
Page 1 of 41
12481
044334R_55
All Compact NS circuit breakers are suitable for isolation as defined in IEC standard 60947-2: b the isolation position corresponds to the O (OFF) position b the operating handle cannot indicate the OFF position unless the contacts are effectively open b padlocks may not be installed unless the contacts are open. Installation of a rotary handle or a motor mechanism does not alter the reliability of the position-indication system. The isolation function is certified by tests guaranteeing: b the mechanical reliability of the position indication system b the absence of leakage currents b overvoltage withstand capacity between upstream and downstream connections.
E18569
Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102 (IK degree of protection against external mechanical impacts).
With toggle
IP40
IK07
IP40
IK07
standard / VDE
ON
O O F
IP40
IK07
ON
IK07
E28440
IP55
IK08
ON
ON F
OF
IP40
IK07
1 m n u
O
O
I
h
Page 2 of 41
12481
PB101050_33
Connections
Compact NS250H
Compact NS630N
Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 40 C 65 C Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Type of circuit breaker Ultimate breaking capacity (kA rms) lcu AC 220/240 V 50/60 Hz 380/415 V 440 V 500 V 525 V 660/690 V Service breaking capacity (kA rms) lcs % Icu Suitability for isolation Utilisation category Durability (C-O cycles) mechanical electrical 440 V In/2 In Electrical characteristics as per NEMA AB1 (H.I.C.) Breaking capacity (kA) 240 V 480 V 600 V Electrical characteristics as per UL508 Breaking capacity (kA) 240 V 480 V 600 V Protection Trip units Overload protection long ime Ir (In x ) Short-circuit protection short time lsd (Ir x ) instantaneous Ii (In x ) Ear h-fault protection lg (In x ) Zone selective interlocking ZSI Add-on earth-leakage protection add-on Vigi module combination with Vigirex relay Current measurements Additional measurement, indication and control auxiliaries Indication contacts MX shunt and MN undervoltage releases Voltage-presence indicator Current-transformer module and ammeter module Insulation-monitoring module Remote communication by bus Device-status indication Device remote operation Transmission of settings Indication and identification of protection devices and alarms Transmission of measured current values Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons Dimensions (mm) W x H x D fixed, front connections 2-3P / 4P Weight (kg) fixed, front connections 3P / 4P Source changeover system (see section on source changeover systems) Manual, remote-operated and automatic source changeover systems
PB101044_42
(1) 2P in 3P case for type N only (2) specific trip units are available for operational voltages > 525 V (3) NS100N et U u 500 V: Ics = 50 % Icu (4) operational voltage y 500 V
Page 3 of 41
12481
NS125E
3, 4 b b b 125 750 8 500 E 25 16/10 10 6 50 % b A 10000 6000 6000 E 5 5 E non interchangeable 12.5 125 (A) b b b b -
NS100
2 (1), 3, 4 b b b b b b b b b 100 100 750 8 690 750 N SX 85 90 36 50 35 50 25 36 22 35 8 10 100 % (3) b A 50000 50000 30000 N SX 85 90 35 50 8 20 N SX 85 85 25 50 10 10
NS160
2 (1), 3, 4 b b b b b b b b b 160 150 750 8 690 750 N 85 36 35 30 22 8 100 % b A 40000 40000 20000 N 85 35 20 N 85 35 10
NS250
2 (1), 3, 4 b b b b b b b b b 250 220 750 8 690 750 N 85 36 35 30 22 8 100 % b A 20000 20000 10000 N 85 35 20 N 85 35 18
NS400
3, 4 b b b b b b b b b 400 320 750 8 690 750 N 85 50 42 30 22 10 (2) 100 % b A 15000 12000 6000 N 85 42 20 N -
NS630
3, 4 b b b b b b b b b 630 500 750 8 690 750 N H 85 100 50 70 42 65 30 50 22 35 10 (2) 20 (2) 100 % (4) b A 15000 8000 4000 N H 85 100 42 65 20 35 N H -
H 100 70 65 50 35 10
SX 90 50 50 36 35 10
H 100 70 65 50 35 10
SX 90 50 50 36 35 10
H 100 70 65 50 35 10
H 100 70 65 50 35 20 (2)
H 100 65 35 H 85 65 10
L 200 130 50 L -
SX 90 50 20 SX 85 50 10
H 100 65 35 H 85 65 10
L 200 130 50 L -
SX 90 50 20 SX 85 50 18
H 100 65 35 H 85 65 18
L 200 130 50 L -
H 100 65 35 H -
L 200 130 50 L -
L 200 130 50 L -
TM (thermal-magnetic) b b b b b b b b b b b -
STR22 (electronic) b b b b b -
STR23 (electronic) b b b b b b b b b b
STR53 (electronic) b b b b b b b b
b b -
b b -
b b b b b
Page 4 of 41
12481
DB112530
Compact NS800L
E45178R_68
Compact NS2000H
front connection rear connection front connection with bare cables wi hdrawable (on chassis) front connection rear connection Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 50 C 65 C (1) Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz Type of circuit breaker Ultimate breaking capacity (kA rms) lcu AC 220/240 V 50/60 Hz 380/415 V 440 V 500/525 V 660/690 V Service breaking capacity (kA rms) lcs Value or % Icu manual operation electrical operation Short-time withstand current (kA rms) lcw AC 50/60 Hz 1 s 3s Integrated instantaneous protection kA peak 10 % Suitability for isolation Utilisation category Durability (C-O cycles) mechanical electrical 440 V In/2 In 690 V In/2 In Pollution degree Electrical characteristics as per Nema AB1 Breaking capacity at 60 Hz (kA) 240 V 480 V 600 V Protection and measurements Interchangeable control units Overload protection long time Ir (In x ) Short-circuit protection short time Isd (Ir x ) instantaneous Ii (In x ) Ear h-fault protection lg (In x ) Residual ear h-leakage protection In Zone selective interlocking ZSI Protection of the fourth pole Current measurements Power measurements Advanced protection Remote communication by bus Device-status indication Device remote operation Transmission of settings Indication and identification of protection devices and alarms Transmission of measured current values Additional indication and control auxiliaries Indication contacts Voltage releases MX shunt release/MN undervoltage release Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons Dimensions fixed devices, front connections (mm) 3P HxWxD 4P Weight fixed devices, front connections (kg) 3P 4P Source changeover system (see section on "source changeover systems") Manual, remote-operated and automatic source changeover systems
(1) 65 C with vertical connections. See the temperature derating tables for other types of connections. (2) Ics: 100 % Icu for breaking capacity 440V/500V/660V Ics: 75 % Icu for breaking capacity 220V/380V. (3) Except 1600b-3200.
