053-052 ISSUE 2
Press
(up) or
Press (right) when the first digit is correctly entered. The digit you have just entered will now show # for security.
Repeat this process for the other digits of the PIN number. You can press move back to adjust one of the previous digits.
When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN. If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed :
EDITING A PARAMETER Enter the editor as described above. Press the left or right buttons to cycle to the section you wish to view/change. To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the up or down buttons to change the parameter to the required value. Press to save the value. The parameter ceases flashing to indicate that it has been saved. button.
afte NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure security. NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security. NOTE: More comprehensive module configuration is possible using the 75xx series PC configuration software. configuration software. Please contact us for further details NOTE: The contents of the tables overleaf may differ depending on the actual module configuration.
ADJUSTABLE PARAMETERS
Front Panel Configuration Editor (Factory default settings are shown in bold italicised text)
Section
Input settings
Values
0bar - 4bar (1.17bar) 0bar - 4bar (1.03bar) 80C - 140C (115C) 80C - 140C (120C) 0 -10s (0s) 0 - 60m (5s) 0 - 60m (0s) 0 - 60s (10s) 0 - 60s (10s) 0 - 30s (10s) 0 - 10s (0s) 0 - 60m (0s) 0 - 60m (30s) 0 - 60m (1m) 0 - 30s (30s) 0- 10m (1m) 0 -10m (1m) 0- 30s (2s) 50V-360V ph-N (184V) 50V-360V ph-N (196V) 52V-330V(230V) 50V-360V ph-N (265V) 50V-360V ph-N (277V) 0Hz - 75Hz (40Hz) 0Hz - 75Hz (42Hz) 0Hz - 74Hz (50Hz) 0Hz - 75Hz (55Hz) 0Hz - 75Hz (57Hz) 100% - 200% full load rating (100%) 50% - 300% full load rating (200%) 0% - 200% full load rating (35kW) 1% - 100% full load rating (10%) 0RPM - 6000RPM (disabled) 0RPM - 6000RPM (disabled) 0RPM - 6000RPM (disabled) 0RPM - 6000RPM (disabled) 0% - 10% (0%) 0V - 40V (10V) 0V - 40V (30V) 0V - 40V (6V) ENGLISH, OTHERS Enable, Disable Enable, Disable 3 Phase 4 wire 1 Phase 2 wire 3 phase 3 wire 2 phase 3 wire L1 & L2 3 phase 4 wire EDISON DELTA 2 phase 3 wire L1 & L3 0A - 8000A (500A) Enable, Disable
Section
Power
Values
0MW-20MW (245kW) 0MVA-20MVAr (258kVAr) 0%-100% (3.0%) 0%-100% (80%) 0%-100% (70%) 0%-100% (172kW) 0%-100% (1.0pfF OkVAr 0%) Enable Disable None, VAr Share, VAr Fixed Export 0 30m (1s) None, Shutdown, Electrical Trip, Latched Warning, Unlatched Warning Power Cycle After Exit Power Cycle After Exit
Timers
Generator
Engine
or right
Press the up
or down
Display AC System
To save paremeters scroll to `save changes and exit followed by the down
buttton
To cancel changes scroll to `Abandon changes and exit followed by the down
button
Generator Full Load Current Droop Droop % Display Clock Misc. CT Contrast Date and Time Run Priority Auto Scroll Time Generator CT Primary Rating Generator CT Secondary Rating
Running Editor
0% - 5%
|
dd mmm yyyy hh:mm:ss 1-16 (1) 0 - 10s (2.0s) 0A - 8000A (600A) 1A, 5A
Factory Settings l
English Other 1-16 (1) 0-100% (0) 0-100% (50) Yes, No Yes, No 0-100 % (0) 0-100 % (0) Yes-No
DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4 x 7.1 x 1.6)
PANEL CUTOUT:
220mm x 160mm (8.7 x 6.3)