SMC-FLEX
MODULAR DESIGN
CURRENT RANGE
Product Rating
5 25 43 60 85 108 135 201 251 317 361 480 625 780 970 1250
Line Current
5 25 43 60 85 108 135 201 251 317 361 480 625 780 970 1250
Delta Current
9 43 74 104 147 187 234 348 435 549 625 831 850 900 1200 1600
The SMC-Flex provides intelligence, unmatched performance, flexibility, diagnostics, and communication in a modular compact design for controlling either a standard squirrel-cage induction motor or a star-delta motor.
COMPACT SIZE
The SMC-Flex integrates a bypass to minimize heat generation during run time. The bypass automatically closes when the motor reaches its nominal speed, resulting in a cooler-running component and reduction in enclosure size.
200690V AC, 50/60 Hz 100240V AC or 24V AC/DC (5480) 110120V AC (6251250) 230240V AC (625 1250)
MOTOR CONNECTION
Line Connection Optional Line Side Isolation Contactor
STARTING MODES
Soft Start Soft Stop Current Limit Full Voltage Kick Start Preset Slow Speed Linear Speed Start and Stop Dual Ramp Pump Start and Stop Smart Motor Braking Accu-Stop Slow Speed with Braking
Standard
X X X X X X X X
Pump Control
X X X X
Braking Control
X X X X X
X X X
FEATURES
Flexibility in Trip Class (10, 15, 20, 30, OFF)
Overload
Diagnostics
Delta Connections
Standard Squirrel-Cage Induction Motor Star-Delta Motor DeviceNet, ControlNet, EtherNet, Remote I/O, RS-485, Profibus, Interbus
Motor Control
Communication Metering
Three-phase Voltages Power Usage in kWH* Power Factor of the Running Motor Elapsed Time of Motor Operation
2 Inputs 4
I/O
UNSURPASSED ADVANTAGES
FEATURES
Built-in Overload
BENEFITS
Multiple overload trip class selection Less products to inventory Ease of selection Ease of setup Reduced footprint Reduced footprint Minimal heat loss Reduced enclosure size Reduced total cost
Integral Bypass
Reduction in inventory Cost savings Flexibility of system configuration No external components to purchase Less product to inventory
Built-in power monitoring Takes mystery out of motor operation No additional investment required Minimize panel space Minimal parameters to set up Ease of setup Ease of operation Multilingual for a diverse workforce
LCD Display
Product Modularity
Ease of maintenance
CONFIGURABLE TO:
Normal/Up-to-speed/External bypass/ Fault/Alarm/Network Control N.O./N.C.
SMC-3
The SMC-3 provides 3 Phase Control and unmatched performance in a compact design for your standard squirrel cage or STAR-Delta induction motors. It features microprocessor-controlled electronic overload with adjustable trip class, motor and system diagnostics, configurable auxiliary contacts, and multiple START and STOP modes. All of these combined features provide a highly accurate, reliable, and efficient smart motor controller with the smallest footprint in the industry. Line Connection CURRENT RANGE
Product Rating
3 9 16 19 25 30 37 43 60 85 108 135 201 251 317 361 480
Line Current
3 9 16 19 25 30 37 43 60 85 108 135 201 251 317 361 480
Delta Current
5 16 28 33 43 52 64 74 104 147 187 234 348 435 549 625 831
Motor
VOLTAGE RANGE
200600V AC 50/60Hz
CONTROL VOLTAGE
100240V AC or 24V AC/DC
Delta
STARTING MODES
Soft Start, Kick Start, Current Limit Start, or Soft Stop
FEATURES
Flexibility in trip class (10, 15, 20 or OFF) Selectable overload reset (Manual or Automatic)
Overtemperature in power section Phase reversal (selectable) Phase loss / Open load Phase imbalance Shorted SCRs
Full 3-phase control Standard squirrel cage induction motor or Star-Delta motors Compressors Fans Conveyors
FEATURES
Built-in Overload True 3-Phase Control Advanced Diagnostics Digital Adjustments Add-on Configurable Auxiliary Contacts
UNSURPASSED ADVANTAGES
EASY AND SECURE SETUP
DIP switches allow for easy, precise, and secure setting of the START/STOP profile, overload, connection type, trip class, and auxiliary contact characteristics. The motor FLC setting is easily accomplished using the rotary pot located on the front of the device.
LED DISPLAY
An LED display clearly relays device status information including RUN, FAULT diagnostics, and OFF.
SMC-Delta Softstarter
600 % Full 350 Load Current Run 100 100 0
Run
SMC-FLEX
Power pole
Fan assembly
Feed-through wiring
Control terminal blocks Power connections for standard squirrel-cage induction motor or star-delta motors
EASE OF MAINTENANCE
Modular power structure Removable control module Changeable fan assembly
PROTECTION
Power termination covers IP2X Protection is dead front (IP2X)
ADVANCED DIAGNOSTICS
PTC Input Ground Fault Detection additional current transformer required Catalog Number 825-CBCT or Flex-Core 126-252 depending on frame sizes
COMMUNICATION
The Allen-Bradley family of 20-COMM DPI communication interfaces allows the SMC-Flex to be connected to multiple network types including DeviceNet, ControlNet, EtherNet, Remote I/O, RS-485, Modbus, Profibus and Interbus. All connections are built into the SMCFlex so no additional panel space is required.
Power structure
Control module
8
SMC-3
AVAILABLE CONFIGURATIONS
IEC 1-N.O. NEMA
Snap-on fan module runs silently and is easy to install Fan is installed as standard for 43... 135 A SMC-3
SMCs
SMC-Flex, Standard
Allen-Bradley SMCs provide innovative starting and stopping solutions for ample design flexibility with minimal control module options meeting the needs of most production applications. To help identify which start and stop profiles, described in the following pages, are included in each control module option, use the following code:
SMC-3
SOFT START
By reducing starting torque surges, Soft Start provides smooth, stepless motor acceleration while minimizing damage to gears, couplings and belts.