Page 5 of 41
12481
NS630b
3, 4 b b b (except LB) N H b b b b b b b b b b 630 630 800 8 690 N 50 50 50 40 30 100 % 75 % 19.2 40 b B 10000 6000 5000 4000 2000 3 N 50 35 25
NS800
NS1000
3, 4 b b b N b b b b b 1000 1000 800 8 690 N 50 50 50 40 30 100 % 75 % 19 2 40 b B 10000 6000 5000 4000 2000 3 N 50 35 25
NS1250
3, 4 b b b N b b b b b
NS1600
3, 4 b b b N b b b b 1600 1510 800 8 690 N 50 50 50 40 30 75 % 75 % 19.2 40 b B 10000 5000 2000 2000 1000 3 N 50 35 25
NS1600b
3, 4 b N b 1600 1550 800 8 690 N 85 70 65 65 65 100 % (2) 100 % (2) 32 130 b B 5000 3000 2000 2000 1000 3 N 85 65 50
NS2000
NS2500 NS3200
L b b b b 800 800
LB b b b
H b b b b b
L b b b b
H b b b b b
H b b b b
L 150 150 130 100 100 % 100 % A 4000 3000 3000 2000 L 125 100 -
LB 200 200 200 100 75 100 % A 4000 3000 3000 2000 LB 200 200 100
1250 1250 800 8 690 H L N 70 150 50 70 150 50 65 130 50 50 100 40 42 30 75 % 100 % 100 % 50 % 100 % 75 % 19.2 19.2 40 40 b B A B 10000 6000 4000 5000 5000 3000 4000 4000 3000 3000 2000 2000 2000 3 H L N 65 125 50 50 100 35 50 25
H 70 70 65 50 42 75 % 50 % 19.2 40 B
H 70 70 65 50 42 50 % 50 % 19 2 40 B
H 125 85 85 75 % 75 % 32 130 B
H 65 50 50
H 65 50 50
H 125 85 Micrologic 5.0 P (3) Micrologic 6.0 P (3) b b b b b b b b b b b b b b b b b b b b b b b b b b b Micrologic 7.0 P (3) b b b b b b b b b b b b b
Micrologic 5.0 b b b b b b -
Micrologic 2.0 A b b b b b b b b b b
Micrologic 5.0 A b b b b b b b b b b b b b
Micrologic 6.0 A b b b b b b b b b b b b b
Micrologic 7.0 A b b b b b b b b b b b b b b b
Page 6 of 41
12481
Compact NS100 to 250 circuit breakers, types N, SX, H and L, may be equipped with either a TM thermalmagnetic trip unit or an STR22 electronic trip unit. A mechanical mismatch-protection system avoids breaker and trip unit mismatches.
13 TM-D
16
25
40
63
80
100
250
Standard protection
Ir
Im
10 9
5 6
.9
.8
x 250A 0 Ir Im I
x 250A
Ir
Im
Protection
The protection functions may be set using the adjustment dials. Overload protection Thermal protection with an adjustable threshold. Short-circuit protection Magnetic protection with a fixed or adjustable pick-up, depending on the rating. Protection of the fourth pole On four-pole circuit breakers, the trip units can be of the: 4P 3d type (neutral unprotected), 4P 3d + N/2 type (neutral protection at 0.5 In) or 4P 4d type (neutral protection at In).
TM16D to 250D
16 b b b b 25 b b b b 32 b b b b 40 b b b b 50 b b b b 63 b b b b 80 b b b b 100 b b b b 125 b b b 160 b b 200 250
TM16G to 63G
b
16 b b b b
25 b b b b
40 b b b b
63 b b b b
adjustable from 0.8 to 1 x In fixed adjustable 190 300 400 500 500 500 640 800 190 300 400 500 500 500 1000 1250 1250 1250 5 to 10 x ln no protection 56 1 x Ir 56 63 0.5 x Ir
80 80
125 125
no protection 1 x Ir
Page 7 of 41
12481
1 2 3 4 5 6 7
long-time threshold (overload protection) Ir long-time tripping delay short-time pick-up (short-circuit protection) Isd short-time tripping delay instantaneous pick-up (short-circuit protection) Ii test connector percent load indication
Protection
The protection functions may be set using the adjustment dials. Overload protection True rms long-time protection with an adjustable threshold. Short-circuit protection Short-time and instantaneous protection: b short-time protection with an adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up. Protection of the fourth pole On four-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d (neutral protection at In). Protection of an overloaded neutral (OSN): For 4-pole circuit breakers, special protection of systems with high 3rd order harmonic contents. In position 4P 4d, the switch sets the neutral protection threshold to 1.6 x Ir.