SOFT STOP
The Soft Stop option extends the stopping time to minimize load shifting or spillage.
FULL-VOLTAGE START
In the Full-Voltage Start mode, the SMC performs like a solid-state contactor, achieving full in-rush current and locked rotor torque.
10
KICK START
Activate the Selectable Kickstart function to provide an extra pulse of torque. This optional feature is ideal for overcoming stiction wherever high-friction loads are encountered.
11
SMCs
12
150-SG001-US-P
For more information, please visit www.ab.com
13
as part of a truly integrated architecture simplifies your start-up reduces your installed cost makes it easier for you to access essential plant and production data
14
Bulletin 150
SMC Flex Controller Features Soft Start Kickstart Current Limit Dual Ramp Start Full Voltage Soft Stop Pump Control Preset Slow Speed Linear Speed SMB Smart Motor Braking Accu-Stop Slow Speed with Braking Motor Protection Communication Metering Keypad Programming/ LCD Display Inside Delta Connection Product Selection S = Standard Feature O = Optional Feature 200690V 11250 A S S S S S S O S S O O O S S S S S Page 16
15
Bulletin 150
Table of Contents
Description of Features......................... Cat. No. Explanation Product Selection ...... Options .......................... Accessories.................. Specifications.............. Approximate Dimensions and Shipping Weights....... 18 19 20 30 31 33
38
Standards Compliance/Approvals
UL 508 EN/IEC 60947-4-2 cULus Listed (open type) File No. E96956 CE Marked (open type) per EMC Directive and Low Voltage Directive CCC (108480 A)
Modes of Operation
The SMC Flex controller provides the following modes of operation as Standard: Soft Start This method covers the most general applications. The motor is given an initial torque setting, which is user adjustable. From the initial torque level, the output voltage to the motor is steplessly increased during the acceleration ramp time, which is user adjustable. Selectable Kickstart The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started. It is intended to provide a current pulse, for a selected period of time. Current Limit Start This method provides current limit start and is used when it is necessary to limit the maximum starting current. The starting current is user adjustable. The current limit stating time is user adjustable. Dual Ramp Start This starting method is useful on applications with varying loads, starting torque, and start time requirements. Dual Ramp Start offers the user the ability to select between two separate start profiles with separately adjustable ramp times and initial torque settings. Full Voltage Start This method is used in applications requiring across-the-line starting. The SMC controller performs like a solid-state contactor. Full inrush current and locked-rotor torque are realized. The SMC may be programmed to provide full voltage start in which the output voltage to the motor reaches full voltage in 1/4 second. Linear Speed Acceleration With this type of acceleration mode, a closed-loop feedback system maintains the motor acceleration at a constant rate. The required feedback signal is provided by a DC tachometer coupled to the motor (tachometer supplied by user 05V DC, 4.5V DC = 100% speed). Kickstart is available with this mode. Preset Slow Speed This method can be used on applications that require a slow speed for positioning material. The Preset Slow Speed can be set for either Low, 7% of base speed, or High, 15% of base speed. Reversing is also possible through programming. Speeds provided during reverse operation are Low, 10% of base speed, or High, 20% of base speed. Soft Stop The Soft Stop option can be used in applications requiring an extended stop time. The voltage ramp down time is use adjustable from 0 to 120 seconds. The load will stop when the voltage drops to a point where the load torque is greater than the motor torque.
16
Bulletin 150
Braking Control
SMB Smart Motor Braking This option provides motor braking for applications that require the motor to stop faster than a coast to rest. Braking control, with automatic zero speed shut off, is fully integrated into the compact design of the SMC controller. This design facilitates a clean, straight forward installation and eliminates the requirement for additional hardware such as braking contactors, resistors, timers, and speed sensors. The microprocessor based braking system applies braking current to a standard squirrel-cage induction motor. The strength of the braking current is programmable from 150400% of full-load current. Accu-Stop This option is used in applications requiring controlled position stopping. During stopping, braking torque is applied to the motor until it reaches preset slow speed (7% or 15% of rated speed) and holds the motor at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Braking current is programmable from 0400% of full-load current. Slow Speed Current is programmable from 0450% of full-load current. Slow speed can be programmed for either 7% (low) or 15% (high). Slow Speed with Braking Slow Speed with Braking is used on applications that require slow speed (in the forward direction) for positioning or alignment and also require braking control to stop. Slow speed adjustments are 7% (low) or 15% (high) of rated speed. Slow speed acceleration current is adjustable from 0450%. Slow speed running current is adjustable from 0450% of full-load current. Braking current is adjustable from 0400%.
Not intended to be used as an emergency stop. Refer to the applicable standards for emergency stop requirments.
17
Bulletin 150
Note: The motor thermal capacity usage allows the user to monitor the amount of overload thermal capacity usage before the SMC Flex controllers built-in electronic overload trips. Built-in DPI Communication Capabilities A serial interface port is provided as standard, which allows connection to a Bulletin 20 Human Interface Module and a variety of Bulletin 20-COMM Communication Modules. This includes AllenBradley Remote I/O, DeviceNet, ControlNet, Ethernet, ProfiBUS, Interbus, and RS485-DF1. LCD Display The SMC Flex controllers three-line 16-character backlit LCD display provides parameter identification using clear, informative text. Controller set up can be performed quickly and easily without the use of a reference manual. Parameters are arranged in an organized four-level menu structure for ease of programming and fast access to parameters. Keypad Programming Programming of parameters is accomplished through a five-button keypad on the front of the SMC Flex controller. The five buttons include up and down arrows, an Enter button, a Select button, and an Escape button. The user needs only to enter the correct sequence of keystrokes for programming the SMC Flex controller. Auxiliary Contacts Four fully programmable hard contacts are furnished as standard with the SMC Flex controller: Aux #1, Aux #2, Aux #3, Aux #4 N.O./N.C. Normal/Up-to-Speed/External Bypass/Fault/Alarm/Network Network I/O The SMC Flex can have up to two (2) inputs and four (4) outputs controlled via a communication network. The output contacts use the auxiliary contacts. Ground Fault Input The SMC Flex can monitor for ground fault conditions. An external core balance current transformer is required for this function. See SMC Flex User Manual for additional information. Tach Input A motor tachometer is required for the Linear Speed Start mode. Please see the Specifications section page 36 for tachometer characteristics. PTC Input A motor PTC input can be monitored by the SMC Flex. In the event of a fault, the SMC Flex will shut down and indicate a motor PTC fault.