E58711
4P 4d
Indications
A LED on the front indicates the percent load: b ON - load is > 90 % of Ir setting b flashing - load is > 105 % of Ir setting.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.
STR22SE
40 b b b 80 b b 100 b b b 160 b b b
STR22SE OSN
250 (1) 160 b b 0.250.63 48 settings 90...180 5...7.5 3.2...5.0 250 (1) b
STR22GE
40 b b b 100 b b b 160 b b 250 (1) b
at 1.5 x Ir at 6 x Ir at 7.2 x Ir Short-circuit protection (Short Time) Pick-up (A) Isd = Ir x 2...10 2...10 2...10 Accuracy 15 % 8 settings 8 settings 8 settings Time delay (ms) fixed fixed fixed max. resettable time y 40 y 40 y 40 max. break time y 60 y 60 y 60 Short-circuit protection (Instantaneous) Pick-up (A) Ii fixed u 11 x In fixed u 7 x In fixed u 11 x In Protection of the fourth pole Neutral unprotected 4P 3d no protection no protection Neutral protection at 0.5 In 4P 3d + N/2 0.5 x Ir 0.8 x Ir Neutral protection at In 4P 4d 1 x Ir 1.6 x Ir (1) If the STR22SE, STR22SE OSN and STR22GE 250 A trip units are used in high-temperature environments, the setting must take into account the thermal limitations of the circuit breaker. The overload protection setting may not exceed 0.95 at 60 C or 0.9 at 70 C.
Setting example
What is the overload-protection threshold of a Compact NS250 circuit breaker equipped with an STR22SE 160 A trip unit set to Io = 0.5 and Ir = 0.8 ? Answer: In x Io x Ir = 160 x 0.5 x 0.8 = 64 A.
E25979
Io
.8 .9
Ir
1 .88 .85 .8 .9 .93 .95 .98 1
x Io
.7 .63 .5
x In
Page 8 of 41
12481
Compact NS400 to 630 circuit breakers, types N, H and L, 3-pole and 4-pole, may be equipped with any of the STR23SE, STR23SV, STR53UE and STR53SV electronic trip units. The STR53UE and STR53SV trip units offer a wider range of settings and the STR53UE offers a number of optional protection, measurement and communications functions.
DB105116
40 60
250
400
500
600
Standard protection with selectivity Protection of systems supplied by generators. Protection of long cables
Selection of the trip unit depends on the type of distribution system protected and the operational voltage of the circuit breaker. Protection for all types of circuits, from 60 to 630 A, is possible with only five trip-unit catalogue numbers, whatever the circuit-breaker operational voltage: b U y 525 V: STR23SE, STR23SE OSN or STR53UE b U > 525 V: STR23SV or STR53SV. Trip units do not have a predefined rating. The tripping threshold depends on the circuit breaker rating and the LT (long time) current setting. For example, for an STR23SE trip unit set to the maximum value, the tripping threshold is: v 250 A, when installed on a Compact NS400 250 A v 630 A, when installed on a Compact NS630.
t 1 2
STR 23 SE
Io Ir
1 .88 .85 .8 .9 .93 .95 .98 1
x Io
alarm
90 105 %Ir
Isd
5 4 3 2
x Ir
3 4 5
+
8 .9
6 7 8 10
Ir Isd
.7 .63 .5
x In
0 1 2 3 4 5 6 7
Ir Isd
li
test
long-time threshold (overload protection) Ir long-time tripping delay short-time pick-up (short-circuit protection) Isd short-time tripping delay instantaneous pick-up (short-circuit protection) Ii test connector percent load indication
Protection
The protection functions may be set using the adjustment dials. Overload protection Long-time protection with an adjustable threshold and fixed tripping delay: b Io base setting (6-position dial from 0.5 to 1) b Ir fine adjustment (8-position dial from 0.8 to 1). Short-circuit protection Short-time and instantaneous protection: b short-time protection with an adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up. Protection of the fourth pole On four-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d (neutral protection at In). Protection of an overloaded neutral (OSN): For 4-pole circuit breakers, special protection of systems with high 3rd order harmonic contents. In position 4P 4d, the switch sets the neutral protection threshold to 1.6 x Ir.
Indications
A LED on the front indicates the percent load: b ON - load is > 90 % of Ir setting b flashing - load is > 105 % of Ir setting.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.
Page 9 of 41
12481
0
1 2 3 4 5 6 7 8 9
long-time threshold (overload protection) long-time tripping delay short-time pick-up (short-circuit protection) short-time tripping delay instantaneous pick-up (short-circuit protection) optional earth-fault pick-up optional earth-fault tripping delay test connector battery and lamp test pushbutton
Protection
The protection functions may be set using the adjustment dials. Overload protection Long-time protection with adjustable threshold and tripping delay: b Io base setting (6-position dial from 0.5 to 1) b Ir fine adjustment (8-position dial from 0.8 to 1). Short-circuit protection Short-time and instantaneous protection: b short-time protection with adjustable pick-up and tripping delay, with or without constant It b instantaneous protection with adjustable pick-up. Protection of the fourth pole On four-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3d (neutral unprotected), 4P 3d + N/2 (neutral protection at 0.5 In) or 4P 4d (neutral protection at In).
the STR53UE electronic trip unit" section on the following pages). With the earth-fault option (T) on the STR53UE electronic trip unit, an external neutral sensor can be installed (situation for a three-pole circuit breaker in a distribution system with a neutral). Available ratings of external neutral sensors: 150, 250, 400, 630 A.