18
Bulletin 150
150 F135
a b
F
c
a
B
d
D
e
B 8L
f g
152H F480
a b
F
c
a
BD
d
B 59 8B
e f g
Bulletin Number Code 152H 153H Description Solid-State Controller with Fusible Disconnect Solid-State Controller with Circuit Breaker
b
Controller Ratings Code F5 F25 F43 F60 F85 F108 F135 F201 F251 F317 F361 F480 F625 F780 F970 F1250 Description 5 A, 3 Hp @ 460V AC 25 A, 15 Hp @ 460V AC 43 A, 30 Hp @ 460V AC 60 A, 40 Hp @ 460V AC 85 A, 60 Hp @ 460V AC 108 A, 75 Hp @ 460V AC 135 A, 100 Hp @ 460V AC 201 A, 150 Hp @ 460V AC 251 A, 200 Hp @ 460V AC 317 A, 250 Hp @ 460V AC 361 A, 300 Hp @ 460V AC 480 A, 400 Hp @ 460V AC 625 A, 500 Hp @ 460V AC 780 A, 600 Hp @ 460V AC 970 A, 800 Hp @ 460V AC 1250 A, 1000 Hp @ 460V AC
b
Controller Ratings Code F5 F25 F43 F60 F85 F108 F135 F201 F251 F317 F361 F480 F625 F780 Description 5 A, 3 Hp @ 460V AC 25 A, 15 Hp @ 460V AC 43 A, 30 Hp @ 460V AC 60 A, 40 Hp @ 460V AC 85 A, 60 Hp @ 460V AC 108 A, 75 Hp @ 460V AC 135 A, 100 Hp @ 460V AC 201 A, 150 Hp @ 460V AC 251 A, 200 Hp @ 460V AC 317 A, 250 Hp @ 460V AC 361 A, 300 Hp @ 460V AC 480 A, 400 Hp @ 460V AC 625 A, 500 Hp @ 460V AC 780 A, 600 Hp @ 460V AC
c
Enclosure Type Code F N Description NEMA Type 4/12 (IP65) (Non-Combination Only) Open Code F
c
Enclosure Type Description NEMA Type 4/12 (IP65)
d
Line Voltage, 120V AC Control Voltage Code HD AD BD CD Description 200208V AC, 3-phase, 50 and 60 Hz 230V AC, 3-phase, 50 and 60 Hz 400460V AC, 3-phase, 50 and 60 Hz 500575V AC, 3-phase, 50 and 60 Hz
d
Input Line Voltage Open Type Code B C Z H A B C Description 200460V AC, 3-phase, 50 and 60 Hz 200575V AC, 3-phase, 50 and 60 Hz 230690V AC, 3-phase, 50 and 60 Hz (Open Only) Non-Combination Enclosed Only 200208V AC, 3-phase, 50 and 60 Hz 230V AC, 3-phase, 50 and 60 Hz 400460V AC, 3-phase, 50 and 60 Hz 500575V AC, 3-phase, 50 and 60 Hz
e
Control Options Code Blank B D Description Standard Pump Control Braking Control
e
Control Voltage Code D R E A Description 100240V AC (5480 A units) 24V AC/DC (5480 A units) (Open Only) 110/120V AC (6251250 A units) 230/240V AC (6251250 A units)
f
Horsepower Cat. No. 33 34 35 36 37 38 Hp Rating 0.5 0.75 1 1.5 2 3 Cat. No. 39 40 41 42 43 44 45 Hp Rating 5 7.5 10 15 20 25 30 Cat. No. 46 47 48 49 50 51 Hp Rating 40 50 60 75 100 125 Cat. No. 52 54 56 57 58 59 Hp Rating 150 200 250 300 350 400 Cat. No. 60 61 62 63 65 67 Hp Rating 450 500 600 700 800 1000
f
Options (Select Only One) Code Blank B D Description Standard Pump Control Braking Control
g
Options (see page 30 for a full listing) Code 8L 8M 8B Description Line-Mounted Protective Module Load-Mounted Protective Module Line- and Load-Mounted Protective Modules
g
Options (Non-Combination only) Code 8L 8M 8B Description Line-Mounted Protective Module (enclosed only) Load-Mounted Protective Module (enclosed only) Line- and Load-Mounted Protective Modules (enclosed only)
Load-side MOVs not available with Pump and Braking options, or on Delta-connected motors. MOVs can be field installed for open type units. For a listing of available options, please see page 30.
Load-side MOVs not available with Pump and Braking options. For a listing of available options, please see page 30.