Fault indications
A LED signals the type of fault: b overload (long-time protection) or abnormal internal temperature (> Ir) b short-circuit (short-time protection) or instantaneous (> Isd) b earth fault (if earth-fault protection option installed) (> Ig) b microprocessor malfunction: v both (> Ig) and (> Isd) LEDs ON v (> Ig) LED ON (if earth-fault protection option (T) installed). Battery powered. Spare batteries are supplied in an adapter box. The LED indicating the type of fault goes OFF after approximately ten minutes to conserve battery power. The information is however stored in memory and the LED can be turned back ON by pressing the battery/LED test pushbutton. The LED automatically goes OFF and the memory is cleared when the circuit breaker is reset.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories. The test pushbutton tests the battery and the (%Ir), (> Ir), (> Isd) and (> Ig) LEDs.
Self monitoring
The circuit breaker trips if a microprocessor fault or an abnormal temperature is detected.
Options
Four options are available: b earth-fault protection T b ammeter I b zone selective interlocking ZSI b communications option COM.
Page 10 of 41
12481
STR53SV
150 b 250 b 400 b 630 b
Options
Indication of fault type b (standard) Zone selective interlocking ZSI b (2) Communications COM b (2) Built-in ammeter I b (2) Earth-fault protection T b (2) (1) If the trip units are used in high-temperature environments, the setting must take into account the thermal limitations of the circuit breaker. The overload protection setting may not exceed 0.95 at 60 C or 0.9 at 70 C for the Compact NS400, and 0.95 at 50 C, 0.9 at 60 C or 0.85 at 70 C for the Compact NS630. (2) This option is not available for the STR53SV trip unit.
Setting example
What is the overload-protection threshold of a Compact NS400 circuit breaker equipped with an STR23SE (or STR23SV) trip unit set to Io = 0.5 and Ir = 0.8 ? Answer. In x Io x Ir = 400 x 0.5 x 0.8 = 160 A. The identical trip unit, with identical settings but installed on a Compact NS630 circuit breaker, will have an overload-protection threshold of: 630 x 0.5 x 0.8 = 250 A.
E25979
Io
.8 .9
Ir
1 .88 .85 .8 .9 .93 .95 .98 1
x Io
.7 .63 .5
x In
Page 11 of 41
12481
Possible combinations: bI b I+T b I + COM b I + T + COM b ZSI b ZSI + I b ZSI + I + T b ZSI + I + COM b ZSI + I + T + COM
Residual
0.2 to 1 adjustable, 8 settings adjustable, 4 settings 60 140 230 350 y 140 y 230 y 350 y 500
Ammeter (I)
A digital display continuously indicates the current of the phase with the greatest load. The value of each current (I1, I2, I3, Ineutral) may be successively displayed by pressing a scroll button. LEDs indicate the phase for which the current is displayed. Ammeter display limits: b minimum current u 0.2 x In. Lower currents are not displayed b maximum current y 10 x In.
Page 12 of 41
12481
Micrologic 2.0 and 5.0 control units protect power circuits. Micrologic 5.0 offers time discrimination for short-circuits as well.
Protection
Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection can be cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I2t type (ON or OFF) for short-time delay. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2) or neutral protection at Ir (4P 4d).
E46026A
Indications
Overload indication by alarm LED on the front; the LED goes on when the current exceeds the long-time trip threshold.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation after installing the trip unit or accessories.
1 2 3 4 5 6
long-time threshold and tripping delay overload alarm (LED) short-time pick-up and tripping delay instantaneous pick-up fixing screw for long-time rating plug test connector
Note. Micrologic control units are equipped with a transparent leadseal cover as standard.
Page 13 of 41
12481
Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Instantaneous Pick-up (A) accuracy: 10 % Time delay Isd = Ir x
Micrologic 2.0
DB105117
t Ir
0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 other ranges or disable by changing long-time rating plug 0.5 1 2 4 8 12 16 20 12.5 25 50 100 200 300 400 500 0.7 (1) 1 2 4 8 12 16 20 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 20 minutes before and after tripping
1 24 600 24 16.6
tr
Isd 0 I
1.5
2.5
10
Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) accuracy: 10 % Time setting tsd (s) Time delay (ms) at 10 x Ir (I2t off or I2t on) Instantaneous Pick-up (A) accuracy: 10 % Time delay Isd = Ir x settings
Micrologic 5.0
Micrologic 5.0 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 other ranges or disable by changing long-time rating plug 0.5 1 2 4 8 12 16 20 12.5 25 50 100 200 300 400 500 0.7 (1) 1 2 4 8 12 16 20 0.7 (2) 0.69 1.38 2.7 5.5 8.3 11 13.8 20 minutes before and after tripping
DB105118
1 24 600 24 16.6
Ir
I2t on
tr
I2t off
Isd tsd Ii 0 I
1.5
10
I2t Off 0 I2t On tsd (max. resettable time) 20 tsd (max. break time) 80 Ii = In x 2
10
12
15
off
Page 14 of 41
12481
Protection
Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection can be cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I2t type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of I2t type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. q Protected against nuisance tripping. k DC-component withstand class A up to 10 A. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral protection at Ir (4P 4d). Zone selective interlocking (ZSI) A ZSI terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.
E46028
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold. Micrologic A control units measure the true (rms) value of currents. They provide continuous current measurements from 0.2 to 20 In and are accurate to within 1.5 % (including the sensors). A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig,In, stored-current (maximeter) and setting values by successively pressing the navigation button. The optional external power supply makes it poss ble to display currents < 20 % In. Below 0.05 In, measurements are not significant. Between 0.05 and 0.2 In, accuracy is to within 0.5 % In + 1.5 % of the reading.
"Ammeter" measurements
Communication option
In conjunction with the COM communication option, the control unit transmits the following: b settings b all ammeter measurements b tripping causes b maximeter readings.
1 2 3 4 5 6 7 8 9 10 11 12 13 long-time threshold and tripping delay overload alarm (LED) at 1,125 Ir short-time pick-up and tripping delay instantaneous pick-up earth-leakage or earth-fault pick-up and tripping delay earth-leakage or earth-fault test button long-time rating plug screw test connector lamp test, reset and battery test indication of tripping cause digital display three-phase bargraph and ammeter navigation buttons
Fault indications
LEDs indicate the type of fault: b overload (long-time protection Ir) b short-circuit (short-time Isd or instantaneous li protection) b earth fault or earth leakage (Ig or In) b internal fault (Ap). Battery power The fault indication LEDs remain on until the test/reset button is pressed. Under normal operating conditions, the battery supplying the LEDs has a service life of approximately 10 years.
Test
A mini test kit or a portable test kit may be connected to the test connector on the front to check circuit-breaker operation. For Micrologic 6.0 A and 7.0 A control units, the operation of earth-fault or earth-leakage protection can be checked by pressing the test button located above the test connector.
Note. Micrologic A control units come with a transparent lead-seal cover as standard.
Page 15 of 41
12481
Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 %
Micrologic 2.0 A
DB105117
0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 other ranges or disable by changing long-time rating plug 0.5 1 2 4 8 12 16 20 12.5 25 50 100 200 300 400 500 0.7 (1) 1 2 4 8 12 16 20 0.7 (2) 0.69 1 38 2.7 5.5 8.3 11 13.8 20 minutes before and after tripping
1 24 600 24 16.6
t Ir
tr
Instantaneous
Pick-up (A) accuracy: 10 % Time delay Isd = Ir x 1.5 2 25 3 4 5 6 8 10 0 max resettable time: 20 ms; max break time: 50 ms
Isd I
Ammeter
Continuous current measurements Display from 20 to 200 % of In accuracy: 1.5 % (including sensors) Maximeters
Micrologic 2.0 A
I1 I2 I3 IN no auxiliary source (where I > 20 % In) I1 max. I2 max. I3 max. IN max.
Protection
Long time Current setting (A) Ir = In x tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) Isd = Ir x accuracy: 10 % Time setting tsd (s) settings Time delay (ms) at 10 x Ir (I2t off or I2t on) Instantaneous Pick-up (A) accuracy: 10 % Time delay Earth fault Pick up (A) accuracy: 10 %
1 24 600 24 16.6
Ir
I2t on
tr
I2t off
Isd tsd
1.5
25 02 02 140 200 4
10 0
Ii I
I2t Off 0 I2t On tsd (max. resettable time) 20 tsd (max. break time) 80 Ii = In x 2
10
12
15
off
DB118584
Time setting tg (s) Time delay (ms) at In or 1200 A (I2t off or I2t on) Residual earth leakage (Vigi) Sensitivity (A) accuracy: 0 to -20 % Time delay t (ms)
Ig = In x In y 400 A 400 A < In < 1250 A In u 1250 A settings I2t Off I2t On tg (max. resettable time) tg (max. break time) In
DB105120
max. resettable time: 20 ms ; max. break time: 50 ms Micrologic 6.0 A A B C D E F G H 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 500 640 720 800 880 960 1040 1120 0 0.1 02 0.3 0.4 0.1 02 0.3 0.4 20 80 140 230 350 80 140 200 320 500 Micrologic 7.0 A 0.5 1 2 3 5 7 10 20 140 140 200 230 230 320 350 350 500 800 800 1000
t
I2t on
J 1 1 1200
Ig tg
I2t off
30
In t
Ammeter
Continuous current measurements Display from 20 to 200 % of In accuracy: 1.5 % (including sensors) Maximeters
Note. All current-based protection functions require no auxiliary source. The test / reset button resets maximeters, clears the tripping indication and tests the battery.
Page 16 of 41
12481
Micrologic P control units include all the functions offered by Micrologic A. In addition, they measure voltages and calculate power and energy values. They also offer new protection functions based on currents, voltages, frequency and power reinforce load protection in real time.
The adjustable protection functions are identical to those of Micrologic A (overloads, short-circuits, earth-fault and earth-leakage protection). Fine adjustment Within the range determined by the adjustment dial, fine adjustment of thresholds (to within one ampere) and time delays (to within one second) is poss ble on the keypad or remotely using the COM option. IDMTL (Inverse Definite Minimum Time Lag) setting Coordination with fuse-type or medium-voltage protection systems is optimised by adjusting the slope of the overload-protection curve. This setting also ensures better operation of this protection function with certain loads.