19
Bulletin 150
Motor Current (A) 15 5...25 8.6...43 12...60 17...85 27108 34135 67201
Max. kW, 50 Hz
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
20
Bulletin 150
Motor Current (A) 15 5...25 8.6...43 12...60 17...85 27108 34135 67201
Max. kW, 50 Hz 1.1 5.5 11 15 22 30 37 55 75 90 110 132 200 250 315 400
Max. Hp, 60 Hz 1 7.5 15 20 30 40 50 75 100 125 150 200 250 300 400 500
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
21
Bulletin 150
Motor Current (A) 15 5...25 8.6...43 12...60 17...85 27108 34135 67201
Max. kW, 50 Hz 2.2 11 22 30 45 55 75 110 132 160 200 250 355 450 560 710
Max. Hp, 60 Hz 3 15 30 40 60 75 100 150 200 250 300 400 500 600 800 1000
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
22
Bulletin 150
Motor Current (A) 1...5 5...25 8.6...43 12...60 17...85 27108 34135 67201
Max. kW, 50 Hz 2.2 15 22 37 55 75 90 132 160 200 250 315 450 560 710 900
Open Type Line-Connected Motors Motor Current (A) 27108 34135 67201 84251 106317 120361 160480 Max. kW, 50 Hz 90 132 160 200 315 355 450 630 800 1000 1200 Max. Hp, 60 Hz 100 175 200 250 400 450 600 800 1000 1300 1600 Control Power 100240V AC, 50/60 Hz 100240V AC, 50/60 Hz 100240V AC, 50/60 Hz 100240V AC, 50/60 Hz 100240V AC, 50/60 Hz 100240V AC, 50/60 Hz 100240V AC, 50/60 Hz 110/120V AC, 50/60 Hz 230/240V AC, 50/60 Hz 110/120V AC, 50/60 Hz 230/240V AC, 50/60 Hz 110/120V AC, 50/60 Hz 230/240V AC, 50/60 Hz 110/120V AC, 50/60 Hz 230/240V AC, 50/60 Hz Cat. No. 150-F108NZD 150-F135NZD 150-F201NZD 150-F251NZD 150-F317NZD 150-F361NZD 150-F480NZD 150-F625NZE 150-F625NZA 150-F780NZE 150-F780NZA 150-F970NZE 150-F970NZA 150-F1250NZE 150-F1250NZA
690/Y
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
23
Bulletin 150
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
24
Bulletin 150
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
25
Bulletin 150
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
26
Bulletin 150
Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 31 for terminal lug kits. Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation. Line and load termination are provided as standard.
27
Bulletin 150
kW, 50 Hz 0.37 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 11 15
Hp, 60 Hz 0.5 0.75 1 1.5 2 3 5 5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300
Controller Current Rating 5A 5A 5A 25 A 25 A 25 A 25 A 25 A 43 A 60 A 85 A 85 A 108 A 135 A 201 A 201 A 251 A 317 A 361 A 480 A 625 A 780 A 5A 5A 5A 25 A 25 A 25 A 25 A 25 A 43 A 43 A 60 A 85 A 85 A 108 A 135 A 201 A 201 A 251 A 317 A 361 A 480 A 625 A 780 A
200
230
These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Allen-Bradley distributor.
28
Bulletin 150
kW, 50 Hz 0.37 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
Hp, 60 Hz 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 500 600 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 600 800
400/460
30 37 45 55 75 90 110 132 160 200 250 250 355 450 0.37 0.55 0.75 1.1 2.2 3.7 5.5 7.5 11 15 18.5 22 22 37 45 55 75 90 110 132 160 200 250 295 315 315 450 560
500/575
These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Allen-Bradley distributor.
29
Bulletin 150
Enclosed Options
Option Start-Stop Push Button Start-Stop Push Button with H-O-A Selector Switch Soft Stop Push Button Pump Stop Push Button Push Buttons Slow Speed Push Button Brake Push Button Accu-Stop/Slow Speed Push Button Emergency Stop Fault Reset Selector Switch Hand-Off-Auto Selector Switch SMC-Off-Bypass Selector Switch Transformer Pilot Light - Green Power On Indicator Pilot Lights Transformer Pilot Light - Red Run Indicator Push-to-Test Pilot Light - Red Run Indicator Control Circuit Transformer (fused primary and secondary) Additional 100 VA Control Circuit Transformer (fused primary and secondary) Control Circuit Transformer 1000 VA Control Circuit Transformer (fused primary and secondary) 1600 VA Control Circuit Transformer (fused primary and secondary) 2000 VA Control Circuit Transformer (fused primary and secondary) 480V Line Side Protective Module 600V Line Side Protective Module Protective Modules 480V Load Side Protective Module 600V Load Side Protective Module 480V Both Line and Load Side Protective Modules 600V Both Line and Load Side Protective Modules Human Interface Module Door-mounted, Full Numeric (Type 4/12) Remote I/O RS-485 Communication Module DeviceNet Ethernet/IP Control Net Disconnect Auxiliary Circuit Breaker Auxiliary Service Entrance Label U.L. Label Oil Pump Starter N.O. disconnect auxiliary mounted on operating mechanism N.C. disconnect auxiliary mounted on operating mechanism Internal N.O. circuit breaker auxiliary Internal N.C. circuit breaker auxiliary Service Entrance Label U.L. Label NEMA Size 1 509 and Solid-State Overload Description Cat. No. Modification -1 -1F 1XA 1XB 1XC 1XD 1XE -1E -FR -3 -3B -4G -4R -5R -6P -6PX -6PK -6PL -6PM -8L -8M -8B -HC3 -20R -20S -20D -20E -20C -98 -99 -98X -99X -SEL -UL -OPS
Add the designated letter to the end of the cat. no. Example: To add the Pump Control option: Cat. No. 150-F361NBDB or Cat. No. 152H-F361FBDB-57. Option push buttons are available only when the corresponding option module is selected. Example: Cat. No. 150-F108FBDB-1XB. Bypass contactor and overload are not included with this option. A -NB or -BP needs to be added to the catalog string to add these devices.
30
Bulletin 150
The same protective module mounts on the line or load side of the SMC-Flex. For applications requiring both line and load side protection, two protective modules must be ordered.
Line and Load terminals are provided as standard on enclosed SMCs. 585 A units have box lugs standard. No additional lugs are required. The 1250 A device requires (1) 100-DL630 and (1) 100-DL860 per connection. When a multi-conductor lug is required, refer to the User Manual for appropriate lug catalog number.
31
Bulletin 150
150-TC2
150-TC3
32
Bulletin 150
Protection and Diagnostics Metering Alarm Contact Status Indication Auxiliary Contacts Pump Control
Customer supplied.
33
Bulletin 150
N/A
Power Circuit
Control Circuit
AC-53B:3.0-50:1750 AC-53B:3.0-50:3550 IP20 N/A IP2X (with terminal covers) IP00 (open device) RC Snubber Network None Metal Oxide Varistors: 220 Joules None 100240V AC or 24V AC/DC 110/120V AC and 230/240V AC N/A 240V N/A 3000V 1600V AC 2000V 50/60 Hz 85V AC, 19.2V DC / 20.4V AC 20 mA @120V AC / 40 mA @ 240V AC, 7.6 mA @ 24V AC/DC 50V AC, 10V DC / 12V AC <10 mA AC, <3 mA DC
34
Bulletin 150
Max. Ampere Tested European Style 6,9 gRB 73xxx400 6,6URD33xxx500 6,9 gRB 73xxx400 6,6URD33xxx500 6,9 gRB 73xxx630 6,6URD33xxx700 6,9 gRB 73xxx630 6,6URD33xxx700 6,9 gRB 73xxx800 6,6URD33xxx900 6,9 gRB 73xxx800 6,6URD33xxx900 9 URD 73xxx1250 6,6URD33xxx1250 6,6URD33xxx1400 6,6URD33xxx1400 2 fuses in parallel 6,6URD33xxx1250 2 fuses in parallel 6,6URD33xxx1250
Consult local codes for proper sizing of short circuit protection. Non-time delay fuses (K5 5480V (8.7831 A) devices; Class L 6251250V (8501600 A) devices). High capacity fault rating when used with time delay class CC, J, or L fuses.
35
Bulletin 150
1480 A
Steady State Heat Dissipation with Control and Fan Power (Watts)
5 25 43 60 85 108 135 201 251 317 361 480 625 780 970 1250
Auxiliary Contacts 19/20 (Aux #1) 29/30 (Aux #2) 31/32 (Aux #3) 33/34 (Aux #4)
Type of Control Circuit Number of Contacts Type of Contacts Type of Current Rated Operational Current Conventional Thermal Current Ith AC/DC Make/Break VA Utilization Category Response Resistance Reset Resistance Short-Circuit Trip Resistance Max. Voltage at PTC Terminals (RPTC = 4 k) Max. Voltage at PTC Terminals (RPTC = open) Max. No. of Sensors. Max. Cold Resistance of PTC Sensor Chain Response Time
Tach Input Heatsink fans can be powered by either 110/120V AC or 220/240V AC.
36
Bulletin 150
585 A Power Terminals Terminals 108135 A 201251 A 317480 A 6251250 A Power Terminal Markings Control Terminals
37
Bulletin 150
Controller Rating (A) 5 25 43 60 85 108 135 201 251 317 361 480 625 780 970 1250
IP65 (Type 4/12) Disconnect Rating (A) B Height Non-Combination Controller 610 (24) 610 (24) 610 (24) 610 (24) 610 (24) 762 (30) 762 (30) 965 (38) 965 (38) 1295 (51) 1295 (51) 1295 (51) 2286 (90) 2286 (90) 2286 (90) 2286 (90) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 610 (24) 610 (24) 762 (30) 762 (30) 914 (36) 914 (36) 914 (36) 762 (30) 762 (30) 762 (30) 762 (30) 254 (10) 254 (10) 254 (10) 254 (10) 254 (10) 305 (12) 305 (12) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 508 (20) 508 (20) 508 (20) 508 (20) A Width C Depth
9701250 rated devices are only available as Type 1and require a door-mounted fan, capable of delivering 240 cfm.
38
Bulletin 150
Use this row for 460V -58 and 575V -59. Use this row for 460V -59 and 575V -60 and -61. 9701250 rated devices are only available as Type 1and require a door-mounted fan, capable of delivering 240 cfm.
39
Bulletin 150
Table of Contents
Cat. No. Explanation ............... 42 Product Selection..................... 43 Typical Wiring Diagrams ........ 53 Specifications............................. 55 Approximate Dimensions ...... 59 Enclosed Options ..................... 61 Accessories ............................... 61
The controllers offer two voltage ranges: 200480V AC and 200600V AC. All voltage ranges will operate at either 50 or 60 Hz.
1480 A Range Built-In Electronic Motor Overload Protection Built-In SCR/Run Bypass Delta Compatibility
Standards Compliance/Approvals
UL 508 CSA C22.2 No. 14 EN/IEC 60947-4-2 cULus Listed (Open Type) (File No. E96956) CE Marked (Open Type) per EMC Directive and Low Voltage Directive
40
Bulletin 150
Phase Imbalance
The unit monitors for imbalance between phase currents. To prevent motor damage, the unit will trip if the difference between the minimum phase current and the maximum phase current exceeds 65% for 3 seconds, and a fault will be indicated.
Shorted SCR
Prior to every start and during starting, the unit will check all SCRs for shorts and unit load connections to the motor. If there is a shorted SCR in the SMC-3 and/or open load, the start will be aborted and a shorted SCR or open load fault will be indicated. This prevents damage from phase imbalance.
Over-temperature
The SMC-3 monitors the SCR temperature by means of internal thermistors. When the power poles maximum rated temperature is reached, the microcomputer switches off the SMC, a TEMP fault is indicated via LED, and the 97/98 fault contact closes.
Push to Test
The unit with control wiring can be tested for fault conditions by using the Push to Test function. Hold down the Reset button for 7 seconds to activate the fault Aux (97, 98) and shut down the SMC-3. To clear, either push the Reset button or cycle control power to the device.