DB101485
Neutral protection On three-pole circuit breakers, neutral protection may be set using the keypad or remotely using the COM option, to one of four positions: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral protection at Ir (4P 4d) and neutral protection at 1,6 Ir (4P 3d + 1,6N). Neutral protection at 1,6 Ir is used when the neutral conductor is twice the size of the phase conductors (major load imbalance, high level of third order harmonics). On four-pole circuit breakers, neutral protection may be set using a three-position switch or the keypad: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral protection at Ir (4P 4d). Neutral protection produces no effect if the long-time curve is set to one of the IDMTL protection settings.
Measurements
The Micrologic P control unit calculates in real time all the electrical values (V, A, W, VAR, VA, Wh, VARh, VAh, Hz), power factors and cos j factors. The Micrologic P control unit also calculates demand current and demand power over an adjustable time period. Each measurement is associated with a minimeter and a maximeter. In the event of tripping on a fault, the interrupted current is stored. The optional external power supply makes it possible to display the value with the circuit breaker open or not supplied.
The last ten trips and alarms are recorded in two separate history files. Maintenance indications (contact wear, operation cycles, etc.) are recorded for local access.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Long-time current setting and tripping delay. Overload signal (LED). Short-time pick-up and tripping delay. Instantaneous pick-up. Earth-leakage or earth-fault pick-up and tripping delay. Earth-leakage or earth-fault test button. Long-time rating plug screw. Test connector. Lamp + battery test and indications reset. Indication of tripping cause. High-resolution screen. Measurement display. Maintenance indicators. Protection settings. Navigation buttons. Hole for settings lockout pin on cover.
The M6C (six contacts) auxiliary contacts may be used to signal threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P control unit or remotely using the COM option.
Note: Micrologic P control units come with a non-transparent lead-seal cover as standard.
Page 17 of 41
12481
Protection
Long time (rms) Current setting (A) Ir = In x Tripping between 1.05 and 1.20 x Ir Time setting Time delay (s) Accuracy: 0 to -30 % Accuracy: 0 to -20 % Accuracy: 0 to -20 % IDMTL set ing Curve slope Thermal memory (1) 0 to -40 % - (2) 0 to -60 % Short time (rms) Pick-up (A) Isd = Ir x Accuracy: 10 % Time setting tsd (s) Settings Time delay (ms) at 10 Ir (I2t Off or I2t On) Instantaneous Pick-up (A) Accuracy: 10 % Time delay Earth fault Pick-up (A) Accuracy: 10 %
1.5 0 20 80 2
10
I2t Off I2t On tsd (max resettable time) tsd (max break time) Ii = In x
10
12
15
off
Time setting tg (s) Time delay (ms) at In or 1200 A (I2t Off or I2t On) Residual earth leakage (Vigi) Sensitivity (A) Accuracy: 0 to -20 % Time delay Dt (ms)
Ig = In x In y 400 A 400 A < In < 1250 A In u 1250 A Settings tg (max resettable time) tg (max break time) In Settings t (max resettable time) t (max break time)
Max resettable time: 20 ms Max break time: 50 ms Micrologic 6.0 P A B C D 0.3 0.3 0.4 0.5 0.2 0.3 0.4 0.5 500 640 720 800 0 0.1 0.2 0.3 0.1 0.2 0.3 20 80 140 230 80 140 200 320 Micrologic 7.0 P 0.5 1 2 3 60 60 140 140 140 200 230 230 320 350 350 500
10
20
30
2 to 30 % x Uaverage 1 to 40 s 100 to Umax between phases 1.2 to 10 s Umin to 1200 between phases 1.2 to 10 s
rP Fmin Fmax
Note: all current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker.
DB112384
J 1 1 1200
DB112383
Page 18 of 41
12481
DB114641
DB114642
Measurements ..........................................................................
Instantaneous values The value displayed on the screen is refreshed every second. Minimum and maximum values of measurements are stored in memory (minimeters and maximeters). Currents
I rms Default display. Display of a maximum current I max rms Voltages U rms V rms U average rms U unbalance Power, energy P active, Q reactive, S apparent E active, E reactive, E apparent A A A A V V V % W, Var, VA Wh, VARh, VAh 1 E-fault 1 E-fault 2 2 3 N E-leakage 3 N E-leakage
DB101135
DB101136
PF Hz
Display of a voltage.
Display of a power.
DB101137
DB101138
Demand metering The demand is calculated over a fixed or sliding time window that may be programmed from 5 to 60 minutes. According to the contract signed with the power supplier, an indicator associated with a load shedding function makes it possible to avoid or minimise the costs of overrunning the subscribed power. Maximum demand values are systematically stored and time stamped (maximeter). Currents
I demand I max demand A A A A W, Var, VA W, Var, VA 1 E-fault 1 E-fault Totals Totals 2 2 3 N E-leakage 3 N E-leakage
Power
P, Q, S demand P, Q, S max demand
Minimeters and maximeters Only the current and power maximeters may be displayed on the screen.
Histories ....................................................................................
Display of a frequency. Display of a demand power.
The last ten trips and alarms are recorded in two separate history files that may be displayed on the screen. b tripping history: v type of fault v date and time v values measured at the time of tripping (interrupted current, etc.) b alarm history: v type of alarm v date and time v values measured at the time of the alarm.