41
Bulletin 150
150 C
a b
30
c
F
d a
B
e
D 8L
f g
152H C
a b
30
c a
F
d
BD
e
43 8L
f g
Bulletin Number Code 150 Description Solid-State Controller Code 152H 153H
Bulletin Number Description Solid-State Controller with Fusible Disconnect Solid-State Controller with Circuit Breaker
b
Controller Type Code C Description SMC-3
b
Controller Type Code C Description SMC-3
c
Ampere Ratings Code 3 9 16 19 25 30 37 43 60 85 108 135 201 251 317 361 480 Description 3A 9A 16 A 19 A 25 A 30 A 37 A 43 A 60 A 85 A 108 A 135 A 201 A 251 A 317 A 361 A 480 A Code 3 9 16 19 25 30 37 43 60 85 108 135 201 251 317 361 480
c
Ampere Ratings Description 3A 9A 16 A 19 A 25 A 30 A 37 A 43 A 60 A 85 A 108 A 135 A 201 A 251 A 317 A 361 A 480 A
d
Enclosure Type Code N F Description Open IP65 (NEMA 4/12) Code F
d
Enclosure Type Description IP65 (NEMA 4/12)
e
Input Line Voltage Open Type Code B C H A B C Description 200460V AC, 3-Phase, 50/60 Hz 200600V AC, 3-Phase, 50/60 Hz Non-Combination Enclosed Only 200208V AC, 3-Phase, 50/60 Hz 230V AC, 3-Phase, 50/60 Hz 400460V AC, 3-Phase, 50/60 Hz 500575V AC, 3-Phase, 50/60 Hz
Cat. No. 33 34 35 36 37 38 Hp Rating 0.5 0.75 1 1.5 2 3 Cat. No. 39 40 41 42 43 44 45
e
Input Line Voltage Open Type Code HD AD BD CD Description 200208V AC, 3-Phase, 50/60 Hz 230V AC, 3-Phase, 50/60 Hz 400460V AC, 3-Phase, 50/60 Hz 500575V AC, 3-Phase, 50/60 Hz
f
Horsepower Hp Rating 5 7.5 10 15 20 25 30 Cat. No. 46 47 48 49 50 51 Hp Rating 40 50 60 75 100 125 Cat. No. 52 54 56 57 58 59 Hp Rating 150 200 250 300 350 400 Cat. No. 60 61 62 63 65 67 Hp Rating 450 500 600 700 800 1000
f
Control Voltage Code D R Description 100240V AC 24V AC/DC (Open Type only)
g
Options Code 8L Description Line Mounted Protective Module (Enclosed Type only)
g
Options Code 8L Description Line Mounted Protective Module (Enclosed Type only)
42
Bulletin 150
Motor Current (A) Max. kW, 50Hz 13 39 5.316 6.319 9.227.7 1030 12.337 14.343 2060 28.385 27108 34135 67201 84251 106317 120361 160480
Max. Hp, 60 Hz 0.5 0.752 1.53 1.53 37.5 37.5 510 510 7.515 1025 2030 2540 4060 5075 60100 75125 100150
200/208
Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation.
43
Bulletin 150
Motor Current (A) 13 39 5.316 6.319 9.227.7 1030 12.337 14.343 2060 28.385 27108 34135 67201 84251 106317 120361 160480
Max. Hp, 60 Hz 0.5 0.752 1.55 25 37.5 510 510 515 7.520 1530 2040 2550 4075 50100 60125 75150 100200
230
Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation.
44
Bulletin 150
Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation.
45
Bulletin 150
500/575
Motor FLA rating should fall within specified current range for unit to operate properly. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. Separate 120V or 240V single phase is required for fan operation.
46
Bulletin 150
200/208
Motor FLA rating should fall within specified current range for unit to operate properly. Separate 120V or 240V single phase is required for fan operation.
47
Bulletin 150
230
Motor FLA rating should fall within specified current range for unit to operate properly. Separate 120V or 240V single phase is required for fan operation.
48
Bulletin 150
380/400/415/460
Motor FLA rating should fall within specified current range for unit to operate properly. Separate 120V or 240V single phase is required for fan operation.
49
Bulletin 150
500/575
Motor FLA rating should fall within specified current range for unit to operate properly. Separate 120V or 240V single phase is required for fan operation.
50
Bulletin 150
kW 0.37 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 55 75 90 110 147
Hp (0.5 = 1/2, 0.75 = 3/4, 7.5 = 7-1/2) 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 60 75 100 125 150 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 75 100 125 150 200
200/208
60 85 85 108 135 201 251 317 361 480 3 9 9 9 9 16 25 30 37 43 60 85 85 108 135 201 251 317 361 480
152H-C108FHD-45 153H-C108FHD-45 152H-C135FHD-46 153H-C135FHD-46 152H-C201FHD-48 153H-C201FHD-48 152H-C251FHD-49 153H-C251FHD-49 152H-C317FHD-50 153H-C317FHD-50 152H-C361FHD-51 153H-C361FHD-51 152H-C480FHD-52 153H-C480FHD-52 152H-C3FAD-33 152H-C9FAD-34 152H-C9FAD-35 152H-C9FAD-36 152H-C9FAD-37 152H-C16FAD-38 152H-C25FAD-39 152H-C30FAD-40 152H-C37FAD-41 152H-C43FAD-42 152H-C60FAD-43 152H-C85FAD-44 152H-C85FAD-45 153H-C3FAD-33 153H-C9FAD-34 153H-C9FAD-35 153H-C9FAD-36 153H-C9FAD-37 153H-C16FAD-38 153H-C25FAD-39 153H-C30FAD-40 153H-C37FAD-41 153H-C43FAD-42 153H-C60FAD-43 153H-C85FAD-44 153H-C85FAD-45
230
152H-C108FAD-46 153H-C108FAD-46 152H-C135FAD-47 153H-C135FAD-47 152H-C201FAD-49 153H-C201FAD-49 152H-C251FAD-50 153H-C251FAD-50 152H-C317FAD-51 153H-C317FAD-51 152H-C361FAD-52 153H-C361FAD-52 152H-C480FAD-54 153H-C480FAD-54
These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
51
Bulletin 150
kW 0.37 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 110 147 185 220 295 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 147 185 220 257 375
Hp (0.5 = 1/2, 0.75 = 3/4, 7.5 = 7-1/2) 0.5 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 150 200 250 300 400 0.75 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 200 250 300 350 500
460
152H-C108FBD-49 153H-C108FBD-49 152H-C135FBD-50 153H-C135FBD-50 152H-C201FBD-52 153H-C201FBD-52 152H-C251FBD-54 153H-C251FBD-54 152H-C317FBD-56 153H-C317FBD-56 152H-C361FBD-57 153H-C361FBD-57 152H-C480FBD-59 153H-C480FBD-59 152H-C3FCD-34 152H-C3FCD-35 152H-C9FCD-36 152H-C9FCD-37 152H-C9FCD-38 152H-C9FCD-39 152H-C16FCD-40 152H-C16FCD-41 152H-C25FCD-42 152H-C30FCD-43 152H-C37FCD-44 152H-C43FCD-45 152H-C43FCD-46 152H-C60FCD-47 152H-C85FCD-48 152H-C85FCD-49 153H-C3FCD-34 153H-C3FCD-35 153H-C9FCD-36 153H-C9FCD-37 153H-C9FCD-38 153H-C9FCD-39 153H-C16FCD-40 153H-C16FCD-41 153H-C25FCD-42 153H-C30FCD-43 153H-C37FCD-44 153H-C43FCD-45 153H-C43FCD-46 153H-C60FCD-47 153H-C85FCD-48 153H-C85FCD-49
500/575
152H-C108FCD-50 153H-C108FCD-50 152H-C135FCD-51 153H-C135FCD-51 152H-C201FCD-54 153H-C201FCD-54 152H-C251FCD-56 153H-C251FCD-56 152H-C317FCD-57 153H-C317FCD-57 152H-C361FCD-58 153H-C361FCD-58 152H-C480FCD-61 153H-C480FCD-61
These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.