DB101139
DB101140
Page 19 of 41
12481
DB101523
Page 20 of 41
Additional characteristics
Tripping curves
12481
TM25D / TM25G
Page 21 of 41
12481
TM125D / TM160D
DB115272
TM200D / TM250D
DB115273
Page 22 of 41
Additional characteristics
Tripping curves
12481
STR22SE - 160250 A
DB115275
STR22GE - 40100 A
DB115276
STR22GE - 160250 A
DB115277
Page 23 of 41
12481
Page 24 of 41
Additional characteristics
Tripping curves
12481
STR53UE / STR53SV
Page 25 of 41
12481
Thermal-withstand capacities are given for circuit breakers operating in an ambient temperature of 65 C.
Page 26 of 41
Additional characteristics
Tripping curves
12481
(1)
Ig = In x
Ig < 400 A 400 A y Ig y 1200 A Ig > 1200 A
A
03 02 500
B
0.3 0.3 640
C
0.4 0.4 720
D
0.5 0.5 800
E
0.6 0.6 880
F
0.7 0.7 960
Page 27 of 41
12481
Reflex tripping
Compact NS100 to 630 devices incorporate the exclusive reflex-tripping system. This system breaks very high fault currents by mechanically tripping the device via a "piston" actuated directly by the pressure produced in the breaking units resulting from a short-circuit. For high short-circuits, this system provides a faster break and a trip guarantee, as well as natural total discrimination. Reflex-tripping curves are exclusively a function of the circuit-breaker rating.
DB115290
Page 28 of 41
12481
Dimensions
2 poles or 3 poles
E21504 E21502 E21503
4 poles
H1 X H
H3
H5
H7
X
H2 H4 H6
P1 P2 P4 Z
L1
(a) short terminal shields. (b) long terminal shields (available for spreaders on NS400 to 630, pitch 52.5 : L1 = 157.5 mm, L2 = 210 mm). (c) interphase barriers.
Y L L2
Mounting
On backplate 2 poles or 3 poles
E21507 E21508
4 poles
K1 K1 K
K1 K1 K2 K1 K
K1
G1 G
X T
G5
G4
T4 (d)
(d) for rear connection only. For two-pole circuit breakers, the centre hole is not necessary.
4 poles
E21512
U (e)
K1 K
K2 K
G1 G T
G50 G51
G49
X
G48 G47 Z
Page 29 of 41
12481
Front-panel cutouts
Fixed or plug-in circuit breaker Cutout A
E21600
Cutout B
E21603 E21604
Cutout C
E21601
X C
C1
C3 C2
C3 C2
B/C P5 P6
Y R R1
Y R2 R4(3P) R5(4P)
With escutcheon
E21608 E21609
C7
E21602
X C6
X C21 C20
P6 Z
Y R6 R7
Y R12 R13
Dimensions (mm)
Type NS100/160/250 NS400/630 Type NS100/160/250 NS400/630 Type NS100/160/250 NS400/630 C 29 41.5 G5 140 227 H5 321 480 C1 76 116 G47 95 C2 54 92.5 G48 75 C3 108 184 G49 13.5 C6 43 56.5 G50 23 C7 104 146 G51 17.5 C20 34 46 5 H 80 5 127.5 L 52 5 70 R4 108 143 C21 86 126 H1 161 255 L1 105 140 R5 143 188 G 62.5 100 H2 94 142.5 L2 140 185 R6 29 46.5 G1 125 200 H3 188 285 P1 81 95.5 R7 58 93 G4 70 113.5 H4 160.5 240 P2 86 110 R12 43 63
H6 178.5 237
K1 35 45 R1 29 63
K2 70 90 R2 54 71.5
Type P4 P5 NS100/160/250 111 (1) 83 NS400/630 168 107 (1) : P4 = 126 mm for Compact NS250N/H/L. Type NS100/160/250 NS400/630 R13 86 126 T 6 6
T4 22 32
U y 32 y 32
E22046
Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.
Page 30 of 41
12481
Dimensions
Plug-in base
DB110917
4 poles
Chassis
DB110932
2 poles or 3 poles
4 poles
DB110920
Mounting
Through panel M (plug-in base) 2P, 3P K1
E21 526 E21525
4P
K2 K
DB110921
4P
E21588
K2 K
G11 X
G13 X G12
G11 X
G13 X G12
G10
G10
Y K5 K6 K7
Y K5
Y K11
2P, 3P
DB110933 E21534
4P
K22 K20
(a) Short terminal shields for circuit breaker are mandatory. (b) Long terminal shields for plug-in base. (c) Interphase barriers. Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.