52
Bulletin 150
NEMA
53
Bulletin 150
Reversing Configuration
Note: Minimum Off time equals 1.0 s.
IEC
NEMA
54
Bulletin 150
Power Circuit
Non-time delay fuses (K5). Consult local codes for proper sizing of short circuit protection.
55
Bulletin 150
Control Circuit
Controller Rating (A) 3 9 16 19 25 30 37 43 Steady State Heat Dissipation and Overload Current Range 60 85 108 135 201 251 317 361 480
Auxiliary Contacts Rated Operational Voltage Rated Insulation Voltage Rated Impulse Voltage Dielectric Withstand Overvoltage Category Operating Frequency Utilization Category Type of Control Circuit Number of Contacts Type of Contacts Type of Current Rated Operational Current (max.) Conventional Thermal Current Ith Make/Break VA Type of Control Circuit Number of Contacts Type of Contacts Type of Current Rated Operational Current (max.) Conventional Thermal Current Ith Make/Break VA Overvoltage category II, when either control or auxiliary circuit is wired to a SELV or PELV circuit. UL/CSA/NEMA IEC 250V AC/30V DC 250V~/30V DC 250V 250V~ 4 kV 1500V AC 2000V~ III 50/60 Hz 50/60 Hz D300/D300 AC-15/DC Electromagnetic relay 1 Normally Open (N.O.) AC/DC 0.6 A @ 120V~ and 0.3 A @ 240V~ 1A 432/72 Electromagnetic relay 1 Normally Open (N.O.) AC/DC 0.6 A @ 120V~ and 0.3 A @ 240V~ 1A 432/72
56
Bulletin 150
Environmental Operating Temperature Range Storage and Transportation Temperature Range Altitude Humidity Pollution Degree Type of Protection -550 C (23122 F) (open) -540 C (23104 F) (enclosed) -2585 C (-13185 F) 2000 m (6560 ft) 595% (non-condensing) 2 IP2X
Mechanical Ratings Resistance to Vibration Resistance to Shock Operational Non-Operational Operational Non-Operational 337 A Line Power Terminals Cable Size Tightening Torque 4385 A 108135 A 201251 A 317480 A 337 A Load Power Terminals Cable Size Tightening Torque 4385 A 108135 A 201251 A 317480 A All Other Conducted Radio Frequency Emissions Radiated Emissions Electrostatic Discharge EMC Immunity Levels Radio Frequency Electromagnetic Field Fast Transient Surge Transient UL/CSA/NEMA 4 kV Contact and 8 kV Air Discharge IEC Class A Class A 8 kV Air Discharge Per EN/IEC 60947-4-2 Per EN/IEC 60947-4-2 Per EN/IEC 60947-4-2 1.0 G Peak, 0.15 mm (0.006 in.) displacement 2.5 G Peak, 0.38 mm (0.015 in.) displacement 15 G 30 G 2.525 mm2 (144 AWG) 2.32.8 Nm (2025 in-lbs) 2.595 mm2 (143/0 AWG) 11.312.4 Nm (100110 in-lbs) 23 Nm (200 in-lbs) Two M10 x 1.5 diameter holes per power pole Two M12 x 1.75 diameter holes per power pole 2.516 mm2 (146 AWG) 2.32.5 Nm (2022.5 in-lbs) 2.550 mm2 (141 AWG) 11.312.4 Nm (100110 in-lbs) 23 Nm (200 in-lbs) Two M10 x 1.5 diameter holes per power pole Two M12 x 1.75 diameter holes per power pole 0.22.5 mm2 (2414 AWG) 0.50.9 Nm (4.48.0 in-lbs)
Control Terminals
57
Bulletin 150
Trip Class 15
Trip Class 20
100 80 60 40 20 0 0 10 20 30 40 50 60 70 80 90
Current (amps)
150-C43 150-C60 150-C85
SMC-3 Starts per hour (108-135A) 40C, 100% Duty Cycle, 20 sec, 350% (w ith standard fan)
SMC-3 Starts per hour (201480 A) 40C, 100% Duty Cycle, 20 sec, 350% (with standard fan)
200
180
160
140
120
Start/Hour
165 115 65 15
100 80
60
40
20
60
160
260 C u r r e n t (A m ps )
360
460
58
Bulletin 150
Open Type
B 139.7 (5-1/2) 206 (8.11) 443.7 (17.47) 560 (22.05) 600 (23.62)
C 100 (4-21/64) 130 (5.12) 205.2 (8.08) 265.3 (10.45) 298 (11.73)
E 132 (5-13/64) 198 (7.8) 367 (14.45) 504.1 (19.85) 539.2 (21.23)
G 2 (1/16) 2 (1/16)
Mounting Hole Size 4.6 (0.18) 5.3 (0.21) 7.5 (0.295) 11.5 (0.45) 11.5 (0.45)
Weight kg (lbs) 0.86 (1.9) 2.25 (5.0) 15 (33) 30.4 (67) 45.8 (101)
A Width 224 (9) 406 (16) 762 (30) 965 (38) 1295 (51)
B Height 305 (12) 305 (12) 610 (24) 762 (30) 914 (36)
C Depth 152 (6) 203 (8) 305 (12) 356 (14) 356 (14)
59
Bulletin 150
Controller Rating (A) 3 9 16 25 30 37 43 60 85 108 135 201 251 317 361 480 3 9 16 25 30 37 43 60
85
IP65 (Type 4/12) Disconnect Rating (A) 30 A/J 30 A/J 30 A/J 30 A/J 60 A/J 60 A/J 60 A/J 100 A/J
100 A/J
B Height Non-Combination Controller 305 (12) 305 (12) 305 (12) 305 (12) 305 (12) 305 (12) 356 (14) 356 (14) 356 (14) 762 (30) 762 (30) 965 (38) 965 (38) 1295 (51) 1295 (51) 1295 (51) Combination Controllers with Fusible Disconnect 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 610 (24)
610 (24)
A Width 305 (12) 305 (12) 305 (12) 305 (12) 305 (12) 305 (12) 406 (16) 406 (16) 406 (16) 610 (24) 610 (24) 762 (30) 762 (30) 914 (36) 914 (36) 914 (36) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16)
406 (16)
C Depth 152 (6) 152 (6) 152 (6) 152 (6) 152 (6) 152 (6) 203 (8) 203 (8) 203 (8) 305 (12) 305 (12) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 203 (8) 203 (8) 203 (8) 203 (8) 203 (8) 203 (8) 203 (8) 254 (10)
254 (10)
85 108 135 201 251 317 361 480 3 9 16 25 30 37 43 60 85 108 135 201 251 317 361 480
100 A/J 200 A/J 200 A/J 400 A/J 400 A/J 600 A/J 600 A/J 600 A/J 15 A 15 A 20 A 30 A 40 A 50 A 80 A 100 A 125 A 175 A/175 A Plug 225 A/225 A Plug 300 A/300 A Plug 400 A/400 A Plug 600 A/600 A Plug 600 A/600 A Plug 800 A/800 A Plug
762 (30) 965 (38) 965 (38) 965 (38) 965 (38) 1524 (60) 1524 (60) 1524 (60)
Combination Controllers with Circuit Breaker
610 (24) 762 (30) 762 (30) 762 (30) 762 (30) 965 (38) 965 (38) 965 (38) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 406 (16) 762 (30) 762 (30) 762 (30) 762 (30) 914 (36) 914 (36) 914 (36)
305 (12) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 203 (8) 203 (8) 203 (8) 203 (8) 203 (8) 203 (8) 254 (10) 254 (10) 254 (10) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14)
356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 356 (14) 610 (24) 610 (24) 610 (24) 965 (38) 965 (38) 965 (38) 965 (38) 1295 (51) 1295 (51) 1295 (51)
Dimensions for FHD-43, FAD-44, FBD-47, and FCD-48. Dimensions for FHD-44, FAD-45, FBD-48, and FCD-49
60
Bulletin 150
Option Push Buttons Selector Switch Pilot Light Start-Stop Push Button Hand-Off-Auto Selector Switch Transformer Pilot Light - Red Run Indicator 480V Line Side Protective Module 600V Line Side Protective Module Protective Module 480V Load Side Protective Module 600V Load Side Protective Module 480V Both Line and Load Side Protective Module 600V Both Line and Load Side Protective Module 1 N.O. auxiliary contact Auxiliary Contacts 2 N.O. auxiliary contacts 1 N.O. and 1 N.C. auxiliary contacts Disconnect Auxiliary
Description
Control Circuit Transformer Control Circuit Transformer (fused primary and secondary)
N.O. disconnect auxiliary mounted on the operating mechanism N.C. disconnect auxiliary mounted on the operating mechanism
Accessories
Description Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations 1- and 2-pole Quick and easy mounting without tools One block per device only N.O. 1 2 0 1 N.C. 0 0 1 1 Connection Diagram Cat. No. 150-CA10 150-CA20 150-CA01 150-CA11 (Form C)
For Use With 150-C337 150-D364 150-C4385/150-D74147 Replacement 150-C108, 150-C135 150-C201, 150-C251 150-C317C480 Connects 140-M-C to 150-C325/150-D325 Connects 140-M-D to 150-C325/150-D325 Connects 140-M-F to 150-C337/150-D332 Connects 100-C0923 to 150-C319/150-D320 Connects 100-C3037 to 150-C337/150-D332
Pkg. Qty.
Connecting modules to 140-M Electrical interconnection between SMCDelta/SMC-3 and 140-M. Motor protector and SMC must be mounted separately. Connecting modules to 100-C Electrical interconnection between SMCDelta/SMC-3 and 100-C. Contactor and SMC must be mounted separately.
1 1 1 1 1
61
Bulletin 150
Total No. of Line Controller Terminal Lugs Possible Each Side Wire Size #6250 MCM AWG 16 mm2120 mm2 #4500 MCM AWG 25 mm2240 mm2 Line Side 3 6 6 Load Side 3 6 3 6 199-LG1 Pkg. Qty. Cat. No. 199-LF1
Line and Load terminals are provided as standard on enclosed SMCs. 185 A units have box lugs standard. No additional lugs are required. When a multi-conductor lug is required, refer to the Instruction Sheet for appropriate lug catalog number.
Description Marking Tag Sheet 10 sheets with 160 perforated paper labels each, 6 x 17 mm To be used with a transparent cover Transparent Cover 100 each To be used with marking tag sheets
Pkg. Qty. 10
150-C, 150-D
100
100-FMC
150-C, 150-D
193-ER1
Surcharge for special voltages up to 20 pcs. (no surcharge for quantities greater than 20 pcs.)