Page 31 of 41
12481
On backplate N (plug-in base or chassis) Front connection (insulating screen is mandatory between the backplate and the base, supplied with the base) 2P, 3P
E21589 E21590
4P
K1 K
K2 K
G15 X G14
2P, 3P
K2 K K
E21594
4P
K1 K K K2 K K
K1 K K T6
G16 X G14
G18
G15 X T X G19
G15
X
G17
G14
K1
Y K1
K1 K1
Y K1
T5
K1
Y K1
K1 K1
Y K1
Front-panel cutouts
E21619
C11
C17
P44 Z
Y R8
Dimensions (mm)
Type C11 C17 NS100/160/250 103 42.5 NS400/630 155 56 Type G25 G26 NS100/160/250 380 208 NS400/630 567 318.5 Type K13 K20 NS100/160/250 183 35 NS400/630 228 50 Type P10 P12 NS100/160/250 64 32 NS400/630 86 32 (1) P4 = 126 mm for Compact NS250N/H/L. G10 95 150 G27 416 637 K21 70 100 P44 123 147 G11 190 300 G28 380.6 566.1 K22 105 145 P45 76.2 99.3 G12 87 137 G29 416 637 L 52.5 70 R8 74 90 G13 174 274 H16 102.5 157.5 L1 105 140 R9 148 180 G14 77.5 125 H17 205 315 L2 140 185 U y 32 y 32 G15 155 250 H18 103 5 140 L6 92.5 110 T 6 6 G16 66 101 H19 210 280 L7 185 220 T5 24 33 G17 132 202 K 17.5 22.5 L8 216 250 T6 30 33 G18 82 126 K1 35 45 L9 220 265 G19 164 252 K2 70 90 L10 251 295 G20 37.5 75 K5 54.5 71.5 P2 86 110
R9
G21 75 150 K6 109 143 P4 111 (1) 168 G22 111 170.5 K7 144 188 P7 27 27 G23 222 341 K11 74 91.5 P8 45 45 G24 190 283.5 K12 148 183 P9 75 100
Page 32 of 41
12481
Dimensions
E29213
2 poles
H1 X H
H3
H7
X
H2
H6
(a) (b)
Y L3
Y L3 L4
(a) short terminal shields (b) interphase barriers
P1 P2 P4 Z
L5
Mouting
On backplate 1 pole
E29216
2 poles
E21506
K1 K
(c) for rear connection only
On rails 1 pole
DB103754 E21510
2 poles
U K1 K
G1
X G T
Page 33 of 41
12481
Front-panel cutout
Cutout A
E21601 E21600
Cutout B
E21601 E21604
Cutout C
X C
C1
C3
X
C3 C2
C2
B/C P5 P6
Y R R1
R4(1P) R5(2P)
Y R2
With escutcheon
E21609
E21608
C7
X C6
P6 Z
Y R6 R7
Dimensions (mm)
Type NS100/160/250 Type NS100/160/250 Type NS100/160/250 Type NS100/160/250 C 29 H1 161 P1 81 R7 58 C1 76 H2 94 P2 86 T 6 C2 54 H3 188 P4 111 T4 22 C3 108 H4 160.5 P5 83 U y 32 C6 43 H6 178 5 P6 88 C7 104 H7 357 R 14.5 G 62.5 K 17.5 R1 29 G1 125 K1 35 R2 19 G4 70 L3 17.5 R4 38 G5 140 L4 70 R5 73 H 80.5 L5 35 R6 29
E22046
Note. Door cutout dimensions are given for a device position in the enclosure where u 100 + (h x 5) with respect to the door hinge.
Page 34 of 41
12481
Manual control
Front connection (N, H, L)
E47972B
(1)
163,5
254
327
508
200 100
E47973A
107,5 205
Z
F
Y
99,5
105 94
E47913A
113 92,5
123
Z
107,5 140,5 146,5 205
35 70
14
Electrical control
Front and rear connection (N, H, L, LB)
E47897A
105 94
DB105138
123 105
210
234
200 100
X
123
117
F : Datum
107,5 175,5 182 F
Z
70 99,5 (3P) 169,5 (4P)
35 99,5
Note. Dimensions for front and rear connection on electrically operated devices are identical to those for manually operated devices.
Page 35 of 41
12481
Mounting
Front connection
On backplate
DB115348
On rails
DB115349
Rear connection
On backplate or rails 3P
DB115350
4P
DB115351
Note. Mounting parameters for electrically operated devices are identical to those for manually operated devices. X and Y are the symmetry planes for a 3-pole device Z is the back plane of the device.
Page 36 of 41
12481
Toggle control
E59368
E47901A
E59201B
Door cutout A
194 mini
194 mini
201 (1)
181 (1)
E59200A
194 mini
Y
119 (1) 144 (2)
Electrical control
DB105139
Door cutout A
(A)
E47901A
194 mini
Page 37 of 41
12481
Rotary handle
E47955A
Y
E47955A
60 R80
195
X
60
24
25
Z
Door cutout A
E47901A
B
E47956A E47957
D
194 mini
194 mini
194 mini
201 (1)
X
100,5 (1)
201 (1)
100,5 (1)
181 (1)
Door cutout
E47959A
Y
60 R100
E47960A
X
60
24
Z
F
25
F : Datum
Note. X and Y are the symmetry planes for a 3-pole device Z is the back plane of the device.
Page 38 of 41
12481
Electrical control
E47944A E59370B
210 mini
210 mini
160,5
Y
70 (*) 46 (*)
199
X
69 5 5 45,5
X
123
60 mini F
60 mini F
90
Mounting
Bottom mounting on base plate or rails
E47175B DB115356
E47945
Cutouts
Door cutout
E47177B E47178A
234 117
109 (1) 130,8 (2) 161 (1) 183 (2) 259 (1) 307 (2)
102,5
(1) Without escutcheon. (2) With escutcheon. F : Datum Note. X and Y are the symmetry planes for a 3-pole device.
Page 39 of 41
12481
210 mini
E47963A
136 (*)
60 R80
X
93 5
60
24
60 mini
25
Door cutout
E47964B
230 mini
X
109 (1) 130,8 (2)
Door cutout
E47965A
E47967A
60 R200
X
60
X
24
17 F
25
Note.
Page 40 of 41
12481
Dimensions
E59439 E59440
132 mini
165
105
330
X
75
150
210
163 170 340 180 (3P) 195 (3P) 295 (4P) 310 (4P) 210 (3P) 325 (4P) 180 195 210
201
100,5
166 332
C
E59458
Mounting on rails
Y
E59456A
X
119 95,9
Page 41 of 41